Encore
Current to Voltage Transducer / Shunt
OVERVIEW
Verivolt Encore is part of the Verivolt family of current to voltage transducers designed to measure
isolated and ground currents. The main focus of the Encore family is to ease and accelerate measuring the output current from low voltage current sources as well as isolated current transformers
(CT). Particular attention was paid on providing a solution that minimizes cost and improves overall
performance on distributed systems such as substations, building monitoring, power distribution
systems, etc. The Encore series covers the ranges of ±0.1A, ±1A, ±2A, ±3A, ±4A and ±5A with customizable bandwidth of up to 40kHz and 0.2% accuracy
SPECIFICATION
Eletronical
0.1A
0.5A
1A
2A
3A
4A
5A
Scaling Factor (1V output
voltage)
1:1
5:1
10:1
20:1
30:1
40:1
50:1
0.5Arms
2.5Arms
5Arms
10Arms
15Arms
20Arms
25Arms
1Ω
200 mΩ
100 mΩ
50 mΩ
333 mΩ
25 mΩ
20 mΩ
Overload Current (60Hz
sinewave for 10s)
Input impedance at 60Hz
Output impedance
HARDWARE
DESCRIPTION
Verivolt Encore 5c operates as a current to voltage shunt that
generates a ±100mV range signal for it’s nominal input current
range. This signal can then be processed by a computer based
measurement platform. In conjunction with the EasyConnect family, the Encore is the ideal solution for high channel density applications
2k Ω
Accuracy
±0.2%
Bandwidth (-3dB point)
40kHz
Input-Output non-linearity
Output voltage
< 40 ppm/V
±100mV
Gain temperature drift
±25 ppm/°C
Phase mismatch
< 0.05°/kHz
Output type
Single-ended signal
Output impedance
< ±10μV
Output connector
BNC (Plug)
Functional Diagram of Encore
Environmental< ±10μV
Operating
temperature
– 35 to 70 °C
Storage
temperature
– 40 to 80 °C
Merchanical
Mounting example of Encore
Input connector (1-Pin Coaxial)
BNC
Outer Dimensions (Cylindrical
shape)
0.68”Ø x 3.0”
Weight
34 g (1.2 oz)
Due to its compact size and shape, the Encore can be easily
mounted anywhere between the signal source and the data acquisition system. The versions up to 5A may even be used inline
with the cable and not require any mounting at all.
All can be secured to fixtures using cable ties.
(1) Form factor can vary for customized solutions.
650 Washington St, San Francisco, CA 94111
(708) 374-8658
1
MERCHANICAL
DIMENSIONS
HARDWARE
CONFIGURATION
A. Connect BNC cable to sensor output. Make sure the BNC jack is connected to DAQ or at least properly
grounded.
A
Standards and Certifications
● CE
B. Make sure Input Signal cable is
de-energyzed to avoid arcing. Verify if
input connectors are clean. Plug input
signal into input connector of sensor.
C. Secure sensor to avoid accidental
disconnection during operation
C
B
DANGER
THIS SENSOR IS NOT A SAFETY DEVICE AND IS NOT INTENDED TO BE USED AS A SAFETY DEVICE. This sensor is designed only to detect and read certain data in an electronic manner and perform no use apart from that, specifically no safetyrelated use. This sensor product does not include self-checking redundant circuitry, and the
failure of this sensor product could cause either an energized or de-energized output condition, which could result in death, serious bodily injury, or property damage.