WDR-240 series
240W Single Output Industrial DIN RAIL Power Supply
Features :
Single and two phase wide input range 180~550VAC
High efficiency 91% and low power dissipation
Protections: Short circuit / Overload / Over voltage / Over temperature
Cooling by free air convection
Can be installed on DIN rail TS-35/7.5 or 15
UL 508(industrial control equipment)approved
EN61000-6-2(EN50082-2) industrial immunity level
Built-in DC OK relay contact
100% full load burn-in test
3 years warranty
SPECIFICATION
MODEL
OUTPUT
WDR-240-24
WDR-240-48
DC VOLTAGE
24V
48V
RATED CURRENT
10A
5A
CURRENT RANGE
0 ~ 10A
0 ~ 5A
RATED POWER
240W
240W
RIPPLE & NOISE (max.) Note.2 150mVp-p
150mVp-p
VOLTAGE ADJ. RANGE
48 ~ 55V
1.0%
24 ~ 28V
VOLTAGE TOLERANCE Note.3 1.0%
LINE REGULATION
0.5%
LOAD REGULATION
1.0%
18ms / 400VAC
HOLD UP TIME (Typ.)
INPUT
1.0%
800ms, 150ms/400VAC
SETUP, RISE TIME
VOLTAGE RANGE
0.5%
Note.6 180 ~ 550VAC
1500ms, 150ms/230VAC at full load
18ms / 230VAC at full load
254 ~ 780VDC
FREQUENCY RANGE
47 ~ 63Hz
EFFICIENCY (Typ.)
91%
AC CURRENT (Typ.)
INRUSH CURRENT (Typ.)
1A/400VAC
2A/230VAC
COLD STAR 50A
LEAKAGE CURRENT
100M Ohms / 500VDC / 25 / 70% RH
SAFETY & ISOLATION RESISTANCE
EMI CONDUCTION & RADIATION Compliance to EN55022 (CISPR22), EN61204-3 Class B
EMC
(Note 4)
Compliance to EN61000-3-2,-3
HARMONIC CURRENT
EMS IMMUNITY
MTBF
OTHERS
DIMENSION
PACKING
NOTE
Compliance to EN61000-4-2,3,4,5,6,8,11, ENV50204, EN55024, EN61000-6-2 (EN50082-2), EN61204-3, heavy industry level, criteria A approved
141.1Khrs min. MIL-HDBK-217F (25 )
63*125.2*113.5mm (W*H*D)
1.06Kg; 12pcs/13.7Kg/1.06CUFT
1. All parameters NOT specially mentioned are measured at 400VAC input, rated load and 25 of ambient temperature.
2. Ripple & noise are measured at 20MHz of bandwidth by using a 12" twisted pair-wire terminated with a 0.1uf & 47uf parallel capacitor.
3. Tolerance : includes set up tolerance, line regulation and load regulation.
4. The power supply is considered a component which will be installed into a final equipment. The final equipment must be re-confirmed that it still meets
EMC directives.
5. Installation clearances : 40mm on top, 20mm on the bottom, 5mm on the left and right side are recommended when loaded permanently with full power.
In case the adjacent device is a heat source, 15mm clearance is recommended.
6. Derating may be needed under low input voltage. Please check the derating curve for more details.
File Name:WDR-240-SPEC 2010-11-09
WDR-240 series
240W Single Output Industrial DIN RAIL Power Supply
Mechanical Specification
Unit:mm
113.5
Case No. 979B
125.2
TB1
DC OK
1
63
DC OK
3
+V ADJ.
2
TB2
1
2
3
4
5
6
+
Terminal Pin No. Assignment (TB1)
35
Pin No.
1
2
3
ADMISSIBLE DIN-RAIL:TS35/7.5 OR TS35/15
Assignment
FG
AC/L2
AC/L1
Terminal Pin No. Assignment (TB2)
Pin No.
1,2
3,4
5,6
Assignment
Relay Contact
DC OUTPUT +V
DC OUTPUT -V
Block Diagram
DC OK
I/P
EMI FILTER
&
RECTIFIERS
POWER
SWITCHING
PFC
CIRCUIT
RECTIFIERS
&
FILTER
+V
-V
O.C.P.
U.V.P.
FG
PFC
CONTROL
O.L.P.
PWM & PFC
CONTROL
DETECTION
CIRCUIT
O.V.P.
DC OK Relay Contact
Contact Close
PSU turns on / DC OK.
Contact Open
PSU turns off / DC Fail.
Contact Ratings (max.) 30V/1A resistive load.
File Name:WDR-240-SPEC 2010-11-09
WDR-240 series
240W Single Output Industrial DIN RAIL Power Supply
Derating Curve
Output derating VS input voltage
100
100
90
80
80
70
LOAD (%)
LOAD (%)
60
40
20
-30
60
50
40
0
10
20
30
40
50
AMBIENT TEMPERATURE ( )
60
70 (VERTICAL)
180
200
300
400
450
500
550
INPUT VOLTAGE (V) 60Hz
File Name:WDR-240-SPEC 2010-11-09