1000 Eaton Boulevard
Cleveland, OH 44122
United States
SmartPro 120V 2000VA 1920W Line-Interactive
Sine Wave UPS, 2U, Extended Run, LCD, USB,
DB9, 8 Outlets
MODEL NUMBER: SMART2000RMXL2U
Highlights
●
Protects equipment against
blackouts, brownouts,
overvoltages, surges and line
noise
●
Keeps AC power running during
blackouts to allow time for file
saves and safe shutdown
●
Maintains continuous 120V
nominal output during
brownouts and overvoltages
●
Enhanced 0.96 power factor
increases system efficiency and
reduces your energy costs
●
Compatible with optional
external battery pack for
extended runtime operation
Applications
●
Protect your small network
server and other network
components against power
surges, line noise, brownouts,
overvoltages and blackouts
Rack-mount UPS offers complete power protection for small network applications, including telecom,
security and digital signage.
●
Operate essential equipment
during short-term power outages
using battery backup power
Features
●
Shut down desktop PCs and
other equipment without data
loss during long-term power
outages
●
Connect high-end security
systems, casino gaming
machines or digital signage in a
small network
●
Extend runtime for DVRs,
wireless routers and other lowpower home network equipment
2000VA/1920W/120V Battery Backup for PC Networks, Security Systems or Digital SignageThe
SmartPro® line-interactive SMART2000RMXL2U UPS system with AVR provides reliable battery backup
and AC power protection against blackouts, brownouts, overvoltages, surges and line noise that can
damage valuable electronics or destroy data. The eight-outlet 120V battery backup with an enhanced 0.96
power factor is ideal protection for small networks, wiring closets, security systems, telecom, high-end PC
gaming, digital signage equipment and other professional applications, including retail, casino and
hotel/motel management.
Allows Time to Back Up Critical Files During a Blackout Backup support allows you to work through
short power failures and gives you enough time to safely save files and shut down your system in case of
a prolonged blackout. Backup time varies according to load, but the line-interactive UPS system should
keep a half load (960W) powered as long as 12 minutes and a full load (1920W) up to 4.5 minutes.
Supports an External Battery Pack for Extended RuntimeIn addition to the user-replaceable internal
battery, the SMART2000RMXL2U supports connection of external battery packs, such as BP48V24-2U,
BP48V60RT-3U and BP48V27-2US (sold separately). During normal operation, incoming utility power
keeps the internal and external batteries fully charged, so backup power will always be available. Output
is reduced to 1600W maximum with external battery packs.
8 NEMA Outlets Protect Your Connected ComponentsFour 5-15R and four 5-15/20R outlets provide
battery backup, 570 joules of surge protection and voltage regulation for your crucial components. Two
independently switched single-outlet load banks (one 5-15R and one 5-15/20R) enable both scheduled
and real-time remote rebooting and load shedding.
Automatic Voltage Regulation (AVR) Corrects Low- and High-Voltage ConditionsAVR protects your
equipment from incremental hardware damage, data loss and performance problems caused by
brownouts and overvoltages. The SMART2000RMXL2U can correct brownouts as low as 83V and
overvoltages as high as 145V back to nominal 120V power continuously, all while keeping the battery fully
charged and ready to take over in case of power failure.
1/6
Package Includes
●
SMART2000RMXL2U 120V
2000VA 1920W Line-Interactive
UPS with 8 Outlets
●
USB cable
●
DB9 cable
●
EPO cable
●
Rack-mounting hardware
●
Owner’s manual
1000 Eaton Boulevard
Cleveland, OH 44122
United States
Combats Line Noise That Can Harm EquipmentEMI (electromagnetic interference) and RFI (radio
frequency interference) are common causes of performance problems and can lead to incremental
hardware damage, data corruption and audio/video transmission problems. The SMART2000RMXL2U
filters out this disruptive line noise on the AC line, so that it won't affect your equipment.
Designed for High Efficiency to Help You Save Money and Protect the EnvironmentA 96% efficiency
rating reduces BTU emissions, energy consumption and, ultimately, your energy costs.
Silenceable Alarm and Easy-to-Read LCD Keep You Informed Around the ClockThe LCD screen
features seven selectable screens of detailed UPS and site power data, as well as advanced user setup
and operating preferences. It rotates for comfortable viewing in both rack and tower configurations. The
audible alarm sounds for power failure, low battery and overloads. You may silence it using the built-in
switch or disable it.
Optional WEBCARDLX Network Interface Offers 24/7 AccessAn accessory slot accommodates the
optional Java-free HTML5-based WEBCARDLX interface (sold separately), which enables full remote
access for site power and UPS status monitoring, configuration, control and email notifications via secure
web browser, SNMP, telnet or SSH. It supports 10/100 Mbps auto-sensing for optimum communication
with an Ethernet network. Automated alerts help prevent accidental overloads, power loss and downtime.
Advanced Communications Ports Allow for Automatic Saves and ShutdownsRS-232 and HIDcompliant USB ports connect to a computer running free downloadable PowerAlert® software to enable
safe unattended file saves and system shutdown in case of a prolonged power failure. Cables are
included.
Versatile Installation OptionsHardware is included for mounting the SmartPro UPS system in 2U of
space in an EIA-standard 19-inch 4-post rack. Using optional mounting accessories (sold separately), you
can adapt the SMART2000RMXL2U for 2-post, front-rail, 4-post short-depth, tower or wall mounting. The
10-ft. (3.05 m) power cord with NEMA 5-20P plug connects to any compatible AC outlet.
Specifications
OVERVIEW
UPC Code
037332248152
UPS Type
Line-Interactive
INPUT
Input Phase
Single-Phase
Rated input current (Maximum Load)
16.0A
Nominal Input Voltage(s) Supported
120V AC
UPS Input Connection Type
5-20P
UPS Input Cord Length (ft.)
10
UPS Input Cord Length (m)
3.1
Recommended Electrical Service
20A 120V
OUTPUT
Output Capacity (VA)
2000
Output Capacity (kVA)
2
2/6
1000 Eaton Boulevard
Cleveland, OH 44122
United States
Output Capacity (Watts)
1920
Output Capacity (kW)
1.92
Output Capacity Details
Output is reduced to 1600 watts maximum when used with external battery packs
Power Factor
0.96
Nominal Voltage Details
120v nominal output in battery mode
Frequency Compatibility
60 Hz
Output Voltage Regulation (Line
Mode)
-14%, +6%
Output Voltage Regulation (Battery
Mode)
+/- 5%
Load Management Receptacles
Two switched single outlet load banks (1 5-15/20R & 1 5-15R)
Output AC Waveform (AC Mode)
Pure Sine wave
Output AC Waveform (Battery
Mode)
Pure Sine wave
Nominal Output Voltage(s)
Supported
110V; 115V; 120V
Output Receptacles
(4) 5-15R; (4) 5-15/20R
Individually Controllable Load Banks
Yes
BATTERY
Battery Type
Valve Regulated Lead Acid (VRLA)
Runtime Full Load (min.)
4.5 min. (1920W)
Runtime Half Load (min.)
12 min. (960W)
Expandable Runtime
Yes
Expandable Runtime Description
Maximum output capacity is 1600 watts when used with external battery packs
External Battery Pack Compatibility
BP48V24-2U (limit 1); BP48V60RT-3U (multi-pack compatible); BP48V272US (multi-pack compatible)
DC System Voltage (VDC)
48
Battery Recharge Rate (Included
Batteries)
Less than 4.5 hours from 10% to 90% (typical, full load discharge)
Battery Access
Front panel battery access door
Internal UPS Replacement Battery
Cartridge
RBC94-2U
Battery Replacement Description
Hot-swappable, user replaceable batteries
VOLTAGE REGULATION
Voltage Regulation Description
Automatic voltage regulation (AVR) maintains line power operation with an input voltage range of 83 to 145
Overvoltage Correction
Voltage reduction of 12% applies when input is between 127 and 145
3/6
1000 Eaton Boulevard
Cleveland, OH 44122
United States
Undervoltage Correction
Voltage boost of 12% applies when input voltage is between 96 and 108
Severe Undervoltage Correction
Voltage boost of 24% applies when input voltage is between 83 and 95
USER INTERFACE, ALERTS & CONTROLS
Front Panel LCD Display
Front panel LCD information and configuration screen offers detailed UPS and site power status and operating data,
plus configuration of voltage, operating mode, alarm function and a variety of additional options (see manual for
detailed LCD configuration and monitoring options)
Switches
3 pushbutton switches control OFF / ON power status, MODE selection and MUTE / ENTER control functions
Alarm Cancel Operation
Power-fail alarm can be temporarily silenced using alarm-cancel switch; silent mode alarm configuration option
available
Audible Alarm
Audible alarm indicates UPS startup, power-failure, low-battery, overload, UPS fault and remote shutdown
conditions
SURGE / NOISE SUPPRESSION
UPS AC Suppression Joule Rating
570
UPS AC Suppression Response
Time
Instantaneous
EMI / RFI AC Noise Suppression
Yes
PHYSICAL
Primary Form Factor
Rackmount
Rack Height
2U
Cooling Method
Fan
Included Mounting Accessory
Description
Included 4POSTRAILKIT mounting bracket enables installation in 4 post racks from 20.5 to 36 inches (521 to
914mm)
Installation Form Factors Supported
with Included Accessories
4 post 19 inch rackmount
Installation Form Factors Supported
with Optional Accessories
2 post rackmount ( 2POSTRMKITWM ); 2-4 post front rail
rackmount ( UPSHDEARKIT ); 4 post rackmount short-depth ( 4POSTRAILKITWM ); Tower ( 29USTAND ); Wallmount ( 2POSTRMKITWM )
Minimum Required Rack Depth (cm)
58.42
Minimum Required Rack Depth
(inches)
23
Minimum Required Rack Depth with
External Battery Pack (cm)
67
Minimum Required Rack Depth with
External Battery Pack (in.)
26.5
Minimum Required Rack Depth
without External Battery Pack (cm)
62
Minimum Required Rack Depth
without External Battery Pack (in.)
24.5
4/6
1000 Eaton Boulevard
Cleveland, OH 44122
United States
Optional Mounting Accessory Notes
Optional 2-9USTAND enables upright tower UPS placement; 2POSTRMKITWM enables wall-mount and 2-post rackmount installation;
4POSTRAILKITWM enables installation in 4-post short-depth
racks from 14.5 to 23.5 inches (368 to 597mm); UPSHDEARKIT enables installation in 2 or 4-post
racks using front vertical rails only, without rear support
Primary UPS Depth (mm)
490
Primary UPS Height (mm)
88
Primary UPS Width (mm)
440
Shipping Dimensions (hwd / in.)
8.50 x 24.30 x 21.60
Shipping Weight (kg)
35.47
UPS Housing Material
Steel
UPS Power Module Dimensions
(hwd, in.)
3.46 x 17.32 x 19.29
UPS Power Module Weight (kg)
26.13
UPS Power Module Weight (lbs.)
57.6
Unit Weight (lbs.)
57.600
Unit Weight (kg)
26.13
ENVIRONMENTAL
Operating Temperature Range
32° to 104°F (0° to 40°C)
Storage Temperature Range
5° to 122°F (-15° to 50°C)
Relative Humidity
0 to 95%, non-condensing
AC Mode BTU / Hr. (Full Load)
306
AC Mode Efficiency Rating (100%
Load)
96%
Battery Mode Heat Dissipation
(BTU/Hr) @ Full Load
1157
Audible Noise
45 dBA maximum, front side 1m
COMMUNICATIONS
Network Management Cards
WEBCARDLXE
Network Monitoring Port Description
Supports detailed monitoring of UPS and site power conditions
PowerAlert Software
For local monitoring via the UPS’s built-in communication ports, download PowerAlert software at
https://tripplite.eaton.com/products/power-alert
Communications Cable
USB and DB9 cabling included
WatchDog Compatibility
Supports Watchdog application, OS and hard-reboot restart options for remote applications
Network UPS Tools (NUT)
Compatibility
NUT compatible. See a full list of NUT compatible Tripp Lite UPS systems at https://networkupstools.org/stablehcl.html?manufacturer=Tripp%20Lite
5/6
1000 Eaton Boulevard
Cleveland, OH 44122
United States
Network Management Card
Description
Network management card optional
Communications Interface
DB9 Serial; EPO (emergency power off); Slot for SNMP/Web interface; USB (HID enabled)
LINE / BATTERY TRANSFER
Transfer Time
5 milliseconds (line to battery mode); 1 millisecond (battery to line mode)
Low Voltage Transfer to Battery
Power (Setpoint)
83
High Voltage Transfer to Battery
Power (Setpoint)
145
FEATURES & SPECIFICATIONS
Cold Start (Startup in Battery Mode
During a Power Failure)
Cold-start operation supported
High Availability UPS Features
Auto Probe Monitoring and Reboot (requires WEBCARDLX); Automatic Voltage Regulation (AVR); Hot swappable
batteries; Remote management; Surge/noise protection
Green Energy-Saving Features
Greater than 95% efficiency - GREEN UPS; Individually controllable load banks
Grounding Details
Back panel grounding lug
APPLICATIONS
UPS Applications
Large Network
STANDARDS & COMPLIANCE
Product Certifications
CSA (Canada); NOM (Mexico); UL 1778
Product Compliance
RoHS; FCC Part 15 Class A (USA)
WARRANTY & SUPPORT
Product Warranty Period
(Worldwide)
2-year warranty, 3 year with registration. Note: Registration is required for 3-year
warranty.
Connected Equipment Insurance
(U.S., Canada & Puerto Rico)
$250,000 Ultimate Lifetime
Insurance
© 2023 Eaton. All Rights Reserved.
Eaton is a registered trademark. All other trademarks
are the property of their respective owners.
6/6