MEDIUM VOLTAGE DIN Fuse-Links
MV DIN
12kV, Current Limiting Back-Up Fuse-Links, 6.3 to 200 Amps
Standards/Approvals:
DIN 43625, VDE 0670 part 4, VDE 0670 part
402 and IEC 60282-1 (2005)
Description:
Catalogue Symbol:
12TDLEJ(amp)
12THLEJ(amp)
12TKLEJ(amp)
12TXLEJ(amp)
12TFMSJ(amp)
Class of Operation:
Dimensional Data:
Fuse Reference
Back-up as IEC 60282-1 (2005)
A
C
D
Weight (Kg)
64
2.6
TDLEJ
292
54
51
TKLEJ
292
80
76
THLEJ
292
TXLEJ
67
292
TFMSJ
88
442
1.7
3.5
88
80
3.7
76
5.1
EJ Outline
E = Spring Striker 80N to IEC 60282-1 designation “medium”
Force x Travel diagram for 80N Din striker
100
All fuse-links are packed individually.
MOQ: 3
Packaging 100% recyclable
Technical Data:
DIN fuse-links
12kV
Rated voltage:
Amps:
6.3A to 200A
Rated breaking capacity: 50kA
Rated frequency:
50 - 60Hz
Suitable for outdoor and indoor use
RoHS compliant
S = Spring Striker 50N to DIN 43625 and IEC 60282-1
designation “medium”
Force x Travel diagram for 50N Din striker
60
90
50
80
70
40
60
Force (N)
Force (N)
Packaging:
SJ Outline
Striker Diagrams:
50
30
40
20
30
20
10
10
0
A range of medium voltage DIN Fuses,
complete with sealed striker, suitable for
transformer protection. The fuses can be
used even where there is no secondary LV
protection, provided they are used with fuse
switches fitted with instantaneous striker
tripping.
0
4
8
12
16
20
Travel (mm)
24
28
32
36
0
0
REV B - 10/4/2007
4
8
12
16
Travel (mm)
20
24
28
32
Form No. 12kV DIN
Page 1 of 13
Data sheet 720104
MEDIUM VOLTAGE DIN Fuse-Links
MV DIN
12kV, Current Limiting Back-Up Fuse-Links, 6.3 to 200 Amps
Table of Ratings:
Standard Approvals:
Technical Data:
Part Number
In (A)
6.3
12TDLEJ16
16
12TDLEJ20
12TDLEJ25
12TDLEJ31.5
12TDLEJ40
12TDLEJ50
12TDLEJ63
12THLEJ80
12TFMSJ160
63
63
80
87
31.2
235
36
47
10.6
60
7.81
72
5.74
85
3.99
610
93
4.30
217
5.74
85
3.80
272
50
28
13.5
560
63
24
17.2
687
485
Minimum PreArcing
18
23.4
388
Joule Integral (I2t)
16
39.1
272
63
* Not compliant with VDE 0670 part 402
16
63
63
160
54.6
131
168
63
100
53
143
63
200
10
63
63
125
222
111
63
W
23
73
63
50
160
12THMEJ100
63
40
mΩ
35
63
31.5
12TXLEJ160*
12TXLEJ200*
63
25
Cold Resistance
& Watts Loss in
Free Air
I3 (A)
63
20
100
12TKLEJ125
I1 (kA)
10
12THLEJ100
Minimum
Breaking
Capacity
Breaking
Capacity
Current Rating
12TDLEJ6.3
12TDLEJ10
DIN 43625, VDE 0670 part 4, VDE 0670 part 402 and IEC 60282-1 (2005)
6.3, 10, 16, 20. 25, 31.5, 40, 50, 63, 80, 100, 125, 160 and 200 Amps
333
3.65
139
Length
Diameter
Weight
292
51
1.7
292
51
1.7
mm
Maximum
Operating
9.8 X 101
2.8 X 102
1.0 X 103
2.3 X 103
2.6 X 102
5.2 X 102
292
3.9 X 103
5.4 X 103
8.1 X 102
1.4 X103
7.9 X 103
2.0 X 104
4.0 X 104
1.1 X 105
1.5 X 105
2.0 X 104
5.0 X 104
1.7
51
292
1.7
51
292
1.7
51
292
1.7
64
292
2.6
64
292
2.6
76
292
3.5
88
292
1.4 X 105
3.5 X 105
1.7
51
292
5.0 X 105
6.5 X 105
1.7
51
292
9.1 X 104
1.4 X 105
3.5 X 105
1.7
51
292
2.5 X 104
3.1 X 104
4.7 X 104
kg
51
292
8.4 X 103
1.5 X 104
2.4 X 103
2.8 X 103
4.3 X 103
mm
3.7
88
442
3.7
64
442
3.7
76
5.1
Cross-Reference
MESA
12TDLEJ6.3
12TDLEJ10
12TDLEJ16
12TDLEJ20
12TDLEJ25
12TDLEJ31.5
12TDLEJ40
12TDLEJ50
12TDLEJ63
67120.0060
67120.0100
67120.0160
67120.0200
67120.0250
67120.0320
67120.0400
67120.0500
67120.0630
3000413
3000413
3000413
3000413
3000413
3000413
3000413
3000413
3001213
CF-12/6,3
CF-12/10
CF-12/16
CF-12/20
CF-12/25
CF-12/31,5
CF-12/40
CF-12/50
CF-12/63
12TXLEJ160
12TXLEJ200
67220.1600
67220.2000
3002013
3002014
N/A
N/A
12THLEJ80
12THLEJ100
12TKLEJ125
67120.0800
67120.1000
67120.1250
3001213
3001213
3001213
(80N Striker)
(50N Striker)
4236014
4236015
4236016
42350014
42350015
42350016
4236005
4236006
4236007
4236008
4236009
4236010
4236011
4236012
4236013
CF-12/80
CF-12/100
N/A
Watts Loss Comparison
4235005
4235006
4235007
4235008
4235009
4235010
4235011
4235012
4235013
4236017
N/A
4235017
N/A
51006 511 M0
51006 512 M0
51006 513 M0
51006 514 M0
51006 515 M0
51006 516 M0
51006 517 M0
51006 518 M0
51006 519 M0
ES 6509 006
ES 6509 010
ES 6509 016
ES 6509 020
ES 6509 025
ES 6509 030
ES 6509 040
ES 6509 050
ES 6509 063
IB-D1
IB-D1
IB-D1
IB-D1
IB-D1 & IB-D2
IB-D1 & IB-D2
IB-D1 & IB-D2
IB-D2
IB-D2
1YMB531042M0001
1YMB531042M0002
1YMB531042M0003
1YMB531042M0004
1YMB531002M0004
1YMB531002M0014
1YMB531002M0005
1YMB531002M0006
1YMB531002M0007
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
51006 520 M0
51006 521 M0
N/A
ES 6509 080
ES 6509 100
N/A
IB-D3
IB-D3
N/A
1YMB531002M0021
1YMB531002M0022
1YMB531043M0010
Lowest Watts Loss
Part Number
Watts Loss
Watts Loss
Watts Loss
MESA Watts
loss
Watts Loss
Watts Loss
Watts Loss
Watts Loss
12THLEJ80
12THLEJ100
12TKLEJ125
72
85
93
82
96
117
76
104
159
102
120
-
77
104
152
102
120
-
108
112
-
95
120
-
12TDLEJ6.3
12TDLEJ10
12TDLEJ16
12TDLEJ20
12TDLEJ25
12TDLEJ31.5
12TDLEJ40
12TDLEJ50
12TDLEJ63
12TXLEJ160
12TXLEJ200
10
16
16
18
24
28
36
47
60
217
333
* derating factor apply
19
29
21
25
31
39
46
62
60
217
333
14
23
28
23
29
38
50
56
63
173
292*
16
18
37
42
52
59
74
70
82
-
15
10
19
23
33
46
56
44
65
200
-
16
18
37
42
52
59
74
70
82
-
19
18
35
36
38
41
56
74
89
-
12
19
27
28
29
36
50
52
64
-
Watts Loss
46
25
34
38
47
41
52
70
78
82
101
125
-
Form No. 12kV DIN
Page 2 of 13
Data sheet 720104
DRN
APPD
DATE
VIRTUAL PRE-ARCING TIME IN SECONDS
0.01
0.1
1
10
100
1000
10000
10
APPD
DATE
DRN
FUSE TYPES: TXL
DRN
DATE
10/4/07
MPJ
RE-DRAWN ON EXCEL. ECN11268
APPD
TEL. 01509 882600 FAX 01509 882786
PF 1197
100000
12kV, Current Limiting Back-Up Fuse-Links, 6.3 to 200 Amps
BURTON-ON-THE-WOLDS LEIC, LE12 5TH, UK.
100
1000
10000
R.M.S. SYMMETRICAL PROSPECTIVE CURENT IN AMPERES
B
200A
160A
CURVES RELATE TO MEAN PRE_ARCING TIMES WITH A TOLERANCE OF ±10% ON CURRENT
TIME- CURRENT CHARACTERISTIC
FOR 12kV FUSE-LINKS
MEDIUM VOLTAGE DIN Fuse-Links
MV DIN
Time Current Characteristics
Form No. 12kV DIN
Page 3 of 13
Data sheet 720104
DATE
DRN
MBC added ECN11268
26/3/07
MPJ
0.01
0.1
1
10
100
1000
10000
C
10
DATE
DRN
26/3/07
MPJ
Update ECN11237
APPD
B
HH
21/3/07
1st ISSUE ECN11220
APPD
A
BURTON-ON-THE-WOLDS LEIC, LE12 5TH, UK.
1000
10000
TEL. 01509 882600 FAX 01509 882786
R.M.S. SYMMETRICAL PROSPECTIVE CURENT IN AMPERES
DATE
DRN
100
6.3A
10A
16A
20A
25A
31.5A
40A
50A
63A
80A
100A
125A
CURVES RELATE TO MEAN PRE_ARCING TIMES WITH A TOLERANCE OF ±10% ON CURRENT
PF 1275
100000
FUSE TYPES: TDL/THL/TKL
12kV, Current Limiting Back-Up Fuse-Links, 6.3 to 200 Amps
APPD
VIRTUAL PRE-ARCING TIME IN SECONDS
TIME- CURRENT CHARACTERISTIC
FOR 12kV FUSE-LINKS
MEDIUM VOLTAGE DIN Fuse-Links
MV DIN
Time Current Characteristics
Form No. 12kV DIN
Page 4 of 13
Data sheet 720104
APPD
DATE
DRN
VIRTUAL PRE-ARCING TIME IN SECONDS
0.01
0.1
1
10
100
1000
10000
10
16/4/07
MPJ
M LENGTH ONLY ECN11268
APPD
DATE
DRN
B
HH
21/3/07
1st ISSUE ECN11220
APPD
A
BURTON-ON-THE-WOLDS LEIC, LE12 5TH, UK.
1000
TEL. 01509 882600 FAX 01509 882768
R.M.S. SYMMETRICAL PROSPECTIVE CURENT IN AMPERES
DATE
DRN
100
100A (THM)
125A (TKM)
160A (TFM)
10000
100000
FUSE TYPES: THM / TKM / TFM
CURVES RELATE TO MEAN PRE_ARCING TIMES WITH A TOLERANCE OF ±10% ON CURRENT
TIME- CURRENT CHARACTERISTIC
FOR 12kV FUSE-LINKS
PF 1280
MEDIUM VOLTAGE DIN Fuse-Links
12kV, Current Limiting Back-Up Fuse-Links, 6.3 to 200 Amps
MV DIN
Time Current Characteristics
Form No. 12kV DIN
Page 5 of 13
Data sheet 720104
MEDIUM VOLTAGE DIN Fuse-Links
MV DIN
12kV, Current Limiting Back-Up Fuse-Links, 6.3 to 200 Amps
Cut-Off Curves
REF. No. PF 2275
CUT-OFF CURRENT
CHARACTERISTIC
FOR 12kV FUSE-LINKS
FUSE TYPE
TDL/THL/TKL
NOTES
1. CURVES SHOW EXTREME MAXIMUM VALUES WHICH WILL NOT BE EXCEEDED UNDER CONDITIONS STATED IN 2
AND 3 BELOW.
2. FOR HIGH VALUES OF PROSPECTIVE CURRENT A SYMMETRICAL FAULT GIVES THE HIGHEST CUT-OFFCURRENT.
FOR LOW VALUES OF PROSPECTIVE CURRENT, WHERE THERE IS LITTLE OR NO CURRENT LIMITATION, AN
ASYMMETRICAL FAULT PASSES THE HIGHEST PEAKCURRENT. THE CURVES ARE THEREFORE BASED ON THE
DEGREE OF ASYMMETRY WHICH GIVES THE MAXIMUM CUT-OFF CURRENT AT ANY PARTICULAR VALUE OF
PROSPECTIVE CURRENT.
3. CURVES RELATE TO FREQUENCY OF 50 Hz AND A RECOVERY VOLTAGE EQUAL TO THE FUSE RATED VOLTAGE.
100000
PEAK CUT-OFF CURRENT IN AMPERE S
40A
63A
80A
100A
20A
25A
125A
10000
1000
10A
6.3A
100
100
DRN
DATE
APPD
50A
C
1000
16A
31.5A
10000
100000
R.M.S. SYMMETRICAL PROSPECTIVE CURRENT IN AMPERES
DRN
DATE
APPD
B
DRN MPJ
DATE 21/3/07
APPD
1st ISSUE
MPJ ECN11220
A
PF2275
BURTON-ON-THE-WOLDS, LEICS., LE12 5TH, U.K. TEL +44 (0) 1509 882600
FAX +44 (0) 1509 882786
Form No. 12kV DIN
Page 6 of 13
Data sheet 720104
MEDIUM VOLTAGE DIN Fuse-Links
MV DIN
12kV, Current Limiting Back-Up Fuse-Links, 6.3 to 200 Amps
Cut-Off Curves
REF. No. PF 2280
CUT-OFF CURRENT
CHARACTERISTIC
FOR 12kV FUSE-LINKS
FUSE TYPE
THM TKM TFM
NOTES
1. CURVES SHOW EXTREME MAXIMUM VALUES WHICH WILL NOT BE EXCEEDED UNDER CONDITIONS STATED IN 2
AND 3 BELOW.
2. FOR HIGH VALUES OF PROSPECTIVE CURRENT A SYMMETRICAL FAULT GIVES THE HIGHEST CUT-OFFCURRENT.
FOR LOW VALUES OF PROSPECTIVE CURRENT, WHERE THERE IS LITTLE OR NO CURRENT LIMITATION, AN
ASYMMETRICAL FAULT PASSES THE HIGHEST PEAKCURRENT. THE CURVES ARE THEREFORE BASED ON THE
DEGREE OF ASYMMETRY WHICH GIVES THE MAXIMUM CUT-OFF CURRENT AT ANY PARTICULAR VALUE OF
PROSPECTIVE CURRENT.
3. CURVES RELATE TO FREQUENCY OF 50 Hz AND A RECOVERY VOLTAGE EQUAL TO THE FUSE RATED VOLTAGE.
100000
PEAK CUT-OFF CURRENT IN AMPERE S
100A (THM)
160A (TFM)
10000
1000
100
100
DRN
DATE
APPD
125A (TKM)
C
1000
10000
100000
R.M.S. SYMMETRICAL PROSPECTIVE CURRENT IN AMPERES
DRN MPJ
DATE 16/4/07
APPD
B
M LENGTH ONLY
MPJ ECN11268
DRN MPJ
DATE 21/3/07
APPD
1st ISSUE
MPJ ECN11220
A
PF2280
BURTON-ON-THE-WOLDS, LEICS., LE12 5TH, U.K. TEL +44 (0) 1509 882600
FAX +44 (0) 1509 882786
Form No. 12kV DIN
Page 7 of 13
Data sheet 720104
MEDIUM VOLTAGE DIN Fuse-Links
MV DIN
12kV, Current Limiting Back-Up Fuse-Links, 6.3 to 200 Amps
Cut-Off Curves
REF. No. PF 2197
CUT-OFF CURRENT
CHARACTERISTIC
FOR 12kV FUSE-LINKS
FUSE TYPE
TXL
NOTES
1. CURVES SHOW EXTREME MAXIMUM VALUES WHICH WILL NOT BE EXCEEDED UNDER CONDITIONS STATED IN 2
AND 3 BELOW.
2. FOR HIGH VALUES OF PROSPECTIVE CURRENT A SYMMETRICAL FAULT GIVES THE HIGHEST CUT-OFFCURRENT.
FOR LOW VALUES OF PROSPECTIVE CURRENT, WHERE THERE IS LITTLE OR NO CURRENT LIMITATION, AN
ASYMMETRICAL FAULT PASSES THE HIGHEST PEAKCURRENT. THE CURVES ARE THEREFORE BASED ON THE
DEGREE OF ASYMMETRY WHICH GIVES THE MAXIMUM CUT-OFF CURRENT AT ANY PARTICULAR VALUE OF
PROSPECTIVE CURRENT.
3. CURVES RELATE TO FREQUENCY OF 50 Hz AND A RECOVERY VOLTAGE EQUAL TO THE FUSE RATED VOLTAGE.
100000
PEAK CUT-OFF CURRENT IN AMPERE S
160A
10000
1000
100
100
DRN
DATE
APPD
200A
C
1000
10000
100000
R.M.S. SYMMETRICAL PROSPECTIVE CURRENT IN AMPERES
DRN
DATE
APPD
B
DRN MPJ
DATE 20/4/07
APPD
1st ISSUE
MPJ ECN11268
A
PF2197
BURTON-ON-THE-WOLDS, LEICS., LE12 5TH, U.K. TEL +44 (0) 1509 882600
FAX +44 (0) 1509 882786
Form No. 12kV DIN
Page 8 of 13
Data sheet 720104
MEDIUM VOLTAGE DIN Fuse-Links
12kV, Current Limiting Back-Up Fuse-Links, 6.3 to 200 Amps
MV DIN
ASTA Certificate
Form No. 12kV DIN
Page 9 of 13
Data sheet 720104
MEDIUM VOLTAGE DIN Fuse-Links
12kV, Current Limiting Back-Up Fuse-Links, 6.3 to 200 Amps
MV DIN
KEMA Certificate
Form No. 12kV DIN
Page 10 of 13
Data sheet 720104
MEDIUM VOLTAGE DIN Fuse-Links
12kV, Current Limiting Back-Up Fuse-Links, 6.3 to 200 Amps
MV DIN
KEMA Certificate
Form No. 12kV DIN
Page 11 of 13
Data sheet 720104
MEDIUM VOLTAGE DIN Fuse-Links
12kV, Current Limiting Back-Up Fuse-Links, 6.3 to 200 Amps
MV DIN
KEMA Report
This report of performance details 12kV DIN rated fuse-links tested in accordance with IEC60282-1:2005 to
demonstrate correct operation on a 7.2kV system
Form No. 12kV DIN
Page 12 of 13
Data sheet 720104
MEDIUM VOLTAGE DIN Fuse-Links
12kV, Current Limiting Back-Up Fuse-Links, 6.3 to 200 Amps
MV DIN
KEMA Report
This report of performance details tests to IEC60282-1:2005 clause 7.6.3 to demonstrate the fuse-links ability
to withstand arcing for greater than 0.1 seconds
Form No. 12kV DIN
Page 13 of 13
Data sheet 720104