Data sheet
7KM4212-0BA00-3AA0
SENTRON, measuring device, 7KM PAC4200, LCD, L-L: 690 V, L-N: 400 V, 5 A,
3-phase, Modbus TCP, optional Modbus RTU / PROFINET / PROFIBUS / DI/DO,
apparent/active/reactive energy / cos phi, harmonics: 2.-64., THD, class 0.2 acc. to
IEC61557-12 or cl. 0.2S acc. to IEC62053-22, wide-range pwr sup. unit AC/DC,
screw terminals
Model
product brand name
SENTRON
product designation
Measuring device for power system quality measurement
design of the product
compact
product type designation
7KM PAC4200
Measurements
measuring procedure
● for voltage measurement
TRMS
● for current measurement
TRMS
type of measured value detection
complete
voltage curve
Sinusoidal or distorted
measurable line frequency
● initial value
45 Hz
● full-scale value
65 Hz
operating mode for measured value detection automatic line
frequency detection
Yes
operating mode for measured value detection
● set at 50 Hz
No
● set to 60 Hz
No
Supply voltage
design of the power supply
Wide-range power supply
type of voltage of the supply voltage
AC/DC
supply voltage at AC
95 ... 240 V
supply voltage at DC
110 ... 340 V
Degree of protection protection class
protection class IP on the front
IP65
operating resource protection class when installed
II
Suitability
suitability for operation
Installation in stationary panels in closed rooms
Product Functions
product function
● voltage measurement
Yes
● current measurement
Yes
● active power measurement
Yes
● reactive power measurement
Yes
● frequency measurement
Yes
Display and operation
design of the display
LCD
height of the display
54 mm
width of the display
72 mm
7KM42120BA003AA0
Page 1/6
5/17/2024
Subject to change without notice
© Copyright Siemens
color of the background of the display
white
illuminance of display backlight adjustable
Yes
time-controlled reduction of the illuminance of display backlight
possible
Yes
display contrast adjustable
Yes
national language on the display screen is supported
ger, en, fr, spa, ita, por, tur, rus, chi, pol
number of keys
4
Communication
transfer rate minimum
10 000 kbit/s
transfer rate maximum
100 000 kbit/s
number of interfaces according to Fast Ethernet
1
type of electrical connection of the fast Ethernet interface
RJ45 (8P8C)
protocol at the Ethernet interface is supported
MODBUS TCP
transfer rate 1 for Ethernet
10 Mbit/s
transfer rate 2 for Ethernet
100 Mbit/s
Fault limits
reference condition for metering accuracy
according to IEC61557-12
formula for relative total measurement inaccuracy
● for measured variable voltage
+/- 0.2 %
● for measured variable current
+/- 0.2 %
● for measured variable output factor
+/- 2 %
● for measured variable active energy
Class 0.2 according to IEC61557-12 and/or class 0.2S according to IEC6205322
● for measured variable reactive energy
Class 2 according to IEC61557-12 and/or IEC62053-23
● for measured variable THD
+/- 2 %
Inputs Outputs
number of digital inputs
2
type of electrical connection at the digital inputs
screw-type terminals
operating conditions for digital inputs external voltage supply
Yes
input voltage at digital input at DC maximum
30 V
number of digital outputs
2
type of switching output
solid state
digital output version
switching or pulse output function
operating voltage as output voltage at DC maximum permissible
30 V
type of electrical connection at the digital outputs
screw-type terminals
output current
● at digital output with signal maximum
0.2 mA
● at digital output for signal maximum
27 mA
● at the digital outputs at DC limited to 100 ms maximum
300 mA
internal resistance at the digital outputs
55 Ω
standard for pulse emitter
according to IEC62053-31
pulse duration
● initial value
30 ms
● full-scale value
500 ms
adjustable time period minimum
10 ms
switching frequency at digital output maximum
20 Hz
property of the output short-circuit proof
Yes
measuring category for digital signals
CATI
Measuring inputs
measurable supply voltage between (PE)N and L at AC
maximum rated value
400 V
measurable supply voltage between (PE)N and L at AC
● minimum
11.5 V
● maximum
480 V
measurable supply voltage between the line conductors at AC
maximum rated value
690 V
measurable supply voltage between the line conductors at AC
● minimum
20 V
● maximum
828 V
voltage measuring range extension with external voltage
transformers
yes
line conductors and neutral conductors internal resistance for
1.05 MΩ
7KM42120BA003AA0
Page 2/6
5/17/2024
Subject to change without notice
© Copyright Siemens
voltage measurement
measuring category for voltage measurement
CAT III
measurable current
● 1 at AC rated value
1A
● 2 at AC rated value
5A
relative measurable current at AC
● minimum
1%
● maximum
120 %
current measuring range extension with external current
transformers
Yes
zero point suppression for current measurement
0 ... 10 %
apparent power consumption for current measurement
● with measuring range 1 A per phase
4 mVA
● with measuring range 5 A per phase
0.115 VA
measuring category for current measurement
CATIII
Connections
type of connectable conductor cross-sections
● at the measurement inputs for voltage solid
1x (0.5 ... 4 mm²), 2x (0.5 ... 2.5 mm²)
● at the measurement inputs for voltage finely stranded with
core end processing
1x (0.5 ... 2.5 mm²), 2x (0.5 ... 1.5 mm²)
● at the measurement inputs for voltage for AWG cables
solid
2x 20 to 14
● at the measurement inputs for current solid
1x (0.5 ... 4 mm²), 2x (0.5 ... 2.5 mm²)
● at the measurement inputs for current finely stranded with
core end processing
1x (0.5 ... 2.5 mm²), 2x (0.5 ... 1.5 mm²)
● at the measurement inputs for current for AWG cables
solid
2x 20 to 14
type of electrical connection
● at the measurement inputs for voltage
screw-type terminals
● at the measurement inputs for current
screw-type terminals
Mechanical Design
fastening method standard rail mounting
No
size of Power Monitoring Device
size 96
height
96 mm
width
96 mm
depth
82 mm
installation depth
77 mm
net weight
543 g
mounting position
vertical
Environmental conditions
ambient temperature during operation
● minimum
-10 °C
● maximum
55 °C
ambient temperature during storage
● minimum
-25 °C
● maximum
70 °C
relative humidity at 25 °C without condensation during operation
maximum
95 %
installation altitude at height above sea level maximum
2 000 m
degree of pollution
2
Certificates
certificate of suitability as EC Declaration of Conformity
IEC 61010-1: 2001 (2nd Ed.) with Corr. 1, EN 61010-1: 2001 (2nd Ed.) and DIN
EN 61010-1:2002 with "Berichtigung 1"
reference code according to EN 61346-2
P
Approvals Certificates
General Product Approval
Confirmation
7KM42120BA003AA0
Page 3/6
5/17/2024
Subject to change without notice
© Copyright Siemens
Test Certificates
Type Test Certificates/Test Report
other
Miscellaneous
Confirmation
Dangerous Good
Environment
Dangerous Goods Information
Environmental Confirmations
Environmental Confirmations
Further information
Information on the packaging
https://support.industry.siemens.com/cs/ww/en/view/109813875
Information- and Downloadcenter (catalogues, leaflets,...)
http://www.siemens.com/energy-automation
Industry Mall (Online ordering system)
https://mall.industry.siemens.com/mall/en/en/Catalog/product?mlfb=7KM4212-0BA00-3AA0
Service&Support (Manuals, Certificates, Characteristics, FAQs,...)
https://support.industry.siemens.com/cs/ww/en/ps/7KM4212-0BA00-3AA0
Image database (product images, 2D dimension drawings, 3D models, device circuit diagrams, ...)
http://www.automation.siemens.com/bilddb/cax_en.aspx?mlfb=7KM4212-0BA00-3AA0
CAx-Online-Generator
http://www.siemens.com/cax
Tender specifications
http://www.siemens.com/specifications
99
77
7KM42120BA003AA0
Page 4/6
90
96
96
5/17/2024
Subject to change without notice
© Copyright Siemens
-X2
V1 V2 V3 VN L/+ N/-
-X4
FE
DIC DI1 DI0 DOC DO1 DO0
LAN
-P
-X1 IL1/k
last modified:
7KM42120BA003AA0
Page 5/6
IL1/l
IL2/k
IL2/l
IL3/k
-X3
IL3/l
3/12/2024
5/17/2024
Subject to change without notice
© Copyright Siemens
7KM42120BA003AA0
Page 6/6
5/17/2024
Subject to change without notice
© Copyright Siemens
很抱歉,暂时无法提供与“7KM4212-0BA00-3AA0”相匹配的价格&库存,您可以联系我们找货