CP series CP1L CPU Unit
CP1L-EM@@D@-D/CP1L-EL@@D@-D
CP1L-M@@DR-A/CP1L-L@@DR-A
The Standard Package-type PLC
• "CP1L-EM" and "CP1L-EL" has a standard-feature Ethernet port.
• "CP1L-M" and "CP1L-L" has a standard-feature USB port.
• Function blocks (FB) allow you to build up modular structure and programming of ladder diagrams.
CP1L-L CPU Units
with 10 Points
CP1L-EL CPU Units
with 20 Points
CP1L-EM CPU Units
with 40 Points
CP1L-M CPU Units
with 60 Points
Features
• Complete with a standard-feature Ethernet port. "CP1L-EM" and "CP1L-EL" only.
• Pulse output for two axes. Advanced power for high-precision positioning control.
• High-speed Counters. Differential phases for four axes.
• Eight interrupt inputs are built in. Faster processing of approximately 500 instructions speeds up the entire system.
• Serial Communications. Two ports. Select Option Boards for either RS-232C or RS-485 communications.
• USB Peripheral Port. Another standard feature.
• The Structured Text (ST) Language. Makes math operations even easier.
• Can be used for the CP1W series and CJ series Unit. The extendibility of it is preeminently good.
• LCD displays and settings. Enabled using Option Board.
1
CP1L
Ordering Information
● International Standards
• The standards are abbreviated as follows: U: UL, U1: UL (Class I Division 2 Products for Hazardous Locations), C: CSA, UC: cULus,
UC1: cULus (Class I Division 2 Products for Hazardous Locations), CU: cUL, N: NK, L: Lloyd, and CE: EC Directives.
• Contact your OMRON representative for further details and applicable conditions for these standards.
■ CPU Units
Specifications
CPU Unit
CP1L-EM CPU Units with 40
Points
CP1L-EM CPU Units with 30
Points
CP1L-EL CPU Units with 20
Points
CP1L-M CPU Units with 60
Points
CP1L-M CPU Units with 40
Points
CP1L-M CPU Units with 30
Points
CP1L-L CPU Units with 20
Points
CPU type
Memory capacity: 10K steps
High-speed counters:
100 kHz, 4 axes
Pulse outputs: 100 kHz, 2 axes
(Models with transistor outputs
only)
Memory capacity: 10K steps
High-speed counters:
100 kHz, 4 axes
Pulse outputs: 100 kHz, 2 axes
(Models with transistor outputs
only)
Memory capacity: 5K steps
High-speed counters:
100 kHz, 4 axes
Pulse outputs: 100 kHz, 2 axes
(Models with transistor outputs
only)
Memory capacity: 10K steps
High-speed counters:
100 kHz, 4 axes
Pulse outputs: 100 kHz, 2 axes
(Models with transistor outputs
only)
Memory capacity: 10K steps
High-speed counters:
100 kHz, 4 axes
Pulse outputs: 100 kHz, 2 axes
(Models with transistor outputs
only)
Memory capacity: 10K steps
High-speed counters:
100 kHz, 4 axes
Pulse outputs: 100 kHz, 2 axes
(Models with transistor outputs
only)
Memory capacity: 5K steps
High-speed counters:
100 kHz, 4 axes
Pulse outputs: 100 kHz, 2 axes
(Models with transistor outputs
only)
Power
supply
Output method
Inputs
Outputs
Relay output
DC power
supply
DC power
supply
Transistor output
(sinking)
24
16
CP1L-EM40DT1-D
Relay output
CP1L-EM30DR-D
18
12
Transistor output
(sinking)
12
8
AC power
supply
CP1L-M60DR-A
CP1L-M60DT-A
AC power
supply
AC power
supply
CP1L-M60DR-D
Transistor output
(sourcing)
CP1L-M60DT1-D
Relay output
CP1L-M40DR-A
Transistor output
(sinking)
CP1L-M40DT-A
24
16
CP1L-M40DR-D
CP1L-M40DT-D
Transistor output
(sourcing)
CP1L-M40DT1-D
Relay output
CP1L-M30DR-A
Transistor output
(sinking)
CP1L-M30DT-A
Transistor output
(sinking)
18
12
CP1L-M30DR-D
CP1L-M30DT-D
Transistor output
(sourcing)
CP1L-L20DR-A
Transistor output
(sinking)
CP1L-L20DT-A
Transistor output
(sinking)
Transistor output
(sourcing)
UC1, N,
L, CE
UC1, N,
L, CE
UC1, N,
L, CE
CP1L-M30DT1-D
Relay output
Relay output
DC power
supply
24
CP1L-M60DT-D
Relay output
DC power
supply
36
Transistor output
(sinking)
Transistor output
(sinking)
CE
CP1L-EL20DT1-D
Relay output
Relay output
DC power
supply
CP1L-EL20DT-D
Transistor output
(sinking)
Relay output
CE
CP1L-EL20DR-D
Transistor output
(sourcing)
DC power
supply
CP1L-EM30DT-D
CE
CP1L-EM30DT1-D
Relay output
AC power
supply
CP1L-EM40DT-D
Transistor output
(sourcing)
Transistor output
(sinking)
Standards
CP1L-EM40DR-D
Transistor output
(sourcing)
DC power
supply
Model
12
8
CP1L-L20DR-D
CP1L-L20DT-D
UC1, N,
L, CE
CP1L-L20DT1-D
Windows are either registered trademarks or trademarks of Microsoft Corporation in the United States and/or other countries.
Other company names and product names in this document are the trademarks or registered trademarks of their respective companies.
2
CP1L
Specifications
CPU Unit
CP1L-L CPU Units with 14
Points
CP1L-L CPU Units with 10
Point
CPU type
Memory capacity: 5K steps
High-speed counters:
100 kHz, 4 axes
Pulse outputs: 100 kHz, 2 axes
(Models with transistor outputs
only)
Memory capacity: 5K steps
High-speed counters:
100 kHz, 4 axes
Pulse outputs: 100 kHz, 2 axes
(Models with transistor outputs
only)
Power
supply
AC power
supply
Output method
AC power
supply
Model
Relay output
CP1L-L14DR-A
CP1L-L14DT-A
Transistor output
(sinking)
8
6
CP1L-L14DR-D
CP1L-L14DT-D
Transistor output
(sourcing)
CP1L-L14DT1-D
Relay output
CP1L-L10DR-A
Transistor output
(sinking)
CP1L-L10DT-A
Relay output
DC power
supply
Outputs
Transistor output
(sinking)
Relay output
DC power
supply
Inputs
6
4
CP1L-L10DR-D
Transistor output
(sinking)
CP1L-L10DT-D
Transistor output
(sourcing)
CP1L-L10DT1-D
Standards
UC1, N,
L, CE
UC1, N,
L, CE
Note: 1. CP1L PLCs are supported by CX-Programmer version 7.1 or higher, except for EM40, EM30, EL20, M60, and L10 CPU Units.
CP1L-EM40/EM30/EL20 CPU Units are supported by CX-Programmer version @@@ or higher.
The 60-point CPU Units are supported by CX-Programmer version 7.2 or higher.
The 10-point CPU Units are supported by CX-Programmer version 7.3 or higher.
Update The CX-Programmer version automatically from the website using CX-Programmer version 7.0 (included with CX-One version 2.0).
2. Purchase an Option Unit (sold separately) if you will use RS-232C, RS-422A/485, Ethernet, or LCD.
■ Options for CPU Units
Name
Specifications
Model
Standards
CP1W-CIF01
RS-232C Option Board
UC1, N,
L, CE
RS-422A/485 Option Board
Can be mounted in either CPU Unit Option Board slot 1 or 2. *1
RS-422A/485 (Isolated-type)
Option Board
CP1W-CIF11
CP1W-CIF12
UC1, N,
L, CE
Ethernet Option Board
Can be mounted in either CPU Unit Option Board slot 1 or 2. *1 *2
CP1W-CIF41
UC1, N,
L, CE
Analog Input Option Board
Can be mounted in either CPU Unit Option Board slot 1 or 2. *3
2 analog inputs. 0-10V(Resolution:1/4000), 0-20mA (Resolution:1/2000).
CP1W-ADB21
CE
Analog Output Option Board
Can be mounted in either CPU Unit Option Board slot 1 or 2. *3
2 analog outputs. 0-10V (Resolution:1/4000).
CP1W-DAB21V
CE
Analog I/O Option Board
Can be mounted in either CPU Unit Option Board slot 1 or 2. *3
2 analog inputs. 0-10V(Resolution:1/4000), 0-20mA(Resolution:1/2000).
2 analog outputs. 0-10V (Resolution:1/4000).
CP1W-MAB221
CE
LCD Option Board
Can be mounted only in the CPU Unit Option Board slot 1. *1
CP1W-DAM01
UC1, L,
N, CE
Memory Cassette
Can be used for backing up programs or auto-booting.
CP1W-ME05M
UC1, N,
L, CE
*1. Cannot be used for the CP1L-L10.
*2. When using CP1W-CIF41 Ver.1.0, one Ethernet port can be added.
*3. CP1L-EM / EL only.
3
CP1L
■ Programming Devices
Specifications
Name
FA Integrated Tool
Package CX-One Lite
Version 4.@
Number of
licenses
CX-One Lite is a subset of the complete
CX-One package that provides only the Support Software
required for micro PLC applications.
CX-One Lite runs on the following OS.
OS: Windows XP (Service Pack 3 or higher), Vista or 7
Note: Except for Windows XP 64-bit version.
Model
Media
Standards
1 license
CD
CXONE-LT01C-V4
---
1 license *1
DVD *2
CXONE-AL01D-V4
---
CX-One Lite Ver. 4.@ includes Micro PLC Edition CXProgrammer Ver. 9.@.
FA Integrated Tool
Package CX-One
Ver. 4.@
CX-One is a package that integrates the Support Software for
OMRON PLCs and components. CX-One runs on the
following OS.
OS: Windows XP (Service Pack 3 or higher), Vista or 7
Note: Except for Windows XP 64-bit version.
CX-One Ver. 4.@ includes CX-Programmer Ver. 9.@.
Programming Device
Connecting Cable for
CP1W-CIF01 RS-232C
Option Board *3
USB-Serial Conversion Cable *3
Connects Personal Computers, D-Sub 9-pin (Length: 2.0 m)
Connects Personal Computers, D-Sub 9-pin (Length: 5.0 m)
For anti-static connectors
XW2Z-200S-CV
XW2Z-500S-CV
Connects Personal Computers, D-Sub 9-pin (Length: 2.0 m)
XW2Z-200S-V
Connects Personal Computers, D-Sub 9-pin (Length: 5.0 m)
XW2Z-500S-V
USB-RS-232C Conversion Cable (Length: 0.5 m) and PC driver (on a CD-ROM disc) are
included.
Complies with USB Specification 1.1
On personal computer side: USB (A plug connector, male)
On PLC side: RS-232C (D-sub 9-pin, male)
Driver: Supported by Windows 98, Me, 2000, and XP
CS1W-CIF31
---
N
Note: 1. CP1L PLCs are supported by CX-Programmer version 7.1 or higher, except for EM40, EM30, EL20, M60, and L10 CPU Units.
CP1L-EM40/EM30/EL20 CPU Units are supported by CX-Programmer version @@@ or higher.
The 60-point CPU Units are supported by CX-Programmer version 7.2 or higher.
The 10-point CPU Units are supported by CX-Programmer version 7.3 or higher.
Update The CX-Programmer version automatically from the website using CX-Programmer version 7.0 (included with CX-One version 2.0).
2. The CX-One and CX-One Lite cannot be simultaneously installed on the same computer.
*1. Multi licenses are available for the CX-One (3, 10, 30 or 50 licenses).
*2. The CX-One is also available on CD (CXONE-AL@@C-V4).
*3. Cannot be used with a peripheral USB port.
To connect to a personal computer via a peripheral USB port, use commercially-available USB cable (A or B type, male).
The following tables lists the Support Software that can be installed from CX-One
CX-One Lite
Ver.4.@
Support Software in CX-One
Support Software in CX-One
CX-One Lite
Ver.4.@
CX-One
Ver.4.@
Yes
Micro PLC Edition CX-Programmer
Ver.9.@
Yes
No
CX-Drive
Ver.2.@
Yes
CX-Programmer
Ver.9.@
No
Yes
CX-Process Tool
Ver.5.@
No
Yes
CX-Integrator
Ver.2.@
Yes
Yes
Faceplate Auto-Builder for NS
Ver.3.@
No
Yes
Yes
Switch Box Utility
Ver.1.@
Yes
Yes
CX-Designer
Ver.3.@
Yes
CX-Protocol
Ver.1.@
No
Yes
NV-Designer
Ver.1.@
Yes
Yes
CX-Simulator
Ver.1.@
Yes
Yes
CX-Thermo
Ver.4.@
Yes
Yes
CX-Position
Ver.2.@
No
Yes
CX-ConfiguratorFDT
Ver.1.@
Yes
Yes
CX-Motion-NCF
Ver.1.@
No
Yes
CX-FLnet
Ver.1.@
No
Yes
CX-Motion-MCH
Ver.2.@
No
Yes
Network Configurator
Ver.3.@
Yes
Yes
CX-Motion
Ver.2.@
No
Yes
CX-Server
Ver.4.@
Yes
Yes
Note: For details, refer to the CX-One Catalog (Cat. No: R134).
4
CX-One
Ver.4.@
CP1L
■ Expansion Units
Name
Output method
Inputs
Outputs
Model
Relay
Transistor (sinking)
24
16
CP1W-40EDT
Transistor (sourcing)
CP1W-32ER
Transistor (sinking)
---
32
CP1W-32ET
Transistor (sourcing)
N, L, CE
CP1W-32ET1
Relay
CP1W-20EDR1
Transistor (sinking)
12
8
CP1W-20EDT
Transistor (sourcing)
U, C, N, L, CE
CP1W-20EDT1
Relay
CP1W-16ER
Transistor (sinking)
---
16
CP1W-16ET
Transistor (sourcing)
N, L, CE
CP1W-16ET1
---
8
Relay
Transistor (sinking)
---
Transistor (sourcing)
Analog Input Unit
N, L, CE
CP1W-40EDT1
Relay
Expansion I/O Units
Standards
CP1W-40EDR
Analog (resolution: 1/6000)
4
---
CP1W-8ED
8
CP1W-8ER
CP1W-8ET
8
U, C, N, L, CE
CP1W-8ET1
---
CP1W-AD041
UC1, N, L, CE
Analog Output Unit
CP1W-DA041
2
CP1W-DA021
UC1, CE
2
1
CP1W-MAD11
U, C, N, L, CE
8
(I/O link input bits)
8
(I/O link input bits)
CP1W-SRT21
Analog (resolution: 1/6000)
Analog I/O Unit
Analog (resolution: 1/6000)
CompoBus/S I/O Link
Unit
---
Temperature Sensor
Unit
4
---
2 thermocouple inputs
CP1W-TS001
4 thermocouple inputs
CP1W-TS002
2 platinum resistance thermometer inputs
CP1W-TS101
4 platinum resistance thermometer inputs
CP1W-TS102
U, C, N, L, CE
CP1L (L Type) CPU Units with 10 points do not support Expansion Units.
■ I/O Connecting Cable
Name
Specifications
Model
I/O Connecting Cable
80 cm (for CP1W/CPM1A Expansion Units)
CP1W-CN811
Standards
UC1, N, L, CE
Note: An I/O Connecting Cable (approx. 6 cm) for horizontal connection is provided with CP1W/CPM1A Expansion Units.
■ Optional Products, Maintenance Products and DIN Track Accessories
Name
DIN Track
End Plate
Specifications
Model
Length: 0.5 m; Height: 7.3 mm
PFP-50N
Length: 1 m; Height: 7.3 mm
PFP-100N
Length: 1 m; Height: 16 mm
PFP-100N2
There are 2 stoppers provided with CPU Units and I/O Interface Units as
standard accessories to secure the Units on the DIN Track.
PFP-M
Standards
---
5
CP1L
General Specifications
Item
Type
AC power supply models
Model
CP1L-@@@-A
DC power supply models
CP1L-@@@-D
Power supply
100 to 240 VAC 50/60 Hz
24 VDC
Operating voltage range
85 264 VAC
20.4 to 26.4 VDC
Power consumption
50 VA max. (CP1L-M60/-M40/-M30@@-A) (See page 27)
30 VA max. (CP1L-L20/-L14/-L10@@-A)
20 W max. (CP1L-M60/-M40/-M30@@-D) (See page 27)
13 W max. (CP1L-L20/-L14/-L10@@-D)
Inrush current *
100 to 120 VAC inputs:
20 A max. (for cold start at room temperature)
8 ms max.
200 to 240 VAC inputs:
40 A max. (for cold start at room temperature), 8 ms max.
30 A max. (for cold start at room temperature)
20 ms max.
External power supply
300 mA at 24 VDC (CP1L-M60/-M40/-M30@@-A)
200 mA at 24 VDC (CP1L-L20/-L14/-L10@@-A)
None
Insulation resistance
20 MΩ min. (at 500 VDC) between the external AC terminals
and GR terminals
No insulation between primary and secondary for DC power
supply
Dielectric strength
2,300 VAC at 50/60 Hz for 1 min between the external AC and
GR terminals, leakage current: 5 mA max.
No insulation between primary and secondary for DC power
supply
Noise immunity
Conforms to IEC 61000-4-4. 2 kV (power supply line)
Vibration resistance
Conforms to JIS C0040. 10 to 57 Hz, 0.075-mm amplitude, 57 to 150 Hz, acceleration: 9.8 m/s2 in X, Y, and Z directions for 80
minutes each. Sweep time: 8 minutes × 10 sweeps = total time of 80 minutes)
Shock resistance
Conforms to JIS C0041. 147 m/s2 three times each in X, Y, and Z directions
Ambient operating temperature
0 to 55°C
Ambient humidity
10% to 90% (with no condensation)
Ambient operating environment
No corrosive gas
Ambient storage temperature
−20 to 75°C (Excluding battery.)
Power holding time
10 ms min.
2 ms min.
* The above values are for a cold start at room temperature for an AC power supply, and for a cold start for a DC power supply.
• A thermistor (with low-temperature current suppression characteristics) is used in the inrush current control circuitry for the AC power supply. The thermistor will
not be sufficiently cooled if the ambient temperature is high or if a hot start is performed when the power supply has been OFF for only a short time. In those cases
the inrush current values may be higher (as much as two times higher) than those shown above. Always allow for this when selecting fuses and breakers for
external circuits.
• A capacitor charge-type delay circuit is used in the inrush current control circuitry for the DC power supply. The capacitor will not be charged if a hot start is
performed when the power supply has been OFF for only a short time, so in those cases the inrush current values may be higher (as much as two times higher)
than those shown above.
6
CP1L
Performance Specifications
● CP1L CPU Unit (EM/EL Type)
Type
Item
CP1L-EM40 (40 points)
CP1L-EM30 (30 points)
CP1L-EL20 (20 points)
CP1L-EM40D@-@
CP1L-EM30D@-@
CP1L-EL20D@-@
Models
Control method
Stored program method
I/O control method
Cyclic scan with immediate refreshing
Program language
Ladder diagram
Function blocks
Maximum number of function block definitions: 128 Maximum number of instances: 256
Languages usable in function block definitions: Ladder diagrams, structured text (ST)
Instruction length
1 to 7 steps per instruction
Instructions
Approx. 500 (function codes: 3 digits)
Instruction execution time
Basic instructions: 0.55 μs min. Special instructions: 4.1 μs min.
Common processing time
0.4ms
Program capacity
10K steps
FB program memory
Number of tasks
288 (32 cyclic tasks and 256 interrupt tasks)
Scheduled interrupt tasks
Input interrupt tasks
1 (interrupt task No. 2, fixed)
6 (interrupt task No. 140 to 145, fixed)
(Interrupt tasks can also be specified and executed for high-speed counter interrupts and executed.)
Maximum subroutine number
256
Maximum jump number
256
I/O areas
5K steps
10K steps
Input bits
24: CIO 0.00 to CIO 0.11 and
CIO 1.00 to CIO 1.11
18: CIO 0.00 to CIO 0.11 and
CIO 1.00 to CIO 1.05
12: CIO 0.00 to CIO 0.11
Output bits
8: CIO 100.00 to CIO 100.07 and
CIO 101.00 to CIO 101.07
12: CIO 100.00 to CIO 100.07 and
CIO 101.00 to CIO 101.03
8: CIO 100.00 to CIO 100.07
1:1 Link Area
1,024 bits (64 words): CIO 3000.00 to CIO 3063.15 (CIO 3000 to CIO 3063)
Serial PLC Link Area
1,440 bits (90 words): CIO 3100.00 to CIO 3189.15 (CIO 3100 to CIO 3189)
Work bits
8,192 bits (512 words): W000.00 to W511.15 (W0 to W511) CIO Area: 37,504 bits (2,344 words):
CIO 3800.00 to CIO 6143.15 (CIO 3800 to CIO 6143)
TR Area
16 bits: TR0 to TR15
Holding Area
8,192 bits (512 words): H0.00 to H511.15 (H0 to H511)
AR Area
Read-only (Write-prohibited): 7168 bits (448 words): A0.00 to A447.15 (A0 to A447)
Read/Write: 8192 bits (512 words): A448.00 to A959.15 (A448 to A959)
Timers
4,096 bits: T0 to T4095
Counters
4,096 bits: C0 to C4095
DM Area
32 Kwords: D0 to D32767
Data Register Area
16 registers (16 bits): DR0 to DR15
Index Register Area
16 registers (32 bits): IR0 to IR15
Task Flag Area
32 flags (32 bits): TK0000 to TK0031
Trace Memory
4,000 words (500 samples for the trace data maximum of 31 bits and 6 words.)
Memory Cassette *
A special Memory Cassette (CP1W-ME05M) can be mounted.
Clock function
Supported. Accuracy (monthly deviation): -4.5 min to -0.5 min (ambient temperature: 55°C),
-2.0 min to +2.0 min (ambient temperature: 25°C), -2.5 min to +1.5 min (ambient temperature: 0°C)
10 Kwords: D0 to D9999, D32000
to D32767
Built-in Ethernet Port (Connecting Support Software, Message Communications, Socket Service)
Communications functions
A maximum of two Serial Communications Option Boards can be
mounted.
A maximum of one Serial
Communications Option Board can
be mounted.
Memory backup
Flash memory: User programs, parameters (such as the PLC Setup), comment data, and the entire DM Area
can be saved to flash memory as initial values.
Battery backup: The Holding Area, DM Area, and counter values (flags, PV) are backed up by a battery.
Battery service life
5 years at 25°C. (Use the replacement battery within two years of manufacture.)
Built-in input terminals
40 (24 inputs, 16 outputs)
30 (18 inputs, 12 outputs)
20 (12 inputs, 8 outputs)
Number of connectable Expansion Units and
Expansion I/O Units
CP-series Expansion Unit and Expansion I/O Units: 3 max.
CP-series Expansion Units and
Expansion I/O Units: 1 max.
Max. number of I/O points
160 (40 built in + 40 per Expansion
(I/O) Unit x 3 Units)
60 (20 built in + 40 per Expansion
(I/O) Unit x 1 Unit)
Interrupt inputs
6 inputs (Response time: 0.3 ms)
Interrupt inputs counter mode
6 inputs (Response frequency: 5 kHz max. for all interrupt inputs), 16 bits Up or down counters
Quick-response inputs
6 points (Min. input pulse width: 50 μs max.)
Scheduled interrupts
1
High-speed counters
4 counters, 2 axes (24-VDC input) 4 inputs:
Differential phases (4x), 50 kHz Single-phase (pulse plus direction, up/down, increment), 100 kHz
Value range: 32 bits, Linear mode or ring mode
Interrupts: Target value comparison or range comparison
Pulse outputs
(models with
transistor outputs
only)
150 (30 built in + 40 per Expansion
(I/O) Unit x 3 Units)
Pulse outputs
Trapezoidal or S-curve acceleration and deceleration (Duty ratio: 50% fixed)
2 outputs, 1 Hz to 100 kHz (CCW/CW or pulse plus direction)
PWM outputs
Duty ratio: 0.0% to 100.0% (specified in increments of 0.1% or 1%)
2 outputs, 0.1 to 6553.5 Hz or 1 to 32,800 Hz
(Accuracy: +1%/0% at 0.1 Hz to 10,000 Hz and +5%/0% at 10,000 Hz to 32,800 Hz)
External analog input
2 input (Resolution: 1/1000, Input range: 0 to 10 V). Not isolated.
* Can be used for program backups and auto-booting.
7
CP1L
● CP1L CPU Unit (M/L Type)
CP1L-M60
(60 points)
CP1L-M40
(40 points)
CP1L-M30
(30 points)
CP1L-L20
(20 points)
CP1L-L14
(14 points)
CP1L-L10
(10 points)
CP1L-M60@@-@
CP1L-M40@@-@
CP1L-M30@@-@
CP1L-L20@@-@
CP1L-L14@@-@
CP1L-L10@@-@
Type
Item
Models
Control method
Stored program method
I/O control method
Cyclic scan with immediate refreshing
Program language
Ladder diagram
Function blocks
Maximum number of function block definitions: 128 Maximum number of instances: 256
Languages usable in function block definitions: Ladder diagrams, structured text (ST)
Instruction length
1 to 7 steps per instruction
Instructions
Approx. 500 (function codes: 3 digits)
Instruction execution time
Basic instructions: 0.55 μs min. Special instructions: 4.1 μs min.
Common processing time
0.4 ms
Program capacity
10K steps
Number of tasks
288 (32 cyclic tasks and 256 interrupt tasks)
Scheduled interrupt tasks
Input interrupt
tasks
5K steps
1 (interrupt task No. 2, fixed)
4 (interrupt task No. 2 (interrupt task No.
140 to 143, fixed)
140 to 141, fixed)
6 (interrupt task No. 140 to 145, fixed)
(Interrupt tasks can also be specified and executed for high-speed counter interrupts and executed.)
Maximum subroutine number 256
Maximum jump number
I/O
areas
256
Input bits
36: CIO 0.00 to CIO
24: CIO 0.00 to CIO 18: CIO 0.00 to CIO
12: CIO 0.00 to CIO 8: CIO 0.00 to CIO
0.11, CIO 1.00 to
0.11 and CIO 1.00
0.11 and CIO 1.00
0.11
0.07
CIO 1.11, and CIO
to CIO 1.05
to CIO 1.11
2.00 to CIO 2.11
6: CIO 0.00 to CIO
0.05
Output bits
24: CIO 100.00 to
CIO 100.07,
CIO 101.00 to CIO
101.07, and CIO
102.00 to CIO
102.07
4: CIO 100.00 to
CIO 100.03
1:1 Link Area
1,024 bits (64 words): CIO 3000.00 to CIO 3063.15 (CIO 3000 to CIO 3063)
Serial PLC Link
Area
12: CIO 100.00 to
24: CIO 0.00 to CIO
CIO 100.07 and
0.11 and CIO 1.00
CIO 101.00 to CIO
to CIO 1.11
101.03
8: CIO 100.00 to
CIO 100.07
6: CIO 100.00 to
CIO 100.05
1,440 bits (90 words): CIO 3100.00 to CIO 3189.15 (CIO 3100 to CIO 3189)
Work bits
8,192 bits (512 words): W000.00 to W511.15 (W0 to W511)
CIO Area: 37,504 bits (2,344 words): CIO 3800.00 to CIO 6143.15 (CIO 3800 to CIO 6143)
TR Area
16 bits: TR0 to TR15
Holding Area
8,192 bits (512 words): H0.00 to H511.15 (H0 to H511)
AR Area
Read-only (Write-prohibited): 7168 bits (448 words): A0.00 to A447.15 (A0 to A447)
Read/Write: 8192 bits (512 words): A448.00 to A959.15 (A448 to A959)
Timers
4,096 bits: T0 to T4095
Counters
4,096 bits: C0 to C4095
DM Area
32 Kwords: D0 to D32767
Data Register Area
16 registers (16 bits): DR0 to DR15
Index Register Area
16 registers (32 bits): IR0 to IR15
Task Flag Area
32 flags (32 bits): TK0000 to TK0031
Trace Memory
4,000 words (500 samples for the trace data maximum of 31 bits and 6 words.)
Memory Cassette
A special Memory Cassette (CP1W-ME05M) can be mounted. Note: Can be used for program backups and auto-booting.
Clock function
Supported. Accuracy (monthly deviation): −4.5 min to −0.5 min (ambient temperature: 55°C),
−2.0 min to +2.0 min (ambient temperature: 25°C), −2.5 min to +1.5 min (ambient temperature: 0°C)
10 Kwords: D0 to D9999, D32000 to D32767
One built-in peripheral port (USB 1.1): For connecting Support Software only.
Communications functions
8
A maximum of two Serial Communications Option Boards can be A maximum of one Serial Communications
Not supported.
mounted.
Option Board can be mounted.
A maximum of two Ethernet Option Board can be mounted.
When using CP1W-CIF41 Ver.1.0, one Ethernet Option Board
can be mounted.
A maximum of one Ethernet Option Board
Not supported.
can be mounted.
Memory backup
Flash memory: User programs, parameters (such as the PLC Setup), comment data, and the entire DM Area can be saved to flash
memory as initial values.
Battery backup: The Holding Area, DM Area, and counter values (flags, PV) are backed up by a battery.
Battery service life
5 years at 25°C. (Use the replacement battery within two years of manufacture.)
Built-in input terminals
60 (36 inputs,
24 outputs)
Number of connectable
Expansion Units and
Expansion I/O Units
CP-series Expansion Unit and Expansion I/O Units: 3 max.
Max. number of I/O points
180 (60 built in + 40 160 (40 built in + 40 150 (30 built in + 40 60 (20 built in + 40
per Expansion (I/O) per Expansion (I/O) per Expansion (I/O) per Expansion (I/O)
Unit × 1 Unit)
Unit × 3 Units)
Unit × 3 Units)
Unit × 3 Units)
54 (14 built in + 40
per Expansion (I/O)
Unit × 1 Unit)
10 (10 built in)
Interrupt inputs
6 inputs (Response time: 0.3 ms)
4 inputs (Response
time: 0.3 ms)
2 inputs (Response
time: 0.3 ms)
40 (24 inputs,
16 outputs)
30 (184 inputs,
12 outputs)
20 (12 inputs,
8 outputs)
14 (8 inputs,
6 outputs)
10 (6 inputs,
4 outputs)
CP-series Expansion Units and Expansion
Not supported.
I/O Units: 1 max.
CP1L
Type
Item
Models
CP1L-M60
(60 points)
CP1L-M40
(40 points)
CP1L-M30
(30 points)
CP1L-L20
(20 points)
CP1L-M60@@-@
CP1L-M40@@-@
CP1L-M30@@-@
CP1L-L20@@-@
CP1L-L14
(14 points)
CP1L-L14@@-@
CP1L-L10@@-@
2 inputs (Response
frequency:
5 kHz max. for all
interrupt inputs),
16 bits
Up or down
counters
2 points (Min. input
pulse width: 50 μs
max.)
Interrupt inputs counter
mode
6 inputs (Response frequency: 5 kHz max. for all interrupt inputs), 16 bits
Up or down counters
4 inputs (Response
frequency:
5 kHz max. for all
interrupt inputs),
16 bits
Up or down
counters
Quick-response inputs
6 points (Min. input pulse width: 50 μs max.)
4 points (Min. input
pulse width: 50 μs
max.)
Scheduled interrupts
1
High-speed counters
4 counters, 2 axes (24-VDC input) 4 inputs: Differential phases (4x), 50 kHz
Single-phase (pulse plus direction, up/down, increment), 100 kHz
Value range: 32 bits, Linear mode or ring mode
Interrupts: Target value comparison or range comparison
Pulse outputs
(models with
transistor outputs only)
CP1L-L10
(10 points)
Pulse
outputs
Trapezoidal or S-curve acceleration and deceleration (Duty ratio: 50% fixed)
2 outputs, 1 Hz to 100 kHz (CCW/CW or pulse plus direction)
PWM
outputs
Duty ratio: 0.0% to 100.0% (specified in increments of 0.1% or 1%)
2 outputs, 0.1 to 6553.5 Hz or 1 to 32,800 Hz (Accuracy: +1%/0% at 0.1 Hz to 10,000 Hz and +5%/0% at 10,000 Hz to 32,800 Hz)
Analog control
1 (Setting range: 0 to 255)
External analog input
1 input (Resolution: 1/256, Input range: 0 to 10 V). Not isolated.
9
CP1L
Built-in Inputs
■ Input Terminal Block Arrangement (Top Block)
● CP1L (20 Inputs)
● CP1L (60 Inputs)
· AC Power Supply Models
L1 L2/N COM 01
00
· AC Power Supply Models
03
02
05
04
07
06
09
08
11
10
00
−
NC
COM 01
00
03
02
03
02
05
04
07
06
09
08
11
10
05
04
07
06
09
08
11
10
Inputs (CIO 0)
01
00
03
02
01
00
Inputs (CIO 1)
Inputs (CIO 0)
· DC Power Supply Models
+
01
03
02
05
04
07
06
09
08
11
L1
L2/N COM
10
00
Inputs (CIO 2)
05
04
07
06
09
08
11
10
01
00
03
02
07
06
09
08
11
10
02
05
04
07
06
09
08
11
10
· DC Power Supply Models
+
−
COM
NC
Inputs (CIO 2)
Inputs (CIO 1)
03
Inputs (CIO 0)
05
04
01
01
00
03
02
05
04
07
06
09
08
11
10
Inputs (CIO 0)
● CP1L (14 Inputs)
● CP1L (40 Inputs)
· AC Power Supply Models
L1
L2/N COM
01
00
· AC Power Supply Models
03
02
05
04
07
06
09
08
11
10
Inputs (CIO 0)
01
00
03
02
05
04
07
06
09
08
11
−
NC
COM
01
00
L2/N COM
01
00
Inputs (CIO 1)
03
02
05
04
07
06
09
08
11
10
01
00
03
02
05
04
07
06
09
08
11
10
+
−
COM
NC
Inputs (CIO 1)
01
00
· AC Power Supply Models
L1 L2/N COM 01
03
05
07
09
11
01
03
02
04
06
08
10
Inputs (CIO 0)
00
02
04
NC
−
NC
COM
00
01
02
05
04
07
06
09
08
11
10
01
00
03
02
Inputs (CIO 1)
05
04
Inputs (CIO 0)
COM 01
03
Inputs (CIO 0)
10
02
· DC Power Supply Models
Inputs (CIO 1)
· DC Power Supply Models
+
03
05
00
00
07
06
05
04
Inputs (CIO 0)
· AC Power Supply Models
01
03
02
● CP1L (10 Inputs)
● CP1L (30 inputs)
L2/N COM
05
04
NC
NC
NC
NC
· DC Power Supply Models
Inputs (CIO 0)
L1
03
02
Inputs (CIO 0)
· DC Power Supply Models
+
L1
10
NC
05
04
NC
00
03
02
05
04
Inputs (CIO 0)
07
06
NC
NC
NC
NC
CP1L
■ Built-in Input Area
Input terminal block
Number of
inputs
Word
Input operation
High-speed counter operation
Origin search
Origin searches enabled for
pulse outputs 0 and 1
Bit
Normal
inputs
00
Normal
input 0
---
---
High-speed
counter 0
(increment)
High-speed counter 0
(phase-A, increment,
or count input)
---
---
---
01
Normal
input 1
---
---
High-speed
counter 1
(increment)
High-speed counter 0
(phase-B, decrement,
or count input)
---
---
---
---
High-speed
counter 2
(increment)
High-speed counter 1
(phase-A, increment,
or count input)
---
Pulse
output 0:
Origin
proximity
input
signal
---
Pulse
output 0:
Origin
proximity
input
signal
02
Normal
input 2
Interrupt
Quick-response inputs
inputs
Operation settings
• High-speed counters enabled
• Phase-Z signal reset
---
Two-phase
Single-phase
CPU Units CPU Units CPU Units
(differential phase x4,
(increment pulse
with 20 to with 14
with 10
up/down, or pulse
input)
60 points points
points
plus direction)
10
CIO 0
03
Normal
input 3
---
---
High-speed
counter 3
(increment)
High-speed counter 1
(phase-B, decrement,
or count input)
---
Pulse
output 1:
Origin
proximity
input
signal
04
Normal
input 4
Interrupt
input 0
Quick-response input 0
Counter 0, phaseZ/reset input
High-speed counter 0
(phase-Z/reset)
---
---
---
---
Pulse
output 0:
Origin
input
signal-
05
Normal
input 5
Interrupt
input 1
Quick-response input 1
Counter 1, phaseZ/reset input
06
Normal
input 6
Interrupt
input 2
Quick-response input 2
Counter 2, phaseZ/reset input
Pulse output 0:
Origin input signal
---
07
Normal
input 7
Interrupt
input 3
Quick-response input 3
Counter 3, phaseZ/reset input
Pulse output 1:
Origin input signal
---
08
Normal
input 8
Interrupt
input 4
Quick-response input 4
---
---
---
---
09
Normal
input 9
Interrupt
input 5
Quick-response input 5
---
---
---
---
---
Pulse
output 0:
Origin
proximity
input
signal
---
---
---
---
14
10
20
30
60
CIO 2
---
---
---
11
Normal
input 11
---
---
---
Pulse
output 1:
Origin
proximity
input
signal
00
Normal
input 12
---
---
---
---
---
---
to
to
to
to
to
to
to
to
to
05
Normal
input 17
---
---
---
---
---
---
---
06
Normal
input 18
---
---
---
---
---
---
---
to
to
to
to
to
to
to
to
to
11
Normal
input 23
---
---
---
---
---
---
---
00
Normal
input 24
---
---
---
---
---
---
---
to
to
to
to
to
to
to
to
to
11
Normal
input 35
---
---
---
---
---
---
---
CIO 1
40
Normal
input 10
High-speed counter 1
(phase-Z/reset)
11
CP1L
Built-in Outputs
■ Output Terminal Block Arrangement (Bottom Block)
● CP1L (60 Outputs)
● CP1L (20 Outputs)
· AC Power Supply Models
+
-
00
01
02
· AC Power Supply Models
04
05
07
00
02
04
05
07
00
02
COM COM COM 03 COM 06 COM 01
03 COM 06 COM 01
CIO 101
CIO 102
CIO 100
· DC Power Supply Models
NC
00
01
02
04
05
07
03 COM 06
+
−
05
07
CIO 100
00
02
04
05
07
00
02
03 COM 06 COM 01
04
05
07
01
02
NC
NC
03
04
06
05
00
07
CIO 100
01
03
COM
02
04
COM
01
02
01
04
03
02
05
COM
04
03
COM(V-)
07
06
05
COM
07
06
CIO 100
03
CP1L-EL20DT1-D
04
06
00
01
03
04
06
V+
NC
00
V-
CP1L-EM40DR-D/CP1L-M40D@-D
02
00
COM COM COM
V+
07
CIO 101
01
07
06
CP1L-EL20DT-D
05
05
· DC Power Supply Models
00
05
COM
CIO 100
COM COM COM COM
NC
04
03
03 COM 06
· AC Power Supply Models
00
02
· DC Power Supply Models
CP1L-EL20DR-D/CP1L-L20D@-D
CIO 102
CIO 101
● CP1L (40 Outputs)
-
01
CIO 100
04
NC COM COM COM 03 COM 06 COM 01
+
00
COM COM COM
COM COM COM COM
05
07
CIO 100
COM
02
COM
05
00
01
02
04
05
07
07
V-
CIO 101
03
COM(V+)
COM
06
CIO 100
CP1L-EM40DT-D
V+
00
V-
01
02
03
COM(V-)
04
COM
06
05
00
07
CIO 100
01
03
COM
02
04
COM
● CP1L (14 Outputs)
06
05
07
+
CIO 101
−
CP1L-EM40DT1-D
V+
00
· AC Power Supply Models
01
02
03
04
06
00
01
03
04
00
01
02
COM COM COM
04
03
05
COM
NC
NC
CIO 100
06
· DC Power Supply Models
V-
COM(V+)
COM
05
07
CIO 100
COM
02
COM
05
07
NC
CIO 101
● CP1L (30 Outputs)
NC
00
01
02
COM COM COM
04
03
CIO 100
· AC Power Supply Models
+
00
01
02
04
05
07
00
● CP1L (10 Outputs)
02
· AC Power Supply Models
COM COM COM
03
COM
06
CIO 100
COM
01
03
CIO 101
· DC Power Supply Models
CP1L-EM30DR-D/CP1L-M30D@-D
NC
NC
00
01
02
COM COM COM
04
03
00
05
COM
07
06
00
COM
02
01
NC
03
01
02
04
03
05
COM
07
06
00
COM
02
01
03
CIO 101
CIO 100
CP1L-EM30DT1-D
V+
V-
00
CIO 100
12
01
COM(V+)
02
04
03
05
COM
07
06
00
COM
CIO 101
00
02
01
03
01
02
NC COM COM COM 03
CIO 100
CIO 101
COM(V-)
02
CIO 100
CIO 100
V+
01
· DC Power Supply Models
CP1L-EM30DT-D
V-
00
COM COM COM 03
05
COM
NC
NC
CP1L
■ Built-in Output Area
Output Terminal
Block
When the
instructions to
the right are not
executed
When a pulse output instruction
(SPED, ACC, PLS2, or ORG) is executed
Number of
outputs
10
CIO 100
Bit
Normal output
00
Normal output 0
01
Normal output 1
02
Normal output 2
CW/CCW
Pulse plus direction
Pulse output 0 (CW)
Pulse output 0 (pulse)
Pulse output 0 (CCW) Pulse output 0 (direction)
Pulse output 1 (CW)
Pulse output 1 (pulse)
Pulse output 1 (CCW) Pulse output 1 (direction)
30
CIO 101
40
CIO 102
CPU Units
with 10 point
PWM output
---
---
---
---
---
PWM output 0
---
---
---
---
Origin search 0
(Error counter
reset output)
PWM output 1
03
Normal output 3
04
Normal output 4
---
---
Origin search 0
(Error counter
reset output)
---
---
05
Normal output 5
---
---
Origin search 1
(Error counter
reset output)
---
---
06
Normal output 6
---
---
---
---
---
07
Normal output 7
---
---
---
---
---
00
Normal output 8
---
---
---
---
---
to
to
to
to
to
to
03
Normal output 11
---
---
---
04
Normal output 12
---
---
---
to
to
to
to
to
to
to
07
Normal output 15
---
---
---
---
---
01
Normal output 16
---
---
---
---
---
to
to
to
to
to
to
to
07
Normal output 23
---
---
---
---
---
14
20
When the origin search function
is used
CPU Units with
14 to 60 points
When the PWM
instruction is
executed
Variable duty ratio
pulse output
Fixed duty ratio pulse output
Word
60
When the origin search function is
set to be used in the PLC Setup,
and an origin search is executed
by the ORG instruction
to
-----
13
CP1L
I/O Specifications for CPU Units
■ Input Specifications
Specifications
Interrupt inputs and
quick-response inputs
Normal inputs
CIO 0.00 to CIO 0.03
CIO 0.04 to CIO 0.09
CIO 0.10, CIO 0.11,
CIO 1.00 to CIO 1.11, and
CIO 2.00 to 2.11
Input voltage
24 VDC +10%/–15%
Applicable sensors
2-wire sensors or 3-wire sensors
Input impedance
3.0 kΩ
4.7 kΩ
Input current
7.5 mA typical
5 mA typical
ON voltage
17.0 VDC min.
14.4 VDC min.
OFF voltage/current
1 mA max. at 5.0 VDC
ON delay
2.5 μs max.
50 μs max.
1 ms max.
OFF delay
2.5 μs max.
50 μs max.
1 ms max.
IN
IN
Input LED
3.0 kΩ
Internal
circuits
IN
COM
3.0 kΩ
910 Ω
IN
Input LED
1000 pF
4.3 kΩ
1000 pF
Circuit configuration
IN
Input LED
Internal
circuits
IN
COM
4.7 kΩ
750 Ω
ITEM
High-speed counter inputs
(phases A and B)
Internal
circuits
COM
● High-speed Counter Function Input Specifications
Input bits: CIO 0.00 to CIO 0.03
Item
Specifications
• Differential phase input mode
• Pulse plus direction input mode
• Increment mode
• Up/down input mode
20.0 μs min.
ON
Phase A
10.0 μs min.
ON/OFF delay
90%
50%
10%
OFF
ON
ON
Phase A
90%
50%
10%
OFF
90%
50%
10%
OFF
T1
2.5 μs min.
2.5 μs min.
T2
T3
T4
T1,T2,T3,T4 : 2.5 μs min
● Interrupt Input Counter Mode
Input bits: CIO 0.04 to CIO 0.09
Item
Specifications
ON
ON/OFF delay
90%
10%
OFF
50 μs min.
50 μs min.
■ Output Specifications
● CPU Units with Relay Outputs
Specifications
Min. switching capacity 5 VDC, 10 mA
Electrical
500
Resis100,000 operations (24 VDC)
tive load
200
30 VDC/250 VAC resistive load
Induc48,000 operations (250 VAC, cosφ = 0.4)
tive load
Mechanical
100
30 VDC τ = 7 ms
20,000,000 operations
ON delay
15 ms max.
OFF delay
15 ms max.
Output LED
50
30
20
10
5
125 VAC cos φ = 0.4
3
2
250 VAC cos φ = 0.4
OUT
L
0.1
Circuit configuration
Internal circuits
0.2 0.3
0.5 0.7
1
2
3
5
10
Contact current (A)
L
OUT
COM
14
125 VAC resistive load
300
Life (x 104)
Service
life of
relay
Note: Under the worst conditions, the service life of output contacts is as shown
on the left.
The service life of relays is as shown in the following diagram as a guideline.
Maximum
250 VAC: 2 A,
24 VDC: 2 A
Common terminal current (A)
Item
Max. switching capacity 2 A, 250 VAC (cosφ = 1), 2 A, 24 VDC 4 A/common)
4
3
0
47 55
Ambient temperature (˚C)
CP1L
● CPU Units with Transistor Outputs (Sinking/Sourcing)
Specifications
Item
CIO 100.00 to CIO 100.03
Max. switching capacity
4.5 to 30 VDC: 300 mA/point, 0.9 A/common, 3.6 A/Unit (See notes 3 and 4.)
Min. switching capacity
4.5 to 30 VDC, 1 mA
Leakage current
0.1 mA max.
Residual voltage
0.6 V max.
ON delay
0.1 ms max.
OFF delay
0.1 ms max.
Fuse
1/common (See note 2.)
CP1L-EL/EM
CPU Unit
Circuit
configuration
CIO 100.04 to CIO 101.07
CIO 102.00 to CIO 102.11
---
1.5 V max.
1 ms max.
Sinking Outputs
Sinking Outputs
Sourcing Outputs
Sourcing Outputs
Sinking Outputs
Sinking Outputs
OUT
OUT
Internal
circuits
OUT
L
OUT
L
Internal
circuits
Internal
circuits
4.5 to 30 VDC
L
4.5 to 30 VDC
COM (−)
CP1L-L/M
CPU Unit
L
COM (−)
Sourcing Outputs
Sourcing Outputs
COM (+)
COM (+)
Internal
circuits
Internal
circuits
OUT
OUT
Note: 1.
2.
3.
4.
Internal
circuits
4.5 to 30 VDC
4.5 to 30 VDC
L
OUT
L
OUT
Do not apply a voltage or connect a load to an output terminal exceeding the maximum switching capacity.
Fuses cannot be replaced by the user.
Also do not exceed 0.9 A for the total for CIO 100.00 to CIO 100.03. (CIO 100.00 to CIO 100.03 is different common.)
A maximum of 0.9 A per common can be switched at an ambient temperature of 50°C.
L
L
0.9
Common
terminal 0.6
current
(A)
0
50 55
Ambient temperature (˚C)
● Pulse outputs
● Pulse outputs
Output bits CIO 100.00 to CIO 100.03
Item
Output bits CIO100.01, CIO 100.03
Specifications
Item
Specifications
Max. switching capacity 30 mA at 4.75 to 26.4 VDC
Max. switching capacity 30 mA at 4.75 to 26.4 VDC
Min. switching capacity
7 mA at 4.75 to 26.4 VDC
Max. output frequency
CP1L: 32.8 kHz
Max. output frequency
100 kHz
PWM output precision
ON duty +5%, −0% at output frequency of 1 kHz
OFF
OFF 90%
Output waveform
ON
ON 10%
ton
Output waveform
T
4 ms min.
2 ms min.
Note: 1. The above values assume a resistive load and do not consider the impedance of the cable connecting the load.
2. The pulse widths during actual use may be smaller than the ones shown
above due to pulse distortion caused by connecting cable impedance.
3. The OFF and ON refer to the output transistor. The output transistor is ON
at level “L”.
ON duty =
ton
× 100%
T
Note: 1. The above values assume a resistive load and do not consider the impedance of the cable connecting the load.
2. The pulse widths during actual use may be smaller than the ones shown
above due to pulse distortion caused by connecting cable impedance.
3. The OFF and ON refer to the output transistor. The output transistor is ON
at level “L”.
15
CP1L
■ Analog Input Specifications
Item
Specifications
Number of analog inputs
1 *1
2 *2
Input signal range
0 to 10V
Max. rated input
0 to 15V
External input impedance
100KΩ min.
Resolution
1/256 *1
1/1000 (full scale) *2
Overall accuracy
0 to 55°C ±3% (full scale)
A/D conversion data
Full scale for 0000 to 1023 (03FF) Hex
Isolation method
-
*1. CP1L-EL CPU Unit or CP1L-EM CPU Unit only.
*2. CP1L-L CPU Unit or CP1L-M CPU Unit only.
■ Built-in Ethernet Specifications (CP1H-EL CPU Units or CP1H-EM CPU Unit Only)
Item
Specifications
Protocol used
TCP/IP, UDP, ARP, ICMP (ping only), BOOTP
Applications
FINS, Socket, SNTP, DNS (client)
Media access method
CSMA/CD
Modulation method
Baseband
Transmission paths
Star form
Baud rate
100 Mbit/s (100Base-TX), 10 Mbit/s (10Base-T)
100 Mbit/s
• Unshielded twisted-pair (UDP) cable
Categories: 5, 5e
• Shielded twisted-pair (STP) cable
Categories: 100 Ω at 5, 5e
10 Mbit/s
• Unshielded twisted-pair (UDP) cable
Categories: 3, 4, 5, 5e
• Shielded twisted-pair (STP) cable
Categories: 100 Ω at 3, 4, 5, 5e
Transmission media
Transmission Distance
100 m (distance between hub and node)
Item
FINS Communications Service Specifications
Number of nodes
254
Message length
1016 bytes max.
Size of buffer
8k
Communications Function
FINS/UDP method
FINS/TCP method
FINS Communications Service (UDP/IP, TCP/IP)
Protocol used
UDP/IP
Port number
9600 (default) Can be changed.
Protection
No
Protocol used
TCP/IP
Number of connections
Up to 2 simultaneous connections and only one connection can be set to client
Port number
9600 (default) Can be changed.
Protection
Yes (Specification of client IP addresses when unit is used as a server)
*1. CX-One version 4.3 or higher is required.
*2. To connect the CP1L CPUs with the NS-series Programmable Terminals via Ethernet, make sure that the system version of NS Series is 8.2 or higher.
16
CP1L
External Interfaces
■ CP1L CPU Unit Nomenclature
● CP1L CPU Units (EL Type) with 20 Points
Terminal Block (Fixed)
Option Board slot
Ethernet port
Terminal Block (Fixed)
● CP1L CPU Units (EM Type) with 40 or 30 Points
●
Option Board slots
1 (left) and 2 (right)
Front
Terminal Block (Removable)
Battery
DIP switch
Memory Cassette slot
External analog
settings
input connector
Ethernet port
Expansion I/O
Unit connector
Terminal Block (Removable)
● CP1L CPU Units (M Type) with 40 Points
●
Option Board Slot 1
Front
Option Board Slot 2
Terminal Block (Removable)
Battery
Peripheral
USB Port
IN
L1
L2/N
COM
01
00
03
02
05
04
07
06
09
08
11
10
01
00
03
05
02
04
00
01
COM
07
06
09
08
11
10
Analog Control
2 3
4
5
6
External analog
settings
input connector
A{
00
A|
01
COM
02
COM
03
COM
04
COM
06
05
07
03
02
04
COM
06
05
07
DIP switch
OUT
Memory
Cassette Slot
Terminal Block (Removable)
Expansion Unit and
Expansion I/O Unit
Connector
17
CP1L
● CP1L CPU Units (L Type) with 20 or 14 Points
● CP1L CPU Units (L Type) with 10 Points
Terminal Block (Fixed)
Terminal Block (Fixed)
IN
L1
Option Board Slot
L2/N
COM
01
00
Memory
Cassette Slot
03
02
05
04
07
06
09
08
11
10
SYSMAC
CP1L
Memory
Cassette Slot
PERIPHERAL
BATTERY
+
-
00
COM
01
COM
02
COM
04
03
05
COM
07
06
OUT
Battery
Battery
Terminal Block (Fixed)
18
Terminal Block (Fixed)
CP1L
Option Unit Specifications
■ Option Unit Specifications
Yes : Supported, No : Not supported
Item
Applicable CPU Units
Interface
CP1L-EM Type CP1L-EL Type
CP1L-M Type
CP1L-L14/L20
CP1L-L10
Yes
No
No
No
No
No
Yes
Yes
Yes
Serial Communications Option Boards
(CP1W-CIF01/CIF11/CIF12)
Yes
Yes
Yes
Yes
No
Ethernet Option Boards
(CP1W-CIF41)
No
No
Yes
Yes
No
Analog I/O Option Boards
(CP1W-MAB21/ADB21/DAB21V)
Yes
Yes
No
No
No
LCD Option Boards
(CP1W-DAM01)
Yes
Yes
Yes
Yes
No
Serial Communications Option Boards
(CP1W-CIF01/CIF11/CIF12)
Yes
No
Yes
No
No
Ethernet Option Boards
(CP1W-CIF41)
No
No
Yes
No
No
Analog I/O Option Boards
(CP1W-MAB21/ADB21/DAB21V)
Yes
No
No
No
No
Ethernet port
Connecting Support Software, Message
Communications, and the other.
Yes
Peripheral USB port
Bus for communications with various kinds of
Support Software running on a personal
computer.
Serial port 1 *
(Option board slot 1)
Serial port 2 *
(Option board slot 2)
* You can choose one from among "Yes".
■ Serial Communications Option Boards (CP1W-CIF01/CIF11/CIF12)
Product name
Model
Specifications
RS-232C Option Board
CP1W-CIF01
One RS-232C port
Connector: D-Sub, 9 pin, female
Maximum transmission distance: 15m
One RS-232C connector (D-Sub, 9 pin, male) is included.
(Plug: XM2A-0901, Hood: XM2S-0911-E)
RS-422A/485 Option Board
CP1W-CIF11
One RS-422A/485 port
Terminal block: using ferrules
Maximum transmission distance: 50m
RS-422A/485 Isolated-type Option Board
CP1W-CIF12
One RS-422A/485 port (Isolated)
Terminal block: using ferrules
Maximum transmission distance: 500m
Serial communications mode *
Host Link, 1:N NT Link,
1:1 NT Link, Noprotocol,
Serial PLC Link Slave,
Serial PLC Link Master,
Serial Gateway converted to
CompoWay/F, and Tool Bus,
1:1 Link Master, and
1:1 Link Slave.
* Serial PLC Link can be used with either serial port 1 or serial port 2.
19
CP1L
■ Ethernet Communications Specifications (CP1W-CIF41)
Item
Specifications
Applicable PLCs
CP1L CPU Units
Note: The Ethernet Option Board cannot be used for the CP1L-L10.
Number of Units that can be mounted
2 sets. (The CP1W-CIF41 Ver.1.0 and Ver.2.0 can be combined and used with one CPU Unit. When using
CP1W-CIF41 Ver.1.0, only one unit can be mounted in an option board slot.)
Protocol used
TCP/IP, UDP
Applications
FINS
Media access method
CSMA/CD
Modulation method
Baseband
Transmission paths
Star form
Baud rate
100 Mbit/s (100Base-TX), 10 Mbit/s (10Base-T)
Transfer
100 Mbit/s
• Unshielded twisted-pair (UDP) cable
Categories: 5, 5e
• Shielded twisted-pair (STP) cable
Categories: 100 Ω at 5, 5e
10 Mbit/s
• Unshielded twisted-pair (UDP) cable
Categories: 3, 4, 5, 5e
• Shielded twisted-pair (STP) cable
Categories: 100 Ω at 3, 4, 5, 5e
Transmission media
Transmission Distance
100 m (distance between hub and node)
Item
FINS Communications Service Specifications
Number of nodes
254
Message length
1016 bytes max.
Size of buffer
8k
Communications Function
FINS/UDP
method
FINS/TCP
method
FINS Communications Service (UDP/IP, TCP/IP)
Protocol used
UDP/IP
Port number
9600 (default) Can be changed.
Protection
No
Protocol used
TCP/IP
Number of connections
Up to 2 simultaneous connections and only one connection can be set to client
Port number
9600 (default) Can be changed.
Protection
Yes (Specification of client IP addresses when unit is used as a server)
Note: 1. CX-Programmer version 8.1 or higher (CX-One version 3.1 or higher) is required.
2. Use CX-Integrator version 2.33 or higher (CX-One version 3.1 or higher) when the system needs to be set the routing tables. However, CX-Integrator does
not support the other functions, using CP1W-CIF41, such as transferring the parameters and network structure.
3. To connect the CP1H/CP1L CPUs with the NS-series Programmable Terminals via Ethernet using CP1W-CIF41, make sure that the system version of NS
Series is 8.2 or higher.
Specifications
Input
Product name
20
Model
Output
Voltage Input
0V to 10V
Current Input
0mA to 20mA
Voltage Output
0V to 10V
Resolution:
1/4000
Resolution:
1/2000
Resolution:
1/4000
Conversion time
Current
consumption
2CH
-
2ms/point
DC 5V
40mA max.
CP1W-DAB21V
-
2CH
2ms/point
DC 5V
150mA max.
CP1W-MAB221
2CH
2CH
6ms/4point
DC 5V
150mA max.
Analog Input Option Board
CP1W-ADB21
Analog Output Option Board
Analog I/O Option Board
CP1L
■ LDC Option Board (CP1W-DAM01)
● Specifications
Item
Mounting port
Communications protocol
Weight
Number of display characters
Display characters
Backlight
Function
CP1L: Option board slot 1
Note: The LCD Option Board cannot be used for the CP1L-L10.
Peripheral bus (Turn ON DIP switch pin 4.)
30 g max.
4 rows × 12 characters: 48 characters max.
5 × 7 dots (alphanumeric, Japanese kana, and symbols). Display switchable between Japanese katakana and English.
Electroluminescence (EL): Normal: Lit green; Error: Flashing red
● LCD Functions
Operation
Changing operating modes
I/O memory
PLC Setup operations
Analog I/O monitor
Error log display
Memory cassette operation
User monitor settings
Description
Change the PLC operating mode without using the CX-Programmer.
Read and change the present values in the memory areas and force-set or force-reset bits.
Read and change the PLC Setup.
Monitor the analog adjustment and present value for the external analog setting input.
Read the log of errors that have occurred.
Transfer and verify user programs between the PLC and memory cassette.
Read the status of up to 16 words and bits with comments. You can use this setting to read data on the startup display.
Message display function
settings
Display a user-set message of up to 48 characters on the LCD Option Board when a specified bit turns ON.
A maximum of 16 screens can be registered for display.
Operation:
Day timer
Use this timer for ON/OFF switching at a
specified times every day from the starting
day of the week to the ending day of the
week. Sixteen timers cam be set from
timer 01 to timer 16.
Starting day of the week
Example: Monday
Ending day of the week
Example: Friday
ON
OFF
Ending time Starting time Ending time
Starting time
Example: 9:00 Example: 17:00
9:00
17:00
Starting time
9:00
Ending time
17:00
Operation:
Timers
Weekly timer
Use this timer for ON/OFF operation in
intervals of one week that starts one day
and ends another day. Sixteen timers cam
be set from timer No. 01 to timer No. 16.
Starting day of the week
Example: Monday
ON
OFF
Starting time
Example: 12:00
Calendar timer
Saving setting
Language
Other functions
Use the calendar timers for ON or OFF
operation in intervals of one year from the
starting day to the ending day. Sixteen
timers can be set from timer 01 to timer 16.
Ending day of the week
Example: Friday
Ending time
Starting time
Example: 8:00
12:00
Ending time
8:00
Operation:
ON
OFF
Starting day
July 1
Ending day
August 31
Set September 1
as the ending day.
Save the various settings that you set with the LCD Option Board to the DM Area of the PLC. You can also write the settings
saved in the PLC to the LCD Option Board.
Changing the display language (Japanese/English)
• Setting the time of the PLC's built-in clock
• Reading system data (e.g., unit version and lot number)
• Setting the backlight lighting time
• Adjusting LCD contrast
• Reading cycle time (e.g., average, maximum, and minimum)
• Clearing data for the LCD Option Board
21
CP1L
Expansion I/O Unit Specifications
■ CP1W-40EDR/40EDT/40EDT1/32ER/32ET/32ET1/20EDR1/20EDT/20EDT1/16ER/16ET/16ET1/8ED/8ER/8ET/8ET1 Expansion I/O Units
Expansion I/O Units can be connected to the CPU Unit to configure the required number of I/O points.
● DC Inputs (CP1W-40EDR/40EDT/40EDT1/20EDR1/20EDT/20EDT1/8ED)
Item
Input voltage
Input impedance
Input current
ON voltage
OFF voltage
ON delay
OFF delay
Specifications
24 VDC +10%/−15%
4.7 kΩ
5 mA typical
14.4 VDC min.
5.0 VDC max.
0 to 32 ms max. (Default: 8 ms) (See note 1.)
0 to 32 ms max. (Default: 8 ms) (See note 1.)
IN
IN
750 Ω
Circuit configuration
Input LED
4.7 kΩ
Internal
circuits
COM
Note: 1. Do not apply a voltage exceeding the rated voltage to an input terminal.
2. Can be set in the PLC Setup to 0, 0.5, 1, 2, 4, 8, 16 or 32 ms. The CP1W40EDR/EDT/EDT1 are fixed at 16 ms.
● Relay Outputs (CP1W-40EDR/32ER/20EDR1/16ER/8ER)
Specifications
2 A, 250 VAC (cosφ = 1), 24 VDC 4 A/common
5 VDC, 10 mA
Circuit configuration
500
150,000 operations (24 VDC)
100,000 operations (24 VAC cos = 0.4)
Internal
circuits
200
100
Output load current (%)
30
20
10
5
OUT
L
3
2
L
OUT
100
50
0
0.1
0.2 0.3
0.5 0.7 1
2
3
5
10
Contact current (A)
COM
22
Relationship between
Output Load Current and
Ambient Temperature
(CP1W-16ER/32ER)
120 VAC resistive load
24 VDC τ = 7 mA
120 VAC cos φ = 0.4
240 VAC cos φ = 0.4
24 VDC/240- VAC
resistive load
300
50
20,000,000 operations
15 ms max.
15 ms max.
Output LED
Note: Under the worst conditions, the service life of output contacts is as shown on
the left. The service life of relays is as shown in the following diagram as a
guideline.
Life (x104)
Item
Max. switching capacity
Min. switching capacity
Resistive
Service Elec- load
trical Inductive
life of
relay
load
Mechanical
ON delay
OFF delay
Maximum
250 VAC: 2 A,
24 VDC: 2 A
Switching frequency: 1,800 operations/h
55
43
Ambient temperature (˚C)
When using the CP1W-32ER, do not
allow more than 24 outputs to be ON
simultaneously regardless of the
ambient temperature.
CP1L
● Transistor Outputs (Sinking/Sourcing)
(CP1W-40EDT/-40EDT1/-32ET/-32ET1/-20EDT/-20EDT1/-16ET/-16ET1/-8ET/-8ET1)
Item
CP1W-40EDT
CP1W-32E
CP1W-40EDT1 CP1W-32ET1
24 VAC +10%/
−5%: 0.3 A/point
4.5 to 30 VDC:
0.3 A/point
0.9 A/common
3.6 A/common
0. 1mA max.
1.5 V max.
0.1ms max.
1 ms max. at 24 VDC
+10%/−5%, 5 to 300 mA
0.9 A/common
1.8 A/common
0.9 A/common
3.6 A/common
16 pts (100%)
8 pts (100%)
Max. switching ca- 4.5 to 30 VDC: 0.3 A/point
pacity (See note
3.)
Leakage current
Residual voltage
ON delay
OFF delay
Max. number of
Simultaneosly ON
Points of Output
Fuse (See note 2.)
Specifications
CP1W-20EDT
CP1W-16ET
CP1W-20EDT1
CP1W-16ET1
24 pts (75%)
16 pts (100%)
8 pts (100%)
Note: 1. Do not apply a voltage or connect a
load to an output terminal exceeding
the maximum switching capacity.
2. The fuses cannot be replaced by the
user.
3. A maximum of 0.9 A per common can
be switched at an ambient temperature of 50°C.
1/common
Sinking Outputs
Output LED
Output LED
OUT
L
Internal
circuits
0.9
0.8
Sourcing Outputs
L
Circuit configuration
CP1W-8ET
CP1W-8ET1
• OUT00/01
4.5 to 30 VDC,
0.2 A/output
• OUT02 to 07
4.5 to 30 VDC,
0.3 A/output
0.9 A/common
1.8 A/common
OUT
COM (−)
COM (+)
24 VDC/
4.5 to
30 VDC
Internal
circuits
OUT
L
L
OUT
Common
terminal
current
(A)
24 VDC/
4.5 to
30 VDC
0
50 55
Ambient temperature (°C)
23
CP1L
■ CP1W-AD041/DA041/DA021/MAD11 Analog Units
Analog values that are input are converted to binary data and stored in the input area, or binary data is output as analog values.
■ Analog Input Unit: CP1W-AD041
Model
■ Analog Output Unit: CP1W-DA041/DA021
CP1W-AD041
Item
Input voltage
Number of inputs
4
Input signal range
0 to 5 V, 1 to 5 V,
0 to 10 V, −10 to 10 V
0 to 20 mA
4 to 20 mA
Max. rated input
±15 V
±30 mA
External input
impedance
1 MΩ min.
Resolution
6000
25°C
±0.3% of full scale
Overall
accuracy 0 to 55°C ±0.6% of full scale
Conversion time
Model
Input current
CP1W-DA041/DA021
Item
Input voltage
Input current
Number of
outputs
DA041: 4, DA021: 2
Output signal range
0 to 5 V, 0 to 10 V,
or −10 to 10 V
0 to 20 mA or 4 to 20 mA
Approx. 250 Ω
Allowable external
output load
resistance
2 kΩ min.
350 Ω max.
±0.4% of full scale
External output impedance
0.5 Ω max.
---
Resolution
6000
±0.8% of full scale
2.0 ms/point
25°C
±0.4% of full scale
Overall
accuracy 0 to 55°C ±0.8% of full scale
Binary data with resolution of 6,000
A/D conversion data Full scale for −10 to 10 V: F448 to 0BB8 hex
Full scale for other ranges: 0000 to 1770 hex
Averaging
Supported.
Open-circuit
detection
Supported.
Insulation resistance
20 MΩ. min. (at 250 VDC, between isolated circuits)
Dielectric strength
500 VAC for 1 min (between isolated circuits)
Isolation method
Photocoupler isolation (between analog inputs and
secondary internal circuits).
No isolation between input signals.
Conversion time
2.0 ms/point
D/A conversion
data
Binary data with resolution of 6,000
Full scale for −10 to 10 V: F448 to 0BB8 hex
Full scale for other ranges: 0000 to 1770 hex
Insulation resistance
20 MΩ min. (at 250 VDC between isolated circuits)
Dielectric strength
500 VAC for 1 min between isolated circuits
Isolation method
Photocoupler isolation between analog inputs and
secondary internal circuits.
No isolation between analog input signals.
■ Analog I/O Unit: CP1W-MAD11
Model
CP1W-MAD11
Item
Analog
Input
Section
Analog
Output
Section
Voltage I/O
2 inputs
Input signal range
0 to 5 V, 1 to 5V, 0 to 10 V, or −10 to 10V
Max. rated input
±15 V
±30 mA
External input impedance
1 MΩ min.
250 Ω
Resolution
Overall
accuracy
0 to 20 mA, 4 to 20 mA
1/6000 (full scale)
25°C
±0.3% of full scale
±0.4% of full scale
0 to 55°C
±0.6% of full scale
±0.8% of full scale
A/D conversion data
Binary data (hexadecimal, 4 digits)
−10 to 10 V: F448 to 0BB8 hex
Full scale for other ranges: 0000 to 1770 hex
Averaging
Supported (Set for each input using a DIP switch.)
Disconnection detection
Supported
Number of outputs
1 output
Output signal range
1 to 5 V, 0 to 10 V, −10 to 10 V
External output max. current
---
Allowable external output
load resistance
1 kΩ min.
600 Ω max.
External input impedance
0.5 Ω max.
---
Resolution
1/6000 (full scale)
Overall
accuracy
25°C
±0.4% of full scale
0 to 55°C
±0.8% of full scale
Data setting
---
D/A conversion data
Binary data (hexadecimal, 4 digits)
−10 to 10 V: F448 to 0BB8 hex
Full scale for other ranges: 0000 to 1770 hex
0 to 20 mA, 4 to 20 mA
Conversion time*
2 ms/point (6 ms for all points)
Isolation method
Photocoupler isolation between analog I/O and internal circuits (There is no isolation between the analog I/O signals.)
* The conversion time is the total time for 2 analog inputs and 1 analog output.
24
Current I/O
Number o f inputs
CP1L
■ Temperature Sensor Units: CP1W-TS001/TS002/TS101/TS102
By mounting a Temperature Sensor Unit to the PLC, inputs can be obtained from thermocouples or platinum resistance thermometers, and temperature measurements can be converted to binary data (4-digit hexadecimal) and stored in the input area of the CPU Unit.
● Specifications
Item
Model
CP1W-TS001/002
CP1W-TS101/102
Number of inputs
2 (TS001), 4 (TS002)
2 (TS101), 4 (TS102)
Input types
K, J switchable (Note: Same for all inputs.)
Pt100, JPt100 switchable (Note: Same for all inputs.)
Indication accuracy
(The larger of the indicated value: ±0.5% and ±2°C (See note.)) ±1
(The larger of the indicated value: ±0.5% and ±1°C) ±1 digit max.
digit max.
Conversion time
250 ms/2 points (TS001, TS101); 250 ms/4 points (TS002, TS102)
Converted temperature data
Binary (4-digit hexadecimal)
Isolation method
Photocoupler isolation between the temperature input signals.
Note: The indication accuracy when using a K-type thermocouple for temperature less than −100°C is ±4°C±1 digit max.
● Input Temperature Ranges for CP1W-TS001/002
(The rotary switch can be used to make the following range and input type settings.)
Input type
K
J
Range (°C)
Range (°F)
−200 to 1300
−300 to 2300
0.0 to 500.0
0.0 to 900.0
−100 to 850
−100 to 1500
0.0 to 400.0
0.0 to 750.0
● Input Temperature Ranges for CP1W-TS101/102
(The rotary switch can be used to make the following range and input type settings.)
Input type
Range (°C)
Range (°F)
Pt100
−200.0 to 650.0
−300 to 1200.0
JPt100
−200.0 to 650.0
−300 to 1200.0
■ CP1W-SRT21 CompoBus/S I/O Link Unit
The CompoBus/S I/O Link Unit functions as a slave for a CompoBus/S Master Unit (or an SRM1 CompoBus/S Master Control Unit) to form an I/O
Link with 8 inputs and 8 outputs between the CompoBus/S I/O Link Unit and the Master Unit.
CompoBus/S Master Unit
(or SRM1 CompoBus/S
Master Control Unit)
CP1W-SRT21
CompoBus/S I/O Link Unit
CP1L
● Specifications
Item
Model
CP1W-SRT21
Master/Slave
CompoBus/S Slave
Number of I/O bits
8 input bits, 8 output bits
Number of words
occupied in CP1L
I/O memory
1 input word, 1 output word
(Allocated in the same way as for
other Expansion Units)
Node number
setting
Set using the DIP switch (before the
CPU Unit is turned ON.)
ON
1 2 3 4 5 6
No.
COMM
ERR
SRT21
EXP
BD H
NC(BS+)
BD L NC(BS-) NC
CS/CJ Series
C200H@ Series
CQM1(H) Series
SRM1 Series
CPM2C-S Series
Special flat cable or VCTF cable
A maximum of 16 Units can be connected
(or 8 Units for CQM1-SRM21-V1).
25
CP1L
I/O Bits and I/O Allocations
With CP1L CPU Units, the beginning input and output words (CIO 0 and CIO 100) are allocated by the CPU Unit one or two words at a time. I/O
bits are allocated in word units in order of connection to Expansion Units and Expansion I/O Units connected to a CPU Unit.
Allocated words
CPU Unit
Inputs
CP1L CPU Unit with 10, 14, or 20 I/O points
CIO 100
CIO 0 and CIO 1
CIO 100 and CIO 101
CIO 0, CIO 1, and CIO 2
CIO 100, CIO 101, and CIO102
CP1L CPU Unit with 30 or 40 I/O points
CP1L CPU Unit with 60 I/O points
Outputs
CIO 0
● Example: I/O Bit Allocations When Expansion Units Are Connected
CPU Unit with 40 I/O Points + Temperature Sensor Unit + Analog Output Unit + Expansion I/O Unit with 40 I/O Points
Inputs
Outputs
CPU Unit with 40 I/O Points
CP1L-M40D@-@
CIO 0.00 to CIO 0.11
CIO 1.00 to CIO 1.11
24 inputs
16 outputs
CIO 100.00 to CIO 100.07
CIO 101.00 to CIO 101.07
2nd Unit
1st Unit
Temperature Sensor Unit Analog Output Unit
CP1W-DA041
CP1W-TS002
CIO 2 to 5
None
None
CIO 102
to CIO 105
3rd Unit
Expansion I/O Unit with 40 I/O Points
CP1W-40ED
CIO 6.00 to CIO 6.11
CIO 7.00 to CIO 7.11
24 inputs
16 outputs
CIO 106.00 to CIO 106.07
CIO 107.00 to CIO 107.07
Expansion Unit and Expansion I/O Units Specifications
■ Maximum Number of CP1W/CPM1A Expansion Unit and Expansion I/O Units
● CP1L (EM, EL, M) CPU Units with 60, 40, or 30 Points
3 max.
● CP1L (L) CPU Units with 20 or 14 Points
1 max.
26
Note: CP1L (L Type) CPU Units with 10 points do not support Expansion Units.
CP1L
Current Consumption
The power consumption shown on page 6 is the maximum power consumption. To obtain the correct power consumption for the system configuration, calculate the power consumption for the external power supply from the current consumption given below for the CPU Unit, Expansion
Units, and Expansion I/O Units.
● CPU Units
Current consumption
Model
External power supply
5 VDC
24 VDC
24 VDC *
CP1L-EM40DR-D
@@@
@@@
---
CP1L-EM40DT-D
@@@
@@@
---
CP1L-EM40DT1-D
@@@
@@@
---
CP1L-EM30DR-D
@@@
@@@
---
CP1L-EM30DT-D
@@@
@@@
---
CP1L-EM30DT1-D
@@@
@@@
---
CP1L-EL20DR-D
@@@
@@@
---
CP1L-EL20DT-D
@@@
@@@
---
CP1L-EL20DT1-D
@@@
@@@
---
CP1L-M60DR-A
0.25 A
0.14 A
0.3 A max. (0.5 A max.)
CP1L-M60DT-A
0.39 A
0.03 A
0.3 A max. (0.6 A max.)
CP1L-M60DR-D
0.25 A
0.14 A
---
CP1L-M60DT-D
0.39 A
0.03 A
---
CP1L-M60DT1-D
0.39 A
0.03 A
---
CP1L-M40DR-A
0.22 A
0.08 A
0.3 A max. (0.6 A max.)
CP1L-M40DT-A
0.31 A
0.03 A
0.3 A max. (0.6 A max.)
CP1L-M40DR-D
0.22 A
0.08 A
---
CP1L-M40DT-D
0.31 A
0.03 A
---
CP1L-M40DT1-D
0.31 A
0.03 A
---
CP1L-M30DR-A
0.21 A
0.07 A
0.3 A max. (0.6 A max.)
CP1L-M30DT-A
0.28 A
0.03 A
0.3 A max. (0.6 A max.)
CP1L-M30DR-D
0.21 A
0.07 A
---
CP1L-M30DT-D
0.28A
0.03 A
---
CP1L-M30DT1-D
0.28 A
0.03 A
---
CP1L-L20DR-A
0.20 A
0.05 A
0.2 A max.
CP1L-L20DT-A
0.24 A
0.03 A
0.2 A max.
CP1L-L20DR-D
0.20A
0.05 A
---
CP1L-L20DT-D
0.24 A
0.03 A
---
CP1L-L20DT1-D
0.24 A
0.03 A
---
CP1L-L14DR-A
0.18 A
0.04 A
0.2 A max.
CP1L-L14DT-A
0.21 A
0.03 A
0.2 A max.
CP1L-L14DR-D
0.18 A
0.04 A
---
CP1L-L14DT-D
0.21 A
0.03 A
---
CP1L-L14DT1-D
0.21 A
0.03A
---
CP1L-L10DR-A
0.16 A
0.03 A
0.2 A max.
CP1L-L10DT-A
0.18 A
0.03 A
0.2 A max.
CP1L-L10DR-D
0.16 A
0.03A
---
CP1L-L10DT-D
0.18 A
0.03 A
---
CP1L-L10DT1-D
0.18 A
0.03 A
---
Note: 1. The current consumption of the CP1W-ME05M Memory Cassette and the CP1W-CIF01/CIF11 Option Boards are included in the current consumption of the
CPU Unit.
2. The current consumption of the following is not included with the current consumption of the CPU Unit: CP1W-CIF12.
Unit
Interface Unit
Model
CP1W-CIF12
Curent consumption
5 VDC
24 VDC
0.075A
---
EXternal power supply
---
3. CPU Units with DC power do not provide an external power supply.
4. The current consumptions given in the following table must be added to the current consumption of the CPU Unit if an Expansion Unit or Expansion I/O Unit
is connected.
5. The external power supply cannot be used if an Expansion Unit or Expansion I/O Unit is connected to a CPU Unit with 14 or 20 I/O points.
* Values in parentheses are the maximum external power supply for a CPU Unit to which an Expansion I/O Unit is not connected. Refer to the CP1L CPU Unit Operation
Manual (Cat. No. W462).
27
CP1L
● Expansion Units and Expansion I/O Units
Unit name
Model
40 I/O points
24 inputs
16 outputs
CP1W-40EDR
CP1W-40EDT1
Expansion I/O Units
CP1W-20EDR1
CP1W-20EDT1
8 outputs
Analog Output Unit
Analog I/O Unit
Temperature Sensor Units
CompoBus/S I/O Link Unit
---
0.049 A
0.131 A
0.113 A
---
0.103 A
0.044 A
0.130 A
---
0.042 A
0.090 A
0.076 A
---
CP1W-8ED
0.018 A
---
CP1W-8ER
0.026 A
0.044 A
0.075 A
---
CP1W-8ET
CP1W-8ET1
Analog Input Unit
0.160 A
CP1W-16ET
CP1W-16ET1
8 inputs
0.090 A
CP1W-20EDT
CP1W-16ER
16 outputs
0.080 A
CP1W-32ET
CP1W-32ET1
20 I/O points
12 inputs
8 outputs
24 VDC
CP1W-40EDT
CP1W-32ER
32 outputs*
Current consumption
5 VDC
4 inputs
CP1W-AD041
0.100 A
0.090 A
4 outputs
CP1W-DA041
0.080 A
0.124 A
2 outputs
CP1W-DA021
0.095 A
0.040 A
2 inputs and 1 output
CP1W-MAD11
0.083 A
0.110 A
K or J thermocouple
inputs
CP1W-TS001
0.040 A
0.059 A
Pt or JPt platinum
resistance
thermometer inputs
CP1W-TS101
0.054 A
0.073 A
8 inputs and 8 outputs
CP1W-SRT21
0.029 A
---
CP1W-TS002
CP1W-TS102
* CP1W-32ER/32ET/32ET1’s maximum number of simultaneously ON points is 24 (75%).
● Others : Equipment that Users internal power supply of PLC
Unit name
Model
24 VDC
CJ1W-CIF11
0.04A
---
NT-AL001
0.15A
---
Backlight
(Green/Orange/red)
NV3W-MG20L
0.2A
---
Backlight
(White/Pink/Red)
NV3W-MR20L
0.2A
---
Link Adapter
Programable Terminal NV3W
28
Current consumption
5 VDC
CP1L
Dimensions
(Unit: mm)
■ CPU Units
CP1L-EM CPU Units with 40 Points
150
85
140
8
Weight:
675 g max.
110 100 90
Four, 4.5 dia.
CP1L-EM CPU Units with 30 Points
130
85
120
8
Weight:
610 g max.
110 100 90
Four, 4.5 dia.
CP1L-EL CPU Units with 20 Points
130
85
120
8
Weight:
610 g max.
110 100 90
Four, 4.5 dia.
29
CP1L
CP1L CPU Units with 60 I/O Points
195
85
185
8
Weight:
820 g max.
110 100 90
Four, 4.5 dia.
CP1L CPU Units with 40 I/O Points
150
85
140
8
Weight:
675 g max.
110 100 90
Four, 4.5 dia.
CP1L CPU Units with 30 I/O Points
130
85
120
8
Weight:
610 g max.
110 100 90
Four, 4.5 dia.
30
CP1L
CP1L CPU Units with 14 or 20 I/O Points
86
85
76
8
Weight:
380 g max.
110 100 90
Two, 4.5 dia.
CP1L CPU Units with 10 I/O Points
66
85
56
8
Weight:
300 g max.
110 100 90
Two, 4.5 dia.
31
CP1L
■ Expansion Units and Expansion I/O Units
CP1W-8E@@
CP1W-SRT21
CP1W-20ED@
CP1W-16E@@
CP1W-AD041/CP1W-DA041/CP1W-DA021
CP1W-MAD11/CP1W-TS@@@
COM
01
03
05
07
09
11
00
02
04
06
08
10
NC
COM
01
00
CH
IN
03
02
IN
CH 00 01 02 03 04 05 06 07
CH 00 01 02 03
08 09 10 11
08 09 10 11
90
20EDR1
90
8ED
OUT
CH
NC
00 01 02 03 04 05 06 07
CH
00
01
02
04
05
07
NC
COM
COM
COM
03
COM
06
EXP
EXP
04
COM
86
06
05
66
50
Unit name
CP1W-40ED@
CP1W-32E@@
Model number
NC
COM
NC
NC
01
00
03
02
05
04
07
06
CH
09
08
11
10
01
00
03
02
05
04
07
06
09
08
380 g
320 g
CP1W-32ER
465 g
CP1W-32ET/-32ET1
325 g
CP1W-20EDR1/-20EDT/-20EDT1
300 g
CP1W-16ER
280 g
CP1W-16ET/-16ET1
225 g
CP1W-8ED
200 g
CP1W-8ER/-8ET/-8ET1
250 g
CP1W-AD041/-DA041/-DA021
200 g
CP1W-MAD11
150 g
Temperature
Sensor Units
CP1W-TS001/-TS002/-TS101/
-TS102
250 g
CompoBus/S
I/O Link Unit
CP1W-SRT21
200 g
11
10
CH
CH
IN
00
01
02
03
04
07
08
09
10
11
00
01
02
03
04
05
06
07
08
09
10
11
00
01
02
03
04
05
05
06
06
07
CH
CH
110 100 90
CH
00
01
02
03
04
05
06
40EDR
07
CH
CH
NC
00
01
02
04
05
07
00
02
04
05
07
NC
COM COM COM
03
COM
06
COM
01
03
COM
06
Analog Units
EXP
Four,
4.5 dia.
8
50
■ CJ-series Special I/O Units and CPU Bus Units
■ CJ Unit Adaptor
CP1W-EXT01
2.7
2.7
16.4
5.7
90
65.5
65
7.6
90
95.4 90
2.7
31
65
2.7
31
89
65.5
32
Weight
CP1W-40EDT/-40EDT1
Expansion I/O
Units
NC
50
CP1W-40ER
150
140
OUT
07
CP1L
Related Manuals
Cat. No.
Model numbers
Manual name
Description
CP1L-L10D@-@
CP1L-L14D@-@
CP1L-L20D@-@
CP1L-M30D@-@
CP1L-M40D@-@
CP1L-M60D@-@
CP Series
CP1L CPU Unit
Operation Manual
Provides the following information on the CP Series:
• Overview, design, installation, maintenance, and
other basic specifications
• Features
• System configuration
• Mounting and wiring
• I/O memory allocation
• Troubleshooting
Use this manual together with the CP1H Programmable
Controllers Programming Manual (W451).
CP Series
CP1H/CP1L CPU Unit Programming
Manual
W451
CP1H-X40D@-@
CP1H-XA40D@-@
CP1H-Y20DT-D
CP1L-L10D@-@
CP1L-L14D@-@
CP1L-L20D@-@
CP1L-M30D@-@
CP1L-M40D@-@
CP1L-M60D@-@
Provides the following information on programming the
CP Series:
• Programming methods
• Tasks
• Programming instructions
CP Series
CP1L CPU Unit Introduction Manual
W461
CP1L-L10D@-@
CP1L-L14D@-@
CP1L-L20D@-@
CP1L-M30D@-@
CP1L-M40D@-@
CP1L-M60D@-@
Describes basic setup methods of CP1L PLCs:
• Basic configuration and component names
• Mounting and wiring
• Programming, data transfer, and debugging using
the CX-Programmer
• Application program examples
CS1G/CS1H/CS1D/CS1W/CJ2H/CJ2M/
CJ1G/CJ1H/CJ1M/CJ1W/CP1H/CP1L/
CP1E/NSJ SYSMAC CS/CJ/CP/NSJ Series
Communications Commands REFERENCE
MANUAL
Describes the communications commands used with
CS-series, CJ-series, and CP-series PLCs and NSJ
Controllers.
W342
SYSMAC CS/CJ/CP/NSJ Series
CS1G/H-CPU@@-EV1, CS1G/H-CPU@@H,
CS1D-CPU@@H, CS1D-CPU@@S,
CJ1H-CPU@@H-R,CJ1G-CPU@@,
CJ1M-CPU@@, CJ1G-CPU@@P,
CJ1G/H-CPU@@H, CJ2H-CPU6@-EIP,
CJ2H-CPU6@,CJ2M-CPU@@,
CS1W-SCU@@-V1, CS1W-SCB@@-V1,
CJ1W-SCU@@-V1, CP1H-X@@@@-@,
CP1H-XA@@@@-@,CP1H-Y@@@@-@,
CP1L-M/L@@@-@, CP1E-E@@D@-@,
CP1E-N@@D@-@, NSJ@-@@@@(B)-G5D,
NSJ@-@@@@(B)-M3D Communications
Commands Reference Manual
W462
33
MEMO
34
Read and Understand This Catalog
Please read and understand this catalog before purchasing the products. Please consult your OMRON representative if you have any questions or
comments.
Warranty and Limitations of Liability
WARRANTY
OMRON's exclusive warranty is that the products are free from defects in materials and workmanship for a period of one year (or other period if specified)
from date of sale by OMRON.
OMRON MAKES NO WARRANTY OR REPRESENTATION, EXPRESS OR IMPLIED, REGARDING NON-INFRINGEMENT, MERCHANTABILITY, OR
FITNESS FOR PARTICULAR PURPOSE OF THE PRODUCTS. ANY BUYER OR USER ACKNOWLEDGES THAT THE BUYER OR USER ALONE HAS
DETERMINED THAT THE PRODUCTS WILL SUITABLY MEET THE REQUIREMENTS OF THEIR INTENDED USE. OMRON DISCLAIMS ALL OTHER
WARRANTIES, EXPRESS OR IMPLIED.
LIMITATIONS OF LIABILITY
OMRON SHALL NOT BE RESPONSIBLE FOR SPECIAL, INDIRECT, OR CONSEQUENTIAL DAMAGES, LOSS OF PROFITS OR COMMERCIAL
LOSS IN ANY WAY CONNECTED WITH THE PRODUCTS, WHETHER SUCH CLAIM IS BASED ON CONTRACT, WARRANTY, NEGLIGENCE, OR
STRICT LIABILITY.
In no event shall the responsibility of OMRON for any act exceed the individual price of the product on which liability is asserted.
IN NO EVENT SHALL OMRON BE RESPONSIBLE FOR WARRANTY, REPAIR, OR OTHER CLAIMS REGARDING THE PRODUCTS UNLESS
OMRON'S ANALYSIS CONFIRMS THAT THE PRODUCTS WERE PROPERLY HANDLED, STORED, INSTALLED, AND MAINTAINED AND NOT
SUBJECT TO CONTAMINATION, ABUSE, MISUSE, OR INAPPROPRIATE MODIFICATION OR REPAIR.
Application Considerations
SUITABILITY FOR USE
OMRON shall not be responsible for conformity with any standards, codes, or regulations that apply to the combination of products in the customer's
application or use of the products.
At the customer's request, OMRON will provide applicable third party certification documents identifying ratings and limitations of use that apply to the
products. This information by itself is not sufficient for a complete determination of the suitability of the products in combination with the end product,
machine, system, or other application or use.
The following are some examples of applications for which particular attention must be given. This is not intended to be an exhaustive list of all possible
uses of the products, nor is it intended to imply that the uses listed may be suitable for the products:
• Outdoor use, uses involving potential chemical contamination or electrical interference, or conditions or uses not described in this catalog.
• Nuclear energy control systems, combustion systems, railroad systems, aviation systems, medical equipment, amusement machines,
vehicles, safety equipment, and installations subject to separate industry or government regulations.
• Systems, machines, and equipment that could present a risk to life or property.
Please know and observe all prohibitions of use applicable to the products.
NEVER USE THE PRODUCTS FOR AN APPLICATION INVOLVING SERIOUS RISK TO LIFE OR PROPERTY WITHOUT ENSURING THAT THE
SYSTEM AS A WHOLE HAS BEEN DESIGNED TO ADDRESS THE RISKS, AND THAT THE OMRON PRODUCTS ARE PROPERLY RATED AND
INSTALLED FOR THE INTENDED USE WITHIN THE OVERALL EQUIPMENT OR SYSTEM.
PROGRAMMABLE PRODUCTS
OMRON shall not be responsible for the user's programming of a programmable product, or any consequence thereof.
Disclaimers
CHANGE IN SPECIFICATIONS
Product specifications and accessories may be changed at any time based on improvements and other reasons.
It is our practice to change model numbers when published ratings or features are changed, or when significant construction changes are made.
However, some specifications of the products may be changed without any notice. When in doubt, special model numbers may be assigned to fix or
establish key specifications for your application on your request. Please consult with your OMRON representative at any time to confirm actual
specifications of purchased products.
DIMENSIONS AND WEIGHTS
Dimensions and weights are nominal and are not to be used for manufacturing purposes, even when tolerances are shown.
PERFORMANCE DATA
Performance data given in this catalog is provided as a guide for the user in determining suitability and does not constitute a warranty. It may represent
the result of OMRON's test conditions, and the users must correlate it to actual application requirements. Actual performance is subject to the OMRON
Warranty and Limitations of Liability.
ERRORS AND OMISSIONS
The information in this document has been carefully checked and is believed to be accurate; however, no responsibility is assumed for clerical,
typographical, or proofreading errors, or omissions.
Note: Do not use this document to operate the Unit.
OMRON Corporation
Industrial Automation Company
Authorized Distributor:
Tokyo, JAPAN
Contact: www.ia.omron.com
Regional Headquarters
OMRON EUROPE B.V.
Wegalaan 67-69-2132 JD Hoofddorp
The Netherlands
Tel: (31)2356-81-300/Fax: (31)2356-81-388
OMRON ELECTRONICS LLC
One Commerce Drive Schaumburg,
IL 60173-5302 U.S.A.
Tel: (1) 847-843-7900/Fax: (1) 847-843-7787
OMRON ASIA PACIFIC PTE. LTD.
No. 438A Alexandra Road # 05-05/08 (Lobby 2),
Alexandra Technopark,
Singapore 119967
Tel: (65) 6835-3011/Fax: (65) 6835-2711
OMRON (CHINA) CO., LTD.
Room 2211, Bank of China Tower,
200 Yin Cheng Zhong Road,
PuDong New Area, Shanghai, 200120, China
Tel: (86) 21-5037-2222/Fax: (86) 21-5037-2200
© OMRON Corporation 2012 All Rights Reserved.
In the interest of product improvement,
specifications are subject to change without notice.
Printed in Japan
Cat. No. P81-E1-01
@@@@ (0507)