1000 Eaton Boulevard
Cleveland, OH 44122
United States
SmartPro 230V 750VA 500W Line-Interactive Sine
Wave UPS, Tower, Network Card Options, USB,
DB9 Serial
Highlights
●
750VA line interactive tower
UPS; Sine wave output
●
220/230/240V nominal output
during brownouts and
overvoltages
●
Add optional WEBCARDLX with
latest version of PADM20 for
enhanced remote management
●
Front panel status LEDs with
load level and battery capacity
display
●
C14 input; 6 C13 outlets;
Includes 2 C13 to C14 cables
MODEL NUMBER: SMX750SLT
Package Includes
Description
Tripp Lite's SMX750SLT intelligent, line-interactive sine wave UPS system protects servers, networking
accessories and telecommunications equipment from blackouts, voltage fluctuations and transient surges.
Large internal batteries offer 15 minutes half load runtime and 5 minutes full load runtime. 750VA/500 watt
power handling capability and full-time sine wave output offers guaranteed compatibility with networking,
telecom and other sensitive electronic applications. Includes 6 protected C13 output receptacles total.
Network management interfaces support communications via USB, RS-232 and slot for network
management card options. HID-compliant USB interface enables integration with built-in power
management and auto shutdown features of Windows and Mac OS X. Network communications ports
enable detailed monitoring of equipment load levels, self-test data and utility power conditions. PowerAlert
UPS monitoring software is available via free download. Single line Tel/DSL and network Ethernet line
surge suppression. Built-in audible alarm and 9 LEDs offer status notification for line power, battery
power, battery charge level, load level, plus AVR boost and trim operational status information. Network
grade AC surge suppression protects equipment from damage and performance problems resulting from
transient surges. Attractive, all-black tower housing.
Features
●
SMX750SLT line-interactive UPS offers battery derived sine wave AC output during power outages,
voltage regulation during brownouts and overvoltages, plus network-grade AC surge suppression
●
750VA/500 watt power handling capability with full-time sine wave output offers guaranteed
compatibility with networking, telecom and other sensitive electronic devices
●
Large internal batteries offer runtimes of 15 minutes at half load (325VA/250 watts) and 5 minutes at full
load (750VA/500 watts)
●
Intelligent battery management system extends battery life
●
Automatic Voltage Regulation (AVR) circuits maintain user-selectable 220, 230 or 240V nominal output
over an input voltage range of 151 to 290
●
Includes 6 C13 output receptacles
●
IEC320-C14 input connection accepts a variety of detachable cordsets
●
Compatible with Tripp Lite UPS management card options WEBCARDLX, RELAYIOCARD,
SNMPWEBCARD
●
Optional WEBCARDLX (sold separately) with the latest version of PowerAlert Device Manager firmware
(PADM20) provides enhanced remote management capabilities
1/5
●
SMX750SLT UPS System
●
USB and serial cabling
●
User manual with warranty
information
1000 Eaton Boulevard
Cleveland, OH 44122
United States
●
PADM20 and PowerAlert Element Manager (PAEM) form a powerful tool for expanding maintenance
functions in large installations, including firmware update checks and backup and restoration of device
configurations
●
USB & Serial ports enable data-saving unattended shutdown when used with Tripp Lite's PowerAlert
software, available via FREE download from tripplite.eaton.com/products/power-alert
●
HID-compliant USB interface enables integration with built-in power management and auto shutdown
features of Windows and Mac OS X
●
Supports Tripp Lite's WatchDog software application (requires optional WATCHDOGSW)
●
9 LEDs offer continuous status information of UPS operating parameters and site power quality
●
Hot-swappable batteries allow on-site battery replacement without powering off connected equipment
●
Single line Tel/DSL and network Ethernet line surge suppression
Specifications
OVERVIEW
UPC Code
037332124388
UPS Type
Line-Interactive
INPUT
Input Phase
Single-Phase
Rated input current (Maximum Load)
3.6A (220V), 3.5A (230V), 3.4A (240V)
Nominal Input Voltage(s) Supported
220V AC; 230V AC; 240V AC
UPS Input Connection Type
C14 inlet
UPS Input Connection Description
IEC320-C14 input connection accepts a variety of detachable cordsets to match country or site-specific wall
receptacles
OUTPUT
Output Capacity (VA)
750
Output Capacity (kVA)
0.75
Output Capacity (Watts)
500
Output Capacity (kW)
0.5
Power Factor
0.7
Nominal Voltage Details
230V default (voltage selection via back panel switches)
Frequency Compatibility
50 / 60 Hz
Frequency Compatibility Details
Automatic frequency selection
Output Voltage Regulation (Line
Mode)
-11%, +6%
Output Voltage Regulation (Battery
Mode)
+/- 5%
Included Output Power Cables
Includes 2 C13 to C14 output power cables
Output AC Waveform (AC Mode)
Sine wave
2/5
1000 Eaton Boulevard
Cleveland, OH 44122
United States
Output AC Waveform (Battery
Mode)
Pure Sine wave
Nominal Output Voltage(s)
Supported
220V; 230V; 240V
Output Receptacles
(6) C13
Individually Controllable Load Banks
No
BATTERY
Battery Type
Valve Regulated Lead Acid (VRLA)
Runtime Full Load (min.)
5 min. (500W)
Runtime Half Load (min.)
15 min. (250W)
Expandable Runtime
No
DC System Voltage (VDC)
24
Battery Recharge Rate (Included
Batteries)
Less than 4 hours to 90% (typical, full load discharge)
Battery Access
Battery access door
Internal UPS Replacement Battery
Cartridge
RBC24-SLT
Battery Replacement Description
Hot-swappable, user replaceable batteries
VOLTAGE REGULATION
Voltage Regulation Description
Automatic voltage regulation (AVR) maintains line power operation with an input voltage range of 151 to 290V
Overvoltage Correction
Voltage reduction of 12% applies when input is 232-266 (220V), 244-278 (230V), 254-290 (240V); Voltage setpoints
±5% tolerance
Undervoltage Correction
Voltage boost of 15% applies when input is 175-198 (220V), 182-206 (230V), 190-216 (240V); Voltage setpoints
±5% tolerance
Severe Undervoltage Correction
Voltage boost of 30% applies when input is 151-174 (220V), 158-181 (230V), 166-190 (240V); Voltage setpoints
±5% tolerance
USER INTERFACE, ALERTS & CONTROLS
Switches
2 Switches control off/on power status and alarm-cancel/self-test operation; rear panel protected switches support
nominal voltage selection
Alarm Cancel Operation
Power-fail alarm can be silenced using alarm-cancel switch
Audible Alarm
Audible alarm indicates power failure and overload conditions
LED Indicators
9 LEDs indicate line power, battery power, AVR, overload and replace battery status - with a 3-LED level meter for
load and battery charge level
SURGE / NOISE SUPPRESSION
UPS AC Suppression Joule Rating
504
UPS AC Suppression Response
Time
Instantaneous
UPS Dataline Suppression
1 line TEL/DSL (1 in / 1 out); 10/100Base T Ethernet
3/5
1000 Eaton Boulevard
Cleveland, OH 44122
United States
EMI / RFI AC Noise Suppression
Yes
PHYSICAL
Primary Form Factor
Tower
Cooling Method
Fan
Installation Form Factors Supported
with Included Accessories
Tower
Primary UPS Depth (mm)
337
Primary UPS Height (mm)
260
Primary UPS Width (mm)
171
Shipping Dimensions (hwd / in.)
14.00 x 9.75 x 18.50
Shipping Dimensions (hwd / cm)
35.56 x 24.76 x 46.99
Shipping Weight (lbs.)
38.60
Shipping Weight (kg)
17.51
UPS Housing Material
Steel
UPS Power Module Dimensions
(hwd, cm)
26.04 x 17.14 x 33.66
UPS Power Module Dimensions
(hwd, in.)
10.25 x 6.75 x 13.25
UPS Power Module Weight (kg)
15.47
UPS Power Module Weight (lbs.)
34.1
Unit Dimensions (hwd / in.)
10.250 x 6.750 x 13.250
Unit Weight (lbs.)
34.1000
Unit Weight (kg)
15.47
ENVIRONMENTAL
Operating Temperature Range
32° to 104°F (0° to 40°C)
Storage Temperature Range
5° to 122°F (-15° to 50°C)
Relative Humidity
0 to 95%, non-condensing
AC Mode BTU / Hr. (Full Load)
73
AC Mode Efficiency Rating (100%
Load)
96%
Operating Elevation (ft.)
Up to 10,000 ft
Audible Noise
Audible Noise < 50 dBA at Front Side 1 Meter
Operating Elevation (m)
Up to 3,000m
COMMUNICATIONS
4/5
1000 Eaton Boulevard
Cleveland, OH 44122
United States
Network Management Cards
SNMPWEBCARD; WEBCARDLX ; RELAYIOCARD
Network Monitoring Port Description
Supports detailed monitoring of UPS and site power conditions
PowerAlert Software
For local monitoring via the UPS’s built-in communication ports, download PowerAlert software at
https://tripplite.eaton.com/products/power-alert
Communications Cable
USB and DB9 cabling included
WatchDog Compatibility
Supports Watchdog application, OS and hard-reboot restart options for remote applications
Network Management Card
Description
Network management card optional
Communications Interface
DB9 Serial; Slot for SNMP/Web interface; USB (HID enabled)
LINE / BATTERY TRANSFER
Transfer Time
4-8 milliseconds
Low Voltage Transfer to Battery
Power (Setpoint)
151 (220V), 158 (230V), 166 (240V); Voltage setpoints ±5% tolerance
High Voltage Transfer to Battery
Power (Setpoint)
266V (220V), 278V (230V) or 290V (240V); Voltage setpoints ±5% tolerance
FEATURES & SPECIFICATIONS
Cold Start (Startup in Battery Mode
During a Power Failure)
Cold-start operation supported
High Availability UPS Features
Auto Probe Monitoring (requires WEBCARDLX); Automatic Voltage Regulation (AVR); Hot swappable batteries;
Remote management; Sine wave output; Surge/noise protection
Green Energy-Saving Features
Greater than 95% efficiency - GREEN UPS
STANDARDS & COMPLIANCE
Product Certifications
GOST (Russia); EN 62040-1; EN 62040-2
Product Compliance
RoHS; SASO (Saudi Arabia); CE (Europe)
WARRANTY & SUPPORT
Product Warranty Period
(International)
2-year limited warranty
Product Warranty Period (Mexico)
2-year limited warranty
Product Warranty Period (Puerto
Rico)
2-year limited warranty
© 2023 Eaton. All Rights Reserved.
Eaton is a registered trademark. All other trademarks
are the property of their respective owners.
5/5