Embedded Power for Business-Critical Continuity
LPS200-M Series
250 Watts
Total Power: Input Voltage: # of Outputs: 125 - 250 Watts 90 - 264 Vac Single
Rev. 7.9.09_#98 LPS200-M Series of 3
Special Features
• • • • • • • • • • • • • Medical and ITE safeties Active power factor correction 3” x 5” footprint Less than 1U high EN61000-3-2 compliant Remote sense Power fail Adjustable main output Built-in Class B EMI filter Overvoltage protection Overload protection Thermal overload protection Isolated 12V Fan output
Electrical Specifications
Input
Input range: Frequency: Inrush current: Efficiency: EMI/RFI: Power factor: Safety ground leakage current: 90 - 264 Vac; 120 - 300 Vdc 47-63 Hz 50 A max., cold start @ 25 °C 86% typical at full load FCC Class B conducted; CISPR22 Class B conducted; EN55022 Class B conducted; VDE0878PT3 Class B conducted 0.99 typical 2 75 uA @ 50/60 Hz, 264 Vac input
Output
125 W for convection (100 W for LPS202-M) ; 250 W (200 W for LPS202-M) with 30CFM forced air Adjustment range: ±10% minimum on the main outputs Fan output: 12 V @ 0.5 A convection, @ 1 A forced air isolated, ±10% Hold-up time: 16 ms @ 250 W load, 120 Vac input Short circuit protection on all outputs. Case overload protected @ 110-160% Overload protection: above rating Overvoltage protection: 15-50% above nominal output Maximum power: Logical Control Power failure: Open collector logic signal goes high 100-500 msec after main output; it goes low at least 6 msec before loss of regulation C ompensates for 0.5 V lead drop min. Will operate without remote sense connected. Reverse connection protected.
Safety
• • • • • TUV 60950, 60601-1 UL 60950, 60601-1 cULus 60950, 60601-1 CB Certificate & report CE Mark (LVD)
Remote sense:
Embedded Power for Business-Critical Continuity
Environmental Specifications
Operating temperature: Storage temperature: Electromagnetic susceptibility: Humidity: Vibration: MTBF demonstrated: 0° to 50 °C ambient derate each output as 2.5% per degree from 50° to 70 °C. -20 °C start up -40 °C to +85 °C Designed to meet EN61000-4; -2, -3, -4, -5, -6, -8, -11 Level 3 Operating; non-condensing 10% to 95% RH IEC68-2-6 to the levels of IEC721-3-2 >550,000 hours at full load and 25 °C ambient conditions
Rev. 7.9.09_#98 LPS200-M Series 2 of 3
Ordering Information
Model Number LPS202-M LPS203-M LPS204-M LPS205-M LPS208-M Output Voltage 5 V 12 V 15 V 24 V 48 V Minimum Load 0 A 0 A 0 A 0 A 0 A Maximum Load with Convection Cooling 20 A 10.3 A 8.3 A 5.2 A 2.6 A Maximum Load with 30CFM Forced Air 40 A 20.8 A 16.6 A 10.4 A 5.2 A Peak Load Regulation2 44 A 22 A 18 A 11.5 A 5.8 A ±2% ±2% ±2% ±2% ±2% Ripple P/P (PARD)3 50 mV 120 mV 150 mV 240 mV 480 mV
1. Peak current lasting
很抱歉,暂时无法提供与“LPS200-M_0907”相匹配的价格&库存,您可以联系我们找货