SLD Series
The SLD Series is designed to protect 3-phase equipment against
PHASE UNBALANCE, PHASE LOSS, UNDER VOLTAGE and PHASE
REVERSAL conditions.
OPERATION
With normal operating voltage present on all three phases in the proper
phase sequence, the internal relay will energize (PICK-UP). When an
incorrect phase sequence or phase loss occurs or the three-phase line
voltages fall outside the preset unbalance or under voltage settings, the
internal relay will de-energize (DROP-OUT). When all conditions return
to normal, the relay will reset.
The Adjustable Release Delay is provided to ignore momentary voltage
fluctuations that cause nuisance tripping.
Both Delta and Wye systems may be monitored. In Wye Systems,
connections to neutral are not required.
NOTE: When a phase is lost while the motor is running, a condition
known as regeneration occurs where a voltage is induced into the open
phase nearly equal in magnitude to the normal phase-to-phase voltage.
The SLD series is designed to detect this condition when properly
adjusted.
STYLE "E"
STYLE "A"
IND. CONT. EQ.
496Y
Phase & Under Voltage Monitor
DIMENSIONS (INCHES)
PHASE VOLTAGE MONITORS
The SLD Series is UL Listed under UL File Number E55826.
SPECIFICATIONS
OPERATING
VOLTAGE
See Table Below
TRANSIENT
PROTECTION
1000 Volts For 8 mSEC
RESET
Automatic
PHASE SEQUENCE
ABC (will not operate CBA)
PHASE UNBALANCE 2% to 10%, Adjustable
RANGE
INDICATORS LED
STYLE "A"
Glows When All Conditions Are Normal
RESPONSE TIMES Operate
Release
30 mSEC
0.1 to 20 SEC, Adjustable (on
Under Voltage only); 100 mSEC on
Phase Reversal and Unbalance
TEMPERATURE
RATING
32° to +131°F (0° to +55°C)
-49° to 185°F (-45° to +85°C)
Operate
Storage
STYLE "E"
WIRING
U.S. PATENT 4,331,995
NUMBER
WEIGHT
MODEL
NUMBER
13.5 oz.
OPERATING
VOLTAGE
UNDER VOLTAGE
DROPOUT RANGE
POWER
REQUIRED
HYSTERESIS
SLD-120-ASA
120 VAC
95-115 Adj.
2.5 VAC
SLD-230-ASA 208/240 VAC
185-230 Adj.
3 VA Max.
5.0 VAC
SLD-380-ASA
380 VAC
315-390 Adj.
10 VAC
SLD-440-ASA 440/480 VAC
370-460 Adj.
SLD-120-ALE
120 VAC
95-115 Adj.
5 VAC
SLD-230-ALE 208/240 VAC
185-230 Adj.
SLD-380-ALE
380 VAC
315-390 Adj.
7 VA Max
10 VAC
SLD-440-ALE 440/480 VAC
370-460 Adj.
All voltage referenced are phase-to-phase.
Diversified Electronics
800.727.5646
OUTPUT RATING
ENCLOSURE
SPDT, 10 Amp, Resistive @ 240 VAC
1/2 HP @ 240 VAC
A
DPDT, 5 Amps, Resistive; 345 VA,
Inductive @ 240 VAC
DPDT, 3 Amps, Resistive; 360 VA,
Inductive @ 600 VAC
E
atcdiversified.com
161