0
登录后你可以
  • 下载海量资料
  • 学习在线课程
  • 观看技术视频
  • 写文章/发帖/加入社区
会员中心
创作中心
发布
  • 发文章

  • 发资料

  • 发帖

  • 提问

  • 发视频

创作活动
EDSX5-85D

EDSX5-85D

  • 厂商:

    FUJI(富士电机)

  • 封装:

  • 描述:

    EDSX5-85D - ELECTRONIC TRANSMITTER with FIELDBUS - Fuji Electric

  • 数据手册
  • 价格&库存
EDSX5-85D 数据手册
ELECTRONIC TRANSMITTER with FIELDBUS DATA SHEET Fieldbus is a standard digital communication protocol between field instruments and upper control system. This fieldbus standard enables interactive communication among the number of I&C manufactures simultaneously and also the usage by exchanging fieldbus instruments. FCX-AII Series Electronic Transmitters with FOUNDATION FIELDBUS and PROFIBUS is a fieldbus transmitters utilizing a unique micromachined capacitance silicon sensor with state-of -the-art microporcessor technology and converting the signal of silicon sensor to fieldbus protocol. This fieldbus transmitter can provide many merits of fieldbus as shown in the following “FEATURES”. FEATURES 1. Fuji Original IC “Frontier-1+ Fieldbus IC” “Frontier-1+” the original Fieldbus interface controller IC, developed by Fuji Electric based on IEC Fieldbus Physical Layer Specification, is installed in FCX-AII (Fieldbus version.). 2. Interoperability FCX-AII transmitter comply with the latest Foundation Fieldbus specification and PROFIBUS-PA specification and provide full interactive interoperability to other transmitters. In addition, FOUNDATION FIELDBUS FCX-AII transmitters are certified and registered by ITK4.0, the latest standard for Interoperability Testing. 3. Reduction of wiring cost The reduction of wiring cost of instrumentation is realizing due to multi-drop wiring of fieldbus instruments comparing to the current instruments. 4. High accuracy, high stability and high reliability High resolution data transmission with digital communication lead high accuracy, high stability and high reliability. 5. Abundant alarm functions and self-diagnosis Abundant alarm and maintenance function defined in Fieldbus specification in addition to process data can be well supported. The self-diagnosis including failure of pressure sensor, abnormal of temperature etc. are also provided. EDSX5-85d Date Jul. 31, 2007 Model Configuration Differential pressure/flow transmitter [model : FDC] (Standard version and Hydroseal diaphragm version) Reference page Common specifications Individual specifications Code symbols Outline diagram 4 5 11 31 Common specifications Individual specifications Code symbols Outline diagram Pressure transmitter [type : FDG] (Standard version and Hydroseal diaphragm version) Reference page 4 6 13 33 Absolute pressure transmitter [model : FDA] Reference page Common specifications Individual specifications Code symbols Outline diagram 4 7 15 35 Level transmitter [model : FDE] Reference page Common specifications Individual specifications Code symbols Outline diagram 4 7 17 36 Remote seal type differential pressure/flow transmitter [model : FDD] Remote seal type pressure transmitter [model : FDB] Reference page Common specifications Individual specifications Code symbols Outline diagram 4 7 19 38 Common specifications Individual specifications Code symbols Outline diagram Reference page 4 8 21 39 2 Small frange type level transmitter [model : FDY] Reference page Common specifications Individual specifications Code symbols Outline diagram 4 8 23 41 Small frange remote seal type differential pressure/flow transmitter [model : FDX] Reference page Common specifications Individual specifications Code symbols Outline diagram 4 9 25 43 Small frange remote seal type pressure transmitter [model : FDW] Reference page Common specifications Individual specifications Code symbols Outline diagram 4 9 27 46 3 SPECIFICATIONS (1) Common specifications Function and Performance Liquid, gas, and vapour Digital signal based on fieldbus FOUNDATION protocol or PROFIBUS-PA. Power supply: Transmitter operates on 9V to 32V DC at transmitter terminals. Quiescent draw current: 16± 2mA Standard: Foundation fieldbus Fieldbus Foundation specification(H1). (basic device, device type 113, AI function block) PROFIBUS PROFILE. Order No.3042 PROFIBUS-PA Version 3.0 Service: Output signal: Humidity limit: 0 to 100% RH Dielectric strength: 500V AC, 50/60Hz 1 min., between circuit and earth. Insulation resistance: More than 100MΩ at 500V DC. Structure and Material Electrical connections: G1/2, 1/2-14 NPT, Pg13.5, or M20 × 1.5 conduit, as specified. And 1 conduit or 2 conduits, as specified. Process connections: Model FDC, FDG, FDA FDE, FDY (LP side) FDE, FDY (HP side) FDB, FDD, FDW, FDX Process connections 1/4-18NPT PROFIBUS-PA or Rc1/4 on 54mm centers, as specified. Meets DIN 19243. ANSI, DIN or JIS raised face frange. See CODE SYMBOLS of each model (5th digit). Transmission cycle (Macro cycle): Foundation fieldbus PROFIBUS-PA 250ms min. 250ms fix. Hazardous locations: Authorities ATEX Factory Mutual CSA Flameproof Ex II2 GD -EExd IIC T5/T6 Class I II III Div. 1 Groups B thru. G Class I II III Div. 1 Groups C thru. G Ex do IIB+H2 T4 Note JIS      Ex iaIIC T4 FISCO  (Approval pending)      Zero/span adjustment: Zero and span are adjustable from the host system. Zero is also adjustable externally from the adjustment screw. Indication: None or 5-digit LCD meter, as specified. Burnout direction: Selectable from the host system. If self-diagnostic detect transmitter failure, the output will be driven to either “Output Hold”, “Output Overscale” or “Output Underscale” modes. Temperature limit: Ambient: – 40 to +85°C (–20 to +80°C for LCD indicator) (– 40 to +60°C for arrester option) (–10 to +60°C for fluorinated oil filled transmitters)  (–10 to +85°C for silicone oil   FDB, “H, S, K”)  (+20 to +85°C for silicone oil  FDD   “J, T”)  Ambient: – 15 to +65°C  (–15 to +60°C for arrester   FDW, option)  (–10 to +60°C for fluorinated  FDX,  oil filled transmitter)  FDY  (–10 to +60°C for silicone oil   “H, S”) For explosionproof units (flameproof or intrinsic safety), ambient temperature must be within the limits specified in each standard. Process: See individual specifications Storage: – 40 to +90°C (FDW, FDX, FDY ··· – 40 to +70°C) Process-wetted parts material: See CODE SYMBOLS of each model (7th digit) Non-wetted parts material: Electronics housing: Low copper die-cast aluminum alloy finished with polyester coating (standard), or 316 stainless steel (SCS14 per JIS G5121), as specified. Bolts and nuts: Cr-Mo alloy (standard), 304 stainless steel or 630 stainless steel, as specified. See CODE SYMBOLS of each model. Fill fluid: Silicone oil (standard) or fluorinated oil (Daifloil) Mounting bracket: 304 stainless steel Environmental protection: IEC IP67 and NEMA 6/6P Mounting: Model FDC, FDG, FDA FDE, FDY FDB, FDD, FDW, FDX Process connections On 60.5mm (JIS 50A) pope using mounting or direct wall mounting. Direct process mounting. Optional Specifications Varies with model or material. So refer to CODE SYMBOLS. Indicator: An optional 5-digit LCD meter with engineering unit is also available. Oxygen service: Special cleaning procedures are followed throughout the process to maintain all process wetted parts oil-free. The fill fluid is fluorinated oil. Chlorine service: The fill fluid is fluorinated oil. Degreasing: Process-wetted parts are cleaned, but the fill fluid is standard silicone oil. Not for use on oxygen or chlorine measurement. 4 NACE specification: Metallic materials for all pressure boundary parts comply with NACE MR-01-75. ASTM B7M or L7M bolts and 2HM nuts (Class II) are available. Static pressure rating for code “3” (16 MPa) is degraded to 10MPa. Vacuum service: Special silicone oil and filling procedure are applied. See Fig. 1. Optional tag plate: An extra stainless steel tag with customer tag data is wired to the transmitter. Coating of cell: Cell’s surface is finished with epoxy/ polyurethane double coating. Specify if environment is extremely corrosive. Over range limit: To maximum static pressure limit Process temperature and negative pressure tolerance limit: (For details, see Fig. 1) Filled oil Silicone oil (*1) Fluorinated oil Silicone oil 13th code Y, G, N W, A, D R Process temperatuer –40 to +120°C –20 to +80°C –15 to +120°C Negative pressure tolerance limit 2.7 kPa abs Atmospheric pressure 2.7 kPa abs Lower limit of static pressure (vacuum limit): Silicone oil filled sensor: See Fig. 1 Fluorinated oil filled sensor: 66kPa abs (500mmHg abs) at temperature below 60°C Accuracy rating: (including linearity, hysteresis, and repeatability) Reference conditions, silicone oil fill, 316SS isolating diaphragms. Accessories Oval flanges: (Model FFP, refer to Data Sheet No. EDS6-10) Converts process connection to 1/2 -14 NPT or to Rc1/2; in carbon steel or in 316 stainless steel. (Model FFN, refer to Data Sheet No. EDS6-10) Available in Carbon steel or in 316 stainless steel and in pressure rating 16MPa or 42MPa. Connection diagram CK CK (M4 screws) Equalizing valves: Max span above 32kPa model: For spans greater than 1/10 of URL: ± 0.07% of span For spans below 1/10 of URL: 0.1 × URL ± 0.02+0.05 % of span Span Max span 1kPa, 6kPa model: For spans greater than 1/10 of URL: ± 0.1% of span For spans below 1/10 of URL: 0.1 × URL ± 0.05+0.05 % of span Span Stability: ± 0.1% of upper range limit (URL) for 3 years Temperature effect: Effects per 28 °C change between the limits of – 40°C and +85°C ( ( ) ) Range code (6th digit in Code symbols) “1”/1kPa max. span “2”/6kPa max. span “3”/32kPa max. span “5”/130kPa max. span “6”/500kPa max. span “8”/3000kPa max. span Zero shift ± 0.225% Total effect ± 0.25% Do not connect. Field bus ± 0.0875% ± 0.1075% Static pressure effect: (2) Individual specifications Zero-based spans, reference conditions, silicone oil fill, SS316 isolating diaphragms, output in linear mode, digital trim values equal to the span setpoints and capillary length of 1.5m. Static pressure code (5th digit in Code symbols) “1” /1kPa sensor “2” /6kPa sensor “2” “3” “4” Zero shift (% of URL) ± 0.2% / 1MPa ± 0.2% / 3.2MPa ± 0.05%/10MPa Span shift –0.2% /3.2MPa –0.2% /3.2MPa –0.2% /10MPa Diffential Pressure / Flow Transmitter : FDC Static pressure, range limit: Type F DC F DC F DC F DC F DC F DC F DC F DC F DC F DC F DC F DC F DC 11 22 23 25 26 33 35 36 38 43 45 46 48 Static pressure [MPa] –0.1 to + 3.2 Range limit [kPa] +/– 1 +/– 6 +/– 32 +/– 130 +/– 500 +/– 32 +/– 130 +/– 500 +/– 3000 +/– 32 +/– 130 +/– 500 +/– 3000 Overrange effect: Static pressure code (5th digit in Code symbols) “1” / 1kPa sensor “2” / 6kPa sensor “2” “3” “4” Zero shift (% of URL) ± 0.3% / 1MPa ± 0.1% / 3.2MPa ± 0.1% /10MPa ± 0.1% /16MPa ± 0.25% /42MPa –0.1 to + 10 –0.1 to + 16 –0.1 to + 42 –0.1 to + 30 Mounting position effect: Zero shift, less than 0.12kPa for a 10° tilt in any plane. No effect on span. This error can be corrected by adjusting Zero. Mass{weight}: Transmitter approximately 4.4kg without options. 5 Diffential Pressure / Flow Transmitter Hydroseal Diaphragm version: FDC Static pressure, range limit: Type F DC F DC 33 35 Static pressure [MPa] –0.1 to 16 –0.1 to 16 Range limit [KPa] +/– 32 +/– 130 Filled oil Silicone oil Fluorinated oil Silicone oil 13th code Y, G, N W, A, D R Process temperatuer –40 to +100°C –20 to +80°C –15 to +100°C Negative pressure tolerance limit 2.7 kPa abs Atmospheric pressure 2.7 kPa abs Over range limit: To maximum static pressure limit Process temperature and negative pressure tolerance limit: (For details, see Fig. 1) Filled oil Silicone oil Fluorinated oil Silicone oil 13th code Y, G, N W, A, D R Process temperatuer –20 to +120°C –20 to +80°C –15 to +120°C Negative pressure tolerance limit 2.7 kPa abs Atmospheric pressure 2.7 kPa abs Lower limit of static pressure (vacuum limit): Silicone oil filled sensor: See Fig. 1 Fluorinated oil filled sensor: 66kPa abs (500mmHg abs) at temperature below 60°C Accuracy rating: (including linearity, hysteresis, and repeatability) Reference conditions, silicone oil fill, 316SS isolating diaphragms. For spans greater than 1/10 of URL: ± 0.15% of span For spans below 1/10 of URL: 0.1×URL ± 0.1+0.05 % of span Span Stability: ± 0.15% of upper range limit (URL) for 3 years Temperature effect: Effects per 28°C change between the limits of – 40°C and +85°C ( ) Zero shift ± 0.175% Total effect ± 0.2% Static pressure effect: Zero shift (% of URL) ± 0.15% /10MPa{100bar} Span shift –0.2% /10MPa{100bar} Lower limit of static pressure (vacuum limit): Silicone oil filled sensor: See Fig. 1 Fluorinated oil filled sensor: 66kPa abs (500mmHg abs) at temperature below 60°C Accuracy rating: (including linearity, hysteresis, and repeatability) Reference conditions, silicone oil fill, 316SS isolating diaphragms. Max span below 10000kPa model: For spans greater than 1/10 of URL: ± 0.07% of span For spans below 1/10 of URL: 0.1 × URL ± 0.02+0.05 % of span Span Max span 50000kPa model: For spans greater than 1/10 of URL: ± 0.1% of span For spans below 1/10 of URL: 0.1 × URL ± 0.05+0.05 % of span Span Stability: ± 0.1% of upper range limit (URL) for 3 years Temperature effect: Effects per 28 °C change between the limits of – 40°C and +85°C Zero shift: ± 0.0875% Total effect: ± 0.1075% Overrange effect: Zero shift; 0.2% of URL for any overrange to maximum limit Mounting position effect: Zero shift, less than 0.1kPa for a 10° tilt in any plane. No effect on span. This error can be corrected by adjusting Zero. Mass{weight}: Transmitter approximately 3.4kg without options. ( ( ) ) Overrange effect: Range code (6th digit in Code symbols) “3” “5” Zero shift (% of URL) 1 % URL / 16MPa 0.6 % URL / 16MPa Pressure Transmitter Hydroseal Diaphragm version: FDG Static pressure, range limit: Type FDG 07 FDG 08 FDG 09 Static pressure [MPa] –0.1 to 0.5 –0.1 to 3 –0.1 to 10 Range limit [kPa] Lower limit Permissible negative pressure limit Upper limit 500 3000 10000 Over range limit [MPa] 1.5 9 15 Mounting position effect: Zero shift, less than 0.12kPa for a 10° tilt in any plane. No effect on span. This error can be corrected by adjusting Zero. Mass{weight}: Transmitter approximately 4.4kg without options. Process temperature and negative pressure tolerance limit: (For details, see Fig. 1) Filled oil Silicone oil Fluorinated oil 13th code Y, G, N W, A, D Process temperatuer –20 to +100°C –20 to +80°C Negative pressure tolerance limit 2.7 kPa abs Atmospheric pressure Pressure Transmitter : FDG Range and overrange limit: Type F DG F DG F DG F DG F DG 01 02 03 04 05 Range limit [kPa] Lower limit Permissible negative pressure limit Upper limit 130 500 3000 10000 50000 Overrange limit [MPa] 1 1.5 9 15 75 Process temperature and negative pressure tolerance limit: (For details, see Fig. 1) Lower limit of static pressure (vacuum limit): Silicone oil filled sensor: See Fig. 1 Fluorinated oil filled sensor: 66kPa abs (500mmHg abs) at temperature below 60°C Accuracy rating: (including linearity, hysteresis, and repeatability) Reference conditions, silicone oil fill, 316SS isolating diaphragms. For spans greater than 1/10 of URL: ± 0.15% of span For spans below 1/10 of URL: 0.1 x URL ± 0.1+0.05 % of span Span ( ) 6 ± 0.15% of upper range limit (URL) for 3 years Temperature effect: Effects per 28°C change between the limits of – 40°C and +85°C Zero shift: ± 0.2% Total effect: ± 0.225% Overrange effect: Zero shift; 0.4% of URL for any overrange to maximum limit Mounting position effect: Zero shift, less than 0.1kPa for a 10° tilt in any plane. No effect on span. This error can be corrected by adjusting Zero. Mass {weight}: Transmitter approximately 3.4kg without options. Stability: Over range limit: To maximum static pressure limit Process temperature and negative pressure tolerance limit: (For details, see Fig. 2, Fig. 3) Filled oil Fluorinated oil Silicone oil 13th code W, A, D H J Y, G S T K Process temperatuer –20 to +120°C –15 to +250°C 85 to +300°C –40 to +120°C –15 to +250°C 85 to +300°C –15 to +150°C Negative pressure tolerance limit Atmospheric pressure 2.7 kPa abs 0.13 kPa abs Low pressure side contact liquid temperature on transmitter of Code “H, J, S, T” is 120°C or lower. Low pressure side contact liquid temperature of Code “K” is 85°C or lower. Absolute Pressure Transmitter : FDA Range and overrange limit: Type F DA F DA F DA F DA 01 02 03 04 0 0 0 0 to to to to Range limit [kPa abs] +16 +130 +500 +3000 Overrange limit [MPa] 0.5 0.5 1.5 9 Lower limit of static pressure (vacuum limit): Silicone oil filled sensor: See Fig. 1 Fluorinated oil filled sensor: 66kPa abs (500mmHg abs) at temperature below 60°C Accuracy rating: (including linearity, hysteresis, and repeatability) Reference conditions, silicone oil fill, 316SS isolating diaphragms. (Standard) For spans greater than 1/10 of URL: ± 0.2% of span For spans below 1/10 of URL: 0.1 × URL ± 0.1+0.1 % of span Span (Option) (Code: 21th digit H, K) For span greater than 1/10 of URL: 0.1% of span For span below 1/10 of URL: 0.1 × URL ± 0.05+0.05 % of span Span Stability: ± 0.2% of upper range limit (URL) for 3 years Temperature effect: Effects per 28°C change between the limits of – 40°C and + 85°C (Standard) Zero shift: ± 0.35% of URL Total effect: ± 0.5% of URL (Option) (Code: 21th digit J, K) Zero shift: ± 0.3% of URL Total effect: ± 0.4% of URL Static pressure effect: Zero shift: ± 0.2% of URL / 1MPa Span shift: – 0.2% of calibrated span / 1MPa Overrange effect: Zero shift; ± 0.1% of URL for flange rating pressure Mounting position effect: Zero shift, less than 0.3kPa for a 10° tilt in any plane. (No extension) No effect on span. This error can be corrected by adjusting zero. Mass{weight}: Transmitter approximately 13kg without options. Process temperature and negative pressure tolerance limit: Process temperature; –40 to +85°C Negative pressure; Depends on measuring range. Accuracy rating: (including linearity, hysteresis, and repeatability). Reference conditions, silicone oil fill, 316SS isolating diaphragms. (Standard) For spans greater than 1/10 of URL: ± 0.2% of span For spans below 1/10 of URL: 0.1 × URL ± 0.1+0.1 % of span Span (Option) (code: 21th digit H) (Not available for Max span 16kPa abs, 130kPa abs) For spans greater than 1/10 of URL: ± 0.1% of span For spans below 1/10 of URL: 0.1 × URL ± 0.05+0.05 % of span Span Stability: ± 0.2% of upper range limit (URL) for 3 years Temperature effect: Effect per 28°C change between the limits of – 40°C and +85°C Zero shift: ± 0.225% Total effect: ± 0.25% Overrange effect: Zero shift; ± 0.2% of URL for any overrange to maximum limit Mounting position effect: Zero shift, less than 0.1kPa for a 10° tilt in any plane. No effect on span. This error can be corrected by adjusting zero. Mass{weight}: Transmitter approximately 3.4kg without options. ( ( ) ) ( ) ( ) Remote Seal Type Diffential Pressure / Flow Transmitter: FDD Static pressure, range limit: Type Static pressure 3 5 6 Range limit [kPa] +/– 32 +/– 130 +/– 500 F DD F DD F DD Level Transmitter : FDE Static pressure, range limit: Type F DE F DE F DE 3 5 6 Static pressure Range limit [kPa] +/– 32 +/– 130 +/– 500   Up to flange rating    Up to flange rating  7 Over range limit: To maximum static pressure limit Process temperature and negative pressure tolerance limit: (For details, see Fig. 2, Fig. 4) Filled oil Fluorinated oil Silicone oil 13th code W, A, D H J Y, G S T K Process temperatuer –20 to +120°C –15 to +250°C +85 to +300°C –40 to +120°C –15 to +250°C +85 to +300°C –15 to +200°C Negative pressure tolerance limit Atmospheric pressure 2.7 kPa abs 0.13 kPa abs FDY FDY 5 6 Note: * Excluding effect by temperature difference between the seals. Static pressure effect: Zero shift; 0.2% of URL for flange rating pressure Span shift: – 0.2% of calibrated span for flange rating pressure Overrange effect: Zero shift; 0.1% of URL for flange rating pressure Mass {weight}: Transmitter approximately 15kg without options. Over range limit: To maximum static pressure limit Process temperature and negative pressure tolerance limit: (For details, see Fig. 2) Process Negative pressure temperatuer tolerance limit Fluorinated oil W, A, D –20 to +80°C Atmospheric pressure Silicone oil H 0 to +250°C Y, G –40 to +120°C 2.7 kPa abs S 0 to +250°C Low pressure side contact liquid temperature on transmitter of Code “H, S” is 120°C or lower. Filled oil 13th code Remote Seal Type Pressure Transmitter: FDB Range, and overrange limit: Type F DB F DB F DB F DB F DB 1 2 3 4 5 Range limit [kPa] –100 –100 –100 –100 –100 to to to to to +130 +500 +3000 +10000 +50000 Overrange limit [MPa] 1 1.5 9 15 75 Lower limit of static pressure (vacuum limit): Silicone oil filled sensor: See Fig. 1 Fluorinated oil filled sensor: 66kPa abs (500mmHg abs) at temperature below 60°C Accuracy rating: (including linearity, hysteresis, and repeatability) Reference conditions, silicone oil fill, 316SS isolating diaphragms. (Standard) For spans greater than 1/10 of URL: ± 0.25% of span For spans below 1/10 of URL: 0.1 x URL ± 0.17+0.08 % of span Span (Option) (Code: 21th digit H, K) For spans greater than 1/10 of URL: ± 0.1% of span For span below 1/10 of URL: 0.1 x URL ± 0.05+0.05 % of span Span Process temperature and negative pressure tolerance limit: (For details, see Fig. 2, Fig. 4) Filled oil Fluorinated oil Silicone oil 13th code W, A, D H J Y, G S T K Process temperatuer –20 to +120°C –15 to +250°C 85 to +300°C –40 to +120°C –15 to +250°C 85 to +300°C –15 to +200°C Negative pressure tolerance limit Atmospheric pressure 2.7 kPa abs 0.13 kPa abs 8    Accuracy rating: (including linearity, hysteresis, and repeatability) Reference conditions, silicone oil fill, 316SS isolating diaphragms. (Standard) For spans greater than 1/10 of URL: 0.2% of span For spans below 1/10 of URL: 0.1 × URL ± 0.1+0.1 % of span Span (Option) (Code; 21th digit H,K) For spans greater than 1/10 of URL: 0.1% of span For spans below 1/10 of URL: 0.1 × URL ± 0.05+0.05 % of span Span Stability: ± 0.2% of upper range limit (URL) for 3 years Temperature effect (*): Effects per 28°C change between the limits of – 40°C and +85°C (Standard) Zero shift: ± 0.35% of URL Total effect: ± 0.5% of URL (Option) (Code; 21th digit J,K) Zero shift: ± 0.3% of URL Total effect: ± 0.4% of URL Accuracy rating: (including linearity, hysteresis, and repeatability) Reference conditions, silicone oil fill, 316SS isolating diaphragms. (Standard) For spans greater than 1/10 of URL: ± 0.2% of span For spans below 1/10 of URL: 0.1 × URL ± 0.1+0.1 % of span Span (Option) (Code; 21th digit H,K) Not available for Max span 50000kPa model. For spans greater than 1/10 of URL: ± 0.1% of span For spans below 1/10 of URL: 0.1 × URL ± 0.05+0.05 % of span Span ( ) ( ) ( ( ) ) ± 0.1% of upper range limit (URL) for 3 years Temperature effect: Effect per 28°C change between the limits of – 40°C and +85°C (Standard) Zero shift: ± 0.35% of URL Total effect: ± 0.5% of URL (Option) (Code; 21th digit J,K) Zero shift: ± 0.3% of URL Total effect: ± 0.4% of URL Overrange effect: Zero shift; 0.2% of URL for any overrange to maximum limit Mass {weight}: Transmitter approximately 10kg without options. Stability: Small Frange Level Transmitter : FDY Static pressure, range limit: Type Static pressure Up to flange rating Range limit [kPa] +/– 130 +/– 500 ( ( ) ) ± 0.2% of upper range limit (URL) for 3 years Temperature effect: Effects per 28°C change between the limits of – 15°C and + 65°C Zero shift; ± 0.5% Total shift; ± 0.75% (Option) (Code: 21th digit J, K) Zero shift; ± 0.5% Total shift; ± 0.75% Stability: Where, URL: Maximum span (Upper Range Limit) Static pressure effect: Zero shift; 0.2% of URL/1MPa (10 bar) Span shift: – 0.2% of calibrated span / 1MPa Overrange effect: Zero shift; 0.1% of URL for flange nominal pressure Mass {weight}: Transmitter approximately 15kg without options. Small Frange Remote Seal Type Pressure Transmitter: FDW Range, and overrange limit: Type FDW FDW 3 4 Range limit [kPa] –100 to +3000 –100 to 10000 Overrange limit [MPa] 4.5 15 Static pressure effect: Zero shift: ± 0.2% of URL/1MPa Span shift: –0.2% of calibrated span /1MPa Overrange effect: Zero shift; ± 0.1% of URL for flange rating pressure Mass{weight}: Transmitter approximately 13kg without options. Process temperature and negative pressure tolerance limit: (For details, see Fig. 2) Filled oil 13th code W, A, D H Y, G S Process temperatuer –20 to +120°C 0 to +250°C –40 to +120°C 0 to +250°C Negative pressure tolerance limit Atmospheric pressure 2.7 kPa abs Small Frange Remote Seal Type Differential Pressure Transmitter: FDX Static pressure, range limit: Type FDX FDX 5 6 Static pressure Range limit [kPa] +/– 130 +/– 500 Fluorinated oil Silicone oil } Up tp flange rating Over range limit: To maximum static pressure limit Process temperature and negative pressure tolerance limit: (For details, see Fig. 2, Fig. 4) Filled oil Fluorinated oil Silicone oil 13th code W, A, D H Y, G S Process temperatuer –20 to +120°C 0 to +250°C –40 to +120°C 0 to +250°C Negative pressure tolerance limit Atmospheric pressure 2.7 kPa abs Accuracy rating: (including linearity, hysteresis, and repeatability) Reference conditions, silicone oil fill, 316SS isolating diaphragms. (Standard) For spans greater than 1/10 of URL: 0.25% of span For spans below 1/10 of URL: 0.1 x URL ± 0.17+0.08 % of span Span ( ( ) ) Accuracy rating: (including linearity, hysteresis, and repeatability) Reference conditions, silicone oil fill, SS316 isolating diaphragms. (Standard) For spans greater than 1/10 of URL: ± 0.25% of span For spans below 1/10 of URL: ± 0.17+0.08 0.1 x URL % of span Span (Option) (Code; 21th digit H) For spans greater than 1/10 of URL: ± 0.1% of span For spans below 1/10 of URL: ± 0.05+0.05 0.1 x URL % of span Span Stability: ± 0.2% of upper range limit (URL) for 3 years Temperature effect: Effect per 28°C change between the limits of – 15°C and +65°C Zero shift: ± 0.5% Total shift; ± 0.75% ( ( ) ) (Option) (Code; 21th digit H,K) For spans greater than 1/10 of URL: 0.1% of span For spans below 1/10 of URL: 0.1 x URL ± 0.05+0.05 % of span Span Stability: ± 0.2% of upper range limit (URL) for 3 years Temperature effect: Effects per 28°C change between the limits of – 15°C and +65°C Zero shift: ± 0.5% Total shift; ± 0.75% (option) (Code; 21th digit J,K) Zero shift: ± 0.5 Total shift; ± 0.75% Where, Maximum span (Upper Range Limit) Note : Above specifications are based on the conditions that flanges and sensor unit are at the same temperature and in the same level. If temperature is different at flanges, capillary or sensor unit, output variation may increase. URL: Where, Maximum span (Upper Range Limit) Note : Above specifications are based on the conditions that flange and sensor unit are at the same temperature and in the same level. If temperature is different at flange, capillary or sensor unit, output variation may increase. URL: Overrange effect: Zero shift; 0.2% of URL/(1.5 x URL) Mass {weight}: Transmitter approximately 10kg without options. 9 Silicone oil (Code:Y,G,N) Silicone oil (Code:R) [kPa abs] 101 101 {1010} [kPa abs] {mbar abs} Sealing liquid:Silicone (Code K) Operating pressure 20 Operating pressure Operating area Operating arear 4 2.7 Non-operating area None-operating area –40 –15 60 85 120 Process temperature[°C ] 0.13 {1.3} –15 Process temperature[°C ] 100 Fig. 1 Relation between process temperature and operating pressure (pressure and differential pressure/flow transmitters) Fig. 3 Relation between process temperature and operating pressure (level transmitters) Filled fluid: Silicone oil (code Y, G) [kPa abs] Filled fluid: Silicone oil (code S) Filled fluid: Silicone oil (code T) 101 Operating pressure [kPa abs] Filled fluid: Silicone oil (code K) 53.3 Operating area Operating pressure 101 Operating area 13.3 Nonoperating area 0.27 0.13 2.7 Non-operating area –40 –15 60 85 120 200 230250 Process temperature 300 [°C] –15 100 Process temperature 200 [°C] Fig. 2 Relation between process temperature and operating pressure (remote seal type pressure, remote seal type differential pressure and level transmitters) Fig. 4 Relation between process temperature and operating pressure (remote seal type pressure, remote seal type differential pressure and level transmitters) 10 CODE SYMBOLS Diffential pressure / flow transmitter : FDC 12345678 9 10 11 12 13 14 15 Oval flange Conduit Process connection connection screw 7/16-20UNF (×1) G1/2 Rc1/4 7/16-20UNF 1/2-14NPT (×1) 1/4-18NPT Combination with 12th 1/4-18NPT digit code “C, E, P, Q” M10 (or M12)(*1) Pg 13.5 (×1) are not available. 1/4-18NPT M10 (or M12)(*1) M20×1.5 (×1) 7/16-20UNF 1/4-18NPT Pg 13.5 (×1) 7/16-20UNF (×2) G1/2 Rc1/4 7/16-20UNF 1/2-14NPT (×2) 1/4-18NPT 1/4-18NPT M10 (or M12)(*1) Pg 13.5 (×2) 1/4-18NPT M10 (or M12)(*1) M20×1.5 (×2) 7/16-20UNF 1/4-18NPT Pg 13.5 (×2) 5, 6, 7 Static Wetted Span limit (*2) Process Diaphragm pressure cover cell body [MPa] [kPa] –0.1 to +3.2 0.1…1 316 stainless steel 316L stainless steel 316 stainless steel 316L stainless steel +Au coating 316 stainless steel Hast. C 316 stainless steel 316L stainless steel 316 stainless steel 316L stainless steel +Au coating 316 stainless steel Hast. C 316 stainless steel 316L stainless steel 316 stainless steel 316L stainless steel +Au coating 316 stainless steel Hast. C 316 stainless steel Monel 316 stainless steel Tantalum 316 stainless steel 316L stainless steel 316 stainless steel 316L stainless steel +Au coating 316 stainless steel Hast. C 316 stainless steel Monel 316 stainless steel Tantalum 316 stainless steel 316L stainless steel 316 stainless steel 316L stainless steel +Au coating 316 stainless steel Hast. C 316 stainless steel Monel 316 stainless steel Tantalum 316 stainless steel 316L stainless steel 316 stainless steel 316L stainless steel +Au coating 316 stainless steel 316L stainless steel 316 stainless steel 316L stainless steel +Au coating 316 stainless steel Hast. C 316 stainless steel Monel 316 stainless steel 316L stainless steel 316 stainless steel 316L stainless steel +Au coating 316 stainless steel Hast. C 316 stainless steel Monel 316 stainless steel 316L stainless steel 316 stainless steel 316L stainless steel +Au coating 316 stainless steel Hast. C 316 stainless steel Monel 316 stainless steel 316L stainless steel 316 stainless steel 316L stainless steel +Au coating Hast. C Hast. C lining Monel Monel lining Tantalum lining Tantalum Hast. C Hast. C lining Monel Monel lining Tantalum lining Tantalum Hast. C Hast. C lining Monel Monel lining Tantalum lining Tantalum 316 stainless steel 316L stainless steel (*3) 316 stainless steel 316L stainless steel (*3) 316 stainless steel 316 stainless steel Hast. C lining 316 stainless steel 316 stainless steel Hast. C lining 316 stainless steel 316 stainless steel Hast. C lining Monel lining Tantalum lining 316 stainless steel 316 stainless steel Hast. C lining Monel lining Tantalum lining 316 stainless steel 316 stainless steel Hast. C lining Monel lining Tantalum lining 316 stainless steel 316 stainless steel 316 stainless steel 316 stainless steel Hast. C lining Monel lining 316 stainless steel 316 stainless steel Hast. C lining Monel lining 316 stainless steel 316 stainless steel Hast. C lining Monel lining 316 stainless steel 316 stainless steel Digit 4 Description Note FDC 4 Digit No. of code Note 1 Note 1 Note 1 Note 1 A B C D E S T V W X Note 2 11V 11J 11H 22V 22J 22H 33V 33J 33H 33M 33T 35V 35J 35H 35M 35T 36V 36J 36H 36M 36T 38V 38J 43V 43J 43H 43M 45V 45J 45H 45M 46V 46J 46H 46M 48V 48J 23B 23L 23U 25B 25L 25U 26B 26L 26U 33C 35C –0.1 to+10 0.1…6 –0.1 to+16 0.32…32 1.3…130 5…500 30…3000 –0.1 to+42 0.32…32 1.3…130 5…500 –0.1 to+30 30…3000 –0.1 to+10 0.32…32 1.3…130 5…500 –0.1 to+16 3.2…32 13…130 Hast. C lining Monel lining Tantalum lining Hast. C lining Monel lining Tantalum lining Hast. C lining Monel lining Tantalum lining 316 stainless steel Note 3 316 stainless steel Note 3 11 12345678 9 10 11 12 13 14 15 Digit 9 Description Digital indicator Arrester Communication type None None Foundation Fieldbus None Yes Foundation Fieldbus Yes None Foundation Fieldbus Yes Yes Foundation Fieldbus None None Profibus None Yes Profibus Yes None Profibus Yes Yes Profibus None (for ordinary locations) TIIS, Flameproof (Conduit seal) TIIS, Flameproof (Cable gland seal) FM, Flameproof (or explosionproof) CSA, Flameproof (or explosionproof) ATEX, Flameproof ATEX, Intrinsic safty (Entity) SAA, Flameproof (or explosionproof) ATEX, FISCO Note FDC 4 Digit No. of code A E P S R V T W 10 A B C D E X K F 4 Approval pending Approval pending Approval pending Approval pending Note 9 11 12 13 14 15 Vent/drain Mounting bracket Specify “A” or “C” for the 7th Standard None Standard Yes, stainless steel digit code “B”, “L”, or “U” Side None Side Yes, stainless steel Extra SS tag plate Stainless steel elec, housing Coating of cell None None None Yes None None None Yes None Yes Yes None (*4) None None Yes Yes None Yes None Yes Yes Yes Yes Yes Treatment Fill fluid Standard Silicone oil Standard Fluorinated oil Degreasing Silicone oil Oxygen service Fluorinated oil (7th digit code “V” only) Chlorine service Fluorinated oil (7th digit code “H”, “T”, “B”, “U”) NACE specification Silicone oil (Not available for 7th digit code “T”, “U” and 15th digit code “A”, “B”) Vacuum service Silicone oil for vacuum use (Not available for 7th digit code “C”) Viton (O-ring) Teflon (gasket) (*8) Cr-Mo alloy hexagon socket head cap screw/carbon steel nut Cr-Mo alloy hexagon bolt/nut NACE bolt/nut (ASTM A193 B7M/A194 2HM) (*5) NACE bolt/nut (ASTM A320 L7M/A194 2HM) 304 stainless steel bolt/304 stainless steel nut (*6) 630 stainless steel bolt/304 stainless steel nut (*7) (*1) (*2) (*3) (*4) (*5) (*6) A C D F Note 4 Y B C E M N P Q Y W G A D N R A B Note 8 A B C D E F Note 5 Note 6 Note 7 Note 1: Note 2: Note 3: Note 4: Note 5: Note 6: The thread is M12, if 42MPa {420bar} static pressure is specified. 100: 1 turn down is possible, but should be used at the span greater than 1/40 of the maximum span for better performance. The diaphragm face is coated with gold and ceramic. Customer tag number can be engraved on standard stainless steel name plate. If extra tag plate is required, select “Yes”. Static pressure should be –0.1 to +10MPa{–1 to +100bar}. Available for 5th digit code “1”, “2”, “3”. In case of stainless steel bolt with 5th digit code “3”, static pressure should be –0.1 to +10MPa {–1 to + 100bar}. Note 7: (*7) Available for 5th digit code “3”, “4”. Note 8: (*8) In case of tropical use, select stainless bolts and nuts. Note 9: (*9) In case of 10th code is “4”(ATEX, FISCO), then the 9th code, E, S, V and W (with arrester option) are not available. 12 Pressure transmitter : FDG 12345678 9 10 11 12 13 14 15 Digit 4 Description Oval flange Process screw connection 7/16-20UNF Rc1/4 1/4-18NPT 7/16-20UNF 1/4-18NPT M10 (or M12)(*1) 1/4-18NPT M10 (or M12)(*1) 1/4-18NPT 7/16-20UNF 7/16-20UNF Rc1/4 1/4-18NPT 7/16-20UNF 1/4-18NPT M10 (or M12)(*1) 1/4-18NPT M10 (or M12)(*1) 1/4-18NPT 7/16-20UNF Span limit Process cover [kPa](*2) 316 stainless steel 1.3…130 316 stainless steel 316 stainless steel 316 stainless steel 316 stainless steel Hast. C lining Monel lining Tantalum lining 316 stainless steel 316 stainless steel 316 stainless steel 316 stainless steel 316 stainless steel Hast. C lining Monel lining Tantalum lining 316 stainless steel 316 stainless steel 316 stainless steel 316 stainless steel 316 stainless steel Hast. C lining Monel lining Tantalum lining 316 stainless steel 316 stainless steel 316 stainless steel 316 stainless steel 316 stainless steel Hast. C lining Monel lining Tantalum lining 316 stainless steel 316 stainless steel 316 stainless steel 316 stainless steel Conduit connection G1/2 1/2-14NPT Pg13.5 M20×1.5 Pg13.5 G1/2 1/2-14NPT Pg13.5 M20×1.5 Pg13.5 Diaphragm 316L stainless steel 316L stainless steel +Au Coating Hast. C Monel Tantalum Hast. C Monel Tantalum 316L stainless steel 316L stainless steel +Au Coating Hast. C Monel Tantalum Hast. C Monel Tantalum 316L stainless steel 316L stainless steel +Au Coating Hast. C Monel Tantalum Hast. C Monel Tantalum 316L stainless steel 316L stainless steel +Au Coating Hast. C Monel Tantalum Hast. C Monel Tantalum 316L stainless steel 316L stainless steel 316L stainless steel 316L stainless steel Note F DG 0 4 Digit No. of code (×1) (×1) (×1) (×1) (×1) (×2) (×2) (×2) (×2) (×2) Combination with 12th digit code Note 1 “C, E, P, Q” are Note 1 not available. Note 1 Note 1 A B C D E S T V W X 6, 7 Wetted cell body Note 2 316 stainless steel 316 stainless steel Hast. C lining Monel lining Tantalum lining Hast. C lining Monel lining Tantalum lining 316 stainless steel 316 stainless steel Hast. C lining Monel lining Tantalum lining Hast. C lining Monel lining Tantalum lining 316 stainless steel 316 stainless steel Hast. C lining Monel lining Tantalum lining Hast. C lining Monel lining Tantalum lining 316 stainless steel 316 stainless steel Hast. C lining Monel lining Tantalum lining Hast. C lining Monel lining Tantalum lining 316 stainless steel 316 stainless steel 316 stainless steel 316 stainless steel 1V 1J 1H 1M 1T 1B 1L 1U 2V 2J 2H 2M 2T 2B 2L 2U 3V 3J 3H 3M 3T 3B 3L 3U 4V 4J 4H 4M 4T 4B 4L 4U 5V 7C 8C 9C 5…500 30…3000 100…10000 500…50000 50…500 300…3000 1000…10000 9 Digital indicator Arrester Communication type None None Foundation Fieldbus None Yes Foundation Fieldbus Yes None Foundation Fieldbus Yes Yes Foundation Fieldbus None None Yes Yes None Yes None Yes Profibus Profibus Profibus Profibus A E P S R V T W 13 12345678 9 10 11 12 13 14 15 Digit 10 Description None (for ordinary locations) TIIS, Flameproof (Conduit seal) TIIS, Flameproof (Cable gland seal) FM, Flameproof (or explosionproof) CSA, Flameproof (or explosionproof) ATEX, Flameproof ATEX, Intrinsic safty (Entity) SAA, Flameproof (or explosionproof) ATEX, FISCO Note F DG 0 4 Digit No. of code A B C D E X K F 4 Approval pending Approval pending Approval pending Approval pending Note5 11 12 13 14 15 Vent/drain Mounting bracket Standard None Specify “A”, or “C” for the 7th Standard Yes, stainless steel digit code “B”, “L”, or “U” Side None Side Yes, stainless steel Extra SS tag plate Stainless steel elec. housing Coating of cell None None None Yes None None None Yes None Note3 (*3) Yes Yes None None None Yes Yes None Yes None Yes Yes Yes Yes Yes Treatment Fill fluid Standard Silicone oil Standard Fluorinated oil Degreasing Silicone oil Oxygen service Fluorinated oil (7th digit code “V” only) Chlorine service Fluorinated oil (7th digit code “H”, “T”, “B”, “U”) NACE specification Silicone oil (Not available for 6th digit code “5”, 7th digit code “T”, “U”, 15th digit code “A”, “B”) Vacuum service Silicone oil for vacuum use(Not available for 7th digit code “C”) Viton (O-ring) Teflon (gasket) (*4) Note4 Cr-Mo alloy hexagon socket head cap screw/carbon steel nut Cr-Mo alloy hexagon bolt/nut NACE bolt/nut (ASTM A193 B7M/A194 2HM) Not available for 6th digit NACE bolt/nut (ASTM A320 L7M/A194 2HM) code “5” 304 stainless steel bolt/304 stainless steel nut 630 stainless steel bolt/304 stainless steel nut Available for 6th digit code “5” A C D F Y B C E M N P Q Y W G A D N R A B A B C D E F Note 1 : (*1) Note 2 : (*2) Note 3 : (*3) Note 4 : (*4) Note 5: (*5) For 50MPa {500bar} units, M12 is provided rather than M10. 100: 1 turn down is possible, but should be used at the span greater than 1/40 of the maximum span for better performance. Costomer tag number can be engraved on standartd stainless steel name plate. If extra tag plate is required, select “Yes”. In case of tropical use, select stainless bolts and nuts. In case of 10th code is “4” (ATEX, FISCO), then the 9th code, E, S, V and W (with arrester option) are not available. 14 Absolute pressure transmitter : FDA 12345678 9 10 11 12 13 14 15 21 Digit 4 Description Process connection Rc1/4 1/4-18NPT 1/4-18NPT 1/4-18NPT 1/4-18NPT Rc1/4 1/4-18NPT 1/4-18NPT 1/4-18NPT 1/4-18NPT Span limit [kPa abs](*1) 1.6…16 Oval flange screw 7/16-20UNF 7/16-20UNF M10 M10 7/16-20UNF 7/16-20UNF 7/16-20UNF M10 M10 7/16-20UNF Process cover 316 stainless steel 316 stainless steel 316 stainless steel 316 stainless steel 316 stainless steel 316 stainless steel 316 stainless steel 316 stainless steel 316 stainless steel 316 stainless steel 316 stainless steel 316 stainless steel 316 stainless steel 316 stainless steel 316 stainless steel Conduit connection G1/2 1/2-14NPT Pg 13.5 M20×1.5 Pg 13.5 G1/2 1/2-14NPT Pg 13.5 M20×1.5 Pg 13.5 Diaphragm 316L stainless steel Hast. C Monel 316L stainless steel Hast. C Monel Tantalum 316L stainless steel Hast. C Monel Tantalum 316L stainless steel Hast. C Monel Tantalum Note FDA 0 4 Digit No. of code (×1) (×1) (×1) (×1) (×1) (×2) (×2) (×2) (×2) (×2) Combination with 12th digit code “C, E, P, Q” are not available. A B C D E S T V W X 6, 7 Wetted cell body Note1 316 stainless steel Hast. C lining Monel lining 316 stainless steel Hast. C lining Monel lining Tantalum lining 316 stainless steel Hast. C lining Monel lining Tantalum lining 316 stainless steel Hast. C lining Monel lining Tantalum lining 1V 1H 1M 2V 2H 2M 2T 3V 3H 3M 3T 4V 4H 4M 4T 1.6…130 5…500 30…3000 9 Digital indicator Arrester Communication type None None Foundation Fieldbus None Yes Foundation Fieldbus Yes None Foundation Fieldbus Yes Yes Foundation Fieldbus None None Profibus None Yes Profibus Yes None Profibus Yes Yes Profibus None (for ordinary locations) TIIS, Flameproof (Conduit seal) TIIS, Flameproof (Cable gland seal) FM, Flameproof (or explosionproof) CSA, Flameproof (or explosionproof) ATEX, Flameproof ATEX, Intrinsic safty (Entity) SAA, Flameproof (or explosionproof) ATEX, FISCO A E P S R V T W 10 A B C D E X K F 4 Approval pending Approval pending Approval pending Approval pending Note4 11 12 Vent/drain Mounting bracket Standard None Standard Yes, stainless steel Side None Side Yes, stainless steel Extra SS tag plate Stainless steel elec. housing None None Yes None None Yes (*2) Yes Yes None None Yes None None Yes Yes Yes A C D F Coating of cell None None None None Yes Yes Yes Yes Note2 Y B C E M N P Q 15 12345678 9 10 11 12 13 14 15 21 Digit 13 14 15 21 Note 1: Note 2: Note 3: Note 4: Description Note Treatment Fill fluid Standard Silicone oil Degreasing Silicone oil NACE specification Silicone oil (7th digit code “T” and 15th digit code “A”, “B” are not available) Viton Note 3 (*3) Cr-Mo alloy hexagon socket head cap screw/carbon steel nut Cr-Mo alloy hexagon bolt/nut NACE bolt/nut (ASTM A193 B7M/A194 2HM) NACE bolt/nut (ASTM A320 L7M/A194 2HM) 304 stainless steel bolt/304 stainless steel nut High accuracy type (*1) (*2) (*3) (*4) FDA 0 4 Digit No. of code Y G N A A B C D E H 100: 1 turn down is possible, but should be used at a span greater than 1/40 of the maximum span for better performance. Customer tag number can be engraved on standard stainless steel name plate. If extra tag plate is required, select “Yes”. In case of tropical use, select stainless bolts and nuts. In case of 10th code is “4” (ATEX, FISCO), then the 9th code, E, S, V and W (with arrester option) are not available. 16 Level transmitter : FDE 12345678 9 10 11 12 13 14 15 21 Digit 4 Description Process connection Rc1/4 1/4-18NPT 1/4-18NPT 1/4-18NPT 1/4-18NPT Rc1/4 1/4-18NPT 1/4-18NPT 1/4-18NPT 1/4-18NPT Oval flange screw 7/16-20UNF 7/16-20UNF M10 M10 7/16-20UNF 7/16-20UNF 7/16-20UNF M10 M10 7/16-20UNF Conduit connection (×1) G 1/2 1/2-14NPT (×1) Pg13.5 (×1) M20×1.5 (×1) Pg13.5 (×1) (×2) G 1/2 1/2-14NPT (×2) Pg13.5 (×2) M20×1.5 (×2) Pg13.5 (×2) Note FDE 4 Digit No. of code Combination with 12th digit code “C, E, P, Q” are not available. A B C D E S T V W X 5 6 7 Material Size and rating 304 stainless JIS 10K 80A steel JIS 10K 100A JIS 30K 80A JIS 30K 100A ANSI/JPI 150LB 3" ANSI/JPI 150LB 4" ANSI/JPI 300LB 3" ANSI/JPI 300LB 4" DIN PN40 DN80 DIN PN16 DN100 JIS 20K 80A ANSI/JPI 600LB 3" Carbon steel JIS 10K 80A JIS 10K 100A JIS 30K 80A JIS 30K 100A ANSI/JPI 150LB 3" ANSI/JPI 150LB 4" ANSI/JPI 300LB 3" ANSI/JPI 300LB 4" DIN PN40 DN80 DIN PN16 DN100 316 stainless JIS 10K 80A steel ANSI/JPI 150LB 3B ANSI/JPI 150LB 4B ANSI/JPI 300LB 3B ANSI/JPI 300LB 4B ANSI/JPI 600LB 3B 0.32 32 1.3 130 5 500 LP side Wetted sensor Diaphragm Process cover body 316 stainless steel 316 stainless steel 316 stainless steel 316 stainless steel 316 stainless steel 316 stainless steel 316 stainless steel 316 stainless steel 316 stainless steel 316 stainless steel 316 stainless steel 316 stainless steel 316 stainless steel 316 stainless steel 316 stainless steel Note 1 0 1 2 3 4 5 6 7 8 9 M R A B C D E F G H J K S T U V W X 3 5 6 9 Hastelloy-C lining 316 stainless steel Hastelloy-C Monel lining 316 stainless steel Monel Tantalum lining 316 stainless steel Tantalum Hastelloy-C lining Hastelloy-C lining Hastelloy-C Monel lining Monel Monel lining Tantalum lining Tantalum Tantalum lining 316 stainless steel 316 stainless steel 316 stainless steel 316 stainless steel 316 stainless steel 316 stainless steel Digital indicator Arrester Communication type None None Foundation Fieldbus None Yes Foundation Fieldbus Yes None Foundation Fieldbus Yes Yes Foundation Fieldbus None None Yes Yes None Yes None Yes Profibus Profibus Profibus Profibus HP side Diaphragm and flange face 316 stainless steel Hastelloy-C Monel Tantalum Diaphragm: 316L stainless steel +Au coating Flange face: 316 stainless steel Hastelloy-C Monel Tantalum Hastelloy-C Monel Tantalum Note 3 Titanium Note 2, 3 Zirconium V C D E J H M T B L U P R A E P S R V T W 17 12345678 9 10 11 12 13 14 15 21 Digit 10 Description None (for ordinary locations) TIIS, Flameproof (Conduit seal) TIIS, Flameproof (Cable gland seal) FM, Flameproof (or explosionproof) CSA, Flameproof (or explosionproof) ATEX, Flameproof ATEX, Intrinsic safty (Entity) SAA, Flameproof (or explosionproof) ATEX, FISCO Note FDE 4 Digit No. of code A B C D E X K F 4 Approval pending Approval pending Approval pending Approval pending Note7 11 12 13 14 15 21 Extension [mm] Applicable material code 0 Any 50 100 (7th digit code “V“ only) 150 200 50 100 (7th digit code “C“, “H“, “B“, only) 150 200 Extra SS tag plate Stainless steel elec. housing Coating of cell None None None Yes None None None Yes None Note 4 Yes (* 4) Yes None None None Yes Yes None Yes None Yes Yes Yes Yes Yes Treatment Fill fluid Standard Silicone oil Standard Fluorinated oil Degreasing Silicone oil Fluorinated oil (7th digit code “V“ only) Oxygen service Fluorinated oil (7th digit code “C”, “E”, “H”, “T”, “B”, “U”) Chlorine service 7th digit code “V”, “C”, “H”, “B” High temp. 250°C High temp. 300°C (* 5) Note 5 High temp. and vacuum (250°C) 7th digit code “V” High temp. and vacuum (300°C) High temp. and high vacuum Silicone oil O-ring /Gasket Teflon membrane Viton (O-ring) None Teflon (gasket) None Viton (O-ring) Yes (5th digit code “0”, “2”, “4”, “6”, “8”, “A”, Teflon (gasket) Yes “C”, “E”, “G”, “J”, “M”, “R”, “S”, “T”, “V”, “X”, and 11th digit code “Y” are available. 13th digit code “H, J, S, T, K” are not available.) Note 6 (* 6) Cr-Mo alloy hexagon socket head cap screw/carbon steel nut Cr-Mo alloy hexagon bolt/nut 304 stainless steel bolt /304 stainless steel nut High accuracy type Low temperature effect type H+J (*1) (*2) (*3) (*4) (*5) (*6) (*7) Y A B C D E F G H Y B C E M N P Q Y W G A D H J S T K A B C D A B E H J K Note 1: Note 2: Note 3: Note 4: Note 5: Note 6: Note 7: 100: 1 turn down is possible, but should be used at a span greater than 1/40 of the maximum span for better performance. Material Code R; 6th digit code “6” is not available. 5th digit code “0, 2, 4, 6, 8, A, C, E, G, J, P, M, R, S, T, V, X” are available. Customer tag number can be engraved on standard stainless steel name plate. If extra tag plate is required, select “Yes” Treatment; None In case of tropical use, select stainless bolts and nuts. In case of 10th code is “4” (ATEX, FISCO), then the 9th code, E, S, V and W (with arrester option) are not available. 18 Remote seal type differential pressure transmitter : FDD 12345678 9 10 11 12 13 14 15 21 Digit 4 Description (×1) G 1/2 1/2-14NPT (×1) Combination with 12th digit code “C, E, P, Q” are not available. Pg13.5 (×1) M20 × 1.5 (×1) (×2) G 1/2 1/2-14NPT (×2) Pg13.5 (×2) M20 × 1.5 (×2) Mounting flange Flange size and rating 304 stainless JIS 10K 80A steel JIS 10K 100A JIS 30K 80A JIS 30K 100A ANSI/JPI 150LB 3" ANSI/JPI 150LB 4" ANSI/JPI 300LB 3" ANSI/JPI 300LB 4" DIN PN16/40 DN80 DIN PN16 DN100 JIS 20K 80A ANSI/JPI 600LB 3" Carbon steel JIS 10K 80A JIS 10K 100A JIS 30K 80A JIS 30K 100A ANSI/JPI 150LB 3" ANSI/JPI 150LB 4" ANSI/JPI 300LB 3" ANSI/JPI 300LB 4" DIN PN16/40 DN80 DIN PN16 DN100 316 stainless JIS 10K 80A steel ANSI/JPI 150LB 3" ANSI/JPI 150LB 4" ANSI/JPI 300LB 3" ANSI/JPI 300LB 4" ANSI/JPI 600LB 3" None 3 inch wafer (wafer type) 4 inch wafer 0.32.... 32 1.3...... 130 5......... 500 Diaphragm Flange face Diaph. extension [mm] 316L stainless 316 stainless 0 steel steel 50 100 (*2) 150 200 Hastelloy-C Hastelloy-C 0 50 100 150 200 316L stainless 316 stainless 0 +Au coating steel Monel Monel 0 Tantalum Tantalum 0 Titanium Titanium 0 (*3) Zirconium Zirconium 0 Digital indicator Arrester Communication type None None Foundation Fieldbus None Yes Foundation Fieldbus Yes None Foundation Fieldbus Yes Yes Foundation Fieldbus None None Yes Yes None Yes None Yes Profibus Profibus Profibus Profibus Note FDD A B C D S T V W 4 0 Digit No. of code 5 0 1 2 3 4 5 6 7 8 9 M R A B C D E F G H J K S T U V W X P Q Note 1 3 5 6 6 7 Note 2 V A B C D H F G K L J M T P R Note 3 9 A E P S R V T W 19 12345678 9 10 11 12 13 14 15 21 Digit 10 Description None (for ordinary locations) TIIS, Flameproof (Conduit seal) TIIS, Flameproof (Cable gland seal) FM, Flameproof (or explosionproof) CSA, Flameproof (or explosionproof) ATEX, Flameproof ATEX, Intrinsic safty (Entity) SAA, Flameproof (or explosionproof) ATEX, FISCO Note FDD 4 0 Digit No. of code A B C D E X K F 4 Approval pending Approval pending Approval pending Approval pending Note 8 11 12 13 14 21 Note 1: Note 2: Note 3: Note 4: Note 5: Note 6: Note 7: Note 8: Capillary Mounting bracket armor of capilary D Note 4 1.5 m 304 Stainless steel PVC (*4) E Note 4 3 304 Stainless steel PVC (*4) L Note 4 5 304 Stainless steel PVC (*4) F Note 4 6 304 Stainless steel PVC (*4) M Note 4 7 304 Stainless steel PVC (*4) N Note 4 8 304 Stainless steel PVC (*4) P Note 4 10 304 Stainless steel PVC (*4) Q Note 5 1.5 304 Stainless steel Stainless steel (*5) R Note 5 3 304 Stainless steel Stainless steel (*5) S Note 5 5 304 Stainless steel Stainless steel (*5) T Note 5 6 304 Stainless steel Stainless steel (*5) V Note 4 7 304 Stainless steel Stainless steel (*4) W Note 4 8 304 Stainless steel Stainless steel (*4) X Note 4 10 304 Stainless steel Stainless steel (*4) Extra SS tag plate Stainless steel elec. housing Coating of cell None None None Y Yes None None B None Yes None C (*6) Note 6 Yes Yes None E None None Yes M Yes None Yes N None Yes Yes P Yes Yes Yes Q Treatment Fill fluid Y Standard Silicone oil W Standard Fluorinated oil G Degreasing Silicone oil A Oxygen service Fluorinated oil (7th digit code “V”, “A”, “B”, “C” and “D”) D Chlorine service Fluorinated oil (7th digit code “H”, “F”, “G”, “K”, “L” and “T”) H High temp. 250°C Silicone oil J High temp. 300°C Silicone oil (*7) Note 7 High temp. and vacuum (250°C) Silicone oil 7th digit code “V”, “A”, “B”, S High temp. and vacuum (300°C) Silicone oil “C”, and “D” T High temp. and high vacuum Silicone oil K None Y Yes (Available for 5th digit code “0”, “2”, “4”, “6”, “8”, “A”, “C”, “E”, “G”, “J”, “P”, C “M”, “R”, “S”, “T”, “V”, “X” and 7th digit code “V”, “H”, “M”, “T”, “P”, “R”. Not available for the 13th digit code “H”, “J”, “S”, “T”, “K”.) H High accuracy type J Low temperature effect type K H+J (*1) 100: 1 turn down is possible, but should be used at a span greater than 1/40 of the maximum span for better performance. (*2) In case of 13th digit code “S”, “T”, “K” and 5th digit code “1”, “3”, “5”, “7”, “B”, “D”, “F”, “H”, “Q”, “K”, “U”, “W” are available. (*3) Available for 6th digit code “2, 3” and 5th digit code “0, 2, 4, 6, 8, A, C, E, G, J, P, M, R, S, T, W”. (*4) Available for 13th digit code “Y, W, G, A, D”. Inquire about in case of 13th other code. (*5) Available for 13th digit code “Y”, “W”, “G”, “A”, “D”, “H”, “J”, “S”, “T”, “K”. (*6) Customer tag number can be engraved on standard stainless steel name plate. If extra tag plate is required, select “Yes”. (*7) Treatment; Standard (*8) In case of 10th code is “4” (ATEX, FISCO), then the 9th code, E, S, V and W (with arrester option) are not available. 20 Remote seal type pressure transmitter : FDB 12345678 9 10 11 12 13 14 15 21 Digit 4 Description G1/2 (×1) 1/2-14NPT (×1) Combination with 12th digit code Pg13.5 (×1) “C, E, P, Q” are not available. M20 × 1.5 (×1) (×2) G1/2 1/2-14NPT (×2) Pg13.5 (×2) M20 × 1.5 (×2) Mounting flange Flange size and rating Ranges 123 45 304 stainless *** JIS 10K 80A steel *** JIS 10K 100A *** ANSI/JPI 150LB “3” *** ANSI/JPI 150LB “4” *** DIN PN16/40 DN80 *** DIN PN16 DN100 *** JIS 20K 80A *** JIS 30K 80A *** ANSI/JPI 300LB 3B *** ANSI/JPI 600LB 3B Carbon steel *** JIS 10K 80A *** JIS 10K 100A *** ANSI/JPI 150LB “3” *** ANSI/JPI 150LB “4” *** DIN PN16/40 DN80 *** DIN PN16 DN100 ** Screw type, JIS/ISO G1 316 stainless *** ANSI/JPI 150LB 3B steel *** ANSI/JPI 150LB 4B *** ANSI/JPI 300LB 3B *** ANSI/JPI 300LB 4B *** ANSI/JPI 600LB 3B None *** 3 inch wafer (wafer type) *** 4 inch wafer 1.3…130 5…500 30…3000 100…10000 Available only with material code “V” 500…50000 Diaphragm Flange face Diaph. extension [mm] 316L stainless 316 stainless 0 steel steel 50 100 (*3) 150 200 Hastelloy-C Hastelloy-C 0 50 100 150 200 316L stainless 316 stainless 0 +Au coating steel Monel Monel 0 Tantalum Tantalum 0 Titanium Titanium 0 (*4) Zirconium Zirconium 0 Digital indicator Arrester Communication type None None Foundation Fieldbus None Yes Foundation Fieldbus Yes None Foundation Fieldbus Yes Yes Foundation Fieldbus None None Yes Yes None Yes None Yes Profibus Profibus Profibus Profibus Note FDB A B C D S T V W 4 Digit No. of code 5 0 1 3 4 6 7 9 M S T A B D E G H K V W X Y U P Q Note 2 1 2 3 4 5 6 7 Note 1 Note 3 V (*1) A B C D H F G K L J M T P R Note 4 9 A E P S R V T W 21 12345678 9 10 11 12 13 14 15 21 Digit 10 Description None (for ordinary locations) TIIS, Flameproof (Conduit seal) TIIS, Flameproof (Cable gland seal) FM, Flameproof (or explosionproof) CSA, Flameproof (or explosionproof) ATEX, Flameproof ATEX, Intrinsic safty (Entity) SAA, Flameproof (or explosionproof) ATEX, FISCO Note FDB 4 Digit No. of code A B C D E X K F 4 Approval pending Approval pending Approval pending Approval pending Note 10 11 12 13 Capillary Mounting bracket Armor of capillary 1.5 m 304 Stainless steel PVC (*5) 3 304 Stainless steel PVC (*5) 5 304 Stainless steel PVC (*5) 6 304 Stainless steel PVC (*5) 7 304 Stainless steel PVC (*5) 8 304 Stainless steel PVC (*5) 10 304 Stainless steel PVC (*5) 1.5 304 Stainless steel Stainless steel (*6) 3 304 Stainless steel Stainless steel (*6) 5 304 Stainless steel Stainless steel (*6) 6 304 Stainless steel Stainless steel (*6) 7 304 Stainless steel Stainless steel (*5) 8 304 Stainless steel Stainless steel (*5) 10 304 Stainless steel Stainless steel (*5) Extra SS tag plate Stainless steel elec. housing Coating of cell None None None Yes None None None Yes None (*7) Yes Yes None None None Yes Yes None Yes None Yes Yes Yes Yes Yes Treatment Fill fluid Standard Silicone oil Standard Fluorinated oil Degreasing Silicone oil Oxygen service Fluorinated oil (7th digit code “V”, “A”, “B”, “C” and “D”) Chlorine service Fluorinated oil (7th digit code “H”, “F”, “G”, “K”, “L” and “T”) High temp. 250°C Silicone oil •Available for 6th digit code “1”, “2” or (* 8) High temp. 300°C Silicone oil “3”. In case of 13th code “S”, “T”, “K”, High temp. and vacuum (250°C) Silicone oil available for 6th digit code “2”, “3” only. High temp. and vacuum (300°C) Silicone oil •Available for 7th digit code “V”, “A”, High temp. and high vacuum Silicone oil “B”, “C” or “D”. Note 5 Note 5 Note 5 Note 5 Note 5 Note 5 Note 5 Note 6 Note 6 Note 6 Note 6 Note 5 Note 5 Note 5 D E L F M N P Q R S T V W X Note 7 Y B C E M N P Q 14 15 21 Note 8 None Yes (Available for the 5th digit code “0”, “2”, “3”, “5”, “6”, “8”, “A”, “C”, “D”, “F”, “G”, “J”, “P”, “R” and 7th digit code “V”, “H”, “M”, “T”, “P”, “R”. Not available for the 13th digit code “H”, “J”, “S”, “T”, “K”.) Note 9 (*9) None (6th digit code “1”, “2”, “3”) Cr-Mo alloy hexagon socket head cap screw/carbon steel nut (6th digit code Cr-Mo alloy hexagon bolt/carbon steel unit “4”, “5”) 304 stainless steel/304 stainless steel (6th digit code “4”) 630 stainless steel/304 stainless steel (6th digit code "5") High accuracy type Low temperature effect type H+J Y W G A D H J S T K Y C Y A B E F H J K Note 1: (*1) If range 4 or 5 is selected, specify material “V” in any cases. Note 2: (*2) 100: 1 turn down is possible, but should be used at a span greater than 1/40 of the maximum span for better performance. Note 3: (*3) Available for 13th digit code “S”, “T”, “K” and 5th digit code “1“,“4“,“7“,“B“,“E“,“H“,“Q“,“T“,“W“,“Y“. Note 4: (*4) Available for 6th digit code "2",“3“ and 5th digit “0“,“3“,“6“,“9“,“A“,“D“,“G“,“P“, “M“,“S“,“T“,“U“,“V“,“X“. Note 5: (*5) Available for 13th digit code “Y, W, G, A, D”. Inquire about in case of 13th other code. Note 6: (*6) Available for 13th digit code “Y”, “W”, “G”, “A”, “D”, “H”, “J”, “S”, “T”, “K”. Note 7: (*7) Customer tag number can be engraved on standard stainless steel name plate. If extra tag plate is required, select “Yes”. Note 8: (*8) Treatment; Standard Note 9: (*9) In case of tropical use, select stainless bolts and nuts. Note 10:(*10) In case of 10th code is “4” (ATEX, FISCO), then the 9th code, E, S, V and W (with arrester option) are not available. 22 Small frange type level transmitter : FDY 12345678 9 10 11 12 13 14 15 21 Digit 4 Description Conduit Oval flange Process connection screw connection 7/16-20UNF (×1) G 1/2 Rc1/4 1/4-18NPT 7/16-20UNF 1/2-14NPT (×1) 1/4-18NPT M10 (or M12) Pg13.5 (×1) 1/4-18NPT M10 (or M12) M20×1.5 (×1) 1/4-18NPT 7/16-20UNF Pg13.5 (×1) 7/16-20UNF (×2) Rc1/4 G 1/2 1/4-18NPT 7/16-20UNF 1/2-14NPT (×2) 1/4-18NPT M10 (or M12) Pg13.5 (×2) 1/4-18NPT M10 (or M12) M20×1.5 (×2) 1/4-18NPT 7/16-20UNF Pg13.5 (×2) Material Size and rating 304 stainless JIS 10K 40A steel JIS 10K 50A JIS 20K 40A JIS 20K 50A JIS 30K 40A JIS 30K 50A ANSI/JPI 150LB 11/2" ANSI/JPI 150LB 2" ANSI/JPI 300LB 11/2" ANSI/JPI 300LB 2" Carbon steel JIS 10K 40A JIS 10K 50A JIS 20K 40A JIS 20K 50A JIS 30K 40A JIS 30K 50A ANSI/JPI 150LB 11/2" ANSI/JPI 150LB 2" ANSI/JPI 300LB 11/2" ANSI/JPI 300LB 2" 3 130 12.5 500 LP side Diaphragm Wetted sensor Process cover body 316 stainless steel 316 stainless steel 316 stainless steel 316 stainless steel 316 stainless steel 316 stainless steel Note FDY 4 Digit No. of code Combination with 12th digit code “C, E, P, Q” are not available. A B C D E S T V W X 5 0 1 2 3 4 5 A B C D G H J K L M Q R S T Note1 5 6 6 7 HP side Diaphragm & flange face 316 stainless steel Diaphragm: 316L stainless steel +Au coating 316 stainless steel 316 stainless steel 316 stainless steel Hastelloy-C 316 stainless steel 316 stainless steel 316 stainless steel Monel 316 stainless steel 316 stainless steel 316 stainless steel Tantalum Flange face: 316 stainless steel Hastelloy-C lining Hastelloy-C 316 stainless steel Hastelloy-C Monel lining Monel 316 stainless steel Monel Tantalum lining Tantalum 316 stainless steel Tantalum Hastelloy-C lining Hastelloy-C Hastelloy-C lining Hastelloy-C Monel Monel lining Monel Monel lining Tantalum Tantalum lining Tantalum Tantalum lining Digital indicator Arrester Communication type None None Foundation Fieldbus None Yes Foundation Fieldbus Yes None Foundation Fieldbus Yes Yes Foundation Fieldbus None None Yes Yes None Yes None Yes Profibus Profibus Profibus Profibus V J C D E H M T B L U 9 A E P S R V T W 23 12345678 9 10 11 12 13 14 15 21 Digit 10 Description None (for ordinary locations) TIIS, Flameproof (Conduit seal) TIIS, Flameproof (Cable gland seal) FM, Flameproof (or explosionproof) CSA, Flameproof (or explosionproof) ATEX, Flameproof ATEX, Intrinsic safty (Entity) SAA, Flameproof (or explosionproof) ATEX, FISCO Note FDY 4 Digit No. of code A B C D E X K F 4 Approval pending Approval pending Approval pending Approval pending Note 4 11 12 13 14 15 21 Extension [mm] Applicable material code 0 Any 50 100 (7th digit code “V” only, 11/2 in. flange is not applicable) 150 200 Extra SS tag plate Stainless steel elec. housing Coating of cell None None None Yes None None None Yes None Yes (*2) Yes None Note 2 None None Yes Yes None Yes None Yes Yes Yes Yes Yes Treatment Fill fluid Standard Silicone oil Standard Fluorinated oil Degreasing Silicone oil Oxygen service Fluorinated oil (7th digit code “V” only) Chlorine service Fluorinated oil (7th digit code “C”, “E”, “H”, “T”, “B”, “U”) High temp. 250°C Silicone oil (7th digit code “V” only) High temp. and vacuum (250°C) Silicone oil (7th digit code “V” only) O-ring / Gasket Teflon membrane Viton (O-ring) None Teflon (gasket) None Viton (O-ring) Yes (11th digit code “Y” only) Teflon (gasket) Yes (13th digit code “H”, “S” are not available.) (*3) Note 3 Cr-Mo alloy hexagon socket head cap screw/carbon steel nut Cr-Mo alloy hexagon bolt/nut 304 stainless steel bolt / 304 stainless steel nut High accuracy type Low temperature effect type H+J Y A B C D Y B C E M N P Q Y W G A D H S A B C D A B E H J K Note 1: (*1) 100: 1 turn down is possible for model FDY, but should be used at a span greater than 1/40 of the maximum span for better performance. Note 2: (*2) Customer tag number can be engraved on standard stainless steel name plate. If extra tag plate is required, select “Yes”. Note 3: (*3) In case of tropical use, select stainless bolts and nuts. Note 4: (*4) In case of 10th code is “4” (ATEX, FISCO), then the 9th code, E, S, V and W (with arrester option) are not available. 24 Small frange remote seal type differential pressure transmitter : FDX 12345678 9 10 11 12 13 14 15 16 17 18 19 20 21 Digit 4 Description (×1) G 1/2 1/2 - 14NPT (×1) Combination with 12th digit code Pg13.5 (×1) “C, E, P, Q” are not available. M20 × 1.5 (×1) (×2) G 1/2 1/2 - 14NPT (×2) Pg13.5 (×2) M20 × 1.5 (×2) Material Size and rating 304 stainless JIS 10K 40A steel JIS 10K 50A JIS 20K 40A JIS 20K 50A JIS 30K 40A JIS 30K 50A ANSI/JPI 150LB 1 1/2" ANSI/JPI 150LB 2" ANSI/JPI 300LB 1 1/2" ANSI/JPI 300LB 2" Carbon steel JIS 10K 40A JIS 10K 50A JIS 20K 40A JIS 20K 50A JIS 30K 40A JIS 30K 50A ANSI/JPI 150LB 1 1/2" ANSI/JPI 150LB 2" ANSI/JPI 300LB 1 1/2" ANSI/JPI 300LB 2" None 40A, 1 1/2B (Wafer type) 50A, 2B Direct mounting adapter connection (* 1) 3........130 12.5...500 Flange face Diaphragm extension(mm) Diaphragm 0 316L stainless steel 316 stainless steel 50 100 (*2) 150 200 0 316L stainless steel +Au coating Hastelloy-C 0 Hastelloy-C Monel 0 Monel Tantalum 0 Tantalum Digital indicator Arrester Communication type None None Foundation Fieldbus None Yes Foundation Fieldbus Yes None Foundation Fieldbus Yes Yes Foundation Fieldbus None None Profibus None Yes Profibus Yes None Profibus Yes Yes Profibus None (for ordinary locations) TIIS, Flameproof (Conduit seal) TIIS, Flameproof (Cable gland seal) FM, Flameproof (or explosionproof) CSA, Flameproof (or explosionproof) ATEX, Flameproof ATEX, Intrinsic safty (Entity) SAA, Flameproof (or explosionproof) ATEX, FISCO Note FDX A B C D S T V W 4 Digit No. of code 5 Note 1 0 1 2 3 4 5 A B C D G H J K L M Q R S T W X Y 5 6 6 7 Note 2 V A B C D J H M T 9 A E P S R V T W 10 A B C D E X K F 4 Approval pending Approval pending Approval pending Approval pending Note 5 25 12345678 9 10 11 12 13 14 15 16 17 18 19 20 21 Digit 11 Description mounting bracket Capillary armor of capillary Stainless steel 1.5m PVC 3m 5m 1.5m Stainless steel 3m 5m Note FDX 4 Digit No. of code (*4) Note4 D E L Q R S 12 13 14 Stainless steel elec. housing Coating of cell Extra tag tag plate None None None Yes None None Note3 None Yes None (*3) Yes Yes None None None Yes Yes None Yes None Yes Yes Yes Yes Yes Treatment Fill fluid Standard Silicone oil (for general use) Fluorinated oil Standard Degreasing Silicone oil Fluorinated oil (7th digit code “V”, “A”, “B”, “C” and “D”) Oxygen service Chlorine service Fluorinated oil (7th digit code “H” and “T”) High temp. 250°C Silicone oil (7th digit code “V”, “A”, “B”, “C” and “D”) High temp. and vacuum (250°C) Silicone oil None Yes (Available for 7th digit code “V”, “H”, “M”, “T”. Not available for 5th digit code “Y” and 13th digit code “H”, “S”.) Y B C E M N P Q Y W G A D H S Y C Note 1: (*1) Note 2: (*2) Note 3: (*3) Note 4: (*4) Note 5: (*5) Direct mounting adapter type is specified at 16th to 20th digit. Direct mounting adapter is available only for 7th digit code “V”. Diaphragm extension is available only for 2" (50A) flanges. Customer tag number can be engraved on standard stainless steel name plate. If extra tag plate is required, select “Yes”. Availalde for 13th digit code “Y, W, G, A, D”. Inquire about in case of 13th other code. In case of 10th code is “4” (ATEX, FISCO), then the 9th code, E, S, V and W (with arrester option) are not available. Specifications of Direct Mounting Adapter {for 15, 20A (1/2, 3/4”) connection} and others Note 1. When odering the instrument with direct mounting adapter, specify “Y” in the 5th digit of Code Symbol, and specify 16th digit to 20th digit. When odering the instrument without direct mounting adapter, nothing should be filled in the 16th to 20th digit. 2. Unless otherwise described in the specifications, leave the 21st digit blank. 12345678 9 10 11 12 13 14 15 16 17 18 19 20 21 Digit Description 16, 17 JIS 10K 15A JIS 10K 20A JIS 20K 15A JIS 20K 20A JIS 30K 15A JIS 30K 20A ANSI/JPI 150LB 1/2" ANSI/JPI 150LB 3/4" ANSI/JPI 300LB 1/2" ANSI/JPI 300LB 3/4" Screw connection Rc1/2 Screw connection Rc3/4 Screw connection Rc1/2 - 14NPT Screw connection Rc3/4 - 14NPT 18 Adapter Bolts/nuts (* 1) 316 Stainless Steel Cr-Mo steel/carbon steel 19 Standard Long type 20 Standard (Teflon) (Only Y, W, G, A and D can be specified on 13th digit). For high temperature (spiral gasket) (Only H and S can be specified on 13th digit). 21 High accuracy type Low temperature effect type H+J Note FDX 4 0 11 12 21 22 31 32 1H 1T 2H 2T SR S2 SN ST Digit No. of code Note 1 W A N 1 2 H J K Note (*1) For connection of transmitter receiving pressure unit and direct mounting adapter 26 Small frange remote seal type pressure transmitter : FDW 12345678 9 10 11 12 13 14 15 16 17 18 19 20 21 Digit 4 Description (×1) G1/2 1/2 - 14NPT (×1) Combination with 12th digit code Pg13.5 (×1) “C, E, P, Q” are not available. M20×1.5 (×1) (×2) G1/2 1/2 - 14NPT (×2) Pg13.5 (×2) M20 X 1.5 (×2) Material Size and rating 304 stainless JIS 10K 40A steel JIS 10K 50A JIS 20K 40A JIS 20K 50A JIS 30K 40A JIS 30K 50A JIS 63K 40A JIS 63K 50A ANSI/JPI 150LB 1 1/2" ANSI/JPI 150LB 2" ANSI/JPI 300LB 1 1/2" ANSI/JPI 300LB 2" ANSI/JPI 600LB 1 1/2" ANSI/JPI 600LB 2" Carbon steel JIS 10K 40A JIS 10K 50A JIS 20K 40A JIS 20K 50A JIS 30K 40A JIS 30K 50A JIS 63K 40A JIS 63K 50A ANSI/JPI 150LB 1 1/2" ANSI/JPI 150LB 2" ANSI/JPI 300LB 1 1/2" ANSI/JPI 300LB 2" ANSI/JPI 600LB 1 1/2" ANSI/JPI 600LB 2" None 40A, 1 1/2B (Wafer type) 50A, 2B Direct mounting adapter connection (* 1) 50.....3000 250...10000 Diaphragm extension (mm) Flange face Diaphragm 0 316L stainless steel 316 stainless steel 50 100 (* 2) 150 200 0 316L stainless steel +Au coating 0 Hastelloy-C Hastelloy-C 0 Monel Monel 0 Tantalum Tantalum Digital indicator Arrester Communication type None None Foundation Fieldbus None Yes Foundation Fieldbus Yes None Foundation Fieldbus Yes Yes Foundation Fieldbus None None Yes Yes None Yes None Yes Profibus Profibus Profibus Profibus Note F DW A B C D S T V W 4 0 Digit No. of code 5 Note 1 0 1 2 3 4 5 6 7 A B C D E F G H J K L M N P Q R S T U V W X Y 3 4 6 7 Note 2 V A B C D J H M T 9 A E P S R V T W 27 12345678 9 10 11 12 13 14 15 16 17 18 19 20 21 Digit 10 Description None (for ordinary locations) TIIS, Flameproof (Conduit seal) TIIS, Flameproof (Cable gland seal) FM, Flameproof (or explosionproof) CSA, Flameproof (or explosionproof) ATEX, Flameproof ATEX, Intrinsic safty (Entity) SAA, Flameproof (or explosionproof) ATEX, FISCO Note F DW 4 Digit No. of code A B C D E X K F 4 Approval pending Approval pending Approval pending Approval pending Note6 11 12 13 14 15 Mounting bracket Capillary Armor of Capillary Stainless steel 1.5m PVC (*5) Note5 3m 5m 1.5m Stainless steel 3m 5m Stainless steel elec. housing Coating of cell Extra SS tag plate None None None Yes None None None Yes None (*3) Note3 Yes Yes None None None Yes Yes None Yes None Yes Yes Yes Yes Yes Treatment Fill fluid Standard Silicone oil Standard Fluorinated oil Degreasing Silicone oil Fluorinated oil (7th digit code “V”, “A”, “B”, “C” and “D”) Oxygen service Chlorine service Fluorinated oil (7th digit code “H” and “T”) High temp. 250°C Silicone oil High temp. and vacuum (250°C) Silicone oil None Yes (Available for 7th digit code “V”, “H”, “M”, “T”. Not availalbe for 5th digit code “Y”, and 13 digit code “H”, “S”.) Note4 (*4) None 6th digit code “3” Cr-Mo alloy hexagon socket head cap bolt/ carbon steel nut 6th digit code “4” Cr-Mo alloy hexagon bolt/carbon steel nut 304 stainless steel bolt/304 stainless steel nut D E L Q R S Y B C E M N P Q Y W G A D H S Y C Y A B E Note 1: (*1) Note 2: Note 3: Note 4: Note 5: (*2) (*3) (*4) (*5) Note 6: (*6) Direct mounting adapter type is specified at 16th to 20th digit. Direct mounting adapter is available only for 7th digit code “V”. Diaphragm extension is available only for 2" (50A) flanges. Customer tag number can be engraved on standard stainless steel name plate. If extra tag plate is required, select “Yes”. In case of tropical use, select stainless bolts and nuts. Available for 13th digit code “Y, W, G, A, D”. Inquire about in case of 13th other code. In case of 10th code is “4”(ATEX, FISCO), then the 9th code, E, S, V and W (with arrester option) are not available. 28 Specifications of Direct Mounting Adapter {for 15, 20A (1/2, 3/4”) connection} and others Note 1. When odering the instrument with direct mounting adapter, specify “Y” in the 5th digit of Code Symbol, and specify 16th digit to 20th digit. When odering the instrument without direct mounting adapter, nothing should be filled in the 16th to 20th digit. 2. Unless otherwise described in the specifications, leave the 21st digit blank. 12345678 9 10 11 12 13 14 15 16 17 18 19 20 21 Digit Description Note 16, 17 JIS 10K 15A JIS 10K 20A JIS 20K 15A JIS 20K 20A JIS 30K 15A JIS 30K 20A JIS 63K 15A JIS 63K 20A ANSI/JPI 150LB 1/2" ANSI/JPI 150LB 3/4" ANSI/JPI 300LB 1/2" ANSI/JPI 300LB 3/4" ANSI/JPI 600LB 1/2" ANSI/JPI 600LB 3/4" Screw connection Rc1/2 Screw connection Rc3/4 Screw connection Rc1/2 - 14NPT Screw connection Rc3/4 - 14NPT 18 Note 1 Adapter Bolts/nuts (* 1) 316 Stainless Steel Cr-Mo steel/carbon steel 19 Standard Long type 20 Standard (Teflon)(Only Y, W, G, A and D can be specified on 13th digit). For high temperature (spiral gasket) (Only H and S can be specified on 13th digit). 21 High accuracy type F DW 4 11 12 21 22 31 32 61 62 1H 1T 2H 2T 4H 4T SR S2 SN ST Digit No. of code W A N 1 2 H Note1: (* 1) For connection of transmitter receiving pressure unit and direct mounting adapter 29 ORDERING INFORMATION When ordering this instrument, specify: 1. CODE SYMBOLS 2. Calibration range (XD_SCALE) and unit (CAL_UNIT) • Unless specified, the range is maximum span. 3. Output scale and unit (OUT_SCALE) • Unless specified, the scale is the same as the calibration range. 4. Output mode (L_TYPE) • Select any of Direct/Indirect Linear/Indirect SORT. • Unless otherwise specified, q In case of output scale in flow rates Indirect SORT (extraction output) w In case of other units Indirect linear (proportional output) 5. Low flow rate cut point (specify only when needed for flow measurement) • Specify in percentages of output scale 6. Output orientation (burnout direction) when abnormality is occurred in the transmitter. Select Hold / Overscale / Underscale. Unless specified, output hold function is supplied. 7. Setting of external zero adjustment SW • Select either of “valid” and “invalid” • Unless otherwise specified, “valid” is selected. 8. Tag No. • Up to 26 alphanumerical characters. • Unless otherwise specified, the tag No. is EFB002 (but, not stamped). 9. Node address (if required) • Unless specified, “0 × F0”(Foundation Fieldbus), “0 × 03”(Profibus) 10. Display scale and unit (specify only for the transmitter with a digital indicator) • For the settable range, contact Fuji Electric Co. Ltd. • No low flow cut is performed • Unless otherwise specified, it conforms to the output scale. 30 OUTLINE DIAGRAM OF EACH STANDARD MODEL (Unit:mm) Differential pressure / flow transmitter : FDC < 7th digit code without : B, L, U > Note 2) Vent/drain plug (When the vent/drain plug attatched on the upper side of the detector) MTG. pipe JIS 50A (2B) “B” Conduit conn.2 “A” Press. conn. In case of 4th digit code “S,V,W,X” Zero ADJ. screw (10) Fastener (Flameproof only) 130 120 43.5 ø80 Up 105 123 52.5 Down 88 U-bolt M8 38 58 37 237 Vent/drain plug Note 1) Cable gland (option) “B” Conduit conn.1 “C” Conduit conn. 4 Holes 9 Dia. 154 Detail “A” (Press. conn.) ø18.5 H 2.5 Detail “B” (Conduit conn.) ø15 Detail “C” Earth terminal ø13 59 43 ø80 Electronics unit 70 8 F Oval flange screw See table 1 17 E 41.3 ø7 D See table 1 See table 1 G 1/2 Press.conn. (Low pressure side) 4-M8 12 4th digit of the code symbols 231 Side vent (option) Sensor unit Press.conn. (High pressure side) Conduit conn. D E F G1/2 1/2-14NPT Press. conn. H Rc1/4 1/4-18NPT 1/4-18NPT 1/4-18NPT 1/4-18NPT Oval flange screw 7/16-20UNF A, S B, T C, V D, W E, X 17 16 8 16 8 8 5 4.5 5 4.5 Pg13.5 M20 1.5 Pg13.5 Screw depth 15 7/16-20UNF Screw depth 15 M10 Screw depth 15 M10 Screw depth 15 7/16-20UNF Screw depth 15 54 70 104 Table 1 Note 1) Cable gland is supplied in case of flameproof packing type. ø11 cable is suitable. Note 2) The pressure connector is located on the down side surface of the detector, when the vent /drain plug is attatched on the upper side of the detector. CONNECTION DIAGRAM CK CK (M4 screws) Do not connect. Field bus 31 Differential pressure / flow transmitter : FDC < 7th digit code : B, L, U > “A” or “B” Press. conn. MTG. pipe JIS 50A (2B) U-bolt M8 Oval flange screw See table 1 “C” Conduit conn.2 Zero ADJ. screw In case of 4th digit code “S,V,W,X” 41.3 (10) Fastener (Flameproof only) Up ø80 52.5 Down 88 120 Note 1) 38 58 4 Holes 9 Dia. 40 240 Vent/drain plug “C” Conduit conn.1 Cable gland (option) “D” Conduit conn. 186 91 Detail “A” (Press. conn.) ø16 Detail “C” (Conduit conn.) ø15 Detail “D” ø13 Electronics unit 43 Earth terminal 2 -0.1 ø12 1 0 +0.2 +0.1 H F 17 ø80 105 70 ø4 Detail “B” (Press. conn) ø16 1/4-18NPT E See table 1 G 1/2 234 Sensor unit Press.conn. (Low pressure side) 4-M8 12 Press.conn. (High pressure side) 10 54 70 ø4 4th digit of the code symbols 104 E G1/2 Conduit conn. F H 17 16 8 16 8 8 5 4.5 5 4.5 Oval flange screw 7/16-20UNF A, S B, T C, V D, W E, X CONNECTION DIAGRAM CK CK (M4 screws) 1/2-14NPT Pg13.5 M20 1.5 Pg13.5 Screw depth 10 7/16-20UNF Screw depth 10 M10 Screw depth 10 M10 Screw depth 10 7/16-20UNF Screw depth 10 Do not connect. Field bus Table 1 Note 1) Cable gland is supplied in case of 10th digit code “C”. ø11 cable is suitable. 32 Pressure transmitter : FDG < 7th digit code without : B, L, U > Note2) Vent/drain plug (When the vent/drain plug attached on the upper side of the detector) “B” Conduit conn.2 MTG. Pipe JIS 50A (2B) Zero ADJ. screw “A” Press. conn. In case of 4th digit code “S,V,W,X” Fastener (Flameproof only) (10) 130 104 43.5 ø80 Up 105 123 52.5 Down 88 U - bolt M8 38 58 37 Vent/drain plug 237 216 (6th digital code “5”) Note1) Cable gland (option) “B” Conduit conn.1 “C” Conduit conn. 4 holes 9 dia. 154 Detail “A” (Press. conn.) ø18.5 H 2.5 Detail “B” (Conduit conn.) ø15 Detail “C” Earth terminal 59 43 ø13 Electronics unit D See table 1 See table 1 G 1/2 41.3 ø7 231 210 (6th digit code “5”) E 17 Oval flange screw See table 1 8 F ø80 Sensor unit 70 Side vent (option) 4-M8 12 4th digit of the code symbols A, S B, T C, V D, W E, X G1/2 Conduit conn. D E F 17 16 8 16 8 8 5 4.5 5 4.5 Press.conn. H Rc1/4 1/4-18NPT 1/4-18NPT 1/4-18NPT 1/4-18NPT Oval flange screw 7/16-20UNF Screw depth15 7/16-20UNF 1/2-14NPT Pg13.5 M20 1.5 Pg13.5 Screw depth15 M10 Screw depth15 M10 Screw depth15 7/16-20UNF Screw depth15 27 54 70 104 Table 1 Note1) Note2) Cable gland is supplied in case of flamproof packing type. ø11 cable is suitable. The pressure connector is located on the down side surface of the detector, when the vent / drainplug is attatched on the upper side of the detector. Field bus CONNECTION DIAGRAM CK CK (M4 screws) Do not connect. 33 Pressure transmitter : FDG < 7th digit code : B, L, U > (10) MTG. Pipe JIS 50A (2B) Zero ADJ. screw U - bolt M8 In case of 4th digit code “S,V,W,X” “C” Conduit conn.2 Fastener (Flameproof only) ø80 105 104 43.5 Up 70 52.5 Down 58 4 holes 9 dia. 40 240 “C” Conduit conn.1 88 38 Cable gland (option) Note) “D” Conduit conn. 155 Detail “A” (Press. conn.) 4th digit code “A. S” ø16 ø12 +0.1 1 2 -0.1 +0.2 0 Detail “C” (Conduit conn.) ø15 Detail “D” ø13 Earth terminal 60 43 ø80 Electronics unit H ø4 E See table 1 Detail “B” 4th digit code “B,C,D,E,T,V,W,X” ø16 1/4-18NPT F 234 G1/2 17 P View from P 4-M8 12 “A” or “B” Press. conn. Vent/drain plug Sensor unit 10 41.3 54 70 ø4 Conduit conn. D E F G1/2 1/2-14NPT Oval flange screw See table 1 Oval flange screw 7/16-20UNF Screw depth10 7/16-20UNF Screw depth10 M10 Screw depth10 M10 Screw depth10 7/16-20UNF Screw depth10 98 104 4th digit of the code symbols A, S B, T C, V D, W E, X 17 16 8 16 8 8 5 4.5 5 4.5 CONNECTION DIAGRAM CK CK (M4 screws) Pg13.5 M20 1.5 Pg13.5 Do not connect. Field bus Table 1 Note) Cable gland is supplied in case of 10th digit code “C”. ø11 cable is suitable. 34 Absolute pressure transmitter : FDA Vent/drain plug Note2) (When the nent/drain plug attached on the upper side of the detector) MTG. Pipe JIS 50A (2B) In case of 4th digit code “S,V,W,X” “B” Conduit conn.2 (10) Fastener (Flameproof only) Zero ADJ. screw “A” Press. conn. 105 123 104 43.5 ø80 Up 52.5 Down U - bolt M8 88 38 58 37 237 Vent / Drain Plug Cable gland (option) Note1) 4 holes 9 dia. “B” Conduit conn.1 “C” Conduit conn. 155 60 43 Detail “A” (Press. conn.) ø7 Datail “B” (Conduit conn.) ø15 Detail “C” Earth terminal Electronics unit ø13 Oval flange screw See table 1 8 F 17 231 Sensor unit E H ø18.5 See Table 1 D See Table 1 G 1/2 41.3 2.5 2-M8 12 Side vent (option) 4th digit of the code symbols A, S B, T C, V D, W E, X G1/2 Conduit conn. D E F 17 16 8 16 8 8 5 4.5 5 4.5 Press.conn. H Rc1/4 1/4-18NPT 1/4-18NPT 1/4-18NPT 1/4-18NPT Oval flange screw 7/16-20UNF 27 70 120 50 1/2-14NPT Pg13.5 M20 1.5 Pg13.5 screw depth15 7/16-20UNF screw depth15 M10 screw depth15 M10 screw depth15 7/16-20UNF screw depth15 Table 1 Note1) Note2) Cable gland is supplied in case of flamproof packing type. CONNECTION DIAGRAM CK CK (M4 screws) ø11 cable is suitable. The pressure connector is located on the down side surface of the detector, when the vent / drainplug is attached on the upper side of the detector. Field bus Do not connect. ø80 70 35 Level transmitter : FDE < 7th digit code without : B, L, U > Vent / drain plug Note 2) (When the vent /drain plug attatched on the upper side of the detector) Flange : ANSI/JPI -150LB-3B “A” L.P. conn. In case of 4th digit code “S, V, W, X” Zero ADJ.screw “B” Conduit conn.2 Fastener (Flameproof only) (10) N holes h dia ø80 43.5 Up 52.5 105 Down L2 L1 Vent / drain plug L 20 Inner of gasket t 41.3 Oval flang screw See table 1 Detail “A” (L.P conn.) ø18.5 “B” Conduit conn.1 88 Note 1) Cable gland (option) “C” Conduit conn. Detail “B” (Conduit conn.) Detail “C” 2.5 48 J 59 27 ø15 ø13 43 143 8 MN øD øE øF øG øH ø7 See table 1 11th degit code Y K See table 1 L (mm) 0 50 100 150 200 Mass apprpx. (kg) 9.5 10 ~ 13 ~ 17 G1/2 L3 H.P. conn. Earth terminal Sensor unit Electronics unit L1 360 L2 160 L3 296 A E B F 10.5 ~ 17.5 354 11 ~ 18 154 290 øD 185 200 210 210 240 191 210 210 229 254 200 220 øE 150 160 170 175 195 152.5 168 168 190.5 200 160 180 øF 126 126 126 151 151 126 126 126 151 151 126 151 øG 100 100 100 103 103 100 100 100 103 103 100 103 øH 73 73 73 96 96 73 73 73 96 96 73 96 t 38 42 48 38 52 44 49 52 44 52 44 40 N-øh 8-19 8-23 8-23 8-19 8-25 4-20 8-23 8-23 8-20 8-23 8-18 8-18 (Flange) JIS-10K-80A JIS-20K-80A JIS-30K-80A JIS-10K-100A JIS-30K-100A ANSI-150LB-3B C G D H 11.5 ~ 18.5 4th digit of the code symbols A, S B, T Conduit conn. K MN G1/2 1/2-14NPT Press.conn. J Rc1/4 1/4-18NPT 1/4-18NPT 1/4-18NPT 1/4-18NPT Oval flage screw 7/16-20UNF 17 8 16 5 8 4.5 ANSI-300LB-3B ANSI-600LB-3B ANSI-150LB-4B ANSI-300LB-4B DIN DIN PN40 PN16 DN80 DN100 C, V D, W E, X Pg13.5 M20 1.5 Pg13.5 16 5 8 4.5 Screw depth15 7/16-20UNF Screw depth15 M10 Screw depth15 M10 Screw depth15 7/16-20UNF Screw depth15 Table 1 Note 1) Cable grand is suppled in case of flamproof packing type. ø11 cable is suitable. Note 2) The pressure connector is located on the down side surface of the detector, when the vent / detector. CONNECTION DIAGRAM CK CK (M4 screws) Do not connect. Field bus 36 17 ø80 Level transmitter : FDE < 7th digit code : B, L, U > Oval flange screw See table 1 “A” or “B” L.P. conn. 41.3 Zero ADJ.screw N holes h dia (10) In case of 4th digit code “S, V, W, X” Fastener (Flameproof only) Flange : ANSI/JPI -150LB-3B ø80 107 52.5 105 Down 88 L2 L1 Vent / drain plug L 20 Inner of gasket 40.5 91 Note 1) Cable gland (option) “C” Conduit conn.1 Earth terminal Detail “A” (L.P. conn.) 4th digit code “S” ø16 186 2 -0.1 +0.2 0 “D” Conduit conn. t Detail “B” (L.P conn.) ø16 1/4-18NPT 10 ø12 +0.1 1 øG øD øE øF øH 46.4 43 ø4 L3 H.P. conn. Sensor unit 11th degit code Y A E B F C G D H L (mm) 0 50 100 150 200 Mass apprpx. (kg) 11.5 ~ 15 12 ~ 19 Detail “C” (Conduit conn.) Electronics unit ø15 MN Detail “D” ø13 350 150 286 CONNECTION DIAGRAM CK CK (M4 screws) K See table 1 G1/2 12.5 ~ 19.5 344 13 ~ 20 144 290 Do not connect. Field bus øH 73 73 73 96 96 73 73 73 96 96 73 96 t 38 42 48 38 52 44 49 52 44 52 44 40 N-øh 8-19 8-23 8-23 8-19 8-25 4-20 8-23 8-23 8-20 8-23 8-18 8-18 (Flange) JIS-10K-80A JIS-20K-80A JIS-30K-80A JIS-10K-100A JIS-30K-100A ANSI-150LB-3B ANSI-300LB-3B ANSI-600LB-3B ANSI-150LB-4B ANSI-300LB-4B DIN DIN PN40 PN16 DN80 DN100 13.5 ~ 20.5 øD 185 200 210 210 240 191 210 210 229 254 200 220 øE 150 160 170 175 195 152.5 168 168 190.5 200 160 180 øF 126 126 126 151 151 126 126 126 151 151 126 151 øG 100 100 100 103 103 100 100 100 103 103 100 103 4th digit of the code symbols A, S B, T C, V D, W E, X Conduit conn. K MN G1/2 1/2-14NPT Oval flage screw 7/16-20UNF Screw depth10 7/16-20UNF Screw depth10 M10 Screw depth10 M10 Screw depth10 7/16-20UNF Screw depth10 17 8 16 5 8 4.5 Pg13.5 M20 1.5 Pg13.5 16 5 8 4.5 Table 1 Note 1) Cable grand is suppled in case of 10th digit code “C”. ø11 cable is suitable. 17 L1 L2 L3 ø80 Up 37 Remote seal type differential pressure transmitter : FDD In case of 4th digit code “S,V,W” MTG. pipe JIS 50A (2B) “A” Conduit conn.2 U-bolt M8 Fastener (Flamproof only) ø80 (10) Up Zero ADJ. screw 105 52.5 Down 38 4 holes 9 dia. 28 88 104 “B” Conduit conn. 228 “A” Conduit conn. 1 Cable gland (option) Note) 58 ø80 70 Inner of gasket øG øH øD No flange is attached in case of 5th digit code “P,Q”. N holes h dia. øF 20 L Detail “A” (Conduit donn.) ø15 t Detail “B” ø13 48 270 43 P øE Earth tarminal Electronics unit KM 17 J See table 1 4th digit of the code symbols G1/2 S M 8 5 4.5 5 222 Conduit donn. J G1/2 1/2-14NPT S L.P. H.P. Sensor unit K 17 16 8 16 A, S B, T C, V D, W Pg13.5 M20 1.5 Table 1 7th digit code øD 185 200 210 210 240 191 210 210 229 254 200 220 øE 150 160 170 175 195 152.5 168 168 190.5 200 160 180 øF 126 126 126 151 151 126 126 126 151 151 126 151 øG 100 100 100 103 103 100 100 100 103 103 100 103 øH 73 73 73 96 96 73 73 73 96 96 73 96 t 38 42 48 38 52 44 49 52 44 52 44 40 P 116 116 116 141 141 116 116 116 141 141 116 141 N-øh 8-19 8-23 8-23 8-19 8-25 4-20 8-23 8-23 8-20 8-23 8-18 8-18 (Flange) JIS-10K-80A JIS-20K-80A JIS-30K-80A JIS-10K-100A JIS-30K-100A ANSI-150LB-3B ANSI-300LB-3B ANSI-600LB-3B ANSI-150LB-4B ANSI-300LB-4B DIN DIN PN40 PN16 DN80 DN100 54 70 120 L Mass. appox. (kg) 0 50 100 150 200 14~19.5 15~30.5 15.5~31 16~31.5 16.5~32 11th digit code D,Q E,R L,S F,T S 11th digit (m) code 1.5 3 5 6 M,V N,W P,X S (m) 7 8 10 V,H,M,T,P,R A,F B,J C,K D,L CONNECTION DIAGRAM CK CK (M4 screws) Do not connect. Field bus NOTE) Cable gland is supplied in case of flamproof packing type. ø11 cable is suitable. 38 Remote seal type pressure transmitter : FDB 1 2 3 FDB 4 Note) Cable gland is supplied in case of flamproof packing type. ø11 cable is suitable. In case of 4th digit code “S,V,W” MTG. pipe JIS 50A (2B) U - Bolt M8 “A” Conduit conn.2 Zero ADJ. Screw (10) Fastener (Flameproof only) Up ø80 105 52.5 Down 38 4 holes 9 dia. 30 88 Cable gland (Option) Note) 58 237 “A” Conduit conn.1 “B” Conduit conn. 104 ø80 70 Inner of gasket Detail “A” (Conduit conn.) ø15 Detail “B” (Conduit conn.) ø13 N holes h dia. øG øH øD øE øF KM J 20 L t See table 1 Earth terminal Mass approx.(kg) 4th digit of the code symbols G1/2 191 43 No flange is attached in case of 5th digit code “P,Q,R” . 60 7th digit code L 0 2-M8 12 A F B J C K D L 50 100 150 200 10.5 11.5 12 12.5 231 V H M T P R 9.5 A, S B, T C, V D, W Conduit conn. J K G1/2 17 1/2-14NPT 16 Pg13.5 8 M20 1.5 Table 1 16 M 8 5 4.5 5 17 P Electronics unit S Sensor unit øD 185 200 210 210 191 210 210 229 200 220 øE 150 160 170 175 152.5 168 168 190.5 160 180 øF 126 126 126 151 126 126 126 151 126 151 øG 100 100 100 103 100 100 100 103 100 103 øH 73 73 73 96 73 73 73 96 73 96 t 38 42 48 38 44 49 52 44 44 40 P 116 116 116 141 116 116 116 141 116 141 N-øh 8-19 8-23 8-23 8-19 4-20 8-23 8-23 8-20 8-18 8-18 (Flange) JIS-10K-80A JIS-20K-80A JIS-30K-80A JIS-10K-100A ANSI-150LB-3B ANSI-300LB-3B ANSI-600LB-3B ANSI-150LB-4B DIN PN40 DN80 DIN PN16 DN100 50 70 120 11th digit code S (m) 1.5 3 5 6 7 8 10 D Q CONNECTION DIAGRAM CK CK (M4 screws) E R L S F T Do not connect. Field bus M V N W P X 39 Remote seal type pressure transmitter : FDB 4 K 5V4 4th of Code symbols “S, V, W” type is attached Zero/span adj. screw FDB U-bolt M8 (10) Mtg. JIS 50A (2B) Fastener (flameproof model only) Up φ80 52.5 70 105 Down 38 30 4 holes 9 dia. 58 237 88 104 20 “A” Conduit conn. With field ind. *Cable gland (option) “B” Conduit conn. 100 45 G1 Packing 53 18 2 φ23.6 –0.2 φ30 –0.1 –0.2 –0.1 191 Earth terminal (both side) See table 1 60 43 Details of “A” φ15 E Details of “B” φ13 S C See table 1 4th of Code symbols S T V W D G1/2 2–M8x12 Conduit conn. D C E G1/2 1/2-14NPT Pg13.5 M20x1.5 17 8 16 5 8 4.5 16 5 Table 1 Earth terminal M4 No. 8-32UNC M4 M4 11th of Code symbols D Q E R L S F T M V N W P X 17 S (m) 1.5 3 5 6 7 70 120 50 CONNECTION DIAGRAM CK CK (M4 screws) Do not connect. Field bus Note *: Cable gland is supplied in case of flameproof packing type. φ11 cable is suitable. 8 10 40 206 φ80 Small frange type level transmitter : FDY < 7th digit code without : B, L, U > Vent / drain plug (When the vent / drain plug attatched on the upper side of the detector) “B” Conduit conn.2 In case of 4th digit code “S, V, W, X” N holes h dia. Up Fastener (Flameproof only) Note2) “A” L. P. conn. (10) In case of frange with 4 bolt holes Zero ADJ. screw 43.5 ø80 52.5 105 Down L2 88 Note) Cable grand (option) L1 Vent / drain plug “B” Conduit conn.1 “C” Conduit conn. L 20 t L.P. conn. 41.3 Oval flange screw See table 1 Detail “A” ø7 Detail “B” ø15 Detail “C” ø13 48 27 143 43 M ø80 øD øE øF ø49 ø48 8 H.P. conn L3 Inner of gasket Sensor unit Electronics unit H ø18.5 2.5 J K G1/2 See table 1 L 11th digit of Code symbols [mm] Y A B C D CONDUIT CONN. J K M G1/2 1/2-14NPT Mass approx, [kg] 9.5 to 12 10 to 17 L1 L2 L3 0 50 100 150 200 360 160 296 10.5 to 17.5 11 to 18 354 154 290 11.5 to 18.5 5th digit of Code symbols 0, G 1, H 2, J 3, K 4, L 5, M A, Q B, R C, S D, T 4TH DIGIT OF THE CODE SYMBOLS øD 140 155 140 155 160 165 127 øE 105 120 105 120 120 130 t 36 36 39 38 42 42 N-øh Flange A, S B, T C, V D, W E, X 17 18 8 1.5 16 8 8 5 4.5 5 4.5 4-19 JIS-10K-40A 4-19 JIS-10K-50A 4-19 JIS-20K-40A 8-19 JIS-20K-50A 4-23 JIS-30K-40A 8-19 JIS-30K-50A 4-16 ANSI/JPI-150LB-1 1/2B 4-20 ANSI/JPI-150-2B 4-23 ANSI/JPI-300LB-1 1/2B 8-20 ANSI/JPI-300LB-2B Pg13.5 M20 Pg13.5 PRESS.CONN. Oval flange screw H 7/16-20UNF Rc1/4 Screw depth15 7/16-20UNF 1/4-18NPT Screw depth15 M10 1/4-18NPT Screw depth15 M10 1/4-18NPT Screw depth15 7/16-20UNF 1/4-18NPT Screw depth15 Table 1 98.4 37.5 152 120.6 39.5 156 114.3 41 165 127 42.5 CONNECTION DIAGRAM CK CK (M4 screws) Note) Cable gland is supplied in case of flamproof packing type. ø11 cable is suitable. Field bus Do not connect. 17 41 Small frange type level transmitter : FDY < 7th digit code : B, L, U > Oval flange screw See Table 1 In case of flange with 4 bolt holes “C” Conduit conn. 2 “A” or “B” L. P. conn. 41.3 Zero ADJ. screw In case of 4th digit code “S,V,W, X” N holes h dia. Up Fastener (Flameproof only) 10 ø80 52.5 115 43.5 107 28 Down 150 350 Vent / drain plug t 20 H.P. conn “C” Conduit conn. 1 Details of “A” 4th of code symbols “A, S” type Details of “B” 4th of code symbols “B, C, D, E, T, V, W, X” type ø16 1/4 -18NPT 88 Note) Cable grand (option) “D” Conduit conn. 91 43 186 1 ø16 ø12+0.1 0 2 –0.1 –0.2 40.5 ø80 ø4 Detail “D” ø13 øD øE øF ø49 286 Inner of gasket Earth terminal Detail “C” Sensor unit Electronics unit ø15 0, G 1, H 2, J 3, K 4, L 5, M A, Q B, R C, S D, T 140 155 140 155 160 165 127 105 120 105 120 120 130 36 36 39 38 42 42 4-19 JIS-10K-40A 4-19 JIS-10K-50A 4-19 JIS-20K-40A 8-19 JIS-20K-50A 4-23 JIS-30K-40A 8-19 JIS-30K-50A 4-16 ANSI/JPI-150LB-1 4-20 ANSI/JPI-150-2B 4-23 ANSI/JPI-300LB-1 1/2B 1/2B K 5th digit of Code øD symbols J See table 1 4th digit of the code symbols A, S B, T C, V D, W E, X G1/2 1/2-14NPT G1/2 Conduit conn. J K M 17 16 8 16 8 8 5 4.5 5 4.5 Oval flange screw 7/16-20UNF 98.4 37.5 Screw depth 10 7/16-20UNF 152 120.6 39.5 158 114.3 41 165 127 42.5 Pg13.5 M20 15 8-20 ANSI/JPI-300LB-2B Note) Cable gland is supplied in case of 10th digit code “C”. ø11 cable is suitable. Pg13.5 Screw depth 10 M10 Screw depth 10 M10 Screw depth 10 7/16-20UNF Screw depth 10 Table 1 CONNECTION DIAGRAM CK CK (M4 screws) Do not connect. Field bus 42 17 øE t N-øh Flange M 10 Small frange remote seal type differential pressure transmitter : FDX U-bolt M8 ø80 52.5 105 (10) MTG. pipe JIS 50A (2B) “A” Conduit conn.2 In case of 4th digit code “S,V,W” Zero ADJ. screw Fastene (Flameproof only) 38 28 4 holes 9 dia. 58 228 88 Note) “B” Conduit conn. N holes h dia. Cable gland (option) Inner of gasket “A” Conduit conn. 1 øD øE ø84 ø49 ø48 20 L Detail “A” ø15 Detail “B” ø13 t No flange is attached in case of 5th digit code “W, X” 48 270 43 Earth terminal Electronics unit M See table 1 S 2-M8 12 L.P. S H.P. Sensor unit Inner of gasket 2-M6 screw depth 9 70 120 62 ø84 ø49 CONNECTION DIAGRAM 71 222 J K G1/2 17 71 ø80 104 70 CK CK (M4 screws) 20 Note : In case of wafer type, flange is excluded from the scope of supply. Mount flange, referring to the view. Do not connect. Field bus 5th digit of code symbols 0,G 1,H 2,J 3,K 4,L 5,M 6,N 7,P A,Q B,R C,S D,T E,U F,V øD 140 155 140 155 160 165 175 185 127 152 156 165 156 165 øE 105 120 105 120 120 130 130 145 98.4 120.6 114.3 127 114.3 127 t 36 36 38 38 42 42 52 54 37.5 39.5 41 42.5 42.5 45.5 N-øh 4-19 4-19 4-19 8-19 4-23 8-19 4-25 8-23 4-16 4-20 4-23 8-20 4-23 8-20 Flange JIS-10K-40A JIS-10K-50A JIS-20K-40A JIS-20K-50A JIS-30K-40A JIS-30K-50A JIS-63K-40A JIS-63K-50A ANSI/JPI-150LB-1 1/2B ANSI/JPI-150LB-2B ANSI/JPI-300LB-1 1/2B ANSI/JPI-300LB-2B ANSI/JPI-600LB-1 1/2B ANSI/JPI-600LB-2B Conduit conn. 4th digit of Code symbols J K M 1/2 A, S G 17 8 B, T C, V D, W 1/2-14NPT 11th digit of Capillary Code symbols length : S [mm] D,Q E,R L,S 1500 3000 5000 16 8 16 5 4.5 5 Pg13.5 M20 1.5 Table 1 7th digit of Code symbols V, H, M, T A B C D L 0 50 100 150 200 Mass approx. [kg] 14 to 19.5 15 to 30.5 15.5 to 31 16 to 31.5 16.5 to 32 NOTE ) Cable gland is supplied in case of flameproof packing type. ø11 cable is suitable. 43 Small frange remote seal type differential pressure transmitter : FDX Long vent/drain plug (option) (102) 25 Vent/drain plug N holes, h dia. ø84 S t øF øE øD L. P. H. P. 20 MTG. pipe JIS 50A(2B) “A” Conduit conn.2 U-bolt M8 80 Zero ADJ. screw ø80 52.5 105 (10) In case of 4th digit code “S,V,W” Fastener (Flameproof only) 38 28 4 holes 9 dia. 58 228 “A” Conduit conn. 1 88 Note) Cable gland (option) 270 48 43 ø15 Detail “B” ø13 “B” Conduit conn. ø80 Earth terminal Electronics unit Detail “A” M K 17 104 70 J Table 1 4th digit of code symbols G1/2 222 Sensor unit Conduit conn. J G1/2 1/2-14NPT A, S B, T C, V D, W K 17 16 8 16 M 8 5 4.5 5 11th digit of Capillary Code symbols length : S [mm] Pg13.5 M20 1.5 D,Q E,R L,S 1500 3000 5000 70 120 øF 51 56 51 56 55 60 34.9 42.9 34.9 42.9 t 12 14 14 16 18 18 11.5 13 14.5 16 N-øh 4-15 4-15 4-15 4-15 4-19 4-19 4-16 4-16 4-16 4-20 Flange JIS-10K-15A JIS-10K-20A JIS-20K-15A JIS-20K-20A JIS-30K-15A JIS-30K-20A ANSI/JPI-150LB 1/2B ANSI/JPI-150LB 3/4B ANSI/JPI-300LB 1/2B ANSI/JPI-300LB 3/4B 62 16th digit of 17th digit of øD code symbols code symbols 1 1 2 2 3 3 1 1 2 2 1 2 1 2 1 2 H T H T 95 100 95 100 115 120 89 98 95 117 øE 70 75 70 75 80 85 60.3 69.9 66.7 82.5 CONNECTION DIAGRAM CK CK (M4 screws) Do not connect. Field bus Note ) Cable gland is supplied in case of flameproof packing type. ø11 cable is suitable. 44 Small frange remote seal type differential pressure transmitter : FDX Long vent/drain plug (option) Vent/drain plug (102) Low press. conn. “D” High press. conn. “D” S 20 MTG. pipe JIS 50A (2B) U- bolt M8 23 Zero ADJ. screw “A” Conduit conn.2 ø84 25 ø80 52.5 105 (10) In case of 4th digit code “S,V,W” Fastener (Flameproof only) 38 28 4 holes 9 dia. 58 228 “A” Conduit conn. 1 Detail “A” ø15 Detail “B” ø13 88 Note) Cable gland (option) “B” Conduit conn CONNECTION DIAGRAM CK CK (M4 screws) 270 48 43 Earth terminal Electronics unit M K 17 Do not connect. J G1/2 Table 1 Field bus ø80 222 104 70 Sensor unit 4th digit of Code symbols A, S B, T C, V D, W G1/2 Conduit conn. J K M 17 8 16 8 16 5 4.5 5 11th digit of Capillary Code symbols length : S [mm] D,Q E,R L,S 1500 3000 5000 1/2-14NPT Pg13.5 M20 1.5 16th digit of Code symbols S S S S 17th digit of Code symbols R N 2 T Press. conn."D" Rc 1/2 1/2-14NPT 70 120 62 Rc3/4 3/4-14NPT NOTE ) Cable gland is supplied in case of 10th digit code “C”. ø11 cable is suitable. 45 Small frange remote seal type pressure transmitter : FDW MTG. pipe JIS 50A (2B) “A” Conduit conn.2 In case of 4th digit code “S,V,W” U - bolt M8 Zero adj. screw Fastener (Flameproof only) (10) ø80 Up 52.5 Down 88 38 4 holes 9 dia. 37 Note) Cable gland (option) 237 “A” Conduit conn.1 “B” Conduit conn. 58 ø80 105 104 70 Detail “A” (Conduit conn.) ø15 Detail “B” (Conduit conn.) ø13 N holes h dia. øD øE ø84 ø49 ø48 M J See table 1 Inner of gasket Inner of gasket 20 L t 2-M6 screw depth 9 K G1/2 60 Earth terminal 17 191 43 No flange is attached in case of 5th digit code “W,X” Electronics unit ø84 ø49 71 71 231 S 20 Sensor unit 7th digit of Code symbols L Mass approx. [kg] 11th digit of Capillary Code symbols length : S [mm] V, H, M, T A B C D 0 50 100 150 200 9.5 10.5 11.5 12 12.5 øE 105 120 105 120 120 130 130 145 98.4 120.6 114.3 127 114.3 127 øt 36 36 38 38 42 42 52 54 37.5 39.5 41 42.5 42.5 45.5 D, Q E, R L, S 1500 3000 5000 70 120 50 5th digit of code symbols øD 0,G 1,H 2,J 3,K 4,L 5,M 6,N 7,P A,Q B,R C,S D,T E,U F,V 140 155 140 155 160 165 175 185 127 152 156 165 156 165 N-øh 4-19 4-19 4-19 8-19 4-23 8-19 4-25 8-23 4-16 4-20 4-23 8-20 4-23 8-20 (Flange) JIS-10K-40A JIS-10K-50A JIS-20K-40A JIS-20K-50A JIS-30K-40A JIS-30K-50A JIS-63K-40A JIS-63K-50A ANSI/JPI-150LB-1 1/2B ANSI/JPI-150LB-2B ANSI/JPI-300LB-1 1/2B ANSI/JPI-300LB-2B ANSI/JPI-600LB-1 1/2B ANSI/JPI-600LB-2B 4TH DIGIT OF THE CODE SYMBOLS Conduit conn. J K M G1/2 1/2-14NPT CONNECTION DIAGRAM CK CK (M4 screws) A, S B, T C, V D, W 17 16 8 16 8 5 4.5 5 Pg13.5 M20 1.5 Table 1 Do not connect. Field bus Note) Cable gland is supplied in case of flamproof packing type. ø11 cable is suitable. 46 Small frange remote seal type pressure transmitter : FDW Long vent/drain p lug (added specification) Vent/drain plug (t) In case of ANSI/JPI-600LB flange (6.4) (102) 25 N holes h dia. S t 20 MTG. pipe JIS 50A (2B) U - bolt M8 80 Zero ADJ. screw In case of 4th digit code “S,V,W” Fastener (flameproof only) (10) “A” Conduit conn.2 ø84 ø80 Up øE øD øF 105 52.5 Down 88 38 4 holes 9 dia. 37 Cable gland (option) note) “B” Conduit conn. 60 191 43 58 237 “A” Conduit conn.1 Detail “A” (Conduit conn.) ø15 Detail “B” (Conduit conn.) ø13 Earth terminal Electronics unit M G1/2 231 11th digit of Capillary Code symbols length : S [mm] J K 17 104 ø80 Sensor unit 70 Table 1 4TH DIGIT OF THE CODE SYMBOLS A, S B, T C, V D, W CONDUIT CONN. J K M G1/2 17 8 1/2-14NPT 16 8 16 øE 70 75 70 75 80 85 85 95 60.3 69.9 66.7 82.5 66.7 82.5 5 4.5 5 øF 51 56 51 56 55 60 55 60 34.9 42.9 34.9 42.9 34.9 42.9 t 12 14 14 16 18 18 23 25 11.5 13 14.5 16 14.5 16 N-øh 4-15 4-15 4-15 4-15 4-19 4-19 4-19 4-23 4-16 4-16 4-16 4-20 4-16 4-20 Pg13.5 M20 1.5 D, Q E, R L, S 1500 3000 5000 16th of 17th of code symbols code symbols øD 1 1 2 2 3 3 6 6 1 1 2 2 4 4 1 2 1 2 1 2 1 2 H T H T H T 95 100 95 100 115 120 120 135 89 98 95 117 95 117 Flange JIS-10K-15A JIS-10K-20A JIS-20K-15A JIS-20K-20A JIS-30K-15A JIS-30K-20A JIS-63K-15A JIS-63K-20A ANSI/JPI-150LB 1/2B ANSI/JPI-150LB 3/4B ANSI/JPI-300LB 1/2B ANSI/JPI-300LB 3/4B ANSI/JPI-600LB 1/2B ANSI/JPI-600LB 3/4B 70 120 50 CONNECTION DIAGRAM CK CK (M4 screws) Do not connect. Field bus NOTE) Cable gland is supplied in case of flamproof packing type. ø11 cable is suitable. 47 Small frange remote seal type pressure transmitter : FDW Long vent/drain plug (added specification) Vent/drain plug (102) 25 Press. conn. “D” S 20 MTG. pipe JIS 50A(2B) U - bolt M8 23 Zero ADJ. screw ø84 In case of 4th digit code “S,V,W” (10) “A” Conduit conn.2 Fastener (Flameproof only) ø80 Up 52.5 Down 38 4 holes 9 dia. 37 88 Note) 58 237 “A” Conduit conn.1 Cable gland (option) “B” Conduit conn. Detail “A” (Conduit conn.) ø15 Detail “B” (Conduit conn.) ø13 CONNECTION DIAGRAM CK CK (M4 screws) 60 191 43 M ø80 Earth terminal 105 104 70 Electronics unit Do not connect. Field bus J K G1/2 Table 1 17 231 11th digit of Capillary Code symbols length : S [mm] D, Q E, R L, S 1500 3000 5000 17 16 8 16 8 5 4.5 5 Press. conn."D" Rc1/2 1/2 -14NPT 4TH DIGIT OF THE CODE SYMBOLS CONDUIT CONN. J K M G1/2 1/2-14NPT Pg13.5 M20 1.5 Sensor unit A, S B, T C, V D, W 16th digit of 17th digit of Code symbols Code symbols S S S S R N 2 T 70 120 50 Rc3/4 3/4 -14NPT Note ) Cable gland is supplied in case of 10th digit code “C”. ø11 cable is suitable. Caution on Safety *Before using this product, be sure to read its instruction manual in advance. Head Office Gate City Ohsaki, East Tower, 11-2, Osaki 1-chome, Shinagawa-ku, Tokyo 141-0032, Japan http://www.fesys.co.jp/eng Instrumentation Div. International Sales Dept. No.1, Fuji-machi, Hino-city, Tokyo, 191-8502 Japan Phone: 81-42-585-6201, 6202 Fax: 81-42-585-6187 http://www.fic-net.jp/eng Information in this catalog is subject to change without notice. Printed in Japan
EDSX5-85D 价格&库存

很抱歉,暂时无法提供与“EDSX5-85D”相匹配的价格&库存,您可以联系我们找货

免费人工找货