THE LEGEND PLUS MULTI-PRESET
MODEL LGPM INSTRUCTION MANUAL
LGPM Cover.indd 1
7/11/2011 2:33:18 PM
INTRODUCTION
The Legend Plus Multi-Preset Unit (LGPM) is another unit in our multipurpose series of industrial control products that are field-programmable for
solving various applications. This series of products is built around the
concept that the end user has the capability to program different indication and
control requirements.
The Legend Plus, which you have purchased, has the same high quality
workmanship and advanced technological capabilities that have made Red
Lion Controls the leader in today’s industrial market.
Red Lion Controls has a complete line of industrial indication and control
equipment, and we look forward to servicing you now and in the future.
CAUTION: Risk of Danger.
Read complete instructions prior to
installation and operation of the unit.
LGPM Cover.indd 2
CAUTION: Risk of electric shock.
7/11/2011 2:33:21 PM
Table of Contents
GENERAL DESCRIPTION · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · 5
Block Diagram · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · 5
Safety Summary · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · 6
Basic Operation · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · 7
Messages · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · 8
User Input Message Request Operation · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · 8
Binary Message Request Operation · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · 8
Output Message Request· · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · 8
Message Cancellation · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · 8
Overflow Indication · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · 9
Peak & Valley · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · 9
Normal Operating Mode · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · 9
Keypad Description · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · 10
Keypad Functions · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · 10
Program Code Number (PRO.CODE) · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · 11
Front Panel Accessible Functions With Program Disable · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · 11
PROGRAMMING GENERAL DESCRIPTION · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · 12
Program Presets & Counter Load Module · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · 13
Preset Values · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · 13
Counter Load Value · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · 13
Program Scale Factors Module · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · 14
Count Scale Factor · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · 14
Rate Scale Factor · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · 14
PROGRAMMING MENUS · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · 15
Program Scaling Module · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · 16
Count Scale Factor (COUNT SF) · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · 16
Rate Scale Factor (RATE SF) · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · 16
Count Scale Multiplier (CNT.SCM) · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · 16
Rate Scale Multiplier (RATE SCM) · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · 16
Rate Conversion Factor (RATE PER) · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · 16
Decimal Point (CNT. DP, RATE DP) · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · 17
Change Count Value With Scale Factor (CHG CNT W/SF) · · · · · · · · · · · · · · · · · · · · · · · · · · 17
-1-
Program Rate Module · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · ·
Minimum And Maximum Update Time · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · ·
Program Counter Module · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · ·
Count Modes (CNT.INPUT) · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · ·
Counter Reset Action · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · ·
Counter Automatic Reset (AUTO RST)· · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · ·
Program User Module · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · ·
Binary Message Request (BIN MSG REQ) · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · ·
No Mode · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · ·
Maintained Reset (MNT RST) · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · ·
Momentary Reset (MOM RST) · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · ·
Reset Output (RST OUT) · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · ·
Set Output (SET OUT) · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · ·
View/Freeze Display (VIEW DS1)· · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · ·
Change Display (CHG DSP)· · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · ·
Request Message (REQ MSG#)· · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · ·
Clear Message (CLR MSG) · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · ·
Skip Preset (SKIP PRS) · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · ·
Counter Load (CNT LD) · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · ·
Print Request (PRINT RQ) · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · ·
Program Disable (PGM.DIS.) · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · ·
Inhibit Count · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · ·
Program Outputs Module · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · ·
Phase · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · ·
Output Modes - Timed, Latched, Boundary Or HI/LO Acting · · · · · · · · · · · · · · · · · · · · · · · · · ·
Rate Output On/Off Delay · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · ·
Output End (Reset) Modes - OUT1 END, OUT2 END · · · · · · · · · · · · · · · · · · · · · · · · · · · · · ·
Output Power Up State (OFF@P.UP, SAVE@P.DN OR ON@P.UP)· · · · · · · · · · · · · · · · · · ·
Reset Output With Count (RST/C-EN OR DS) · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · ·
Request Message (REQMSG#—) · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · ·
Program Display Module · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · ·
Displays 1 To 4 · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · ·
Scroll Speed (SCRO.SPD) · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · ·
Display Intensity (DSP.LEVEL)· · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · ·
-2-
18
18
19
19
20
20
21
22
22
22
22
22
22
23
23
23
23
23
23
23
23
23
24
24
24
24
26
26
26
26
27
27
27
27
Custom Display Lines (CUST.DSP.1 / CUST.DSP.2) · · · · · · · · · · · · · · · · · · · · · · · · · · · · · ·
Program Mnemonic · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · ·
Program Message Module· · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · ·
Message Type · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · ·
Message Text · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · ·
ASCII Table Of Extended Characters · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · ·
ASCII Table Of Standard Characters · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · ·
Message Priority (PRIOR - 1)· · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · ·
Blinking Message (BLNK-YES/NO) · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · ·
Multiplex (MUX - YES/NO) · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · ·
Maintained/Momentary Message Request · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · ·
Message Cancellation · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · ·
Message Time · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · ·
Message Color · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · ·
Program Communication Port Module · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · ·
Baud Rate · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · ·
Parity/ Number Of Data Bits · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · ·
Unit Address · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · ·
Serial Transmit Delay· · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · ·
Program Print Options Module · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · ·
Mnemonics (MNEM-Yes/No) · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · ·
Transmit And Reset (TX&R-Yes/No) · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · ·
Transmit Message #0 (MSG0-Yes/No) · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · ·
Program Options Module· · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · ·
Operator Access · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · ·
Preset Tracking · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · ·
Program Code (PRO.CODE) · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · ·
User/Factory Settings · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · ·
LGPM Factory Settings Chart· · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · ·
LGPM User Settings Programming Sheet · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · ·
SERIAL COMMUNICATIONS · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · ·
Programming Software · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · ·
Installing Software · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · ·
Using Software · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · ·
-3-
27
27
29
29
30
31
32
33
33
33
33
33
33
33
34
34
34
34
34
35
35
35
35
36
36
36
36
37
37
39
42
42
42
42
Communication Format · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · 43
Sending Commands And Data· · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · 43
Receiving Data · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · 46
®
Terminal Emulation Program For IBM PC · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · 47
Serial Connections · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · 48
Terminal Descriptions · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · 48
Connecting To A Host Terminal · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · 49
Troubleshooting Serial Communications · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · 50
INSTALLATION & CONNECTIONS · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · 51
EMC Compliance Installation· · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · 52
Additional EMC Installation Guidelines · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · 52
Wiring Connections · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · 53
User Input Wiring · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · 53
A.C. Power Wiring · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · 53
DC Power Wiring · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · 53
Serial Communications · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · 53
Signal Wiring · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · 54
Inputs A & B · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · 54
DIP Switch Set-Up · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · 55
Various Sensor Output Connections · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · 56
SPECIFICATIONS & DIMENSIONS · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · 57
TROUBLESHOOTING GUIDE · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · 60
APPENDIX “A” - SCALING FOR COUNT INDICATION · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · 63
Scaling For Count Indication · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · 63
Count Scale Multiplier · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · 64
APPENDIX “B” - SCALING FOR RATE INDICATION · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · 66
Rate Scale Multiplier · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · 67
APPENDIX “C” - APPLICATION · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · 69
APPENDIX “D” - ORDERING INFORMATION · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · 72
APPENDIX “E” - FLOWCHART FOLD-OUT· · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · (Insert)
-4-
GENERAL DESCRIPTION
BLOCK DIAGRAM
The Legend Plus Multi-Preset
Counter (LGPM) is a multi-input,
counting panel instrument that offers the
f eatures and p erf o rmance of a
multi-level preset counter and time
interval rate indicator. The LGPM
f eatures six p resets, which can be
assigned to either the rate or count
indicator.
The Legend Plus h as advanced
features that allow the unit to be more
closely coupled to the application. The
unit features a 2 line by 8 character
alphanumeric display, allowing the
value mnemonics and programming
menus to be easily read. The unit is
available in single or dual color display
models. The four scro ll-through
indication displays can be programmed
to show various parameters and to
automatically scroll. On dual color
models, each indication display can be
programmed f or either color. Th e
mnemonics corresponding to the main
display v alues (RATE, PEAK,
VALLEY, COUNT), can be individually
programmed and modified as desired.
For example, the RATE mnemonic can
be reprogrammed to display the word
SPEED, so that when the rate mnemonic
is to be displayed, the mnemonic SPEED
is displayed instead.
Two custom display lines allow the
user to specify the number of digits of a
value to be displayed on a line, along
with any alphanumeric prefix or suffix.
-5-
GENERAL DESCRIPTION (Cont’d)
Input A accepts a signal for the Count and Rate displays. Input B accepts a
signal for the Count display or direction control. In the Anti-coincidence
mode, both inputs are monitored simultaneously, so that no counts are missed,
and the final count can be chosen as the sum or difference of the two inputs.
Rate and Count displays have separate scaling and decimal point
placement, for readouts in different units. The Counter Load feature enables
the operator to modify the count value. This is useful when flawed material
has been counted and it is necessary to adjust the count value accordingly.
The rate operates in the time interval method (1/tau) to calculate the rate
value. This method insures high resolution at all input rates. Averaging can be
accomplished by programming the Minimum and Maximum Update Time for
the desired response. Extensive scaling capabilities allow practically any
reading at very slow input rates.
The construction of the LGPM unit is a lightweight, high impact plastic
case with a clear viewing window. The sealed front panel with the silicone
rubber keypad meets NEMA 4X/IP65 specifications for wash-down and/or
dusty environments, when properly installed. Plug-in style terminal blocks
simplify installation and wiring changes.
This capability allows displays such as; ‘1000 RPM’, ‘99999 Ft’, ‘PRC
9999’, etc.
The Legend Plus also features messaging capabilities that can inform the
user of output actions or other events that occur in a system. Up to ten
messages can be programmed. Messages can be requested by an output status
change, User Input(s), or through serial communications. The messages can be
programmed for block or character scroll, to blink, time out, and to alternately
flash between message and indication display. On dual color models the
message can be programmed to be displayed in either color. This capability is
very useful in drawing the operator’s attention to particular messages.
The program disable DIP switch, a code value, and an external User Input
selected for Program Disable can be utilized to provide multi-level protection
against unwanted changes to data values and unit configuration.
The Legend Plus features enhanced serial communications. The Serial port
can be configured for connection to RS485 or RS232 devices. It can be used
for data retrieval and for programming various data values.
Optional Legend Plus Programming software (SFLGP) for IBM ®
compatible PCs is available to program all the Legend Configuration
parameters, such as, messages, count modes, etc. The software allows unit
configurations to be created, uploaded, down-loaded, and saved to a file for
rapid programming of the Legend unit.
The six Programmable User Inputs can be configured to provide a variety
of functions. Four User Inputs are located on the upper rear terminal block.
The other two inputs are front panel function keys.
The User Inputs can be configured to provide functions such as:
Count Inhibit
Message Request
Message Cancellation
View/Freeze Display
Change Display
Program Disable
SAFETY SUMMARY
All safety related regulations, local codes and instructions that appear in
the manual or on equipment must be observed to ensure personal safety and to
prevent damage to either the instrument or equipment connected to it. If
equipment is used in a manner not specified by the manufacturer, the
protection provided by the equipment may be impaired.
Do not use this unit to directly command motors, valves, or other actuators
not equipped with safeguards. To do so, can be potentially harmful to persons
or equipment in the event of a fault to the unit.
Reset
Counter Load
Output Activation
Output Deactivation
Skip Presets (outputs)
Print Request
The LGPM offers a choice of seven programmable counting modes for use
in applications requiring bidirectional, Anti-coincidence, and Quadrature
counting. The count inhibit function can be utilized with all of these input
response modes by programming User Input 4 for the Inhibit Count function.
-6-
BASIC OPERATION
The signal at Input A is used for the Rate indicator. The rate indicator uses a
time interval method (1/tau) to calculate the rate value. The unit counts on the
negative edge of the input pulses. After the programmed minimum update time
elapses and the next negative edge occurs, the unit saves the number of edges
that occurred during the elapsed time. The number of edges is multiplied by the
Rate Scale Factor, Rate Scale Multiplier, and the Rate Conversion Factor to
calculate the rate value. Averaging can be accomplished by programming the
Rate Minimum Update Time for the desired response. Extensive scaling
capabilities allow practically any desired reading at very slow count rates.
The unit contains a counter that keeps track of the input pulse count. The
unit takes the actual number of pulses counted (internal count value) and
multiplies them by the Count Scale Factor and Count Scale Multiplier. This
results in the desired reading value for the Count display.
The Counter has three Reset Action modes associated with the display;
Reset to Zero (up-count modes), Reset to Preset (down-count modes), or
Reset to the Counter Load value. A Reset can be a manual reset, using a
programmable User Input, or it can be one of the seven programmable
Automatic Reset modes. Both the reset action and automatic reset modes are
programmed in the Program Counter Module.
The Counter displays the scaled number of pulses that have been entered.
When the count equals a Preset, the appropriate output will activate. The
count can be programmed to automatically reset.
During operation of the Legend
Plus, after internal scaling is
complete, any digits remaining to the
right of the least significant digit
(LSD) of the display is examined by
the unit. If this digit is equal to or
greater than 0.5, the LSD of the
display is rounded to the next higher
digit. Any number less than 0.5 is
ignored. During Reset to Preset
modes of operation, any remainder
greater than 0.5 will cause the display
to be rounded up. Due to this rounding
action, the output activation may
appear to be delayed. In actuality the
display may have rounded up or
down, but the internal count had not
yet reached the preset value or zero.
The following is a Block Diagram overview of the basic operation.
-7-
several bits need to be changed. This would be noticeable on the display, if a
user were to utilize a thumbwheel switch to change messages.
MESSAGES
The Legend Plus features messaging capabilities that can inform the user
of output actions or other events that occur in a system. Up to ten messages
can be programmed. Messages can be requested by an output status change,
User Input(s), or through serial communications.
When a message is requested, the unit checks if there is a message already
on the display. If there are no messages on the display, the requested message
is displayed. A message on the display is replaced if, the requested message
has the same or higher priority. If the unit is not at the main display, the unit
stores one message request. If subsequent messages are requested while not at
the main display, the unit stores the last message requested, or the highest
priority message request. The stored message is redisplayed 2.5 seconds after
the user returns to the main display.
If a message is displayed and the user presses the appropriate key to get to
the Preset, Scaling or Programming menu display, the displayed message is
temporarily suspended. While the message is suspended the message timer, if
used, is also halted. The message is redisplayed 2.5 seconds after the user
returns to the main displays and the message timer resumes. If the Up or Down
arrow key is pressed while in the main display loop, the message is also
suspended, and the appropriate programmed display is shown. The message
is redisplayed 2.5 seconds after the last key press.
OUTPUT MESSAGE REQUEST
Each output can be individually programmed to request a specific message
when activated. The appropriate message will be requested regardless of the
method used to activate the output, i.e. User Input, Count/preset processing,
serial command, etc.
Note: The Output must be active for a minimum of 50 msec. for the request to be seen.
MESSAGE CANCELLATION
Messages can be cancelled automatically, or manually. When cancelled,
messages programmed for maintained request, will be re-requested if the
display is available and the request source is still active. A request for a
message of the same or higher priority will cancel the current message on the
display. Messages can also be cancelled by a User Input programmed for
Cancel Message or via the serial port. The three programmable cancellation
options are Latched, Timed, and Til End. (See Program User Message
Cancellation for details).
USER INPUT MESSAGE REQUEST OPERATION
Individual User Inputs can be programmed to activate any of the ten
messages. The messages can be maintained or momentary. Messages can be
assigned a priority from 1 to 8 (1 is highest). This assures that very important
messages are displayed first.
BINARY MESSAGE REQUEST OPERATION
Two, three or all four of the User Inputs can be configured to request
messages in a binary fashion. Messages 1 through 9 can be requested in this
manner. The binary state 0 (all binary inputs inactive) , is used to indicate no
message requested. During the scanning of the binary message request
inputs, if the Input state is the same as the last requested binary message no
change will occur. When an input change occurs, the unit requests the
message number corresponding to the state of the inputs. The inputs must be
stable for 100 msec (debounce time) for the message to be requested (See
Program User Module for more details). Changing the individual binary
message request input lines slowly will cause unwanted message requests, if
-8-
OVERFLOW INDICATION
NORMAL OPERATING MODE
The unit flashes the word “OVERFLOW” (or assigned mnemonic) in the
appropriate display when an overflow condition occurs. An overflow occurs
if the capacity of the display (6-digits) is exceeded or if the internal count
capacity (9-digits) is exceeded. The use of an extremely small Scale
Multiplier and Scale Factor value can cause the internal count capacity to
overflow before the displayed value overflows.
For example, if a Scale Factor of 0.0001 and a Scale Multiplier of 0.001 is
used, for every 10,000,000 count edges received, the display increments by 1.
Before the display reaches 215, the internal counter overflows. When the
capacity of the display is exceeded, the count value is maintained and is valid.
If the internal count capacity is exceeded, the count value is no longer valid.
Use of a Scale Factor larger than “1” can cause the count display to
overflow before 999,999 internal counts are accumulated. The use of a Rate
Scale Factor, Scale Multiplier, and Rate Conversion Factor larger than “1”
can cause the rate display to be in an overflow condition.
The counters should not be allowed to operate in an overflow condition. As
soon as, or before the counters overflow, the information should be recorded
and the counters reset.
In the normal operating mode, the up, down, left, and right arrow keys are used
to scroll through the main display loop. In the main display loop, the four
indication displays, scale factors, and program mode modules are viewed, as
shown below. In the indication display loop, the up and down arrow keys are
used to scroll to each display. The indication displays are referenced as 1 (0
CNT/0 CPS), 2 (PEAK), 3 (VALLEY), and 4 (COUNT), which are the factory
default settings. The indication displays can be programmed to show other
parameters and automatically scroll (See Program Displays Module). The last
indication display that was viewed at power down, is the one viewed on power
up.
The Presets and Counter Load values are accessed from any of the
indication displays or from the programming loop. The Count and Rate scale
factors are accessed from the Scale Factors display or when in the
programming loop from the Program Scaling module. In the Program Mode
display, the operator enters the programming loop to access all parameters to
configure the unit. Shown below is the Main Display Loop.
PEAK & VALLEY
The Peak and Valley registers record the lowest (Valley) and the highest
(Peak) readings of the rate input signal. These values are viewed in the
indication display loop and are updated automatically. A User Input can be
programmed to reset the values to the current rate value individually or by
sending the proper command via the serial communication port. The Peak and
Valley values are NOT retained when power to the unit is removed.
-9-
KEYPAD FUNCTIONS (Cont’d)
- The Up arrow key scrolls through the indication displays. In the
programming loop, this key can be used to scroll through the main
menus. When programming a numerical value, it increments
(decrements, i.e., goes more positive, for negative values) at the
selected digit position. If the key is pushed and held, the value will
scroll (count up) automatically. After 5 counts, the unit enters fast
scroll mode. If the key remains pushed, a digit shift occurs every one
hundred counts until the maximum value or zero (for negative
presets) is reached. When the digit shift occurs, the previously
scrolling digit goes to zero. When zero is reached (for negative
values), the display holds at zero. To go positive, the key must be
released and pushed again.
- The Down arrow key scrolls through the indication displays. In the
v
programming loop, it scrolls through the main menus and sub
menus. When programming a numerical value, it decrements
(increments or goes more negative, for negative values) at the
selected digit position. If the key is pushed and held, the value will
auto scroll (count down automatically). After 5 counts, the unit
enters fast scroll mode. If the key remains pushed, a digit shift
occurs every one hundred counts until zero is reached. When the
digit shift occurs, the previously scrolling digit goes to zero. When
zero is reached, the display holds at zero. To go negative, the key
must be released and pushed again.
ENT - The Enter key enters the programming loop, when “Program Mode” is
displayed from the main display loop. When “Scale Factors” is
displayed, pressing Enter allows access to the scale factors. This key is
also used to save changes to data values. If the data value is a preset or
counter load value, the value is entered and the preset menu is exited.
For all other numeric data values (i.e., Output time, Rate update times,
etc.), the value is entered and the value edit mode is exited. The value is
still viewed in the display, but with no digits flashing.
SEL> - The Select/Right arrow key scrolls right in the main display loop.
When programming a numerical value, it selects the digit to the
right. In a sub-menu loop, it is used to go to the next lower level and
eventually into an edit menu.
KEYPAD DESCRIPTION
The keypad has a key array of two rows by four
columns. Some keys have a dual function. For a
description of key functions during text and
mnemonics editing, see Text Editing in the
Program Message Module. The following is a
description of each key and its function during
programming and normal operation:
^
KEYPAD FUNCTIONS
- Function key F1 is a User Programmable Input. When the key is
pressed, the unit performs the appropriate function as programmed
in the “Program User Module”.
F2 - Function key F2/RST is a User Programmable Input. When the key is
pressed, the unit performs the appropriate function, as programmed
RST
in the “Program User Module”. The “RST” printing on this key is
used as a quick reference for the operator if the function key is
selected for a reset function.
PRS - The PRS key accesses the Preset and Counter Load Module provided
these values are not programmed for ‘loc’k. If all values are
‘loc’ked, pressing the PRS key does nothing. Preset values that are
accessible (changeable), can be changed immediately. Pressing the
SEL> key is no longer necessary to edit preset values. Within the
preset menu, pressing this key saves the value and advances the
display to the next available preset. Pressing the PRS key at the end
of the module exits the module and returns the user to the main
display loop.
“”THEN GOTO 1000:REM “CHECK FOR KEYBOARD INPUT”
50 IF LOC(1) = 0 THEN 40 ELSE 80: REM “CHECK FOR INPUT”
60 IF LOC(1) = 0 THEN 80: REM “SKIP CLEARING OF BUFFER”
70 B$ = INPUT$(LOC(1), #1): REM “CLEAR BUFFER”
80 F = INP(MCR) AND 253: OUT MCR, F: REM “SET FOR RECEIVE MODE”
90 IF INP(LSR) < > TXEMPTY THEN 90: REM “WAIT UNTIL DONE TRANSMITTING”
100 TIMER ON
110 IF LOC(1) = 0 THEN 110
120 B$ = INPUT$(1, #1)
130 IF B$ = CHR$(10) THEN 160: REM “TO PREVENT DOUBLE SPACING ON PRINT”
140 PRINT B$;
160 IF NOT B$ = “” THEN GOTO 90
170 TIMER OFF
200 GOTO 40
300 TIMER OFF: RETURN 40
1000 D = INP(MCR) OR 2: OUT MCR, D; REM “SET FOR TRANSMIT MODE”
1010 PRINT #1, A$; : PRINT A$; : REM “PRINT KEYSTROKE”
1020 IF A$ = “*” THEN PRINT
1030 IF A$ = “*” THEN IF INP(LSR) < > TXEMPTY THEN 1030 ELSE GOTO 60
1040 A$ = INKEY$: IF A$ < > “” THEN GOTO 1000
1050 GOTO 1010
-47-
For connection to an GCM232 Converter Module, refer to diagram below.
SERIAL CONNECTIONS
When wiring, remove the 10-position terminal block, which is on the top
board at the rear of the unit. Refer to the top label and configure the
RS485/RS232 jumpers for the desired interface. Then, refer to the numbers
listed on the label with the terminal description for installing each wire in its
proper location.
For RS485 the data (transceiver) wires connect to the A (+)/TXD and B
(-)/RXD terminals. It is recommended that shielded (screened) cable be used
for serial communications. This unit meets the EMC specifications using
Alpha #2404 cable or equivalent. There are higher grades of shielded cable,
such as, four conductor twisted pair, that offer an even higher degree of noise
immunity. In some applications, a signal ground may be required to establish
a ground reference. The signal ground is required if the equipment does not
have internal bias resistors connected to the transceiver lines. The signal
ground is connected from only one Legend Plus to the equipment. If
necessary, the shield can be used as the signal ground.
For connection to an RS232 port on a computer, refer to diagrams below.
TERMINAL DESCRIPTIONS
COMM. - Common required for some applications.
A (+)/TXD & B (-)/RXD - The Legend Plus transmits and receives on these
two terminals which are connected to the external device.
TX EN. - Used primarily with a Red Lion Controls (RLC) GCM422 module to
interface with an RLC model DMPC printer or connect to a Legend Plus in
a 20 mA communication loop with other units.
When all connections are made, replace the terminal block into its proper
location.
-48-
SERIAL CONNECTIONS
CONNECTING TO A HOST TERMINAL
Six Legend Plus units are used to monitor and control
parts packaging machines in a plant. The Legend Plus units
are located at each machine in the production area of the
building. A communication line is run to an Industrial
computer located in the production office. The drawing
shows the line connection. Each Legend Plus is
programmed f or a d ifferent address and are all
programmed for the same baud rate and parity as the
computer (ex. 9600 baud, parity even). An application
program is written to send and receive data from the units
using the proper commands.
-49-
TROUBLESHOOTING SERIAL COMMUNICATIONS
If problems are encountered when interfacing the Legend Plus(s) and host
devices or printers, the following check list can be used to help find a
solution.
1. Check all wiring. Refer to the previous application examples and use them
as a guide to check your serial communication wiring. Proper polarity of all
Legend Plus(s) and other peripherals must be observed.
2. Check RS232/RS485 configuration jumpers for proper interface selection.
3. If the Legend Plus is connected to a “host computer”, device or printer,
check to make sure that the computer or device is configured with the same
communication format as the Legend Plus. The communication format that
the Legend Plus will accept is; 1 start bit, 7 or 8 data bits, no parity or 1
parity bit (odd or even), and 1 stop bit.
4. Check the baud rate and parity in the Program Communication Module and
make sure all devices on the line have the same baud rate and parity.
5. Check the Legend Plus’s unit address. If the Address command is not used
when transmitting a command to the Legend Plus, the Legend Plus’s address
must be set to 0. See “Sending Commands & Data” for command structure.
6. If two-way communications are to be established between the Legend Plus
and a computer, have the computer receive transmissions from the Legend
Plus first. Activating a User Input, programmed for the print request
function, will initiate transmissions from the Legend Plus.
7. When sending commands to the Legend Plus, an asterisk *(2Ah) must
terminate the command. NO CARRIAGE RETURNS (0Dh) OR LINE
FEED (0Ah) CHARACTERS SHOULD BE SENT TO THE LEGEND
PLUS. If they are sent, the Legend Plus will respond by transmitting an “E”.
8. In multiple unit configurations, make sure each unit has a different address
other than zero. If a transmit value or print request command is issued, an
asterisk (* ) must be sent before sending another transmission.
9. In some RS485 applications, a twisted pair with a signal ground may be
needed to establish a ground reference. The signal ground is required if the
equipment does not shave internal bias resistors connected to the
transceiver lines. The signal ground is connected from only one Legend
Plus to the equipment.
-50-
INSTALLATION & CONNECTIONS
Installation Environment
temperature and provides good air circulation. Placing the unit near devices
that generate excessive heat should be avoided.
The bezel should be cleaned only with a soft cloth and neutral soap
product. Do NOT use solvents. Continuous exposure to direct sunlight may
accelerate the aging process of the bezel.
Do not use tools of any kind (screwdrivers, pens, pencils, etc.) to operate
the keypad of the unit.
Before installing the Legend Plus into the panel, the user should first
become familiar with the unit. Also, it may be desirable to program the unit
and set the appropriate DIP switches for the application. When programming
is complete, all parameters will be saved in nonvolatile memory. The Program
Disable DIP switch used with an external User Input, programmed for the
program disable function, provides various levels of security to prevent
accidental or unauthorized programming changes. The Legend Plus should be
installed in a location that does NOT exceed the maximum operating
Installation
The unit meets NEMA 4X/IP65 requirements for indoor
use, when properly installed. The units are intended to be
mounted into an enclosed panel with a gasket to provide a
water-tight seal. Two mounting clips and screws are
provided for easy installation. Consideration should be
given to the thickness of the panel. A panel that is too thin
may distort and not provide a water-tight seal, therefore the
recommended minimum panel thickness is 1/8" (3.2 mm).
The recommended clearance behind the panel for mounting
clip installation is 3.0" (6.45 cm) H x 4.0" (10.16 cm) W.
After the panel cut-out is completed and deburred,
carefully apply the gasket to the panel. DO NOT APPLY
THE ADHESIVE SIDE OF THE GASKET TO THE
BEZEL. Insert the unit into the panel as depicted in the
drawing. Thread the screws into the clips until the pointed
end just protrudes through the other side. Install each
mounting clip by inserting the case tabs of the clip into the
holes, located on either side of the bezel.
Then snap the rear end of the clip into the case and slide
the clip towards the rear of the unit, locking it in place.
Tighten the screws evenly to apply uniform compression,
thus providing a water-tight seal.
Caution: Only minimum pressure is required to seal panel.
Do NOT over tighten screws.
-51-
EMC COMPLIANCE INSTALLATION
ADDITIONAL EMC INSTALLATION GUIDELINES
This unit complies with the Electromagnetic Compatibility (EMC) standards
listed in the specifications. Compliance to the EMC standards was demonstrated
by means of a test set-up using the following installation methods:
1. Unit installed in a metal panel mounted to an open aluminum rack
connected to earth ground (protective earth).
2. Shielded (screened) cables for Signal and Control inputs, and solid state
outputs (01-06 SNK) with shield drain wire connected to earth ground at
the mounting panel only.
Although this unit is designed with a high degree of immunity to
ElectroMagnetic Interference (EMI), proper installation and wiring methods
must be followed to ensure compatibility in each application. The type of the
electrical noise, source or coupling method into the unit may be different for
various installations. Listed below are some additional EMC guidelines for
successful installation in an industrial environment.
1. Use shielded (screened) cables for all Signal and Control inputs. The shield
(screen) pigtail connection should be made as short as possible. The
connection point for the shield depends somewhat upon the application.
Listed below are the recommended methods of connecting the shield, in
order of their effectiveness.
a. Connect the shield only at the panel where the unit is mounted to earth
ground (protective earth).
b. Connect the shield to earth ground at both ends of the cable, usually
when the noise source frequency is above 1 MHz.
c. Connect the shield to common of the unit and leave the other end of the
shield unconnected and insulated from earth ground.
2. Never run Signal or Control cables in the same conduit or raceway with AC
power lines, conductors feeding motors, solenoids, SCR controls, and
heaters, etc. The cables should be run in metal conduit that is properly
grounded. This is especially useful in applications where cable runs are
long and portable two-way radios are used in close proximity or if the
installation is near a commercial radio transmitter.
3. Signal or Control cables within an enclosure should be routed as far away
as possible from contactors, control relays, transformers, and other noisy
components.
Multi-conductor Cable
Function Used For
Belden #8451 - 2 conductor, #22 AWG
User Input 4/Inhibit
twisted pair w/ foil shield and drain wire
Belden #8771 - 3 conductor, #22 AWG Input A, Input B, User Inputs 1,2 &
with foil shield and drain wire
3, 01-06 SNK (solid state outputs)
Alpha #2404 - 4 conductor, #22 AWG
RS485/RS232
with foil shield and drain wire
3. EMI line filter (Corcom #1VB3) placed on the DC power supply when DC
powered.
Test: EN 61000-4-4 EFT and ENV 50141 RF Conducted Immunity.
4. Ground shield or ferrite suppression core (TDK #ZCAT3035-1330A) at
device end (opposite end from unit) on serial communication cable
eliminates serial transmission garble.
Test: RF Conducted Immunity per ENV 50141
It should be noted that the methods listed above may not be necessary for
every unit installation. For the purpose of EMC testing, every input and
output line on the unit was connected with 25 feet (8 m) of cable. In extremely
high EMI environments, additional measures may be needed. The unit
becomes more immune to EMI with fewer I/O connections. Cable length,
routing and shield termination are very important and can mean the difference
between a successful or troublesome installation.
-52-
ADDITIONAL EMC INSTALLATION GUIDELINES (Cont’d)
4. In extremely high EMI environments, the use of external EMI suppression
devices, such as ferrite suppression cores, is effective. Install them on
Signal and Control cables as close to the unit as possible. Loop the cable
through the core several times or use multiple cores on each cable for
additional protection. Install line filters on the power input cable to the unit
to suppress power line interference. Install them near the power entry point
of the enclosure. The following EMI suppression devices (or equivalent)
are recommended:
Ferrite Suppression Cores for signal and control cables:
Fair-Rite # 0443167251 (RLC #FCOR0000)
TDK # ZCAT3035-1330A
Steward #28B2029-0A0
Line Filters for input power cables:
Schaffner # FN610-1/07 (RLC #LFIL0000)
Schaffner # FN670-1.8/07
Corcom #1VB3
Corcom #1VR3
Note: Reference manufacturer’s instructions when installing a line filter.
5. Long cable runs are more susceptible to EMI pickup than short cable runs.
Therefore, keep cable runs as short as possible.
6. Switching of inductive loads produces high EMI. Use of snubbers across
inductive loads suppresses EMI.
Snubbers:
RLC #SNUB0000
terminal and tighten down the screw until the wire is clamped in tightly. Each
terminal can accept up to two 18-gage wires. After the terminal block is
wired, install it in the proper location at the rear of the unit. Wire each
terminal block in this manner.
WIRING CONNECTIONS
DC POWER WIRING
The DC power is connected to the bottom left terminals TBA 3 & 4 marked
+12 VDC and common. The DC power source must be capable of supplying
the unit’s rated current (250 mA) and be within the specified ±20% variation
limit. It is not necessary to provide battery backup to retain programmable
information. The Legend Plus has non-volatile memory and information is
stored on power down (Refer to block diagram).
USER INPUT WIRING
Programmable external user inputs are digital inputs that are active when
connected to TBC #3 Common. The use of shielded cable is recommended.
Follow the Additional EMC Installation Guidelines for shield connection.
A.C. POWER WIRING
The AC power is connected to the bottom left terminals TBA 1 & 2 marked AC
PWR. The voltage selector switch, located at the side of the unit, is used to select
the proper voltage. The switch is a slide movement type and can be set by using a
small screwdriver. If the switch is toward the front of the unit, it is set for 115
VAC input. If the switch is towards the rear of the unit, it is set for 230 VAC
input. The switch is in the 230 VAC position when shipped from the factory.
Note: Before applying power to the unit make sure the A.C. power switch is set
for the proper voltage setting.
To reduce the chance of noise spikes entering the AC line and affecting the
unit, the AC power should be relatively “clean” and within the specified
±10% variation limit. Connecting power from heavily loaded circuits or
circuits that also power loads that cycle on and off, (contactors, relays,
motors, etc.) should be avoided.
The bottom board has a removable terminal block (TBA) where the solid
state outputs and the power connections are made. The top board has a
removable terminal block (TBB) where the signal inputs, User Inputs, and
serial communications connections are made. When wiring the unit, remove
the terminal block and use the numbers on the top label to identify the position
number with the proper function. All conductors should meet voltage and
current ratings for each terminal. Also cabling should conform to appropriate
standard s o f good installation, local codes and regulations. It is
recommended that power supplied to the unit (AC or DC) be protected by a
fuse or circuit breaker. Strip the wire, leaving approximately ¼" bare wire
exposed (stranded wires should be tinned with solder). Insert the wire into the
SERIAL COMMUNICATIONS
Refer to the Serial Communications section of the manual, for wiring and
operational procedures.
-53-
SIGNAL WIRING
INPUTS A & B
Input A and Input B have the same input circuitry and share the same
common. Input A and Input B each have separate DIP switches for setting the
type of signal input. A Magnetic Pickup or Logic Input signal can be sent to
either input. When a MAGNETIC PICKUP is used, the Sink/Source DIP
switch, for the appropriate input, must be in the “SRC” position or the unit
will not receive the signal. The HI/LO FRQ DIP switch affects the maximum
input frequency at that input.
The Input schematic shows the details of Input A and Input B circuitry.
Each input has three DIP switches associated with its input. The functions of
these switches are as follows:
INPUT A
SW1 - MAG: Sets input for a Magnetic Pickup signal.
Sensitivity: 200 mV peak; hysteresis: 100 mV
LOGIC: Sets input for a Logic signal.
Input trigger levels: VIL = 1.5 V max; VIH = 3.75 V max.
Note: SW2 must be in the “SRC” position for a Magnetic Pickup signal.
SW2 - SNK: Provides a 7.8 KW internal pull-up resistor for sensors with
current sinking outputs.
SRC: Provides a 3.9 KW internal pull-down resistor for sensors with
current sourcing outputs.
SW3 - HI FRQ: Removes damping capacitor and allows operation up to
the max. frequency.
LO FRQ: Connects damping capacitor for switch contact debounce.
Limits count speed to 50 cps max. Min. count pulse ON or OFF
time is 10 msec.
Note: The HI/LO FRQ selection switch must be set on “LO FRQ” when switch
contacts are used to generate count input signals. The “LO FRQ” mode
provides very high immunity against electrical noise pickup. It is
recommended that this mode also be used, whenever possible, with electronic
sensor outputs. The “LO FRQ” mode can be used with any type of sensor
output, provided count pulse widths never decrease below 10 msec, and the
count rate frequency does not exceed 50 Hz.
INPUT B
SW4 - Same as SW1
SW5 - Same as SW2
Note: SW5 must be in the “SRC” position
for a Magnetic Pickup signal.
SW6 - Same as SW3
Note: A Magnetic Pickup type sensor should not be used unless a large enough
signal is provided at all speeds of operation.
-54-
NOTES:
1. SENSOR VOLTAGE AND CURRENT
The +12 VDC (in/out) terminal can supply voltage to a sensor within a
±25% variation, due to line and internal load variations. All RLC sensors
will accommodate this variation.
2. HI/LO FRQ SELECTION
The HI/LO FRQ selection switch must be set on “LO FRQ” when switch
contacts are used to generate count input signals. The “LO FRQ” mode also
provides very high immunity against electrical noise pickup. It is
recommended that this mode also be used, when possible, with electronic
sensor outputs. The “LO FRQ” mode can be used with any type of sensor
output, provided count pulse widths never decrease below 10 msec, and the
count rate frequency does not exceed 50 cps.
3. When shielded cable is used, the shield should be connected to “COMM.”
at the unit and left disconnected at the sensor end.
4. Inputs A and B can accept source pulses from other circuits up to +28 V in
amplitude. For voltages above +28 V, a limiting resistor and zener diode
should be used to limit the voltage at the input.
DIP SWITCH SET-UP
The DIP switches are accessible through the side of the Legend Plus. The
DIP switch positions and their functions are shown below:
-55-
VARIOUS SENSOR OUTPUT CONNECTIONS
COUNT SWITCH OR ISOLATED TRANSISTOR OUTPUTS
CURRENT SOURCE CONNECTED
(COUNT ON OPENING)
CURRENT SINK CONNECTED
(COUNT ON CLOSING)
(See Note 1)
SENSORS WITH -EF
OUTPUT-CURRENT SRC CONN.
SENSORS WITH CURRENT SINK
OPEN COLLECTOR (NPN O.C.)
(COUNT ON FALLING EDGE)
(COUNT ON TURN-ON)
SENSORS WITH CURRENT
SOURCE OUTPUT (PNP O.C.)
(COUNT ON TURN-OFF)
*
*
SEE NOTE 4 FOR INPUT
*
SEE
*
SEE
SEE
NOTE 2
NOTE 2
NOTE 2
RLC SENSOR MODEL: LMP-EC
RLC SENSOR MODELS: ASTC, LMPC, LSC,
PSAC, RPGB, RPGC, RPGH
VOLTAGES GREATER
THAN +12V.
RLC SENSOR MODELS: PR & RR PHOTO-ELECTRICS
2-WIRE PROXIMITY SENSORS
MAGNETIC PICKUPS
A.C. INPUTS FROM INVERTERS,
INTERFACING WITH CMOS
INTERFACING WITH TTL
* SEE
* SEE
Note 2
NOTE 2
A.C. SIGNALS OVER 50VAC PEAK SHOULD
BE ISOLATED BY A STEP DOWN
TRANSFORMER.
-56-
NOTE: IF
EXTERNAL
SUPPLY IS
USED TO POWER CMOS CIRCUIT,
THE VOLTAGE MUST BE > DC
OUT VOLTAGE
NOTE: CIRCUIT
SHOWN FOR STD
TTL OUTPUT. TTL CIRCUITS ARE
AVAILABLE W/OPEN COLLECTOR
OUTPUTS ELIMINATING THE NEED FOR
A DIODE CLAMP.
SPECIFICATIONS & DIMENSIONS
1. DISPLAY: 2X8, 0.3" (7mm) high characters, negative image transmissive
LCD, with Single (green or red) or Dual Color (green and red) LED
backlighting.
2. POWER:
AC Operation: 115/230 VAC ±10%, 50/60 Hz, 10 VA, switch selectable.
DC Operation: +12 VDC ±20% @ 250 mA. max.
3. MEMORY: Non-volatile memory retains all programming information.
Count and Preset values are written to non-volatile memory when power is
interrupted. All other programming parameters are written to memory when
programming mode is exited. If power is removed while in the programming
menus, the parameters are restored to previously saved settings.
Data Retention: 10 years minimum
Message/Mnemonics Memory: 804 bytes available (with factory settings
loaded).
4. SENSOR POWER: +12 VDC ±25% @ 100 mA.
5. INPUTS A and B: DIP Switch selectable to accept count pulses from a
variety of sources including switch contacts, outputs from CMOS or TTL
circuits, and all standard RLC sensors.
DIMENSIONS In inches (mm)
LOGIC: Input trigger levels VIL = 1.5 VMAX; VIH = 3.75 VMIN.
Current sinking: Internal 7.8 KW pulled up to +12 VDC , IMAX = 1.9 mA.
Current sourcing: Internal 3.9 KW pull-down, 7.3 mA @ 28 VDCMAX.
Debounce: Damping capacitor provided for switch contact bounce. Limits
count speed to 50 Hz and input pulse widths to 10 msec minimum.
MAGNETIC PICKUP:
Sensitivity: 200 mV peak.
Hysteresis: 100 mV.
Input impedance: 3.9 KW @ 60 Hz.
Maximum input voltage: ±50 Vp
Note: For magnetic pickup input, the sink/source DIP switch must be in
the SRC position.
6. RATE ACCURACY: +0.01%.
7. RATE MINIMUM INPUT FREQUENCY: 0.01 Hz.
Note: Recommended minimum clearance (behind the panel) for mounting clip installation is 3.0" (76.2)H x 4.0" (101.6)W.
PANEL CUT-OUT
-57-
11. SERIAL COMMUNICATIONS:
Type: Jumper selectable RS485 or RS232.
Can connect up to 32 units when using RS485 interface.
Baud Rate: Programmable from 1200 to 9600.
Maximum Addresses: Programmable from 00 to 99. (Actual number on a
line is limited by hardware specifications)
Transmit Delay: Programmable for 0.002 or 0.100 second.
Data Format: 10 Bit Frame; 1 start bit, 7 or 8 data bits, 1 or no parity bit,
and 1 stop bit. Parity is programmable for either ODD (7 data bits), EVEN
(7 data bits), or NO Parity (8 data bits).
12. OUTPUT(S):
Solid-State: Current sinking NPN open collector transistor.
VCE = 1.1 VSAT @ 100 mA max. VOH = 30 VDC max. (Internal Zener Diode
Protection).
Programmable Timed Output(s): Programmable time ranges from 0.01
to 99.99 seconds, ±0.05% - 11 msec. max.
Output Time Required to Request Message: 50 msec.
Count Boundary Output Response Time: 10 msec. nominal
13. ENVIRONMENTAL CONDITIONS:
Operating Temperature: 0 to 50°C
Storage Temperature: -40 to 70°C
Operating and Storage Humidity: 85% max. relative humidity
(non-condensing) from 0°C to 50°C.
Vibration According to IEC 68-2-6: Operational 5 to 150 Hz, in X, Y, Z
direction for 1.5 hours, 2 g.
Shock According to IEC 68-2-27: Operational 20 g (10 g relay), 11 msec
in 3 directions.
Altitude: Up to 2000 meters
8. MAXIMUM COUNT RATE IN KHz:
MODEL
LGPM (Multi)
CNT + DIR
X1
X2
13
6
QUAD
X1
X2
6
5
X4
2.5
ADD/ADD ADD/SUB
X1*
X1*
12
6
Notes:
1. Maximum count rates given are for counter set for Auto reset with the auto
cycle preset set to an equivalent of 100 count pulses or greater. With auto
cycle presets less than 100 counts the maximum count rates may be lower.
The actual Preset value for 100 count pulses, with Count SF = 0.5000 and
Count Scale Multiplier = X1, would be 50.
2. Maximum count rate given for X2 and X4 count modes are given for 50%
duty cycle signals and Quad signals with 90o phase shift.
* - Inputs A and B count rates summed.
9. MAXIMUM COUNT CAPACITY:
Count: 9 digits internal (non-scaled),
6 digits displayable (scaled).
10. CONTROL INPUTS:
Programmable User Inputs (4):
USR INP 1 to 3: Internal 10 KW pull-up to +5 VDC, VIL = 1.0 VMAX;
VIH = 4.0 VMIN, Vmax = 30 VDC, response time = 30 msec typical, 100 msec
max. (count rate dependent).
USR INP 4/INH: Internal 10 KW pull-up to +5 VDC, VIL = 1.5 VMAX;
VIH = 3.0 VMIN,, Vmax = 30 VDC, response time = 30 msec typical, 100 msec
max. (count rate dependent).
INHIBIT Response time = 50 msec max.
User Inputs Programmed for Binary Message Request: Debounce =
100 msec. (Binary Message Request Inputs must be stable for 100 msec.
before a message is requested).
-58-
14. CERTIFICATIONS AND COMPLIANCES:
SAFETY
IEC 61010-1, EN 61010-1: Safety requirements for electrical
equipment for measurement, control, and laboratory use, Part 1.
IP65 Enclosure rating (Face only), IEC 529
Type 4X Indoor Enclosure rating (Face only), UL50
ELECTROMAGNETIC COMPATIBILITY
Immunity to EN 50082-2
Electrostatic discharge
EN 61000-4-2
Electromagnetic RF fields
EN 61000-4-3
Fast transients (burst)
EN 61000-4-4
RF conducted interference
EN 61000-4-6
Power frequency magnetic fields
EN 61000-4-8
Level 2; 4 Kv contact
Level 3; 8 Kv air
Level 3; 10 V/m
80 MHz - 1 GHz
Level 4; 2 Kv I/O1
Level 3; 2 Kv power
Level 3; 10 V/rms 1
150 KHz - 80 MHz
Level 4; 30 A/m
Emissions to EN 50081-2
RF interference
EN 55011
Enclosure class A
Power mains class A
Note:
1. When the unit is DC powered from terminal TBA pin 5 (common) and
terminal TBA pin 3 (DC OUT/IN) a power line filter was installed,
RLC #LFIL0000 or equivalent, so as not to impair the function of
the unit.
Refer to EMC Compliance Installation for additional information
15. CONSTRUCTION: High impact plastic case with clear viewing
window. This unit is rated for NEMA 4X/IP65 indoor use. Installation
Category II, Pollution Degree 2. Panel gasket and mounting clips included.
16. WEIGHT: 1.5 lbs. (0.68 Kg)
-59-
TROUBLESHOOTING GUIDE
For further technical assistance, contact technical support at the numbers listed
on the back cover of the instruction manual.
PROBLEMS
NO DISPLAY
CHECKSUM
ERROR 1 OR 2 ON DISPLAY
UNIT DOES NOT COUNT
UNIT WILL NOT ACCEPT THE
DESIRED PRESET
UNIT COUNTS INCORRECTLY
POSSIBLE CAUSE
1. Power off
2. Improperly wired
3. Voltage selector switch in the wrong position.
4. Power in a Brown out condition
5. If powered by +12 VDC source, not enough current to
drive Legend Plus.
6. Blank message requested.
REMEDIES
1. Verify power.
2. Check wiring.
3. Check switch position.
4. Verify voltage reading.
5. Verify Source current rating.
6. Check message, Output message request User Input
programming.
7. Mnemonics/Display not programmed properly.
7. Check Display programming.
1. Data error detected by processor.
1. Press “ENT” key.
a. Check all programming parameters.
2. Check signal lines for possible noise sources.
1. No input signal.
1. Check sensor connections.
a. Verify power to sensor.
2. Type of input signal incorrectly selected.
2. Check DIP switch setting on side of unit.
3. Count Inhibited.
3. Disable Count Inhibit.
4. Scale factor and/or multiplier value too small.
4. Check scale factor value and scale multiplier values.
1. When a count scale factor greater than 1 is used, the 1. Unit automatically adjusts preset to be evenly
divisible by the scale factor.
preset value must be evenly divisible by the scale
factor.
1. Input signal type incorrectly selected.
1. Check DIP switches. Set HI/LO FRQ. switch to LO
for a count speed of less than 50 Hz.
2. Inputs improperly connected.
2. Check sensor input connections.
3. Electrical noise interference.
3. Check power source for noise.
a. Check signal wire routing.
4. Incorrect counting mode.
4. Verify programming in “Program Cntr Module”.
5. Scale factor incorrect.
5. Verify scale factor value.
-60-
TROUBLESHOOTING GUIDE (Cont’d)
PROBLEMS
COUNT, PEAK, OR VALLEY
VALUES WILL NOT RESET WHEN
A MANUAL RESET IS PERFORMED
CAN NOT ENTER INTO
PROGRAMMING MENUS
PRESETS, COUNTER LOAD, OR
SCALE FACTORS CAN BE VIEWED
BUT NOT CHANGED
POSSIBLE CAUSE
1. User Input NOT properly programmed.
REMEDIES
1. Verify programming in “Program User Module”.
1. Front panel disabled.
UNIT COUNTS WHILE RESET
IS ACTIVATED
PRESET OR COUNTER LOAD VALUE
LOADS SMALLER NUMBER THAN
WHAT IS ENTERED
OUTPUT WILL NOT RESET
1. User Input Reset mode set for Momentary reset.
1. Check “Front Panel Accessible Functions With
Program Disable” section in manual.
1. Verify programming in “Program Options Module”
sub-menu Operator Access.
2. Check “ Front Panel Accessible Functions With
Program Disable” section of manual.
1. Program User Input to a Maintained reset.
1. Front panel disabled.
1. Entered number exceeds internal count capacity 1. Check scaling. Reduce number of pulses per unit of
(Scale multiplier/Scale factor too small).
measure.
1. Output assigned to wrong display (Count or Rate). 1. Verify programming in “Program Outputs Module”.
2. Reset with count disabled (Program Outputs 2. Verify programming in “Program Outputs Module”.
Module).
3. User Input NOT properly programmed.
3. Verify programming in “Program User Module”.
-61-
TROUBLESHOOTING GUIDE (Cont’d)
PROBLEMS
NO RATE INDICATION
INCORRECT RATE READING
RATE DISPLAY FLASHING OVERFLOW
POSSIBLE CAUSE
1. No signal at Input A.
REMEDIES
1. Check sensor connections.
a. Verify power to sensor.
2. Type of input signal selected incorrectly.
2. Check DIP switch setting on side of unit.
3. Rate Scale factor and/or Rate Scale Multiplier too 3. Check scale factor value and scale multiplier values.
small.
1. Input signal type incorrectly selected.
1. Check DIP switches. Set HI/LO FRQ. switch to LO
for a count speed of less than 50 Hz.
2. Inputs improperly connected.
2. Check sensor input connections.
3. Electrical noise interference.
3. Check power source for noise.
a. Check signal wire routing.
4. Scale factor incorrect.
4. Verify scale factor value.
5. Rate input signal too high of a frequency.
5. Verify input signal.
1. Rate Scale Factor, Multiplier and/or Conversion 1. Check values.
Factor values too large.
2. Minimum update time set too high for input rate. See
Note in “Programming Rate” Section.
-62-
APPENDIX “A” - SCALING FOR COUNT INDICATION
SCALING FOR COUNT INDICATION
For the preceding example, the Total Scaling, “K T ”, is calculated by
plugging in 2 and 48 in the formula:
KT = 2 ÷ 48 = 0.041667
The Legend Plus is factory set to provide 1 count on the display for each
pulse that is input to the unit. In many applications, there is not a one to one
correspondence between input pulses and display units. In these applications
it is necessary for the Legend Plus to scale or multiply the input pulses by a
scaling factor to achieve the proper display units desired (feet, meters,
gallons, etc.). The Count Scale Factor, the Count Scale Multiplier, and the
Number of Count Edges are used in scaling the input pulses to the desired
reading. The number of count edges is determined in the Program Counter
Module. For example, the number of edges for the CNT+DIRX1 mode is one
and the QUAD X4 mode is four. All three are factored together to provide the
Scaling necessary for the Process display. The Count Scale Factor and Scale
Multiplier are programmed in the Program Scaling section.
The first step in scaling requires the Number of Pulses per Display Units to
be obtained. This may require a small amount of deductive reasoning.
As previously stated, the Total Scaling, “KT”, is the combination of the
Count Scale Factor, Scale Multiplier, and Number of Count edges. In many
applications the Total Scaling, “KT”, can be programmed directly into the
Count Scale Factor, “SF”, in which case the Scale Multiplier and Number of
Count Edges can be left at the factory settings of X1.
In some applications, more display resolution may be required. When the
Total Scaling (KT) is greater than 1.0000 and only one edge per count pulse is
used, there may not be enough display resolution.
Example: With a Total Scaling of 2.000, when an input pulse is generated,
the display increments by 2. If the display units are in feet, when 3 feet have
gone by, the display still reads 2. It will not increment again until 4 feet
have been accumulated. With this amount of display resolution it would be
impossible to set the Preset and have the output respond at odd feet
intervals (1, 3, 5, etc.). To increase resolution, the Number of Count edges
must be increased. This can be achieved by selecting the CT+DIRX2 mode
(Count plus direction times 2) in the Program Count Module or by
selecting the QUAD X4 mode, if quadrature counting is being used. If
enough resolution still has not been attained, more input pulses need to be
generated per display unit.
The amount of resolution required varies depending on the particular
application. In cut-to-length applications, a high amount of resolution is
often necessary. However, in totalizing applications, display resolution
may not be important. It should be noted that whenever the number of count
edges is increased to 2 or 4, the maximum count frequency decreases. (See
Specifications for maximum count frequency).
Note: When using 2 or 4 edge counting for length sensor, on/off duty cycle must
be 50% to maintain max. accuracy (mag. pickup will not work).
Example: A 48-tooth gear is mounted to a 2 ft circumference feed roll in a
paper processing plant. It is desired to display the footage of paper
processed per day. In this example, the display units are in feet. A sensor
sensing the gear teeth provides 48 pulses for each revolution of the feed
roll. Each revolution equates to a linear distance of 2 feet. The number of
Display Units desired is 2. The Number of Pulses per Display Units is 48.
When the number of Display Units and the Number of Pulses have been
obtained, the Total Scaling can be calculated.
The Total Scaling, denoted as “KT”, is simply the total amount of scaling
required for the Process. It is obtained by dividing the Display Units by the
Number of Pulses as shown in Formula #1 below.
FORMULA #1: KT = Display Units ÷ Number of Pulses
WHERE:
KT = Total Scaling.
Display Units = The number of desired units (revolutions, feet, 10ths
of feet, meters, etc.) that would be acquired after
the Number of Pulses has occurred.
Number of Pulses = The Number of pulses required to achieve the
number of Display Units.
-63-
Following our continuing example, it is easy to see that the Remaining
Scaling Factor, “KR” (0.041667), cannot fit into the Count Scale Factor Value
without losing significant digits. Using the Formula above and a Scale
Multiplier value of 0.01 allows us to get the maximum number of significant
digits possible for the Count Scale Factor value:
SF = KR ÷ SCM = 0.041667 ÷ 0.01 = 4.1667
Once the Number of Count Edges (NCE) to be used has been determined,
the Remaining Scaling factor required, “KR”, can be calculated. This is the
Total Scaling, “KT”, divided by the Number of Count edges used as shown in
Formula #2:
FORMULA #2: KR = KT ÷ NCE
WHERE:
KR = Remaining Scaling Factor.
KT = Total Scaling.
NCE = Number of Count Edges.
COUNTER SCALING EXAMPLE:
EXAMPLE #1:
A flow sensor provides 62 pulses per gallon. Calculate the scaling required
to provide a display reading in gallons. The number of “Display Units”
displayed after 62 pulses have been counted should be 1.
In our original example, the Total Scaling, “K T” was determined to be
0.041667. Since this value is less than one, sufficient pulse information is
being generated, i.e., there is enough resolution for the units selected. The
Number of Count edges can be left at the factory set value of X1. The Total
Scaling, “KT”, therefore equals the Remaining Scaling Factor, “KR”.
KR = 0.041667 ÷ 1 = 0.041667
If the remaining scaling is between 0.6000 and 5.9999, it can be
programmed directly into the Count Scale Factor value and the X1 factory
setting for the Count Scale Multiplier “SCM”, can be used.
STEP 1 - Calculate the Total Scaling, “KT”, using Formula #1.
FORMULA #1:
KT = Display Units ÷ Number of Pulses = 1 ÷ 62 = 0.016129
STEP 2 - In this application 62 pulses per gallon provides more than enough
resolution, so the Number of Count Edges (Selected in the Program
Counter Module) is set to a value of X1. With an “NCE” value of 1, the
remaining scaling factor required is still 0.016129.
COUNT SCALE MULTIPLIER
The general rule for choosing a SCM value is, when the Remaining Scaling
Factor, “KR”, is less than 0.6000, a SCM value of 0.1 or 0.01 can be used to get
a Count Scale Factor value between 0.6 and 5.9999 or to the point where the
maximum number of significant digits is obtained.
FORMULA #2
KR = KT ÷ NCE = 0.016129 ÷ 1 = 0.016129
STEP 3 - To provide maximum scaling accuracy, a Scale Multiplier value is
chosen that will give the maximum amount of significant digits in the
Count Scale Factor. A value of 0.01 results in a Count Scale Factor Value
of 1.6129.
FORMULA #3
SF = KR ÷ SCM = 0.016129 ÷ 0.01 = 1.6129
FORMULA #3: SF = KR ÷ SCM
WHERE:
SF = Count Scale Factor.
KR = Remaining Scaling Factor.
SCM = Count Scale Multiplier.
-64-
COUNTER SCALING EXAMPLE: (Cont’d)
EXAMPLE #2:
A quadrature Rotary Pulse Generator that provides 100 pulses per
revolution is coupled to a feed roll that is 2.5 feet in circumference. It is
desired to read in feet with display resolution to the nearest hundredth of feet
(0.01).
In this application, the requirement is for the display to read in hundredths
of a foot. A 2.5 ft. distance equates to 250 “Display Units” (hundredths). The
“Number of Pulses” for 2.5 ft. is 100, as stated.
From the information obtained, the Total Scaling, “KT”, can be calculated,
using Formula #1.
KT = Display Units ÷ Number of Pulses = 250 ÷ 100 = 2.5
With a Total Scaling, “KT”, of 2.5, it can easily be seen that for every pulse
that is input, the display increments by 2.5 display units (hundredths). The
application requires resolution to the nearest hundredth of a foot. To get
higher resolution, Quadrature X4 Input Response Mode is selected. This
provides four times the resolution. Using Formula #2, and 4 for the “Number
of Count Edges”, the Remaining Scaling, “KR”, is calculated.
KR = KT ÷ Number of Count Edges = 2.5 ÷ 4 = 0.625
At this point, it can be seen that the Remaining Scaling Factor value of
0.625 fits into the Count Scale Factor value range without losing any
significant digits or scaling it any further. Because of this, the Scale
Multiplier (SCM) factory set value of X1 is used, and 0.6250 is programmed
directly in for the Count Scale Factor, “SF”.
SF = KR ÷ SCM = 0.6250 ÷ 1 = 0.6250
-65-
APPENDIX “B” - SCALING FOR RATE INDICATION
to revolution units. The Legend Plus has a Rate Scale Factor and a Rate
Scale Multiplier to scale pulse units to the desired display units. They are
programmed in the Program Scaling section. Both are used to attain the
Total Scaling, “K T ”. To calculate the Total Scaling, “K T ”, for the
application, the following formula is used.
The Legend Plus offers a simplified method for scaling the rate portion of
the indicator. The method does not require time unit conversions. The desired
time format (Rate Per Second, Rate Per Minute, Rate Per Hour) is simply
selected as part of the programming procedure. Due to the way the rate is
calculated (See “General Description” section), high resolution and accuracy
can be realized at all input rates, slow or fast.
Note: It is not necessary to increase the pulse information to obtain higher
resolution.
The Rate Minimum Update Time can be programmed from 0.1 up to 99.9
seconds to provide averaging in applications where the input pulse spacing is
not stable. The Update time selected, however, will not affect the scaling in
any manner.
Scaling the Rate channel involves programming the Legend Plus so that
input pulses to the unit are scaled to the desired display units (revolutions,
feet, meters, etc.) and in the desired time format (Rate Per Second, Rate per
Minute, Rate Per Hour).
If the rate indicator is to display the rate at which the counter is counting,
the rate indicator can be programmed with the same scaling parameters as the
counter. The only other requirement is that the desired “Rate Conversion
Factor” be selected to provide the rate display in the desired time format, Rate
per Second (X1), Rate per Minute (X60), or Rate per Hour (X3600). This
automatically scales the rate by X1 (1 pulse per second), X60 (60 pulses per
minute), or X3600 (3600 pulses per hour).
Note: The rate uses only the negative edge of the pulse at Input A. The counter
uses both edges of the input pulse for a X2 or X4 count mode. The rate can
show the same reading as the count, but take into consideration the counter
mode selected.
If the rate application is to display a specific Display Unit, then to scale the
rate, it is only necessary to know the number of pulses per display unit desired
or units (feet, revolutions, etc.).
FORMULA #1: KT = Display units ÷ Number of pulses
WHERE:
KT = Total Scaling.
Display Units = The number of desired units (revolutions, feet, 10ths
of feet, meters, etc.) that would be acquired after
the Number of Pulses has occurred.
Number of Pulses = The Number of pulses required to achieve the
number of Display Units.
Using the example previously discussed, the desired display unit would be
1 revolution and the number of pulses per display unit would be 48.
Therefore, the Total Scaling would be 0.020833.
KT = 1 rev ÷ 48 pulses per rev = 0.020833
In many applications the Total Scaling, “KT”, can be programmed directly
into the Rate Scale Factor, “SF”, in which case the Scale Multiplier “SCM”
can be left at the factory setting of X1. However, in some applications, such as
the one above, it may be desired to obtain more significant digits in the Scale
Factor, “SF”.
These situations occur when “KT” does not calculate to an even number
that will fit into the four decimal places available to the Scale Factor. The
following formula can be used to calculate the Scale Factor when an SCM
value other than X1 is needed.
FORMULA #2: SF = KT ÷ SCM
WHERE:
SF = Rate Scale Factor.
KT = Total Scaling.
SCM = Rate Scale Multiplier.
Example: A 48-tooth gear, which is coupled to a shaft, is being sensed and it
is desired to indicate the shaft speed in revolutions, the display units will be
in revolutions. It is obvious that 48 pulses will occur in one revolution. To
convert the pulse units to revolutions, it is necessary for the Legend Plus to
multiply the number of pulses by a scaling factor to convert the pulse units
In this formula, the Total Scaling, previously calculated, is divided by the
Scale Multiplier Value, “SCM”, to obtain the Scale Factor, “SF”.
-66-
RATE SCALE MULTIPLIER
WHERE:
RCF = 60 for display reading in Rate Per Minute or 3600 for display
reading in Rate Per Hour
The general rule for choosing an SCM value is, when the Total Scaling,
“KT”, is less than 0.6000, an SCM value of 0.1 or 0.01 can be used to get a
Scale Factor value between 0.6 and 5.9999, or to the point where the
maximum number of significant digits is obtained. If the Total Scaling, “KT”,
is greater than 5.9999, then an SCM value of 10, 100, or 1000 can be used to
obtain a Scale Factor Value between 0.6 and 5.9999.
In our initial example, the Total Scaling, “K T ” was determined to be
0.020833. It is easy to see that this number cannot be programmed into the
Scale Factor, “SF”, without losing significant digits. Using formula #2 and
the general rules stated above, a Scale Multiplier Value of 0.01 is chosen and
the Scale Factor is calculated as shown below. This will provide the
maximum amount of conversion accuracy possible.
KT ÷ SCM = 0.020833 ÷ 0.01 = 2.0833
In situations where the Total Scaling is already in range of the Scale Factor
(0.0001 to 5.9999) and when there are no significant digits that are lost, the
Total Scaling, “KT”, can be programmed directly into the Scale Factor Value
and a Scale Multiplier value of X1 (the factory set value) can be used.
RATE SCALING EXAMPLE:
EXAMPLE #1:
A 60-tooth gear is mounted to a roll that has a circumference of 2 feet. It is
desired to have a rate readout with a resolution in 10ths of feet per minute.
Calculate the Scale Factor and Scale Multiplier values necessary to provide
the desired readout.
In this example one revolution of the web will provide 60 pulses for 2 feet
of linear travel. Since the desired display units are to be in tenths of feet, it is
necessary to convert 2 feet to tenths (2 ÷ .1 = 20), giving us 20 tenths (display
units). The Total Scaling, “KT”, is calculated by simply plugging in the two
numbers into Formula #1.
KT = Display Units ÷ Number of Pulses = 20 ÷ 60 = 0.333333
To get the maximum number of significant digits in the Scale Factor we use
formula #2 and a Scale Multiplier value of 0.1 as shown below.
SF = KT ÷ SCM = 0.333333 ÷ 0.1 = 3.3333
To obtain rate indication in Feet Per Minute, the Rate Conversion Factor is
programmed for the Rate per Minute mode. A decimal point is programmed to
0.0, which allows the unit to display in 10ths of feet.
Example: If the desired display units are in feet and there are 100 pulses per
foot, the Total Scaling, “KT”, would be 0.01.
KT = Display units ÷ number of pulses = 1 ÷ 100 = 0.01
Since the Total Scaling, “KT”, is exactly 0.01, it can be programmed into
the Scale Factor Value, “SF”, and the Scale Multiplier Value, “SCM”, can be
left at its factory setting of X1. After the Scale Factor and Scale Multiplier
values are selected, all that is necessary to complete the scaling is to choose
the Rate Conversion Factor. The Rate Conversion Factor (RCF) can be
selected to provide indication in Rate per Second (X1), Rate Per Minute
(X60), or Rate per Hour (X3600).
There may be situations where there are many more pulses per display unit
than needed. In these situations the minimum SCM value (0.01) may not
provide enough significant digits in the Scale Factor. To achieve more
significant digits, the Rate Conversion Factor should be set to Rate per
Second and the following formula be used.
SF = KT x RCF ÷ SCM
-67-
EXAMPLE #2:
The shaft of a positive displacement pump has a 14 tooth sprocket that is
being sensed by a magnetic pickup. It is known that the unit pumps 810 liters
of water per minute, when the shaft is turning 400 RPM. It is desired to have a
display readout in liters per minute.
With the Legend Plus, it is not necessary to deal with time unit conversions.
From the information given, we know that when the shaft has turned 400
revolutions, 810 liters of water will have been pumped. The first step we need
to take is to calculate the number of pulses that occur when 810 liters have
been pumped.
Number of Pulses = # of Rev x Pulses per Rev
= 400 Rev x 14 PPR = 5600 pulses.
We now have all the information necessary to scale the rate. The Total
Scaling, “KT”, is calculated using Formula #1 as shown below.
KT = Display Units ÷ Number of Pulses = 810 ÷ 5600 = 0.144643
It is noticed that there are more significant digits in the Total Scaling, “K T”,
than there are available for the Scale Factor, “SF”. To acquire the maximum
amount of significant digits for the Scale Factor, Formula #2 is used and a
Scale Multiplier value of 0.1 is selected.
SF = KT ÷ SCM = 0.144643 ÷ 0.1 = 1.4464
The Scale Factor, “SF”, equals 1.4464 (1.44643 rounded to 4 decimal
places). This provides the maximum amount of conversion accuracy possible.
The final step is to select a Rate Conversion Factor. The Rate Conversion
Factor is chosen to be Rate Per Minute as was required.
-68-
APPENDIX “C” - APPLICATION
A textile manufacturing company uses three
ink jets to mark cloth at various locations. They
need a counter to track the cloth measurement
and p rovide outputs to the ink jets at
predetermined points. Th ey also require
displayed messages to inform their operators of
changing line speed conditions and corrective
actions that need to be taken. With its ability to
monitor rate, count, provide multi-preset
outputs and display user programmed messages,
the Legend Plus Multi-preset counter is the best
unit for the job.
The cloth moves over a
roller with a circumference
of 13.20 inches. A 72 tooth
gear is mounted on the
roller. Due to the size of the
gear, the best sensor would
be the model HESS. The
desired d isplay on the
LGPM is tenths of inches. It
is also desired to display a
rate of tenths of inches per
minute. With the Legend
Plus, the scaling for the rate
is the same as f or the
counter.
Outputs One through Three are programmed to the count
display and will fire the ink jets at the appropriate intervals.
The outputs are programmed for a Timed output. Outputs
Four through Six are assigned to the rate display and will be
programmed to request messages to appear on the display
when the listed event occurs:
Output 4 - Speed up Line #4
Output 5 - Slow down Line #4
Output 6 - Overspd STOP! (Top Priority)
The following is a chart of the necessary programming
as entered into the Legend Plus unit.
-69-
LEGEND PLUS PROGRAM SHEET
RATE
SCALE FACTORS
COUNT SF
RATE SF
CNT. SCM
CNT. D.P.
RATE SCM
RATE PER
RATE D.P.
CHG. CNT/
WITH SF
1.8333
1.8333
X1
0.1
X1
MINUTE
0.1
YES
MIN. TIME
MAX. TIME
NO
NO
NO
NO
NO
NO
NO
NO
OUTPUT 1
ASSIGNED
PHASE
TYPE
ACT/TIME
OUTPUT END
DLY TYPE
ON DL TIME
OF DL TIME
OFF@P.
RST/C
REQ MSG #
5.0
COUNTER
CNT. INPUT
RESET
AUTO. RST
OPTIONS
ACCESS
P1
P2
P3
P4
P5
P6
CTLD.
SF’S
OUTPUTS
1.0
CT+DIRX1
TO ZERO
DISABLED
PRESET TRACKING
P1
P2
P3
P4
P5
P6
TRACK
TRACK
TRACK
TRACK
TRACK
TRACK
PRO. CODE
NONE
NONE
NONE
NONE
NONE
NONE
OUTPUT 3
ASSIGNED
PHASE
TYPE
ACT/TIME
DLY TYPE
ON DL TIME
OF DL TIME
OFF @ P.
RST/C
REQ MSG #
23
PRESETS
P1
P2
P3
P4
P5
P6
CL
36.0
180.0
360.0
1150.0
1250.0
1300.0
0
OUTPUT 5
ASSIGNED
PHASE
TYPE
ACT/TIME
DLY TYPE
ON DL TIME
OF DL TIME
OFF @ P.
RST/C
REQ MSG #
USER INPUTS
BIN. MSG.REQ.
USER INP. 1
USER INP. 3
USER F1
NONE
NO MODE
NO MODE
NO MODE
USER INP. 2
USER INP. 4
USER F2
NO MODE
NO MODE
NO MODE
-70-
TO CNT
+
TIMED
0.5
DISABLED
UP
EN
–
TO CNT
+
TIMED
0.5
DISABLED
UP
EN
–
TO RATE
+
BOUNDARY
HI ACT
NO DLY
UP
EN
3
OUTPUT 2
ASSIGNED
PHASE
TYPE
ACT/TIME
OUTPUT END
DLY TYPE
ON DL TIME
OF DL TIME
OFF @ P.
RST/C
REQ MSG #
OUTPUT 4
ASSIGNED
PHASE
TYPE
ACT/TIME
DLY TYPE
ON DL TIME
OF DL TIME
OFF @ P.
RST/C
REQ MSG #
OUTPUT 6
ASSIGNED
PHASE
TYPE
ACT/TIME
DLY TYPE
ON DL TIME
OF DL TIME
OFF @ P.
RST/C
REQ MSG #
TO CNT
+
TIMED
0.5
DISABLED
UP
EN
–
TO RATE
+
BOUNDARY
LO ACT
NO DLY
UP
EN
2
TO RATE
+
BOUNDARY
HI ACT
NO DLY
UP
EN
4
LEGEND PLUS PROGRAM SHEET (Cont’d)
DISPLAY
DISPLY 1
D1 LINE 1
D1 LINE 2
D1 COLOR
DISPLY 3
D3 LINE 1
D3 LINE 2
D3 COLOR
SCRO. SPD
DSP. LEVEL
DSP. LEVEL
CUST. DSP.
CUST. DSP.1
CUST. DSP.2
G
R
MESSAGE
CUST. DSP. 1
CUST. DSP. 2
GREEN
DISPLY 2
D2 LINE 1
D2 LINE 2
D2 COLOR
RATE-MNE
CUST.DSP.1
GREEN
PEAK-VAL
VALI-VAL
GREEN
DISPLY 4
D4 LINE 1
D4 LINE 2
D4 COLOR
CNT-MNE
CNT-VAL
GREEN
NONE
5
5
VAL-RATE
IPM
VAL-CNT
IN.
MNEMONIC
RATE
PEAK
VALLEY
COUNT
OVERFLOW
SPEED
P
V
INCHES
OVERFLOW
MSG.
TYPE
#
TEXT
PRIORITY
BLINKING
MULTIPLEX
MOM/MNT REQ
2
2L BLOCK
SPEED UP
LINE #4
6
YES
YES
MNT
CANCEL
TIME SEC.
COLOR
TIL END
MSG.
TYPE
3
1L BLOCK
#
TEXT
GREEN
PRIORITY
BLINKING
MULTIPLEX
MOM/MNT REQ
SLOW DOWN
LINE #4
6
NO
YES
MNT
CANCEL
TIL END
-71-
TIME SEC.
COLOR
MSG.
TYPE
TEXT
#
PRIORITY
BLINKING
MULTIPLEX
MOM/MNT REQ
CANCEL
TIME SEC.
COLOR
GREEN
4
2L BLOCK
OVERSPD
STOP!
2
YES
NO
MNT
TIL END
RED
APPENDIX “D” - ORDERING INFORMATION
MODEL NO.
LGPM
SFLGP
DESCRIPTION
Multi Preset (6) Legend Plus w/Grn Backlighting
Multi Preset (6) Legend Plus w/Red Backlighting
Multi Preset (6) Legend Plus w/Dual Color Bcklghtng
Legend Plus Programming Software, 3 ½", 1.44 M disk
APPENDIX “E” - FLOWCHART FOLD-OUT (Insert)
-72-
PART NUMBER
115/230VAC & +12VDC
LGPM0001
LGPM0101
LGPM0201
SFLGP
LIMITED WARRANTY
The Company warrants the products it manufactures against defects in materials and workmanship
for a period limited to two years from the date of shipment, provided the products have been stored,
handled, installed, and used under proper conditions. The Company’s liability under this limited
warranty shall extend only to the repair or replacement of a defective product, at The Company’s
option. The Company disclaims all liability for any affirmation, promise or representation with
respect to the products.
The customer agrees to hold Red Lion Controls harmless from, defend, and indemnify RLC against
damages, claims, and expenses arising out of subsequent sales of RLC products or products
containing components manufactured by RLC and based upon personal injuries, deaths, property
damage, lost profits, and other matters which Buyer, its employees, or sub-contractors are or may be
to any extent liable, including without limitation penalties imposed by the Consumer Product Safety
Act (P.L. 92-573) and liability imposed upon any person pursuant to the Magnuson-Moss Warranty
Act (P.L. 93-637), as now in effect or as amended hereafter.
No warranties expressed or implied are created with respect to The Company’s products except those
expressly contained herein. The Customer acknowledges the disclaimers and limitations contained
herein and relies on no other warranties or affirmations.
LGPM Cover.indd 3
7/11/2011 2:33:21 PM
LGPM/IM - E 07/11
DRAWING NO. LP0283
Red Lion Controls
Headquarters
20 Willow Springs Circle
York PA 17406
Tel +1 (717) 767-6511
Fax +1 (717) 764-0839
LGPM Cover.indd 4
Red Lion Controls
Europe
Printerweg 10
NL - 3821 AD Amersfoort
Tel +31 (0) 334 723 225
Fax +31 (0) 334 893 793
Red Lion Controls
India
54, Vishvas Tenement
GST Road, New Ranip,
Ahmedabad-382480 Gujarat, India
Tel +91 987 954 0503
Fax +91 79 275 31 350
Red Lion Controls
China
Unit 101, XinAn Plaza
Building 13, No.99 Tianzhou Road
ShangHai, P.R. China 200223
Tel +86 21 6113-3688
Fax +86 21 6113-3683
7/11/2011 2:33:21 PM