Data Stream RS485 Digital Transducer
DIN RAIL / PANEL MOUNT
The CRD5100 Series Data Stream Digital Transducers are designed
for complete monitoring of electrical power systems. The digital
technology is used to measure voltage, current, power frequency and
energy in single and three phase designs. The data is streamed over
an RS485 IEEE bus which enables multiple transducers to
communicate through a single master connection. These advanced
sensors are ideal for entire plant or zone monitoring. Also, the
communication algorithm can be ordered with ASCII based control or
modified to MODBUS based control.
Sensing
Voltage, True RMS
Current, True RMS
Active Power, bi-directional
Active Energy, bi-directional
Reactive Power, bi-directional
Reactive Energy, bidirectional Power Factor
Frequency
CRD5110
Single Element - .26” (6.5)
Window 150 to 300 VAC
1 to 25 AAC Input Range
B
Data Stream
Applications
Sub-Metering
Motor Loads
Uninterruptible Power
Systems Remote Monitoring
Load Shedding
Energy Management
CRD5150
Two Element - .26” (6.5)
Window 150 to 300 VAC
1 to 25 AAC Input Range
Features
35mm DIN Rail or Panel Mount
Red LED - Flashes when Power is Connected
Red & Green LED Flash during Communication
24 VDC powered
Use with external current transformers
Highest precision available
Connection diagram printed on case
Regulatory Agencies
CRD5170
Three Element- .26” (6.5)
Window150 to 300 VAC
1 to 25 AAC Input Range
PART NUMBERS
CRD5110
CRD5150
CRD5170
150
300
The Professional
Energy Monitoring
Company
M N TI
ISO 9001:2008 Quality Management System
-
0-150 VAC
0-300 VAC
Available up to and including 600 VAC
1 Element, AC Multifunction RS485 Digital Transducer
3 Phase, 3-Wire AC Multifunction RS485 Digital Transducer
3 Phase, 4-Wire AC Multifunction RS485 Digital Transducer
1
5
15
25
-
0-1 AAC
0-5 AAC
0-15 AAC
0-25 AAC
Above 30 AAC must use 5 amp CT
Note: Add an M at
the end for MODBUS
CRD5110-150-5-M
3500 Scarlet Oak Blvd. St. Louis MO USA 63122 V: 636-343-8518 F: 636-343-5119
Web: http://www.crmagnetics.com
13
E-mail: sales@crmagnetics.com
RS485 Digital Transducer
SPECIFICATIONS
B
Basic Accuracy: .......................0.5%
Calibration: ..............................True RMS Sensing
Thermal Drift: ..........................500 PPM/°C
Operating Temperature1: ..........0°C to +60°C
Installation Category: ..............CAT II
Vibration Tested To: .................IEC 60068-2-6,1995
Pollution Degree: ....................2
Insulation Voltage: ..................2500 VDC
Altitude: ..................................2000 meter max
Frequency Range: .................45Hz ~ 65Hz
MTBF: ....................................Greater than 100K hours
Cleaning: ................................Water-dampened cloth
Supply Voltage2: ......................24 VDC ±10%
Torque Specifications: ....................3.0 inch lbs (0.4Nm)
Response Time: .......................250 ms. max. 0-90% FS
Relative Humidity: .............5% to 95%, Non-Condensing
Output Resolution: ..................................................16 bit
Transducer fanout on common bus: ...................64 max.
Baud Rate3: ...............1200, 2400, 4800, 9600,19.2K .bps
A/D Conversion Type: ..................4th order Delta Sigma
Device Address3: ............................................00 to FF
Data Format: .... .....................................................ASCII
Supply Current:..................Typical 30mA
Max 30mA
Weight:.. ..............................................................0.5 lbs.
1) RH 5% to 95%, non-condensing 2) 0.4% max. ripple Vpp
no flow control, 1 stop bit
Data Stream
3) Factory default settings:
address 01, baud rate 9600, no parity,
LINE
LINE
NN
N
N
LL1
1
2
3
4
9
8
7
6
5
LOAD
LOAD
+
-
SUPPLY
LOAD
L1
L1
N
N
LINE
LINE
LINE
L2
L2
L3
L3
L3
1
2
3
4
9
8
7
6
5
LOAD
LOAD
1
2
3
4
+ 485
+
SUPPLY
CRD5170 3 Element, 4-Wire
CRD485-232
RS485 to RS232 Converter Accessory
Connect PC to RS485 Bus
Connection Diagram
RED INDICATIOR LED
GREEN INDICATOR LED
TX
RX
[26.6]
1.05
1
2
3
4
DIN RAIL
MOUNTING
CLIP
[25]
.98
[31.0]
1.22
485
LOAD
LOAD
SUPPLY
[73.1]
2.88
[83.3]
3.28
9
8
7
6
5
-
CRD5150 Dual Element, 3-Wire
[3.3]
.13
OPTIONAL
MOUNTING
+ 485
-
9
8
7
6
5
CRD5150 Dual Element, 3-Wire
CRD5110 Single Element, 2-Wire
L1
L2
L2
-
SUPPLY
L2
L1
L1
1
2
3
4
+ 485
-
+
LINE
LINE
DATA STREAM
TRANSDUCER
DATA +
9
8
7
6
5
DATAGND
CRD485-232
+5VDC
+
-
COM
RS232
GND
DB 9, FEMALE
SUPPLY
[6.6]
[78.7] .26
3.10
MAX
[76.7]
[64] 3.02
2.52
[5.6]
.22
TYP
ASCII Simplified Programming Commands
[28.3]
1.12
[88.7]
3.49
[35.0]
1.38
[36.6]
1.44
[13.5]
.53
[31.0]
1.22
[19.8] [19.8]
.78
.78
OUTLINE DRAWING
The Professional
Energy Monitoring
Company
M N TI
ISO 9001:2008 Quality Management System
A simplified data structure is used with only 6 commands required for full control of
the transducer. Commands are : Read Transducer Name, Read Configuration, Set
Configuration, Read Measurements, Read Energy Totalizer and Clear Energy
Totalizer. For illustration, the following commands are used to read data from a
CRD5170 3 Phase, 4 Wire Transducer with a device address of 00.
Command Transducer to Read Data: #00A
Transducers Response: >+[% FS VoltageL1-N]+[% FS CurrentL1]+[% FS
VoltageL2-N]+[% FS CurrentL2]+[% FS VoltageL3-N]+[% FS CurrentL3,][+/- % FS
Power][+/-% FS VARS][+/-Power Factor][Frequency]
Command Transducer to Read Energy Totalizer: #00W
Transducer Responds: 01[+/-KWHr]{\[+/-KVHr][check sum]
Note: This is for illustration purposes only, See Applications Guides (Section I
for complete instructions.
3500 Scarlet Oak Blvd. St. Louis MO USA 63122 V: 636-343-8518 F: 636-343-5119
Web: http://www.crmagnetics.com
14