Data Sheet
Telaris EARTH-TEST
Earth Resistance Tester
The Telaris Earth-Test can test the ability of soil and grounding
connection to conduct electricity and provide an electrical
reference point. Good soil conductivity is needed to limit
static electricity charge in potentially flammable situations
and minimize the voltage difference between power return
and earth ground for personal safety. Resistance testing is
done by 2 wire, 3 wire or 4 wire testing methods.
■■ Earth resistance measurement
■■ Specific earth resistance measurement
■■ The integrated constant current measurement principle
allows the application in sandy as well in rocky
environments
■■ Monitoring and display of auxiliary earth and probe
resistances
No hassle
warranty
No waiting.
No shipping
charges.
Our commitment to
high-quality products
and customer service
is demonstrated by
our industry exclusive
“No Hassle” warranty.
In the unlikely event
that an Amprobe Test
Tool requires warranty
service, any of our
local dealers are
authorized to replace
it, on the spot.
■■ Displays the actual test current
■■ Automatic and manual and frequency selection for noise
reduction
■■ Test voltage pre-selection
■■ Clear and large digital display provides the user with an
optimum visual indication of both test values and limits
■■ Auto power off
■■ Specific earth resistance measurement in compliance with
the Wenner principle
(note: $500 MSLP limit)
600V
Amprobe® Test Tools
www.Amprobe.com
Telaris EARTH-TEST Earth Resistance Tester
Data Sheet
Specifications
Display
Meas. Principle
Earth Resistance
Probe-aux. resistance
Test Current Display
Max. Test Current
Test Voltage
Frequency
Safety Complying with
Overvoltage category
Pollution Degree
Power Supply
Dimensions
Weight (inc. batteries)
3 digit; LCD; 1999 Count
Constant voltage / variable current measurement
Range
0.05 to 19.99 Ω; 20 to 199.9 Ω; 200 to 1999 Ω
Resolution
0.01 Ω; 0.1 Ω; 1 Ω
Tolerance
±(4% rdg. + 2 digits )
Range
0.1 to 50 kΩ
Resolution
0.1 kΩ
Tolerance
±(10% rdg. + 3 digits)
Range
0.1 to 13 mA
Resolution
0.1 mA
Tolerance
±(10% rdg. + 3 digits)
approx. 12 mA
max. 25 V / 50 V AC selectable
127 Hz / 140 Hz selectable
EN61010-1/DIN VDE 0411, EN61557-1,5/DIN VDE 0413
CAT III / 300 V
2
6 x 1.5 V(AA), IEC LR6
235 x 105 x 68 mm (9.3 x 4.1 x 2.7 in.)
approx. 640g (1.4 lbs.)
Amprobe® Test Tools
website: www.Amprobe.com
email: info@amprobe.com
Everett, WA 98203
Tel: 877-AMPROBE
Amprobe® Test Tools
Amprobe® Test Tools Europe
Amprobe Test Tools Europe
Beha-Amprobe GmbH
In den Engematten 14
79286 Glottertal, Germany
Tel.: +49 (0) 7684 8009 - 0
©2008 Amprobe Test Tools. All rights reserved.
10/2008 3393515 Rev A
www.Amprobe.com
很抱歉,暂时无法提供与“AMPRB-ET4”相匹配的价格&库存,您可以联系我们找货
免费人工找货