PROTECTS 3-PHASE EQUIPMENT
AGAINST:
• Under Voltage
• Over Voltage
• Phase Loss
• Phase Reversal
• Phase Unbalance
• Phase Shift
• Frequency Shift
SLM Series
• Models available up to 690 VAC
• Automatic or Manual Reset
• Delay-on-Make Timer
• LED Indicators for Fault
Conditions
• Last Fault Memory
SCREWDRIVER ADJUSTMENT FOR:
• Time Delay
• Voltage
• Mode of Operation
IND. CONT. EQ.
496Y
SPECIFICATIONS
VOLTAGE TRIP
POINTS
Drop-Out ±10% of Setting
Pick-Up ± 7% of Setting
Microprocessor Based
3-Phase Monitor
FREQUENCY TRIP Drop-Out ±4% of 60 Hz (380 V, 50 Hz)
POINTS
Pick-Up ±3% of 60 Hz (380 V, 50 Hz)
UNBALANCE TRIP Drop-Out 7%
POINTS
Pick-Up 5%
RESET
Automatic; Manual; Automatic with Memory*
DIMENSIONS (INCHES)
PHASE VOLTAGE MONITORS
PHASE SEQUENCE ABC (Will Not Operate CBA)
OUTPUT RATING DPDT, 360 VA Inductive; 1/2 hp
3 A Resistive @ 600 VAC
SLM (120, 230) ASE - DPDT, 470 VA 10A
Resistive@240VAC
TERMINATIONS
#8-32 Screw Terminals
INDICATORS Designation
Color
State
Condition
LED*
Time Delay
Green
Flashing Timing Output
Normal ON
Energized
*Automatic
with Memory
Under Voltage Red
ON
Fault
MODE: The
Over Voltage
Red
ON
Fault
last fault is
indicated and Phase Sequence, Red
ON
Fault
remains on
Shift
when condiFrequency Shift Red
ON
Fault
tions return
to normal.
Unbalance
Red
ON
Fault
WIRING
The indicator
Operate
extinguishes
Sampling 2 SEC
only with reset
or when new
Reset Delay (Sampling Delay) + (1.5 seconds
fault condition
to 5 minute Delay) Adjustable in one
occurs.
(1) minute increments
Release
Under Voltage
Over Voltage
Frequency Shift
Unbalance
*Phase
Loss/Shift
1.5 SEC, (approx.)
1.5 SEC, (approx.)
1.5 SEC, (approx.)
2.0 SEC, (approx.)
1.0 SEC, (approx.)
TEMPERATURE
RATING
32° to +131°F (0° to +55°C)
-49° to 185°F (-45° to +85°C)
Operate
Storage
POWER REQUIRED 7 VA Typical
TRANSIENT
PROTECTION
2500 Volts for 10 ms
ENCLOSURE
Lexan Surface Mounted
WEIGHT
22 oz.
Diversified Electronics
MODEL
NUMBER
NOMINAL
PHASE-TO-PHASE
VOLTAGE SET POINTS
MAXIMUM
VOLTAGE
SLM-120-ASE 105, 110, 115, 120, 125, 130 143 VAC
S LM-230-ASE 200, 210, 220, 230, 240, 250 275 VAC
SLM-380-ASE 350, 365, 380, 390, 400, 415 457 VAC
SLM-440-ASE 440, 450, 460, 470, 480, 490 540 VAC
SLM-575-ASE
525, 550, 575, 600
690 VAC
*Automatic with Memory MODE: The last fault is indicated and
remains on when conditions return to normal.
The indicator extinguishes only with reset or when new fault
condition occurs.
The SLM Series is UL Listed under UL File Number E55826.