Solid State Contactors (Three-phase)
G3PB-2/-3
CSM_G3PB-2_-3_DS_E_2_1
Compact, Low-cost Solid State Contactors
of an Innovative Construction Ideal for
Three-phase Heaters
• Slim Units with three-phase output.
• Optimum heat sinks attach to models without built-in heat sinks.
• Compact design achieved by optimizing heat sink shape.
• DIN track mounting possible (when using the Y92B-P50 Heat
Sink) in addition to screw mounting.
• Comply with EN60947-4-3 (IEC947-4-3) UL508, and
CSA22.2 No. 14, and bear CE marking.
Refer to Safety Precautions for All Solid State
Relays.
Model Number Structure
■ Model Number Legend
G3PB-@@@-@@-@
1
2 3 4
5 6
7
1. Basic Model Name
G3PB:
Solid State Relay
2. Rated Load Power Supply Voltage
2:
200 VAC
4:
400 VAC
3. Rated Load Current
15:
15 A
25:
25 A
35:
35 A
45:
45 A
4. Terminal Type
B:
Screw terminals
5. Single-phase/3-phase and Number of Elements for 3-phase
2:
3-phase, 2-element models
3:
3-phase, 3-element models
6. 3-phase Type
Blank:
Built-in heat sink
H:
No heat sink (“hockey puck” type)
7. Certification
VD:
Certified by UL, CSA, and VDE
1
G3PB-2/-3
Ordering Information
■ List of Models
Models with Built-in Heat Sinks
Number of
phases
3
Main circuit voltage
100 to 240 VAC
Zero cross
function
Yes
Applicable load current
(with Class-1 AC resistive load)
Number of
elements
15 A max.
25 A max.
35 A max.
45 A max.
200 to 400 VAC
15 A max.
25 A max.
35 A max.
45 A max.
Model
3
G3PB-215B-3-VD
2
G3PB-215B-2-VD
3
G3PB-225B-3-VD
2
G3PB-225B-2-VD
3
G3PB-235B-3-VD
2
G3PB-235B-2-VD
3
G3PB-245B-3-VD
2
G3PB-245B-2-VD
3
G3PB-415B-3-VD
2
G3PB-415B-2-VD
3
G3PB-425B-3-VD
2
G3PB-425B-2-VD
3
G3PB-435B-3-VD
2
G3PB-435B-2-VD
3
G3PB-445B-3-VD
2
G3PB-445B-2-VD
Note: 1. The applicable load current depends on the ambient temperature. For details, refer to Load Current vs. Ambient Temperature in,
Engineering Data on page 7.
2. When ordering, specify the rated input voltage.
Models without Built-in Heat Sinks
Number of
phases
3
Main circuit voltage
Zero cross
function
100 to 240 VAC
Yes
Applicable load current
15 A max.
25 A max.
200 to 400 VAC
Number of
elements
Model
3
G3PB-215B-3H-VD
2
G3PB-215B-2H-VD
3
G3PB-225B-3H-VD
2
G3PB-225B-2H-VD
35 A max.
3
G3PB-235B-3H-VD
2
G3PB-235B-2H-VD
45 A max.
3
G3PB-245B-3H-VD
2
G3PB-245B-2H-VD
15 A max.
25 A max.
3
G3PB-415B-3H-VD
2
G3PB-415B-2H-VD
3
G3PB-425B-3H-VD
2
G3PB-425B-2H-VD
35 A max.
3
G3PB-435B-3H-VD
2
G3PB-435B-2H-VD
45 A max.
3
G3PB-445B-3H-VD
2
G3PB-445B-2H-VD
Note: 1. The applicable load current depends on the heat sink that is connected and the ambient temperature. For details, refer to Load Current
vs. Ambient Temperature in, Engineering Data on page 7.
2. When ordering, specify the rated input voltage.
■ Accessories (Order Separately)
Heat Sinks
Heat resistance (°C/W)
Model
50 cm (1) x 7.3 mm (t)
PFP-50N
1.67
Y92B-P50
Mounting Track
1 m (1) x 7.3 mm (t)
PFP-100N
1.01
Y92B-P100
1 m (1) x 16 mm (t)
PFP-100N2
0.63
Y92B-P150
0.43
Y92B-P200
0.36
Y92B-P250
2
G3PB-2/-3
Specifications
■ Ratings (at an Ambient Temperature of 25°C)
Operating Circuit (Common)
Item
Common
Rated voltage
12 to 24 VDC
Operating voltage range
9.6 to 30 VDC
Rated input current
10 mA max. (at 24 VDC)
Must operate voltage
9.6 VDC max.
Must release voltage
1 VDC min.
Insulation method
Phototriac
Operation indicator
Yellow LED
Main Circuit of Models with Built-in Heat Sinks
Item
G3PB215B-3-VD
G3PB215B-2-VD
G3PB225B-3-VD
G3PB225B-2-VD
G3PB235B-3-VD
G3PB235B-2-VD
Rated load voltage
100 to 240 VAC
Load voltage range
75 to 264 VAC
Applicable load current
(See note.)
0.2 to 15 A at 40°C
0.2 to 25 A at 40°C
0.5 to 35 A at 25°C
Inrush current resistance
(peak value)
150 A
(60 Hz, 1 cycle)
220 A
(60 Hz, 1 cycle)
440 A
(60 Hz, 1 cycle)
Permissible I2t
(half 60-Hz wave)
121 A2s
260 A2s
1260 A2s
Applicable load
(with Class-1 AC resistive
load)
5.1 kW max.
(at 200 VAC)
8.6 kW
(at 200 VAC)
12.1 kW max.
(at 200 VAC)
Item
G3PB415B-3-VD
G3PB415B-2-VD
G3PB425B-3-VD
G3PB425B-2-VD
G3PB435B-3-VD
Rated load voltage
200 to 400 VAC
Load voltage range
180 to 440 VAC
Applicable load current
(See note.)
0.5 to 15 A at 40°C
Inrush current resistance
(peak value)
220 A
(60 Hz, 1 cycle)
Permissible I2t
(half 60-Hz wave)
260 A2s
260 A2s
1260 A2s
Applicable load
(with Class-1 AC resistive
load)
10.3 kW max.
(at 400 VAC)
17.3 kW max.
(at 400 VAC)
24.2 kW max.
(at 400 VAC)
0.5 to 25 A at 40°C
G3PB245B-3-VD
G3PB245B-2-VD
0.5 to 45 A at 25°C
15.5 kW max.
(at 200 VAC)
G3PB435B-2-VD
0.5 to 35 A at 25°C
G3PB445B-3-VD
G3PB445B-2-VD
0.5 to 45 A at 25°C
440 A
(60 Hz, 1 cycle)
31.1 kW max.
(at 400 VAC)
Note: The applicable load current depends on the ambient temperature. For details, refer to Load Current vs. Ambient Temperature in, Engineering
Data on page 7.
3
G3PB-2/-3
Main Circuit of Models without Built-in Heat Sinks
Item
G3PB-215B- G3PB-215B- G3PB-225B- G3PB-225B- G3PB-235B- G3PB-235B- G3PB-245B- G3PB-245B3H-VD
2H-VD
3H-VD
2H-VD
3H-VD
2H-VD
3H-VD
2H-VD
Rated load voltage
100 to 240 VAC
Load voltage range
75 to 264 VAC
Applicable load current
(See note.)
0.2 to 15 A at 40°C
0.2 to 25 A at 40°C
0.2 to 35 A at 25°C
Inrush current resistance
(peak value)
150 A
(60 Hz, 1 cycle)
220 A
(60 Hz, 1 cycle)
440 A
(60 Hz, 1 cycle)
Permissible I2t
(half 60-Hz wave)
121 A2s
260 A2s
1260 A2s
Applicable load
(with Class-1 AC resistive
load)
The applicable load varies with the heat radiation of the Unit. Refer to page 7, Engineering Data for details.
Item
0.2 to 45 A at 25°C
G3PB-415B- G3PB-415B- G3PB-425B- G3PB-425B- G3PB-435B- G3PB-435B- G3PB-445B- G3PB-445B3H-VD
2H-VD
3H-VD
2H-VD
3H-VD
2H-VD
3H-VD
2H-VD
Rated load voltage
200 to 400 VAC
Load voltage range
180 to 440 VAC
Applicable load current
(See note.)
0.5 to 15 A at 40°C
Inrush current resistance
(peak value)
220 A
(60 Hz, 1 cycle)
Permissible I2t
(half 60-Hz wave)
260 A2s
Applicable load
(with Class-1 AC resistive
load)
Refer to page 7, Engineering Data for details.
0.5 to 25 A at 40°C
0.5 to 35 A at 25°C
0.5 to 45 A at 25°C
440 A
(60 Hz, 1 cycle)
260 A2s
1260 A2s
Note: The applicable load current depends on the heat sink that is connected and the ambient temperature. For details, refer to Load Current vs.
Ambient Temperature in, Engineering Data on page 7.
4
G3PB-2/-3
■ Characteristics
Models with Built-in Heat Sinks
Item
G3PB215B-3-VD
G3PB215B-2-VD
G3PB225B-3-VD
G3PB225B-2-VD
G3PB235B-3-VD
G3PB235B-2-VD
Operate time
1/2 of load power source cycle + 1 ms max. (DC input)
Release time
1/2 of load power source cycle + 1 ms max. (DC input)
Output ON voltage drop
1.6 V (RMS) max.
Leakage current
(See note.)
10 mA (at 200 VAC)
Insulation resistance
100 MΩ min. (at 500 VDC)
Dielectric strength
2,500 VAC, 50/60 Hz for 1 min
Vibration resistance
Destruction: 10 to 55 to 10 Hz, 0.375–mm single amplitude (Mounted to DIN track)
Shock resistance
Destruction: 294 m/s2
Ambient temperature
Operating:
Storage:
Ambient humidity
Operating: 45% to 85%
Weight
Approx.
750 g
Certified standards
UL508, CSA22.2 No. 14, EN60947-4-3 (IEC947-4-3)
(From April 1999)
EMC
Emission: EN55011 Group 1 Class B
Immunity: EN61000-6-2
G3PB415B-3-VD
G3PB245B-2-VD
Approx.
1,500 g
Approx.
1,150 g
–30°C to 80°C (with no icing or condensation)
–30°C to 100°C (with no icing or condensation)
Approx.
750 g
Approx.
900 g
Note: The leakage current of phase S will be approximately
Item
G3PB245B-3-VD
G3PB415B-2-VD
Approx.
750 g
Approx.
1,150 g
Approx.
900 g
3 times larger if the 2-element model is applied.
G3PB425B-3-VD
G3PB425B-2-VD
G3PB435B-3-VD
G3PB435B-2-VD
Operate time
1/2 of load power source cycle + 1 ms max. (DC input)
Release time
1/2 of load power source cycle + 1 ms max. (DC input)
Output ON voltage drop
1.8 V (RMS) max.
Leakage current
(See note.)
20 mA (at 400 VAC)
Insulation resistance
100 MΩ min. (at 500 VDC)
Dielectric strength
2,500 VAC, 50/60 Hz for 1 min
Vibration resistance
Destruction: 10 to 55 to 10 Hz, 0.375–mm single amplitude (Mounted to DIN track)
Shock resistance
Destruction: 294 m/s2
Ambient temperature
Operating:
Storage:
Ambient humidity
Operating: 45% to 85%
Weight
Approx.
750 g
Certified standards
UL508, CSA22.2 No. 14, EN60947-4-3 (IEC947-4-3)
EMC
Emission: EN55011 Group 1 Class B
Immunity: EN61000-6-2
G3PB445B-3-VD
G3PB445B-2-VD
–30°C to 80°C (with no icing or condensation)
–30°C to 100°C (with no icing or condensation)
Approx.
750 g
Approx.
900 g
Note: The leakage current of phase S will be approximately
Approx.
750 g
Approx.
1,150 g
Approx.
900 g
Approx.
1,500 g
Approx.
1,150 g
3 times larger if the 2-element model is applied.
5
G3PB-2/-3
Models without Built-in Heat Sinks
Item
G3PB215B3H-VD
G3PB215B2H-VD
G3PB225B3H-VD
G3PB225B2H-VD
Operate time
1/2 of load power source cycle + 1 ms max. (DC input)
Release time
1/2 of load power source cycle + 1 ms max. (DC input)
Output ON voltage drop
1.6 V (RMS) max.
Leakage current
(See note.)
10 mA (at 200 VAC)
Insulation resistance
100 MΩ min. (at 500 VDC)
Dielectric strength
2,500 VAC, 50/60 Hz for 1 min
Vibration resistance
Destruction: 10 to 55 to 10 Hz, 0.375–mm single amplitude
Shock resistance
Destruction: 294 m/s2
Ambient temperature
Operating:
Storage:
Ambient humidity
Operating: 45% to 85%
Certified standards
UL508, CSA22.2 No. 14, EN60947-4-3 (IEC947-4-3)
Weight (Max.)
300 g max.
EMC
Emission: EN55011 Group 1 Class B
Immunity: EN61000-6-2
G3PB235B2H-VD
G3PB245B3H-VD
G3PB245B2H-VD
G3PB445B3H-VD
G3PB445B2H-VD
–30°C to 80°C (with no icing or condensation)
–30°C to 100°C (with no icing or condensation)
Note: The leakage current of phase S will be approximately
Item
G3PB235B3H-VD
G3PB415B3H-VD
G3PB415B2H-VD
3 times larger if the 2-element model is applied.
G3PB425B3H-VD
G3PB425B2H-VD
Operate time
1/2 of load power source cycle + 1 ms max. (DC input)
Release time
1/2 of load power source cycle + 1 ms max. (DC input)
Output ON voltage drop
1.8 V (RMS) max.
Leakage current
(See note.)
20 mA (at 400 VAC)
Insulation resistance
100 MΩ min. (at 500 VDC)
Dielectric strength
2,500 VAC, 50/60 Hz for 1 min
Vibration resistance
Destruction: 10 to 55 to 10 Hz, 0.375-mm single amplitude
Shock resistance
Destruction: 294 m/s2
Ambient temperature
Operating:
Storage:
Ambient humidity
Operating: 45% to 85%
Certified standards
UL508, CSA22.2 No. 14, EN60947-4-3 (IEC947-4-3)
Weight
Approx. 300 g
EMC
Emission: EN55011 Group 1 Class B
Immunity: EN61000-6-2
G3PB435B3H-VD
G3PB435B2H-VD
–30°C to 80°C (with no icing or condensation)
–30°C to 100°C (with no icing or condensation)
Note: The leakage current of phase S will be approximately
3 times larger if the 2-element model is applied.
Heat Sinks
Model
Weight
Y92B-P50
Approx. 450 g
Y92B-P100
Approx. 450 g
Y92B-P150
Approx. 600 g
Y92B-P200
Approx. 850 g
Y92B-P250
Approx. 1,200 g
6
G3PB-2/-3
Engineering Data
Load Current vs. Ambient Temperature
Models with Built-in Heat Sinks
G3PB-225B-3-VD
G3PB-225B-2-VD
Load current (A)
30
25
20
G3PB-235B-3-VD
G3PB-235B-2-VD
30
Derating curve under UL standard
25
22
20
Load current (A)
Load current (A)
G3PB-215B-3-VD
G3PB-215B-2-VD
50
Derating curve under UL standard
40
35
30
28
15
Derating curve under
UL standard
20
10
8
10
7
6
10
8
0
−30 −20
14
20
0
0
-30 -20
40
60
80 100
Ambient temperature (°C)
0
20 25
40
60
80
0
−30 −20
100
0
20 25
Ambient temperature (°C)
40
60
80
100
Ambient temperature (°C)
Note: 1. Please use proper ventilation and cooling.
2. Please note that the derating curve above 28 A is
applicable under the UL standard only with forced
air cooling by fan.
Derating curve under UL standard
45
42
40
G3PB-425B-3-VD
G3PB-425B-2-VD
30
Load current (A)
50
G3PB-415B-3-VD
G3PB-415B-2-VD
Load current (A)
Load current (A)
G3PB-245B-3-VD
G3PB-245B-2-VD
25
20
30
Derating curve under UL standard
25
22
20
30
Derating curve under UL standard
15
20
18
10
12
10
7
6
0
−30 −20
10
8
0
0
20 25
−30 −20
40
60
80
100
Ambient temperature (°C)
0
20
40
60
80
100
Ambient temperature (°C)
Note: 1. Please use proper ventilation and cooling.
2. Please note that the derating curve above 42 A is
applicable under the UL standard only with forced
air cooling by fan.
0
20 25
40
60
80
100
Ambient temperature (°C)
Note: 1. Please use proper ventilation and cooling.
2. Please note that the derating curve above 22 A is
applicable under the UL standard only with forced
air cooling by fan.
G3PB-445B-3-VD
G3PB-445B-2-VD
50
Derating curve under UL standard
40
35
Load current (A)
Load current (A)
G3PB-435B-3-VD
G3PB-435B-2-VD
0
−30 −20
50
Derating curve under UL standard
45
42
40
30
28
30
20
20
18
14
12
10
10
8
0
−30 −20
0
20 25
40
60
80
100
Ambient temperature (°C)
Note: 1. Please use proper ventilation and cooling.
2. Please note that the derating curve above 28 A is
applicable under the UL standard only with forced
air cooling by fan.
0
−30 −20
0
20 25
40
60
80
100
Ambient temperature (°C)
Note: 1. Please use proper ventilation and cooling.
2. Please note that the derating curve above 42 A is
applicable under the UL standard only with forced
air cooling by fan.
7
G3PB-2/-3
Models without Built-in Heat Sinks
G3PB-235B-3H-VD
G3PB-235B-2H-VD
G3PB-245B-3H-VD
G3PB-245B-2H-VD
G3PB-225B-3H-VD
G3PB-225B-2H-VD
G3PB-425B-3H-VD
G3PB-425B-2H-VD
Load current (A)
Load current (A)
G3PB-215B-3H-VD
G3PB-215B-2H-VD
G3PB-415B-3H-VD
G3PB-415B-2H-VD
10
G3PB-225B-3(-2)H-VD
G3PB-425B-3(-2)H-VD
8
Derating curve under UL standard
10
Derating curve under UL standard
8
6
6
5
5
4
4
2
G3PB-435B-3H-VD
G3PB-435B-2H-VD
G3PB-445B-3H-VD
G3PB-445B-2H-VD
G3PB-215B-3(-2)H-VD
G3PB-415B-3(-2)H-VD
2
1.5
0
−30 −20
1.5
0
20
40
60
80
0
−30 −20
100
0
20 25
Ambient temperature (°C)
40
60
80 100
Ambient temperature (°C)
Note: Please use proper ventilation and cooling.
Note: Please use proper ventilation and cooling.
Input impedance (kΩ)
Input current (mA)
Input Voltage vs. Input Current and Input Voltage vs. Input Impedance
Input current
Input impedance
Input voltage (V)
One Cycle Surge Current: Non-repetitive
Note: Keep the inrush current to half the rated value if it occurs repetitively.
G3PB-225B-3 (H)-VD G3PB-425B-3 (H)-VD
G3PB-225B-2 (H)-VD
G3PB-415B-3 (H)-VD G3PB-425B-2 (H)-VD
G3PB-415B-2 (H)-VD
Energized time (ms)
G3PB-235B-3 (H)-VD
G3PB-235B-2 (H)-VD
G3PB-245B-3 (H)-VD
G3PB-245B-2 (H)-VD
G3PB-435B-3 (H)-VD
G3PB-435B-2 (H)-VD
G3PB-445B-3 (H)-VD
G3PB-445B-2 (H)-VD
Inrush current
Inrush current
Inrush current
G3PB-215B-3 (H)-VD
G3PB-215B-2 (H)-VD
Energized time (ms)
Energized time (ms)
8
G3PB-2/-3
Heat Sink Area vs. Load Current
G3PB-425B-3H-VD
Ambient temperature: 80°C
Ambient temperature: 40°C
Aluminum plate (t=3.0 mm)
Heat sink area (cm2)
Heat sink area (cm2)
G3PB-225B-3H-VD
Ambient temperature: 80°C
Ambient temperature: 40°C
Aluminum plate (t=3.0 mm)
Load current (A)
Load current (A)
Note: The heat sink area refers to the combined area of the sides of the heat sink that radiate heat. In the case of G3PB-425B-3H-VD, when a
current of 18 A is allowed to flow through the SSR at 40°C, the graph shows that the heat sink area is about 2,500 cm2. Therefore, if the heat
sink is square, one side of the heat sink must be 36 cm (362 × 2 = 2,592) or longer.
Thermal Resistance Rth (Junction/SSR Back Surface)
Three-phase Models without Heat Sink
Model
Rth (°C/W)
G3PB-215B-3H-VD
1.05
G3PB-225B-3H-VD
0.57
G3PB-235B-3H-VD
0.57
G3PB-245B-3H-VD
0.57
9
G3PB-2/-3
Dimensions
Note: All units are in millimeters unless otherwise indicated.
Models with Built-in Heat Sinks
G3PB-215B-2-VD
G3PB-415B-2-VD
Without Terminal Cover
With Terminal Cover
4.6 dia.
50
80.5 90 100
max.
max.
24
Two, M3.5 × 8
Six, M4 × 12
0.5
20
20
80 max.
Elliptical hole: 4.6 × 5.6
32.2
Mounting holes
Two, 4.5 dia. or M4
30.5
14.6 19.4 max.
55 max.
90±0.3
Terminal Arrangement/Internal Circuit Diagram
50±0.3
G3PB-215B-2-VD
L1/R
L2/S
G3PB-415B-2-VD
(+)
L3/T
L1/R
L2/S
(+)
L3/T
Input circuit
A1
Input circuit
A1
A2
T1/U
Without Terminal Cover
T3/W
A2
T1/U
(−)
T2/V
T3/W
(−)
With Terminal Cover
Four, R2.5
5
60 80.5
max.
24
Two, M3.5 × 8
0.5
20
80 max.
100
110.5 max.
Six, M4 × 12
20
32.2
Mounting Holes
30.5
14.6 19.4 max.
Four, 4.5 dia or M4
70 max.
60±0.3
100±0.3
Terminal Arrangement/Internal Circuit Diagram
L2/S
L3/T
(+)
L1/R
L2/S
L3/T
A1
T2/V
T3/W
(−)
(+)
L1/R
L2/S
G3PB-425B-2-VD
L3/T
A1
A2
T1/U
T2/V
T3/W
(−)
(+)
L1/R
L2/S
L3/T
A1
Input circuit
A2
T1/U
G3PB-415B-3-VD
A1
A2
T1/U
T2/V
T3/W
(−)
(+)
Input circuit
L1/R
G3PB-225B-2-VD
Input circuit
G3PB-215B-3-VD
Input circuit
G3PB-215B-3-VD
G3PB-225B-2-VD
G3PB-415B-3-VD
G3PB-425B-2-VD
T2/V
A2
T1/U
T2/V
T3/W
(−)
10
G3PB-2/-3
G3PB-225B-3-VD
G3PB-235B-2-VD
G3PB-425B-3-VD
G3PB-435B-2-VD
Without Terminal Cover
With Terminal Cover
5
Four, R2.5
80.5 90 110.5
max.
max.
24
Two, M3.5 × 8
0.5
20
Six, M5 × 12
(G3PB-@35B-2-VD)
Six, M4 × 12
(G3PB-@25B-3-VD)
20
32.2
80 max.
100
110.5 max.
Mounting Holes
30.5
14.6 19.4 max.
Four, 4.5 dia or M4
70 max.
90±0.3
100±0.3
Terminal Arrangement/Internal Circuit Diagram
L2/S
L3/T
L1/R
L2/S
L3/T
Input circuit
T3/W
(−)
L3/T
T2/V
Without Terminal Cover
T3/W
(−)
(+)
L1/R
L2/S
L3/T
A1
A2
T1/U
T2/V
T3/W
(−)
(+)
A1
A2
T1/U
A2
T1/U
T2/V
T3/W
(−)
With Terminal Cover
5
Four, R2.5
80.5
130.5
max. 90 max.
24
0.5
20
Two,
Six, M3.5 × 8
M5 × 12
20
80 max.
120
130.5 max.
32.2
Mounting Holes
30.5
14.6 19.4 max.
Four, 4.5 dia or M4
70 max.
90±0.3
120±0.3
Terminal Arrangement/Internal Circuit Diagram
L2/S
L3/T
(+)
L1/R
L2/S
L3/T
A1
T2/V
T3/W
(−)
(+)
L1/R
L2/S
G3PB-445B-2-VD
L3/T
A1
A2
T1/U
T2/V
T3/W
(−)
(+)
L1/R
L2/S
L3/T
A1
Input circuit
A2
T1/U
G3PB-435B-3-VD
A1
A2
T1/U
T2/V
T3/W
(−)
(+)
Input circuit
L1/R
G3PB-245B-2-VD
Input circuit
G3PB-235B-3-VD
Input circuit
G3PB-235B-3-VD
G3PB-245B-2-VD
G3PB-435B-3-VD
G3PB-445B-2-VD
T2/V
L2/S
A1
A2
T1/U
L1/R
G3PB-435B-2-VD
Input circuit
Input circuit
A1
G3PB-425B-3-VD
(+)
Input circuit
L1/R
G3PB-235B-2-VD
(+)
Input circuit
G3PB-225B-3-VD
A2
T1/U
T2/V
T3/W
(−)
11
G3PB-2/-3
Without Terminal Cover
With Terminal Cover
5
Four, R2.5
80.5 150 190.5
max.
max.
24
Two,
M3.5 × 8
Six,
M5 × 12
20
20
32.2
80 max.
120
130.5 max.
Mounting Holes
30.5
14.6 19.4 max.
Four, 4.5 dia or M4
70 max.
150±0.3
Terminal Arrangement/Internal Circuit Diagram
G3PB-445B-3-VD
G3PB-245B-3-VD
L1/R
L2/S
L3/T
(+)
L1/R
L2/S
L3/T
120±0.3
A2
A2
T1/U
T2/V
T3/W
(−)
(+)
A1
A1
Input circuit
0.5
Input circuit
G3PB-245B-3-VD
G3PB-445B-3-VD
T1/U
T2/V
T3/W
(−)
12
G3PB-2/-3
Models without Built-in Heat Sinks
Without Terminal Cover
G3PB-215B-3H-VD
G3PB-215B-2H-VD
G3PB-225B-3H-VD
G3PB-225B-2H-VD
G3PB-235B-3H-VD
G3PB-235B-2H-VD
G3PB-245B-3H-VD
G3PB-245B-2H-VD
G3PB-415B-3H-VD
G3PB-415B-2H-VD
G3PB-425B-3H-VD
G3PB-425B-2H-VD
G3PB-435B-3H-VD
G3PB-435B-2H-VD
G3PB-445B-3H-VD
G3PB-445B-2H-VD
Four, 8 dia.
With Terminal Cover
Four, 4.5 dia.
6
8
4
68
80.5
max.
24
Two, M3.5 × 8
0.5
20
80 max.
20
32.2
68
Six, M4 × 12
(G3PB-@15B@H-VD/-@25B-@H-VD)
Six, M5 × 12
(G3PB-@35B-@H-VD/-@45B-@H-VD)
Mounting Holes
30.5
14.6 19.4 max.
Four, 4.5 dia or M4
68±0.3
68±0.3
Terminal Arrangement/Internal Circuit Diagram
L2/S
L3/T
L1/R
L2/S
L3/T
A1
T3/W
(−)
L1/R
L2/S
L3/T
T2/V
T3/W
L1/R
L2/S
L3/T
T1/U
(−)
T2/V
T3/W
(−)
(+)
A1
A2
A2
T1/U
G3PB-4@5B-2H-VD
(+)
A1
Input circuit
Input circuit
T2/V
(+)
A1
A2
T1/U
G3PB-4@5B-3H-VD
G3PB-2@5B-2H-VD
(+)
Input circuit
L1/R
Input circuit
G3PB-2@5B-3H-VD
A2
T1/U
T2/V
T3/W
(−)
Heat Sinks
Y92B-P50
For model
Y92B-P100
For G3PB-215B-3H-VD
G3PB-225B-2H-VD
G3PB-415B-3H-VD
G3PB-425B-2H-VD
G3PB-215B-2H-VD
G3PB-415B-2H-VD
Four, M4
4.6 dia.
Mounting Holes
100
Four, 4.5 dia. or M4
5
80.5 90
max.
100
max.
60 80.5
max.
68
60±0.3
100±0.3
Four, R2.5
Elliptical
hole:
4.6 x 5.6
68
110.5 max.
80 max.
Mounting Holes
Two, 4.5 dia. or M4
55 max.
70 max.
13
G3PB-2/-3
Y92B-P250
For model G3PB-245B-3-VD
G3PB-445B-3-VD
Y92B-P200
For model G3PB-235B-3H-VD
G3PB-245B-2H-VD
G3PB-435B-3H-VD
G3PB-445B-2H-VD
Y92B-P150
For model G3PB-225B-3H-VD
G3PB-235B-2H-VD
G3PB-425B-3H-VD
G3PB-435B-2H-VD
120
120
Four, M4
100
M4
Depth10
Four, M4
5
5
5
90 130.5
max.
68
90 110.5
max.
68
68 47.6
150
190.5
max.
M4
Depth10
Four, R2.5
68
Four,
R2.5
Four, M4
68
110.5 max.
120
130.5 max.
Four,
R2.5
68
120
130.5 max.
70 max.
70 max.
Mounting Holes
70 max.
Mounting Holes
Mounting Holes
Four, 4.5 dia. or M4
Four, 4.5 dia. or M4
Four, 4.5 dia. or M4
90±0.3
90±0.3
100±0.3
150±0.3
120±0.3
120±0.3
Accessories (Order Separately)
Mounting Tracks
PFP-100N, PFP-50N
PFP-100N2
16
7.3±0.15
4.5
4.5
35±0.3
15 25
10
25
25
25
10
1,000 (500)
(see note)
15 (5)
(see note)
35±0.3 27 24
27±0.15
15 25
10
25
25
1,000
10
25 15
1
29.2
1.5
Note: Values in parentheses indicate dimensions
for the PFP-50N.
ALL DIMENSIONS SHOWN ARE IN MILLIMETERS.
To convert millimeters into inches, multiply by 0.03937. To convert grams into ounces, multiply by 0.03527.
In the interest of product improvement, specifications are subject to change without notice.
14
Read and Understand This Catalog
Please read and understand this catalog before purchasing the products. Please consult your OMRON representative if you have any questions or
comments.
Warranty and Limitations of Liability
WARRANTY
OMRON's exclusive warranty is that the products are free from defects in materials and workmanship for a period of one year (or other period if specified)
from date of sale by OMRON.
OMRON MAKES NO WARRANTY OR REPRESENTATION, EXPRESS OR IMPLIED, REGARDING NON-INFRINGEMENT, MERCHANTABILITY, OR
FITNESS FOR PARTICULAR PURPOSE OF THE PRODUCTS. ANY BUYER OR USER ACKNOWLEDGES THAT THE BUYER OR USER ALONE HAS
DETERMINED THAT THE PRODUCTS WILL SUITABLY MEET THE REQUIREMENTS OF THEIR INTENDED USE. OMRON DISCLAIMS ALL OTHER
WARRANTIES, EXPRESS OR IMPLIED.
LIMITATIONS OF LIABILITY
OMRON SHALL NOT BE RESPONSIBLE FOR SPECIAL, INDIRECT, OR CONSEQUENTIAL DAMAGES, LOSS OF PROFITS OR COMMERCIAL LOSS
IN ANY WAY CONNECTED WITH THE PRODUCTS, WHETHER SUCH CLAIM IS BASED ON CONTRACT, WARRANTY, NEGLIGENCE, OR STRICT
LIABILITY.
In no event shall the responsibility of OMRON for any act exceed the individual price of the product on which liability is asserted.
IN NO EVENT SHALL OMRON BE RESPONSIBLE FOR WARRANTY, REPAIR, OR OTHER CLAIMS REGARDING THE PRODUCTS UNLESS
OMRON'S ANALYSIS CONFIRMS THAT THE PRODUCTS WERE PROPERLY HANDLED, STORED, INSTALLED, AND MAINTAINED AND NOT
SUBJECT TO CONTAMINATION, ABUSE, MISUSE, OR INAPPROPRIATE MODIFICATION OR REPAIR.
Application Considerations
SUITABILITY FOR USE
OMRON shall not be responsible for conformity with any standards, codes, or regulations that apply to the combination of products in the customer's
application or use of the products.
At the customer's request, OMRON will provide applicable third party certification documents identifying ratings and limitations of use that apply to the
products. This information by itself is not sufficient for a complete determination of the suitability of the products in combination with the end product,
machine, system, or other application or use.
The following are some examples of applications for which particular attention must be given. This is not intended to be an exhaustive list of all possible
uses of the products, nor is it intended to imply that the uses listed may be suitable for the products:
• Outdoor use, uses involving potential chemical contamination or electrical interference, or conditions or uses not described in this catalog.
• Nuclear energy control systems, combustion systems, railroad systems, aviation systems, medical equipment, amusement machines, vehicles,
safety equipment, and installations subject to separate industry or government regulations.
• Systems, machines, and equipment that could present a risk to life or property.
Please know and observe all prohibitions of use applicable to the products.
NEVER USE THE PRODUCTS FOR AN APPLICATION INVOLVING SERIOUS RISK TO LIFE OR PROPERTY WITHOUT ENSURING THAT THE
SYSTEM AS A WHOLE HAS BEEN DESIGNED TO ADDRESS THE RISKS, AND THAT THE OMRON PRODUCTS ARE PROPERLY RATED AND
INSTALLED FOR THE INTENDED USE WITHIN THE OVERALL EQUIPMENT OR SYSTEM.
PROGRAMMABLE PRODUCTS
OMRON shall not be responsible for the user's programming of a programmable product, or any consequence thereof.
Disclaimers
CHANGE IN SPECIFICATIONS
Product specifications and accessories may be changed at any time based on improvements and other reasons.
It is our practice to change model numbers when published ratings or features are changed, or when significant construction changes are made.
However, some specifications of the products may be changed without any notice. When in doubt, special model numbers may be assigned to fix or
establish key specifications for your application on your request. Please consult with your OMRON representative at any time to confirm actual
specifications of purchased products.
DIMENSIONS AND WEIGHTS
Dimensions and weights are nominal and are not to be used for manufacturing purposes, even when tolerances are shown.
PERFORMANCE DATA
Performance data given in this catalog is provided as a guide for the user in determining suitability and does not constitute a warranty. It may represent the
result of OMRON’s test conditions, and the users must correlate it to actual application requirements. Actual performance is subject to the OMRON
Warranty and Limitations of Liability.
ERRORS AND OMISSIONS
The information in this document has been carefully checked and is believed to be accurate; however, no responsibility is assumed for clerical,
typographical, or proofreading errors, or omissions.
2008.11
In the interest of product improvement, specifications are subject to change without notice.
OMRON Corporation
Industrial Automation Company
http://www.ia.omron.com/
(c)Copyright OMRON Corporation 2008 All Right Reserved.