Data sheet
6ES7136-6RA00-0BF0
SIMATIC DP, Electronics module f. ET200SP, F-RQ 1x 24 V DC/24..230VAC/5A
ST, 20 mm overall width, 1 relay output (2 NO) Summation output current 5 A, load
voltage 24 V DC and 24.. 230 V AC, Can be used up to PL E (ISO 13849-1: 2008)/
SIL 3 (IEC 61508: 2010) if control takes place by (e.g. 6ES7136-6DB00-0CA0) FDQ
General information
Product type designation
F-RQ 24 ... 48VDC/24 ... 230VAC/5A ST
usable BaseUnits
BU type F0
Color code for module-specific color identification plate
CC42
Product function
● I&M data
Yes; I&M0 to I&M3
Engineering with
● STEP 7 TIA Portal configurable/integrated from version
V13
● STEP 7 configurable/integrated from version
V5.5 SP4 and higher
● PROFINET from GSD version/GSD revision
V2.31
Supply voltage
Rated value (DC)
24 V; Coil voltage
permissible range, lower limit (DC)
20.4 V
permissible range, upper limit (DC)
28.8 V
power supply according to NEC Class 2 required
No
Power
Power available from the backplane bus
100 mW
Power loss
Power loss, typ.
1W
Address area
Address space per module
● Inputs
1 byte
Hardware configuration
Automatic encoding
Yes
● Mechanical coding element
Yes
● Type of mechanical coding element
type C
Digital outputs
Type of digital output
Relays
Number of digital outputs
1
Limitation of inductive shutdown voltage to
No
Controlling a digital input
Yes
Switching capacity of the outputs
● with resistive load, max.
5A
● on lamp load, max.
25 W
Switching frequency
● with resistive load, max.
2 Hz
● with inductive load, max.
0.1 Hz; See data in manual
● with inductive load (acc. to IEC 60947-5-1, DC13), max.
0.1 Hz
● with inductive load (acc. to IEC 60947-5-1, AC15), max.
2 Hz
Total current of the outputs (per module)
6ES71366RA000BF0
Page 1/3
5/7/2024
Subject to change without notice
© Copyright Siemens
horizontal installation
— up to 40 °C, max.
5 A; note derating data in the manual
— up to 50 °C, max.
4 A; note derating data in the manual
— up to 60 °C, max.
3 A; note derating data in the manual
vertical installation
— up to 50 °C, max.
3 A; note derating data in the manual
Relay outputs
● Number of relay outputs
1; 2 NO contacts
● Rated supply voltage of relay coil L+ (DC)
24 V
● Current consumption of relays (coil current of all relays),
max.
70 mA
● external protection for relay outputs
yes; 6 A, see data in manual
● Relay approved acc. to UL 508
Yes; Pilot Duty B300, R300
Switching capacity of contacts
— with inductive load, max.
see additional description in the manual
— with resistive load, max.
see additional description in the manual
— Thermal continuous current, max.
5A
— Switching current, min.
1 mA
— Switching current after exceeding 300 mA, min.
10 mA
— Switching current after exceeding 300 mA, max.
5A
— Rated switching voltage (DC)
24 V
— Rated switching voltage (AC)
230 V
Cable length
● shielded, max.
500 m; for load contacts
● unshielded, max.
300 m; for load contacts
● Control cable (input), max.
10 m
Interrupts/diagnostics/status information
Diagnostics function
Yes
Diagnostics indication LED
● RUN LED
Yes; green/red DIAG LED
● Channel status display
Yes; green LED
Potential separation
Potential separation channels
● between the channels
Yes; for SELV / PELV only
● between the channels and backplane bus
Yes
● between the channels and the power supply of the
electronics
Yes
Permissible potential difference
between channels and backplane bus/supply voltage
250 V AC (reinforced insulation)
Isolation
Isolation tested with
2 545 V DC/2 s (routine test)
Overvoltage category
III (according to IEC/EN 61131-2:2007 and EN 298:2012), II (according to IEC
61131-2:2017 and IEC 61010-2-201)
tested with
● between channels and backplane bus/supply voltage
DC 2 545 V 2 s (routine test), impulse voltage test DC 7 200 V / 5 positive and
5 negative pulses (type test)
● between backplane bus and supply voltage
707 V DC (type test)
Standards, approvals, certificates
Suitable for safety functions
Yes
Highest safety class achievable in safety mode
● Performance level according to ISO 13849-1
PLe
● Category according to ISO 13849-1
4
● SIL acc. to IEC 61508
SIL 3
Probability of failure (for service life of 20 years and repair time of 100 hours)
— Low demand mode: PFDavg in accordance with
SIL2
< 1.00E-04, function test 1x per year
— Low demand mode: PFDavg in accordance with
SIL3
< 1.00E-05, function test 1x per month
— High demand/continuous mode: PFH in accordance
with SIL2
< 1.00E-08 1/h, function test 1x per year
— High demand/continuous mode: PFH in accordance
with SIL3
< 6.00E-09 1/h, function test 1x per month
Ambient conditions
6ES71366RA000BF0
Page 2/3
5/7/2024
Subject to change without notice
© Copyright Siemens
Ambient temperature during operation
● horizontal installation, min.
0 °C
● horizontal installation, max.
60 °C
● vertical installation, min.
0 °C
● vertical installation, max.
50 °C
Dimensions
Width
20 mm
Height
73 mm
Depth
58 mm
Weights
Weight, approx.
56 g
last modified:
3/12/2024
6ES71366RA000BF0
Page 3/3
5/7/2024
Subject to change without notice
© Copyright Siemens