Bussmann®
Transient Voltage Surge Suppression Limiters
TVSS
General Information:
• Designed to protect TVSS systems per UL 1449 Second
Edition Requirements.
• Able to withstand 8x20 µSec surge pulses without opening.
• Limiters are identified by a surge rating and not continuous
current rating.
Dimensional Data
TVSS-(
)
TVSS-(
)-01
Catalog Symbol: TVSS
Physical Size: Refer to “Dimensional Data”
Construction:
Melamine Tube
Nickel Plated Brass End Caps
Voltage Rating: 600Vac
Interrupting Rating:
200,000A RMS Sym.
Agency Approvals:
UL Recognized 600Vac, File E56412
Catalog Symbol and Surge Ratings
CATALOG
8x20µS
NUMBER SURGE RATING
MELTING I2t
(A2s)
CLEARING I2t
(A2s)
Ipeak @ 100kA
60 Hz (A)
TVSS-5
5,000A
559
1,650
4,283
TVSS-10
10,000A
1,788
5,766
6,618
TVSS-15
15,000A
3,760
9,730
7,843
TVSS-20
20,000A
6,020
14.000
8.594
Above catalog numbers are available with Printed Circuit Board Tabs. When
ordering, use suffix “-01”.
CE logo denotes compliance with European Union Low Voltage Directive
(50-1000Vac, 75-1500Vdc). Refer to Data Sheet: 8002 or contact
Bussmann Application Engineering at 636-527-1270 for more information.
9-01-04
SB04303
Recommended fuseblocks/fuseholders for
13/32” x 1-1/2” fuses
See Data Sheets listed below
• Open fuseblocks - 1104, 2104
• Finger-safe fuseholders - 1109, 1102, 1103, 1151
• Panel-mount fuseholders - 2114, 2113, 2108,
• In-line fuseholders - 2127, 2126
Form No. TVSS
Page 1 of 3
Data Sheet: 2141
Bussmann®
Transient Voltage Surge Suppression Limiters
TVSS
TVSS-5
TVSS-10
TVSS-20
Time-Current Characteristic Curves–Average Melt
AMPERE
RATING
300
200
100
TIME IN SECONDS
10
1
.1
2,000
1,000
100
30
20
.01
CURRENT IN AMPERES
9-01-04
SB04303
Form No. TVSS
Page 2 of 3
Data Sheet: 2141
Transient Voltage Surge Suppression Limiters
TVSS
Time-Current Characteristic Curves–Peak Let-Through
Current In Amperes x100
Instantaneous Peak Let Thru Current In Amps x100
200
20
15
10
100
5
10
3
2
10
100
1000
3000
RMS Symmetrical Current In Amperes x100
The only controlled copy of this Data Sheet is the electronic read-only version located on the Bussmann Network Drive. All other copies of this document are by definition uncontrolled. This bulletin is
intended to clearly present comprehensive product data and provide technical information that will help the end user with design applications. Bussmann reserves the right, without notice, to change
design or construction of any products and to discontinue or limit distribution of any products. Bussmann also reserves the right to change or update, without notice, any technical information contained in this bulletin. Once a product has been selected, it should be tested by the user in all possible applications.
9-01-04
SB04303
Form No. TVSS
Page 3 of 3
Data Sheet: 2141