Type TPCC-R
UL Class CC – Current Limiting
Branch Circuit Protection
Time Delay - 13/32”x 1-1/2”
For use as branch circuit protection in general
purpose, lighting, solenoid, control transformer and
motor applications. This fuse provides high current
limiting capabilities and a rejection style ferrule.
Electrical:
600VAC – 250mA -30A
300VDC -250mA -30A
Interrupt Ratings:
200,000A @ 600VAC (100mA-30A)
100,000A @ 300VDC (100mA-30A)
Agency Standards and Listings:
UL Listed to Standard 248-4 File 2137
CSA Certified Standard C22.2 No. 248.4
DC Listed to UL Standard 248
Mechanical Dimensions:
Warning:
www.optifuse.com
Part Number
TPCC-R-250mA
TPCC-R-500mA
TPCC-R-800mA
TPCC-R-1A
TPCC-R-1.125A
TPCC-R-1.25A
TPCC-R-1.4A
TPCC-R-1.5A
TPCC-R-1.6A
TPCC-R-1.8A
TPCC-R-2A
TPCC-R-2.25A
TPCC-R-2.5A
TPCC-R-2.8A
TPCC-R-3A
TPCC-R-3.2A
TPCC-R-3.5A
TPCC-R-4A
TPCC-R-4.5A
TPCC-R-5A
TPCC-R-5.6A
TPCC-R-6A
TPCC-R-6.25A
TPCC-R-7A
TPCC-R-7.5A
TPCC-R-8A
TPCC-R-9A
TPCC-R-10A
TPCC-R-12A
TPCC-R-15A
TPCC-R-17.5A
TPCC-R-20A
TPCC-R-25A
TPCC-R-30A
(619) 593-5050
Ampere Rating
250mA
500mA
800mA
1A
1.125A
1.25A
1.4A
1.5A
1.6A
1.8A
2A
2.25A
2.5A
2.8A
3A
3.2A
3.5A
4A
4.5A
5A
5.6A
6A
6.25A
7A
7.5A
8A
9A
10A
12A
15A
17.5A
20A
25A
30A
-Operation beyond the specified maximum ratings or improper use may result in damage and possible electrical
arcing and/or flame.
-Avoid contact of fuse with chemical solvent. Prolonged contact may damage the device performance.
Note: All specifications subject to change without notice.
Rev A 08/2008 - Page: 1/3
Code F02-01H
Type TPCC-R
UL Class CC – Current Limiting
Branch Circuit Protection
Time Delay - 13/32”x 1-1/2”
Motor
Full Load
Amperes
0.71 - 0.89
0.90 - 1.19
1.20 - 1.34
1.35 - 1.79
1.80 - 2.25
2.26 - 2.69
2.70 - 2.90
2.91 - 3.20
3.21 - 3.75
3.76 - 4.50
4.51 - 5.34
5.35 - 5.69
5.70 - 6.70
6.71 - 7.79
7.80 - 8.88
8.89 - 11.1
11.2 - 13.3
13.4 - 15.2
www.optifuse.com
(619) 593-5050
Fuse Rating*
Minimum
Duty
1.25
1.6
2
2.5
3
4
4
5
5
6
8
10
12
12
15
17.5
20
25
Maximum
Duty
1.6
2
2.5
3
4
5
6
6
7
8
10
12
12
15
17.5
20
25
30
* The National Electrical Code allows time-delay
Class CC fuses to be sized at up to 400% of
motor FLA, if needed.
Note: All specifications subject to change without notice.
Rev A 08/2008 - Page: 2/3
Code F02-01H
Type TPCC-R
UL Class CC – Current Limiting
Branch Circuit Protection
Time Delay - 13/32”x 1-1/2”
www.optifuse.com
(619) 593-5050
Time Current Curve Graph
Peak Let-Thru Current Graph
Note: All specifications subject to change without notice.
Rev A 08/2008 - Page: 3/3