ENTUBE TE (500V 10V) 数据手册
Entube TE
Three Phase
Voltage Sensor
OVERVIEW
The Entube-TE series is designed for high quality three-phase measurements in a very compact
form factor without need for power supplies. This series covers the ranges of ±100V, ±200V,
±300V, ±400V, ±500V, ±750V and ±1000V, with up to 85kHz bandwidth and 0.2% accuracy.
The Entube-TE sensor operates as a differential divider network with an anti-aliasing filter on its
output. It generates a ±5V or ±10V scaled down version of the line-to-line and line-to-ground
voltage on its input terminals. Depending on the software configuration, the sensor outputs
phase-to-phase voltages for Delta configuration, or phase-to-ground for Wye configurations.
This signal can then be processed by most computer based measurement platforms.
One Entube-TE replaces 3 sensors, and only requires one cable for all three signals. This allows
for very high channel densities, while delivering high performance for a low cost.
SPECIFICATION
Entube TE
100V
Bandwidth (-3dB point)
200V
85kHz
Integrated sensor noise
(Referenced to input)
Gain
(Using 10V standard output voltage)
Input Impedance
500V
750V
25kHz
< 60μV
< 100 μV
< 130 μV
< 170 μV
< 220 μV
< 290 μV
10
20
30
40
50
75
100
25kΩ
33kΩ
20kΩ
20kΩ
50kΩ
HARDWARE
DESCRIPTION
1000V
< 30 μV
> 2 MΩ
Eletrical
25kΩ
The Entube-TE is a differential voltage down-converter designed
for 3-phase systems. It outputs all line-to-line and line-to-ground
signal pairs. Delta or Wye measurements can be made depending on the input configuration of the digitizer being used (NRSE
or Differential).
> 3 MΩ
15kΩ
Integrated sensor noise (Referenced to input)
Accuracy (percentage of
reading)
±0.2%
(±0.05% Typical)
Gain (Using 10V standard output voltage)
Max total phase shift at 60Hz
< 0.05°
Common mode rejection
±2000V
Withstanding differential mode
surge voltage
±1000V
Mounting Type
DIN Rail
Connectivity (Connector for
power in and signal out to/
from the sensor)
Input-Output non-linearity
Output voltage
Gain temperature drift
RJ45 Ethernet jack
< 250 ppm
±10V , ±5V
±50 ppm/°C
Differential input dynamic range
Signal Layout
Common mode rejection
52 dB
Power Supply Voltage
None
Output type
Output Offset Voltage
Mechanical
Weight
400V
50kHz
> 1 MΩ
Line Output Impedance
Outer Dimensions
300V
Single-ended signal
< ± 10µV
(on ±10V signal)
Environmental
Operating temperature
– 25 to 70 °C
Storage temperature
– 40 to 80 °C
1.4” x 1.4” x 4.5”
198 g (7.0 oz)
650 Washington St, San Francisco, CA 94111
(708) 374-8658
The three input phases connect to the sensor via a Spring-cage,
while the conditioned signals from the sensor come out on a standard Ethernet jack. The Entube-TE can be mounted anywhere
between the signal source and the data acquisition system. A
female-screw on the
low voltage side of the sensor allows for DIN rail mounting, and
serves as a safety ground.
A standard Ethernet cable is used to carry the conditioned signals
from the sensor. The orange, brown and blue pairs carry phase
voltages; the green connects to ground and DAQ reference.
To avoid limiting the signal bandwidth and to eliminate cross-talk
between pairs, a shielded STP Ethernet cable with a maximum
length of 100m (330’) should be used. This will keep good resolution beyond the 10th harmonic on a typical 60Hz system
1
MERCHANICAL
DIMENSIONS
HARDWARE
CONFIGURATION
A. Safely connect Data Acquistion
ground to ground of sensor.
A
Standards and Certifications
● CE
● RoHS Compliant
B. Securely connect one end of a
RJ45 to the output terminals, and the
other end to the inputs of your breakout board or data acquisition unit
C. Securely connect wire between the
source ofmeasurement and an available Entube TE’s input screw terminal.
C
B
DANGER
THIS SENSOR IS NOT A SAFETY DEVICE AND IS NOT INTENDED TO BE USED AS A SAFETY DEVICE. This sensor is designed only to detect and read certain data in an electronic manner and perform no use apart from that, specifically no safetyrelated use. This sensor product does not include self-checking redundant circuitry, and the
failure of this sensor product could cause either an energized or de-energized output condition, which could result in death, serious bodily injury, or property damage.
2
ENTUBE TE (500V 10V) 价格&库存
很抱歉,暂时无法提供与“ENTUBE TE (500V 10V)”相匹配的价格&库存,您可以联系我们找货
免费人工找货- 国内价格 香港价格
- 1+3804.735211+471.97564