0
登录后你可以
  • 下载海量资料
  • 学习在线课程
  • 观看技术视频
  • 写文章/发帖/加入社区
创作中心
发布
  • 发文章

  • 发资料

  • 发帖

  • 提问

  • 发视频

创作活动
EDSX7-60J

EDSX7-60J

  • 厂商:

    FUJI(富士电机)

  • 封装:

  • 描述:

    EDSX7-60J - LEVEL TRANSMITTER - Fuji Electric

  • 数据手册
  • 价格&库存
EDSX7-60J 数据手册
LEVEL TRANSMITTER DATA SHEET The FCX–A level transmitter accurately measures liquid level 2 and transmits a proportional 4 to 20mA signal. The transmitter utilizes a unique micromachined capacitance silicon sensor with state-of-the-art microprocessor technology to provide exceptional performance and functionality. FKE...4 FEATURES 1. High accuracy 0.2% accuracy for all calibrated spans is a standard feature for all models covering 0.32kPa {3.2mbar} range to 500kPa {5bar} high differential pressure range. 0.1% accuracy is available as option. Fuji’s micro-capacitance silicon sensor assures this accuracy for all elevated or suppressed calibration ranges without additional adjustment. 2. Minimum environmental influence The “Advanced Floating Cell” design which protects the pressure sensor against changes in temperature, static pressure, and overpressure substantially reduces total measurement error in actual field applications. 3. Fuji/HART® bilingual communications protocol and FOUNDATION™ fieldbus and Profibus™ compatibility FCX–A2 series transmitter offers bilingual communications to speak both Fuji proprietary protocol and HART®. Any HART® compatible devices can communicate with FCX–A2. Further, by upgrading electronics FOUNDATION™ fieldbus and Profibus™ are also available. 4. Application flexibility Various options that render the FCX–A2 s uitable for almost any process applications include: – Analog indicator at either the electronics side or terminal side – Full range of hazardous area approvals – Built-in RFI filter and lightning arrester – 5-digit LCD meter with engineering unit – Stainless steel electronics housing – Wide selection of materials – High temperature, high vacuum service. 5. Programmable output Linearization Function Output signal can be freely programmable. (Up to 14 compensated points at approximation.) 6. Burnout current flexibility (Under Scale: 3.2 to 3.8mA, Over Scale: 20.8 to 21.6mA) Burnout signal level is adjustable using Model FXW Hand Held Communicator (HHC) to comply with NAMUR NE43. 7. Dry calibration without reference pressure Thanks to the best combination of unique construction of mechanical parts (Sensor unit) and high performance electronics circuit (Electronics unit), reliability of dry calibration without reference pressure is at equal level as wet calibration. EDSX7-60j Date Mar. 7, 2007 FKE...4 SPECIFICATIONS Functional specifications Service: Liquid, gas, or vapour Static pressure, span, and range limit: Type F KE F KE F KE 3 5 6 Static pressure Span limit [kPa] {m bar} Min. 0.32 {3.2} 1.3 {13} 5 {50} Max. 32 {320} 130 {1300} 500 {5000} Range limit [kPa] {m bar} +/– { +/– +/– { +/– +/– { +/– 32 320} 130 1300} 500 5000} Hazardous locations: Authorities ATEX Flameproof Ex II 2 GD EEx d IIC T6 IP66/67 T85°C Tamb = –40°C to +65°C EEx d IIC T5 IP66/67 T100°C Tamb = –40°C to +85°C Class I Div.1 Groups B, C, D T6 Type 4X Class II III Div.1 Groups E, F, G T6 Type 4X Tamb max = +60°C Class I Div.1 Groups C, D Class II Div.1 Groups E, F, G Class III Div.1 Note) “Seal Not Required” enclosure is allowed. TIIS Ex do IIB+H2 T4 Tamb max = +55°C Maximum process temp. = +120°C Ex d IIC T5 IP66/67 pending Tamb = –40°C to +85°C Ex d IIC T6 IP66/67 pending Tamb = –40°C to +65°C Factory Mutual    Up to flange rating CSA Remark: To minimize environmental influence, span should be greater than 1/40 of the max. span in most applications. – Lower limit of static pressure (vacuum limit) ; Silicone fill sensor: See Fig.1 Fluorinated fill sensor: 66kPa abs (500mmHg abs) at temperature below 60 °C. – The maximum span of each sensor can be converted to different units using factors as below. 1MPa=103kPa=10bar=10.19716kgf/cm2=145.0377psi 1kPa=10mbar=101.9716mmH2O=4.01463inH2O Overrange limit: To maximum static pressure limit Output signal: 4 to 20mA DC with digital signal superimposed on the 4 to 20mA signal Power supply: Transmitter operates on 10.5V to 45V DC at transmitter terminals. 10.5V to 32V DC for the units with optional arrester. Load limitations: see figure below [Ω] 2000 1533Ω IECEx Scheme /SAA Authorities ATEX Intrinsic safety Ex II 1 GD EEx ia IIC T5 Tamb = –40°C to +40°C EEx ia IIC T4 Tamb = –40°C to +80°C Entity Parameters: Ui=28V, Ii=93.3mA, Pi=0.66W, Ci=27nF (Without Arrester), Ci=34.2nF (With Arrester), Li=1.134mH Factory Mutual Class I II III Div.1 Groups A, B, C, D, E, F, G T4 Entity Type 4X Model code 9th digit A,B,D L,P,1,2 Q,S,4,5 E,F,H – 13th digit Y,G,H,J,S,T,K Y,G,H,J,S,T,K Y,G,H,J,S,T,K Y,G,H,J,S,T,K W,A,D Tamb –40°C to +85°C –20°C to +80°C –20°C to +60°C –40°C to +60°C –10°C to +60°C Load resistance 1500 1000 500 250 0 10 600Ω Operating area 24V 16.1 10.5V Power voltage 45V 50 [V] Entity Parameters: Vmax=42.4V, Imax=113mA, Pi=1W, Ci=34.2nF, Li=1.134mH CSA Class I Div.1 Groups A, B, C, D Class II Div.1 Groups E, F, G Class III Div.1 Temp Code T4 Tamb max = +40°C Temp Code T3C Tamb max = +85°C Entity Parameters: Vmax=28V, Imax=93mA, Ci=27nF (Without Arrester), Ci=34.2nF (With Arrester), Li=1.4mH Ex ia IIC T4 Tamb max = +60°C Entity Parameters: Ui=28V, Ii=94.3mA, Pi=0.66W, Ci=32.6nF, Li=1.134mH Ex ia IIC T4 IP66/67 Tamb = –40°C to +70°C Ex ia IIC T5 IP66/67 Tamb = –40°C to +50°C Entity Parameters: Ui=28V, Ii=93.3mA, Pi=0.66W, Ci=0.033µF, Li=1.034mH Note: For communication with HHC(1) (Model: FXW), min. of 250Ω required. TIIS IECEx Scheme /SAA 2 Authorities ATEX Type n Nonincendive Ex II 3 GD EEx nL IIC T5 Tamb = –40°C to +40°C EEx nL IIC T4 Tamb = –40°C to +80°C Specific Parameters: Model without arrester: Ui=42.4V, Ii=113mA, Pi=1W, Ci=27nF, Li=1.134mH Model with arrester: Ui=32V, Ii=113mA, Pi=1W, Ci=34.2nF, Li=1.134mH EEx nAL IIC T5 Tamb = –40°C to +40°C EEx nAL IIC T4 Tamb = –40°C to +80°C Specific Parameters: Model without arrester: Umax=42.4V, Imax=113mA, Pmax=1W Model with arrester: Umax=32V, Imax=113mA, Pmax=1W “Output Underscale”: Adjustable within the range 3.2mA to 3.8mA from HHC(1) 3.2 3.8 4 20 20.8 21.6 [mA] Over scale Burnout Normal operating range Under scale Probable under range Burnout Probable over range Factory Mutual Class I II III Div.2 Groups A, B, C, D, F, G T4 Entity Type 4X Model code 9th digit A,B,D L,P,1,2 Q,S,4,5 E,F,H – 13th digit Y,G,H,J,S,T,K Y,G,H,J,S,T,K Y,G,H,J,S,T,K Y,G,H,J,S,T,K W,A,D Tamb –40°C to +85°C –20°C to +80°C –20°C to +60°C –40°C to +60°C –10°C to +60°C Loop-check output: Transmitter can be configured to provide constant signal 3.8mA through 21.6mA by HHC(1). Temperature limit: Ambient: – 40 to + 85°C (– 20 to + 80°C for LCD indicator) (– 40 to + 60°C for arrester option) (– 10 to + 60°C for fluorinated oil fill transmitter) For explosionproof units (flameproof or intrinsic safety), ambient temperature must be within the limits specified in each standard. Process: Code in the 13th digit of “Code symbols” Fluorinated oil Silicone oil W, A and D H J Y and G S T K Process temperature –20 to 120°C – 15 to 250°C 85 to 300°C – 40 to 120°C –15 to 250°C 85 to 300°C –15 to 150°C 2.7kPa abs {20.3mmHg abs} Lower limit of static press Atmospheric pressure CSA Class I Div.2 Groups A, B, C, D Class II Div.2 Groups E, F, G Class III Div.2 Temp Code T4 Tamb max = +40°C Temp Code T3C Tamb max = +85°C Entity Parameters: Vmax=28V, Ci=27nF (Without Arrester), Ci=34.2nF (With Arrester), Li=1.4mH – TIIS 0.13kPa abs {0.98mmHg abs} Low pressure side contact liquid temperature on transmitter of Code H, J, S, T is 120°C or lower. Low pressure side contact liquid temperature of Code K is 85°C or lower IECEx Scheme /SAA – Zero/span adjustment: Zero and span are adjustable from the HHC(1). Zero and span are also adjustable externally from the adjustment screw (Span adjustment is not available with 9th digit code “L, P, Q, S”). Damping: Adjustable from HHC or local adjustment unit with LCD display. The time constant is adjustable between 0.12 to 32 seconds. Zero elevation/suppression: – 100% to + 100% of URL Normal/reverse action: Selectable from HHC(1) Indication: Analog indicator or 5-digit LCD meter, as specified. Burnout direction: Selectable from HHC(1) If self-diagnostic detect transmitter failure, the analog signal will be driven to either “Output Hold”, “Output Overscale” or “Output Underscale” modes. “Output Hold”: Output signal is hold as the value just before failure happens. “Output Overscale”: Adjustable within the range 20.8mA to 21.6mA from HHC(1) Storage: – 40 to + 90°C Humidity limit: 0 to 100% RH Communication: With HHC(1) (Model FXW, consult Data Sheet No. EDS8-47), following information can be remotely displayed or reconfigured. Note: HHC’s version must be more than 6.0 (or FXW 1– 3), for FCXA2. Items Tag No. Model No. Serial No. Engineering unit Range limit Measuring range Damping Output mode Burnout direction Calibration Output adjust Data Self diagnoses Printer External switch lock Transmitter display Linearize Rerange (Note) (1) HHC: Hand Held Communicator Display v v v v v v v v v v — v v — v v v v Set v v — v — v v — v v v — — — v v v v 3 FKE...4 Programmable output linearization function: Output signal can be characterized with “14 points linear approximation function” from HHC(1). EMC Conformity: EN61326 Physical specifications Electrical connections: G1/2, 1/2-14 NPT, Pg13.5, or M20 x 1.5 conduit, as specified. And 1-conduit or 2-conduit, as specified. Process connections: LP side: 1/4-18 NPT or Rc1/4. HP side: ANSI, DIN, or JIS raised face flange. See OUTLINE DIAGRAM for detailed dimensions. Refer to “Code symbols” Process-wetted parts material: LP side HP side Material code Wetted Diaphragm & Process (7th digit Diaphragm sensor body flange face cover in “Code symbols”) 316 stainless 316L stainless 316 stainless 316L stainless V (*1) 316 stainless 316L stainless 316 stainless 316L stainless J (*1) steel +Au coating C 316 stainless 316L stainless 316 stainless Hastelloy-C 1 (* ) 316 stainless 316L stainless 316 stainless Monel D (*1) E 316 stainless 316L stainless 316 stainless Tantalum (*1) Hastelloy-C Hastelloy-C H 316 stainless Hastelloy-C lining (*1) Monel lining Monel 316 stainless Monel M (*1) Tantalum T 316 stainless Tantalum Tantalum lining (*1) Hastelloy-C Hastelloy-C B Hastelloy-C Hastelloy-C lining Monel lining Monel Monel lining Monel L Tantalum Tantalum U Hastelloy-C Tantalum lining 316 stainless 316L stainless 316 stainless Tantalum P (*1) 316 stainless 316L stainless 316 stainless Zirconium R (*1) Note: (*1) SCS14A per JIS G 5121 (equivalent CF8M per ASTM A351/A351M) Remark: Sensor O-rings: Viton O-ring and teflon gasket selectable. Performance specifications Reference conditions, silicone oil fill, 316SS isolating diaphragms, 4-20 mA analog output in linear mode. Accuracy rating: (including linearity, hysteresis, and repeatability) (Standard) For spans greater than 1/10 of URL: ± 0.2% of span For spans below 1/10 of URL: ± 0.1 + 0.1 0.1 x URL % of span Span ( ( ) (Option) (Code: 21th digit H, K) For span greater than 1/10 of URL: 0.1% of span For span below 1/10 of URL: 0.1 x URL ± 0.05 + 0.05 % of span Span ) ± 0.2% of upper range limit (URL) for 3 years. Temperature effect: Effects per 28°C change between the limits of – 40°C and + 85°C (Standard) Zero shift: ± 0.35% of URL Total effect: ± 0.5% of URL (Option) (Code: 21th digit J, K) Zero shift: ± 0.3% of URL Total effect: ± 0.4% of URL Static pressure effect: Zero shift: ± 0.2% of URL / 1MPa Span shift: – 0.2% of calibrated span / 1MPa Overrange effect: Zero shift; ± 0.1% of URL for flange rating pressure Supply voltage effect: Less than 0.005% of calibrated span per 1V RFI effect: Less than 0.2% of URL for the frequencies of 20 to 1000MHz and field strength 30 V/m when electronics covers on. (Classification: 2-abc: 0.2% span per SAMA PMC 33.1) Update period: 120 msec *) Step response: (without electrical damping) Stability: Range code “3” “5” and “6” Time constant *) 0.55 s 0.3 s Dead time *) 0.2 s *) Faster response is available as option (maximum update rate : 25 times per second) Mounting position effect: Zero shift, less than 0.3kPa{3m bar} for a 10° tilt in any plane. (No extension) No effect on span. This error can be corrected by adjusting zero. Dielectric strength: 500V AC, 50/60Hz 1 min., between circuit and earth. Insulation resistance: More than 100MΩ at 500V DC. Turn-on time: 4 sec Internal resistance for external field indicator: 12Ω or less Non-wetted parts material: Electronics housing: Low copper die-cast aluminum alloy finished with epoxy/ polyurethane double coating (standard), or 316 stainless steel (SCS14A per JIS G5121), as specified. Bolts and nuts: Cr-Mo alloy (standard) or 304 stainless steel Fill fluid: Silicone oil (standard) or fluorinated oil Mounting flange: 304 stainless steel or Carbon steel, as specified Environmental protection: IEC IP67 and NEMA 6 / 6P Flange mounting:See drawings Mass{weight}: Transmitter approximately 13kg without options. Add; 0.5kg for mounting bracket 0.8kg for indicator option 4.5kg for stainless steel housing option 1.0kg per 50mm extension of diaphragm 4 Optional features Indicator: A plug-in analog indicator (2.5% accuracy) can be housed in the electronics compartment or in the terminal box of the housing. An optional 5-digit LCD meter with engineering unit is also available. Local adjustment unit with LCD display: An optional 5-digit LCD meter with Zero/ Span adjustment function, loop-check function and damping adjustment function, is available. Arrester: A built-in arrester protects the electronics from lightning surges. Lightning surge immunity: 4kV (1.2 × 50µs) Oxygen service: Special cleaning procedures are followed throughout the process to maintain all process wetted parts oil-free. The fill fluid is fluorinated oil. Chlorine service: Oil-free procedures as above. Includes fluorinated oil for fill. Degreasing: Process-wetted parts are cleaned, but the fill fluid is standard silicone oil. Not for use on oxygen or chlorine measurement. Vacuum service: Special silicone oil and filling procedure are applied. See Fig.1 and Fig.2 Optional tag plate: An extra stainless steel tag with customer tag data is wired to the transmitter. Coating of cell: Cell’s surface is finished with epoxy/polyurethane double coating. Specify if environment is extremely corrosive. [kPa abs] {mbar abs} Silicone (Code Y,G) Silicone (Code S) Silicone (Code T) 101 {1010} Operating pressure 53.3 {533} Operating area 13.3 {133} 2.7 {27} –40 –15 Fig. 1 60 85 120 Process temperature[°C ] 200 230 250 300 Relation between process temperature and operating pressure [kPa abs] {mbar abs} Sealing liquid:Silicone (Code K) 101 {1010} Operating pressure Operating area Non-operating area 0.13 {1.3} –15 Process temperature[°C ] 150 Fig. 2 Relation between process temperature and operating pressure ACCESSORIES Oval flanges: (Model FFP, refer to Data Sheet No. EDS6-10) Converts process connection to 1/2-14 NPT or to Rc1/2; in carbon steel or in 316 stainless steel. Hand held communicator: (Model FXW, refer to Data Sheet No. EDS 8-47) Z/S board: Parts No.=ZZPFCX4-A070 When Z/S board is mounted on the FCX– A2 a mplifier unit, external adjustment screw will be available for zero and span adjustment. 5 FKE...4 The product conforms to the requirements of the Electromagnetic compatibility Directive 94/9/EC as detailed within the technical construction file number TN513035. The applicable standards used to demonstrate compliance are : EMI (Emission) Frequency range MHz 30 to 230 230 to 1000 ORDERING INFORMATION When ordering this instrument, specify: 1. CODE SYMBOLS 2. Measuring range 3. Output orientation (burnout direction) when abnormality is occurred in the transmitter. Hold / Overscale (21.6mA) / Underscale (3.2mA). Unless otherwise specified, output hold function is supplied. 4. Indication method (indicated value and unit) in case of the actual scale (code D, H, P, S on 9th digit). 5. TAG No. (up to 26 alphanumerical characters), if required. EN61326 : 1997 Class A (standard for Industrial Location) Limits 40dB (µV/m) quasi peak, measured at 10m distance 47dB (µV/m) quasi peak, measured at 10m distance Reference standard CISPR16-1 and CISPR16-2 EMI (Immunity) Phenomenon Electrostatic discharge EN61326: 1997 Annex A (standard for Industrial Location) Test value Basic standard EN61000-4-2 Performance criteria B 4kV (Contact) 8kV (Air) 80 to 1000MHz Electromagnetic 10V/m field 80%AM (1kHz) Rated power frequency magnetic field Burst 30A/m 50Hz 2kV 5kHz 1.2µs/50µs 1kV (Line to line) 2kV (Line to ground) 0.15 to 80MHz 3V 80%AM (1kHz) EN61000-4-3 A EN61000-4-8 A EN61000-4-4 B Surge EN61000-4-5 B Conducted RF EN61000-4-6 A Note) Definition of performance criteria A: During testing, normal performance within the specification limits. B: During testing, temporary degradation, or loss of function or performance which is self-recovering. 6 CODE SYMBOLS 12345678 9 10 11 12 13 14 15 21 Digit 4 Description Process connection Rc1/4 1/4-18NPT 1/4-18NPT 1/4-18NPT 1/4-18NPT Rc1/4 1/4-18NPT 1/4-18NPT 1/4-18NPT 1/4-18NPT Oval flange screw 7/16-20UNF 7/16-20UNF M10 M10 7/16-20UNF 7/16-20UNF 7/16-20UNF M10 M10 7/16-20UNF Conduit connection G 1/2 (×1) 1/2-14NPT (×1) Pg13.5 (×1) M20×1.5 (×1) Pg13.5 (×1) G 1/2 (×2) 1/2-14NPT (×2) Pg13.5 (×2) M20×1.5 (×2) Pg13.5 (×2) Note FKE 4 Digit No. of code Combination with 12th digit code "C, E, P, Q" are not available. A B C D E S T V W X 5 6 7 Material Size and rating 304 stainless JIS 10K 80A steel JIS 10K 100A JIS 30K 80A JIS 30K 100A ANSI/JPI 150LB 3" ANSI/JPI 150LB 4" ANSI/JPI 300LB 3" ANSI/JPI 300LB 4" DIN PN40 DN80 DIN PN16 DN100 JIS 20K 80A ANSI/JPI 600LB 3B Carbon steel JIS 10K 80A JIS 10K 100A JIS 30K 80A JIS 30K 100A ANSI/JPI 150LB 3" ANSI/JPI 150LB 4" ANSI/JPI 300LB 3" ANSI/JPI 300LB 4" DIN PN40 DN80 DIN PN16 DN100 316 stainless JIS 10K 80A steel ANSI/JPI 150LB 3B ANSI/JPI 150LB 4B ANSI/JPI 300LB 3B ANSI/JPI 300LB 4B ANSI/JPI 600LB 3B 0.32 32 {3.2 320} 1.3 130 {13 1300} 5 500 {50 5000} LP side Wetted sensor Diaphragm Process cover body 316 stainless steel 316L stainless steel 316 stainless steel 316 stainless steel 316L stainless steel 316 stainless steel 316 stainless steel 316L stainless steel 316 stainless steel 316 stainless steel 316L stainless steel 316 stainless steel 316 stainless steel 316L stainless steel 316 stainless steel Note 1 0 1 2 3 4 5 6 7 8 9 M R A B C D E F G H J K S T U V W X 3 5 6 316 stainless steel 316 stainless steel 316 stainless steel Hastelloy-C lining Monel lining Tantalum lining 316 stainless steel 316 stainless steel Hastelloy-C lining Hastelloy-C Monel lining Monel Tantalum lining Tantalum Hastelloy-C lining Hastelloy-C Monel lining Monel Tantalum lining Tantalum 316L stainless steel 316 stainless steel 316L stainless steel 316 stainless steel HP side Diaphragm and flange face 316L stainless steel Hastelloy-C Monel Tantalum Diaphram: 316L stainless steel +Au coating Flange face: 316 stainless steel Hastelloy-C Monel Tantalum Hastelloy-C Monel Tantalum Titanium Note 3 Zirconium Note 2, 3 V C D E J H M T B L U P R Note 1: (*1) 100: 1 turn down is possible, but should be used at a span greater than 1/40 of the maximum span for better performance. Note 2: (*2) Material Code R; 6th digit code "6" is not available. Note 3: (*3) 5th digit code "0, 2, 4, 6, 8, A, C, E, G, J" are available. 7 FKE...4 12345678 9 10 11 12 13 14 15 21 Digit Description Note 9 Indicator Arrester None None Z/S board Analog, 0 to 100% linear scale None attached. Analog, custom scale None None Yes Analog, 0 to 100% linear scale Yes Analog, custom scale Yes Digital, 0 to 100% None Digital, custom scale None Digital, 0 to 100% Yes Digital, custom scale Yes Digital, 0 to 100% (Local adjustment unit with LCD display) None Digital, custom scale (Local adjustment unit with LCD display) None Digital, 0 to 100% (Local adjustment unit with LCD display) Yes Digital, custom scale (Local adjustment unit with LCD display) Yes 10 None (for ordinary locations) TIIS, Flameproof (Conduit seal) (Available for 4th digit code "A", "S") TIIS, Flameproof (Cable gland seal) (Available for 4th digit code "A", "S") FM, Flameproof (or explosionproof) (Available for 4th digit code "B", "T") CSA, Flameproof (or explosionproof) (Available for 4th digit code "B", "T") ATEX, Flameproof IECEx Scheme/SAA, Flameproof (Approval pending) TIIS, Intrinsic safety FM, Intrinsic safety and nonincendive CSA, Intrinsic safety and nonincendive ATEX, Intrinsic safety ATEX, Type n IECEx Scheme/SAA, Intrinsic safety FM, Combined of Flameproof and Intrinsic safety 11 Extension [mm] Applicable material code 0 Any 50 100 (7th digit code "V" only) 150 200 50 100 (7th digit code "H" ,"B" ,"C" only) 150 200 12 Extra SS tag plate Stainless steel elec. housing Coating of cell None None None Yes None None None Yes None Note 4 Yes (* 4) Yes None None None Yes Yes None Yes None Yes Yes Yes Yes Yes 13 Treatment Fill fluid Standard Silicone oil Standard Fluorinated oil Degreasing Silicone oil Oxygen service Fluorinated oil (7th digit code "V", "J" only) Chlorine service Fluorinated oil (7th digit code "H", "T", "B", "U", "C" and "E") High temp. 250°C 7th digit code "V", "C", "H", "B" High temp. 300°C High temp. and vacuum (250°C) (* 5) Note 5 7th digit code "V" High temp. and vacuum (300°C) 14 High temp. and high vacuum Silicone oil O-ring /Gasket Teflon membrane Viton (O-ring) None Teflon (gasket) None Viton (O-ring) Yes (5th digit code "0", "2", "4", "6", "8", "A", "C", "E", Teflon (gasket) Yes "G", "J", "M", "R", "S", "T", "V", "X" and 11th digit code "Y" are available. 13th digit code "H, J, S, T, K" are not available.) FKE 4 Digit No. of code A B D E F H L P Q S 1 2 4 5 A B C D E X R G H J K P T V Y A B C D E F G H Y B C E M N P Q Y W G A D H J S T K A B C D Note 4: (*4) Customer tag number can be engraved on standard stainless steel name plate. If extra tag plate is required, select "Yes" Note 5: (*5) Treatment; None 8 12345678 9 10 11 12 13 14 15 21 Digit 15 Description (* 6) Cr-Mo alloy hexagon socket head cap screw/carbon steel nut Cr-Mo alloy hexagon bolt/nut 304 stainless steel bolt /304 stainless steel nut (* 7) High accuracy type Instruction manual attached Low temperature effect type Instruction manual attached H+J Instruction manual attached Instruction manual unattached High accuracy type Instruction manual unattached Low temperature effect type Instruction manual unattached T+U Instruction manual unattached Note Note 6 FKE 4 A B E Digit No. of code 21 Note 7 H J K L T U V Note 6: (*6) In case of tropical use, select stainless bolts and nuts. Note 7: (*7) If other option is not necessary, 21st digit code is blank. In case of 21st digit code is blank, instruction manual attached. 9 FKE...4 OUTLINE DIAGRAM (Unit:mm) < 7digit code : Without "B", "L" and "U" > Note 2) In case of 4th digit code "A.B.C.D.E" Vent / drain plug (When the vent /drain plug attatched on the upper side of the detector) In case of 4th digit code "S.V.W.X" In case of 4th digit code "T" Flange : ANSI/JPI -150LB-3B "A" L.P. conn. 94.5 Fastener (Flameproof only) Zero ADJ.screw 10 Up 8 ø80 52.5 105 105 43.5 Down N holes h dia Note 1) 2 1 Vent / drain plug L 20 Inner of gasket t 41.3 Oval flang screw See table 1 "B" Conduit conn. (27) With field ind. 88 Cable gland (option) "C" Conduit conn. Detail "A" (L.P conn.) ø18.5 Detail "B" (Conduit conn.) Detail "C" 2.5 J 48 27 ø15 ø13 43 143 59 8 MN øD øE øF øG øH ø7 See table 1 3 H.P. conn. Earth terminal Sensor unit Electronics unit K See table 1 MASS APPROX. (kg) 9.5 ~ 13 10 ~ 17 G1/2 11TH DIGIT L (mm) CODE Y A E B F 1 333 2 3 0 50 100 150 200 160 296 10.5 ~ 17.5 327 11 ~ 18 154 290 5th digit of the code symbols 0, A, S M 2, C 1, B 3, D 4, E, T 6, G, V R, X 5, F, U 7, H, W 8, J 9, K øD 185 200 210 210 240 øE 150 160 170 175 195 øF øG øH 73 t P N-øh 8-19 8-23 8-23 Flange JIS 10K 80A JIS 20K 80A JIS 30K 80A 4th digit of the code symbols A, S B, T C, V D, W E, X C G D H 126 100 38 116 42 116 48 116 38 141 52 141 11.5 ~ 18.5 126 100 73 126 100 73 151 103 96 151 103 96 8-19 JIS 10K 100A 8-25 JIS 30K 100A ANSI 150LB 3B ANSI 300LB 3B ANSI 600LB 3B ANSI 150LB 4B ANSI 300LB 4B DIN PN40 DN80 DIN PN16 DN100 Conduit conn. K MN G1/2 17 8 Press.conn. J Rc1/4 1/4-18NPT Oval flage screw 7/16-20UNF SCREW DEPTH15 7/16-20UNF SCREW DEPTH15 M10 SCREW DEPTH15 M10 SCREW DEPTH15 7/16-20UNF SCREW DEPTH15 191 152.5 126 100 73 210 168 126 100 73 210 168 126 100 229 190.5 151 103 254 200 220 200 160 180 73 96 44 116 4-20 49 116 8-23 52 116 8-23 44 141 8-20 52 141 8-23 44 116 8-18 40 141 8-18 1/2-14NPT 18 5 Pg13.5 M20 1.5 Pg13.5 8 4.5 1/4-18NPT 1/4-18NPT 151 103 96 126 100 73 151 103 96 16 5 8 4.5 1/4-18NPT Table 1 Note 1) Note 2) Cable gland is supplied in case of flamproof packing type. ø11 cable is suitable. The pressure connector is located on the down side surface of the detector, when the vent/drainplug is attatched on the upper side of the detector (when the 21th digit of the code symbols: c, e or d). CONNECTION DIAGRAM CK CK 10 17 ø80 < 7th digit code : "B", "L" or "U" > In case of 4th digit code "T" In case of 4th digit code "A.B.C.D.E" Flange : ANSI/JPI -150LB-3B Oval flange screw See table 1 41.3 94.5 In case of 4th digit code "S.V.W.X" Zero ADJ.screw 10 8 Fastener (Flameproof only) 107 Up ø80 52.5 105 105 ø80 Down 2 1 Vent / drain plug "C" Conduit conn. L Inner of gasket 20 t Earth terminal (27) With field ind. 88 N holes h dia Note) "A" or "B" L.P. conn. "D" Conduit conn. Cable gland (option) 91 Detail "A" (L.P. conn.) 4th digit code "S" ø16 1 Detail "B" (L.P conn.) ø16 1/4-18NPT 40.5 186 43 ø12 +0.1 +0.2 2 0 -0.1 øG øD øE øF øH 46.4 H.P. conn. Sensor unit 3 Detail "C" (Conduit conn.) ø15 MN ø4 Electronics unit Detail "D" ø13 Mass apprpx. 11th degit L (mm) (kg) code 1 2 3 Y 11.5 ~ 15 0 323 150 286 A E B F C G D H CONNECTION DIAGRAM CK CK K See table 1 50 100 150 200 12 ~ 19 G1/2 12.5 ~ 19.5 317 144 290 13 ~ 20 13.5 ~ 20.5 5th digit of the code symbols 0, A, S M 2, C 1, B 3, D 4, E, T 6, G, V R, X 5, F, U 7, H, W 8, J 9, K øD 185 200 210 210 øE 150 160 170 175 øF øG øH 73 t P N-øh Flange JIS 10K 80A JIS 20K 80A JIS 30K 80A JIS 10K 100A JIS 30K 100A ANSI 150LB 3B ANSI 300LB 3B ANSI 600LB 3B ANSI 150LB 4B ANSI 300LB 4B DIN PN40 DN80 DIN PN16 DN100 4th digit of the code symbols A, S B, T C, V D, W E, X Conduit conn. K MN G1/2 17 8 5 4.5 5 4.5 Oval flage screw 7/16-20UNF Screw depth10 7/16-20UNF Screw depth10 M10 Screw depth10 M10 Screw depth10 7/16-20UNF Screw depth10 126 100 38 116 8-19 42 116 8-23 48 116 8-23 38 141 8-19 52 141 8-25 44 116 4-20 49 116 8-23 52 116 8-23 44 141 8-20 52 141 8-23 44 116 8-18 40 141 8-18 126 100 73 126 100 73 151 103 96 1/2-14NPT 16 Pg13.5 M20 1.5 Pg13.5 8 16 8 240 195 151 103 96 191 152.5 126 100 73 210 168 126 100 73 210 254 200 220 168 200 160 180 126 100 73 151 103 96 126 100 73 151 103 96 229 190.5 151 103 96 Table 1 Note) Cable gland is supplied in case of flameproof packing type. ø11 cable is suitable. 17 10 11 FKE...4 Caution on Safety *Before using this product, be sure to read its instruction manual in advance. Head Office Gate City Ohsaki, East Tower, 11-2, Osaki 1-chome, Shinagawa-ku, Tokyo 141-0032, Japan http://www.fesys.co.jp/eng Instrumentation Div. International Sales Dept. No.1, Fuji-machi, Hino-city, Tokyo, 191-8502 Japan Phone: 81-42-585-6201, 6202 Fax: 81-42-585-6187 http://www.fic-net.jp/eng Information in this catalog is subject to change without notice. Printed in Japan
EDSX7-60J 价格&库存

很抱歉,暂时无法提供与“EDSX7-60J”相匹配的价格&库存,您可以联系我们找货

免费人工找货