Loop-Powered AC Voltage Transmitter
DIN RAIL / PANEL MOUNT, AVERAGE RMS
The CR4600 Series, Loop-Powered AC Voltage Transmitters
are designed to provide a 4 - 20 mADC output that is
proportional to the average RMS AC voltage input. These
devices are best suited for general applications, such as fixed
frequency voltage supplies.
Applications
Monitor for over/under voltage
Sense phase loss
Power monitoring
Multi-point instrumentation needs
Features
CR4620
35mm DIN Rail or Panel Mount
Outputs isolated from inputs
One or two element
Connection diagram printed on case
Single Element Transmitter
1.0 to 600 VAC Input Range
C
Transducers
Regulatory Agencies
Recognized to meet UL 61010B-1
Constructed to meet CAN/CSA-C22.2, No. 61010-1-2004
Meets requirement of IEC 61010-1 and BS EN 61010-1
E199795
CR4640
Two Element Transmitter
1.0 to 600 VAC Input Range
SINGLE PHASE
CENTER TAP
RESIDENTIAL
CR Magnetics has a wide selection of Potential
Transformers to extend the range of any part.
Contact factory for more information.
CR4640
TYPICAL APPICATION
RESIDENTIAL POWER
Add suffix for input range
50
150
250
500
PART NUMBERS
CR4620
CR4640
-
Single element with 4 - 20 mADC output
Two element with 4 - 20 mADC output
-
0-50 VAC
0-150 VAC
0-250 VAC
0-500 VAC *
Ranges available up to and including
600 VAC
* UL Recognized up to 300 Vac
The Professional
Energy Monitoring
Company
M N TI
ISO 9001:2008 Quality Management System
3500 Scarlet Oak Blvd. St. Louis MO USA 63122 V: 636-343-8518 F: 636-343-5119
Web: http://www.crmagnetics.com
42
E-mail: sales@crmagnetics.com
Loop-Powered AC Voltage Transmitter
DIN RAIL / PANEL MOUNT, AVERAGE RMS
SPECIFICATIONS
Basic Accuracy:........................ 0.5%
Calibration:........... Average Sensing, RMS Calibrated
Thermal Drift:............................ 500 PPM/°C
Operating Temperature:............ 0°C to + 60°C
Installation Category:................ CAT II
Vibration Tested To:.................. IEC 60068-2-6,1995
Pollution Degree:....................... 2
Response Time: ...................... 250 ms
Altitude:..................................... 2000 meter max.
Insulation Voltage:.................... 2500 VDC
Supply Voltage:.................Loop Powered 24 Vdc ±10%
Cleaning:.................. Water-dampened cloth
MTBF:....................... Greater than 100 K hours
Frequency Range:.... 20 Hz - 400 Hz
Typical Load:............. 0 - 300 Ω @ 24 VDC
Relative Humidity:..... 5% to 95%, Non-Condensing
Torque Specs.:........... 3.0 inch lbs. (0.4Nm)
Weight:....................... 0.5 lbs.
+
1
2
3
4
INPUT 1
Vdc
+
9
8
7
6
5
INPUT 2
+
Vdc
+
-
OUTPUT 2
-
OUTPUT 1
-
SUPPLY
Two Element 4 - 20 mADC Output
CR4640
[62.1]
2.45
[5.6]
.22
TYP
-
+
1
2
3
4
INPUT 1
OUTPUT 1
9
8
7
6
5
+
Vdc
-
SUPPLY
[88.7]
3.49
CR4620 One Element with External Voltage
Transformers * *
CR4620 CR4620
+
1
2
3
4
INPUT 1
INPUT 2
[30.4]
1.20
[28.3]
1.12
End View
9
8
7
6
5
Vdc
+ - +
Vdc
+
OUTPUT 2
OUTPUT 1
-
-
-
SUPPLY
CR4640 Two Element with External Voltage
Transformers * *
[36.6]
1.44
OUTLINE DRAWING
CONNECTION DIAGRAM
* * USE CR MAGNETICS LOW AND MEDIUM VOLTAGE POTENTIAL TRANSFORMERS (SECTION G)
NOTE: The building installation must have a switch or circuit-breaker that is in close proximity and within easy reach of the operator. The switch or circuit
breaker shall be marked as the disconnecting device for the equipment.
The Professional
Energy Monitoring
Company
M N TI
ISO 9001:2008 Quality Management System
3500 Scarlet Oak Blvd. St. Louis MO USA 63122 V: 636-343-8518 F: 636-343-5119
Web: http://www.crmagnetics.com
43
E-mail: sales@crmagnetics.com
Transducers
[83.3]
3.28
-
One Element4 - 20 mADC Output
CR4620
DIN RAIL
MOUNTING
CLIP
[73.1]
2.88
+
SUPPLY
[26.6]
1.05
[3.3]
.13
Optional
Mounting
OUTPUT 1
9
8
7
6
5
Top View
C
-
+
1
2
3
4
INPUT 1
很抱歉,暂时无法提供与“CR4620-50”相匹配的价格&库存,您可以联系我们找货
免费人工找货