Data sheet
6EP3311-6SB00-0AY0
LOGO!Power/1AC/5VDC/6.3A
LOGO!Power 5 V / 6.3 A stabilized power supply input: 100-240 V AC
output: 5 V DC / 6.3 A *Ex approval no longer available*
Input
type of the power supply network
1-phase AC or DC
supply voltage at AC
● minimum rated value
100 V
● maximum rated value
240 V
● initial value
85 V
● full-scale value
264 V
input voltage
● at DC
110 ... 300 V
design of input wide range input
Yes
overvoltage overload capability
300 V AC for 1 s
operating condition of the mains buffering
at Vin = 187 V
buffering time for rated value of the output current in the
event of power failure minimum
40 ms
operating condition of the mains buffering
at Vin = 187 V
line frequency
● 1 rated value
50 Hz
● 2 rated value
60 Hz
line frequency
47 ... 63 Hz
input current
● at rated input voltage 120 V
0.71 A
● at rated input voltage 230 V
0.37 A
current limitation of inrush current at 25 °C maximum
50 A
I2t value maximum
3 A²·s
fuse protection type
internal
● in the feeder
Recommended miniature circuit breaker: from 10 A characteristic B or
from 6 A characteristic C
Output
voltage curve at output
Controlled, isolated DC voltage
output voltage at DC rated value
5V
output voltage
● at output 1 at DC rated value
5V
relative overall tolerance of the voltage
3%
relative control precision of the output voltage
● on slow fluctuation of input voltage
0.1 %
● on slow fluctuation of ohm loading
0.1 %
residual ripple
● maximum
100 mV
● typical
30 mV
voltage peak
6EP33116SB000AY0
Page 1/3
7/5/2022
Subject to change without notice
© Copyright Siemens
● maximum
100 mV
● typical
50 mV
adjustable output voltage
4.6 ... 5.4 V
product function output voltage adjustable
Yes
type of output voltage setting
via potentiometer
display version for normal operation
Green LED for output voltage OK
behavior of the output voltage when switching on
No overshoot of Vout (soft start)
response delay maximum
0.5 s
voltage increase time of the output voltage
● typical
100 ms
output current
● rated value
6.3 A
● rated range
0 ... 6.3 A; +55 ... +70 °C: Derating 2%/K
supplied active power typical
31.5 W
product feature
● bridging of equipment
number of parallel-switched equipment resources for
increasing the power
Yes
2
Efficiency
efficiency in percent
80 %
power loss [W]
● at rated output voltage for rated value of the output
current typical
8W
● during no-load operation maximum
0.3 W
Closed-loop control
relative control precision of the output voltage with rapid
fluctuation of the input voltage by +/- 15% typical
0.2 %
relative control precision of the output voltage at load step
of resistive load 10/90/10 % typical
7%
setting time
● load step 10 to 90% typical
1 ms
● load step 90 to 10% typical
1 ms
Protection and monitoring
design of the overvoltage protection
Yes, according to EN 60950-1
response value current limitation typical
8.2 A
property of the output short-circuit proof
Yes
design of short-circuit protection
Constant current characteristic
enduring short circuit current RMS value
● maximum
8.2 A
overcurrent overload capability in normal operation
overload capability 150% Iout rated typ. 200 ms
display version for overload and short circuit
-
measuring point for output current
50 mV =^ 6.3 A
overcurrent overload capability when switching on
150% Iout rated typ. 200 ms
Safety
galvanic isolation between input and output
Yes
galvanic isolation
Safety extra-low output voltage Uout acc. to EN 60950-1 and EN 50178
operating resource protection class
Class II (without protective conductor)
protection class IP
IP20
Approvals
certificate of suitability
● CE marking
Yes
● UL approval
Yes; cULus-Listed (UL 508, CSA C22.2 No. 107.1), File E197259;
cURus-Recognized (UL 60950, CSA C22.2 No. 60950), File E151273
● CSA approval
Yes; cULus-Listed (UL 508, CSA C22.2 No. 107.1), File E197259;
cURus-Recognized (UL 60950, CSA C22.2 No. 60950), File E151273
● cCSAus, Class 1, Division 2
No
● ATEX
No
certificate of suitability
● IECEx
No
● NEC Class 2
No
● ULhazloc approval
No
6EP33116SB000AY0
Page 2/3
7/5/2022
Subject to change without notice
© Copyright Siemens
● FM registration
type of certification CB-certificate
No
Yes
certificate of suitability
● EAC approval
Yes
certificate of suitability shipbuilding approval
Yes
shipbuilding approval
ABS, BV, DNV GL, LRS
Marine classification association
● American Bureau of Shipping Europe Ltd. (ABS)
Yes
● French marine classification society (BV)
Yes
● DNV GL
Yes
● Lloyds Register of Shipping (LRS)
Yes
● Nippon Kaiji Kyokai (NK)
No
EMC
standard
● for emitted interference
EN 55022 Class B
● for mains harmonics limitation
not applicable
● for interference immunity
EN 61000-6-2
environmental conditions
ambient temperature
● during operation
-25 ... +70 °C; with natural convection
● during transport
-40 ... +85 °C
● during storage
-40 ... +85 °C
environmental category according to IEC 60721
Climate class 3K3, 5 … 95% no condensation
Mechanics
type of electrical connection
screw-type terminals
● at input
L, N: 1 screw terminal each for 0.5 ... 2.5 mm2 single-core/finely
stranded
● at output
+, -: 1 screw terminal each for 0.5 ... 2.5 mm²
● for auxiliary contacts
-
width of the enclosure
54 mm
height of the enclosure
90 mm
depth of the enclosure
53 mm
required spacing
● top
20 mm
● bottom
20 mm
● left
0 mm
● right
0 mm
net weight
0.2 kg
product feature of the enclosure housing can be lined up
Yes
fastening method
Snaps onto DIN rail EN 60715 35x7.5/15, direct mounting in different
mounting positions
MTBF at 40 °C
2 654 280 h
other information
Specifications at rated input voltage and ambient temperature +25 °C
(unless otherwise specified)
6EP33116SB000AY0
Page 3/3
7/5/2022
Subject to change without notice
© Copyright Siemens
很抱歉,暂时无法提供与“6EP33116SB000AY0”相匹配的价格&库存,您可以联系我们找货