Data sheet
7KM2112-0BA00-3AA0
SENTRON, measuring instrument, 7KM PAC3200, LCD, L-L: 690 V,
L-N: 400 V, 5 A, 3-phase, Modbus TCP, optionally Modbus RTU /
PROFINET / PROFIBUS, apparent / active / reactive energy, class
0.5 according to IEC61557-12 or Class 0.5S according to IEC6205322, wide voltage range power supply unit, AC/DC, screw terminal
Model
Product brand name
SENTRON
Product designation
7KM PAC3200
Design of the product
basic
Product type designation
Measuring instrument
Type of measured value detection
complete
Design of the power supply
Wide-range power supply
General technical data
Cutout width
92 mm
Cutout height
92 mm
Size of Power Monitoring Device / company-specific
size 96
Operating mode for measured value detection
● automatic line frequency detection
Yes
● set at 50 Hz
No
● set to 60 Hz
No
Pulse duration
● initial value
30 ms
● Full-scale value
500 ms
7KM2112-0BA00-3AA0
Page 1/9
06/15/2018
Subject to change without notice
© Copyright Siemens
Voltage curve
Sinusoidal or distorted
Measurable line frequency / initial value
45 Hz
Measurable line frequency / Full-scale value
65 Hz
Measuring procedure / for voltage measurement
RMS
MTBF
185.8 y
Reference code / acc. to DIN 40719 extended
according to IEC 204-2 / acc. to IEC 750
P
Supply voltage
Supply voltage frequency / rated value
● minimum
65 Hz
● maximum
45 Hz
Type of voltage / of the supply voltage
AC/DC
Measuring category / for supply voltage
CATIII
Apparent power consumption
● with expansion module / maximum
8 V·A
● without expansion module / typical
6 V·A
Relative symmetrical tolerance / of the supply voltage
10 %
Protection class
Protection class IP
● on the front
IP65
● Rear side
IP20
Operating resource protection class / when installed
II
Electricity
Measurable current / 2 / at AC / Rated value
5 A
Suitability
Suitability for operation
Installation in stationary control panels in closed rooms
Adjustable time period / minimum
10 ms
Product function
Product function
● reactive power measurement
Yes
● frequency measurement
Yes
● pulse measurement
Yes
● voltage measurement
Yes
● Current measurement
Yes
● active power measurement
Yes
Display and operation
Design of the display
LCD
Number of keys
4
Color / of the background of the display
white
7KM2112-0BA00-3AA0
Page 2/9
06/15/2018
Subject to change without notice
© Copyright Siemens
National language / on the display screen / is
supported
ger, en, fr, spa, ita, por, tur, chi
Horizontal image resolution
128
Vertical screen resolution
96
Refresh time / on display
● minimum
0.33 s
● maximum
3 s
Communication
Refresh time / at the interface
● minimum
0.33 s
● maximum
1 s
Number of interfaces / acc. to Fast Ethernet
1
Design of cable / connectable / Twisted pair
Yes
Protocol
● at the Ethernet interface / is supported
MODBUS TCP
● is supported
Modbus TCP
Transfer rate
● minimum
10 000 kbit/s
● maximum
10 000 kbit/s
Fault limits
Reference condition / for metering accuracy
Acc. to IEC62053-22 and IEC62053-23
Formula for relative total measurement inaccuracy
● for measured variable reactive energy
Class 2 according to IEC61557-12 and/or IEC62053-23
● for measured variable output
+/- 0,5 %
● for measured variable output factor
+/- 0,5 %
● for measured variable voltage
+/- 0,3 %
● for measured variable current
+/- 0,2 %
● for measured variable active energy
Cl. 0.5 acc. to... IEC62053-22
Inputs Outputs
Input voltage / at digital input
● initial value for signal-recognition
13 V
● at DC / rated value
24 V
● Full-scale value for signal recognition
8 V
Number of digital outputs
1
Number of digital inputs
1
Digital output version
switching or pulse output function
Input current / at digital input
● for signal
7 mA
Output current
● at digital output / with signal / maximum
0.2 mA
● at digital output / for signal / maximum
27 mA
7KM2112-0BA00-3AA0
Page 3/9
06/15/2018
Subject to change without notice
© Copyright Siemens
● at the digital outputs / at DC / maximum
100 mA
Output delay / at digital output
● for signal to / maximum
5 ms
● for signal to / maximum
5 ms
Operating voltage / as output voltage / at DC /
maximum permissible
30 V
Property of the output / Short-circuit proof
Yes
Input delay time / at digital input
● for signal to / maximum
5 ms
● for signal to / maximum
5 ms
Internal resistance / at the digital outputs
55 Ω
Measuring category / for digital signals
CATII
Switching frequency / at digital output / maximum
17 Hz
Transfer rate
● 1 / for fast Ethernet
10 Mbit/s
Measuring inputs
Outer conductors and neutral conductors internal
1.05 MΩ
resistance / for voltage measurement
Measurable supply voltage
● between (PE)N and L / at AC / minimum
40 V
● between (PE)N and L / at AC / maximum
480 V
● between (PE)N and L / at AC / maximum rated
value
400 V
● between the outer conductors / at AC /
minimum
70 V
● between the outer conductors / at AC /
maximum
831 V
● between the outer conductors / at AC /
maximum rated value
690 V
Voltage measuring range extension / with external
voltage transformers
Yes
Current measuring range extension / with external
current transformers
Yes
Measuring category / for voltage measurement
CATIII
Supply voltage / between the outer conductors / at
AC / maximum permissible
831 V
Consumed active power / for current measurement /
per phase
115 mW
Continuous current / at AC / maximum permissible
10 A
Measuring category / for current measurement
CATIII
Zero-point suppression / for current measurement
0,1 ... 10 %
Relative measurable current / at AC
● minimum
1 %
● maximum
120 %
7KM2112-0BA00-3AA0
Page 4/9
06/15/2018
Subject to change without notice
© Copyright Siemens
Measuring procedure / for current measurement
TRMS
Measurable current / 1 / at AC / Rated value
1 A
Connections
Type of connectable conductor cross-sections
● at the digital inputs / at AWG conductors / solid
2x 24 ... 18
● at the digital inputs / solid
1x (0.2 ... 2.5 mm²), 2x (0.2 ... 1.0 mm²)
● at the digital inputs / finely stranded / with core
end processing
1x (0.25 ... 2.5 mm²), 2x (0.25 ... 1.0 mm²)
● at the digital outputs / at AWG conductors /
solid
2x 24 ... 18
● at the digital outputs / solid
1x (0.2 ... 2.5 mm²), 2x (0.2 ... 1.0 mm²)
● at the digital outputs / finely stranded / with core
end processing
1x (0.25 ... 2.5 mm²), 2x (0.25 ... 1.0 mm²)
● at the inputs for supply voltage / at AWG
conductors / solid
2x 20 to 14
● at the inputs for supply voltage / solid
1x (0.5 ... 4 mm²), 2x (0.5 ... 2.5 mm²)
● at the inputs for supply voltage / finely stranded
/ with core end processing
1x (0.5 ... 2.5 mm²), 2x (0.5 ... 1.5 mm²)
● at the measurement inputs for voltage / at AWG
conductors / solid
2x 20 to 14
● at the measurement inputs for voltage / solid
1x (0.5 ... 4 mm²), 2x (0.5 ... 2.5 mm²)
● at the measurement inputs for voltage / finely
stranded / with core end processing
1x (0.5 ... 2.5 mm²), 2x (0.5 ... 1.5 mm²)
● at the measurement inputs for current / at AWG
conductors / solid
2x 20 to 14
● at the measurement inputs for current / solid
1x (0.5 ... 4 mm²), 2x (0.5 ... 2.5 mm²)
● at the measurement inputs for current / finely
stranded / with core end processing
1x (0.5 ... 2.5 mm²), 2x (0.5 ... 1.5 mm²)
Type of electrical connection
● at the measurement inputs for voltage
screw-type terminals
● of the fast Ethernet interface
RJ45 (8P8C)
Mechanical Design
Height
96 mm
Height / of the display
54 mm
Width
96 mm
Width
● of the display
72 mm
Depth
56 mm
Mounting position
vertical
Installation depth
51 mm
Mounting type / panel mounting
Yes
Net weight
451 g
7KM2112-0BA00-3AA0
Page 5/9
06/15/2018
Subject to change without notice
© Copyright Siemens
Environmental conditions
Installation altitude / at height above sea level /
maximum
2 000 m
Standard
● for EMC for industrial sector
IEC 61000-6-2 respectively IEC 61326-1:2005, table 2
● for EMC against unloading
IEC 61000-4-2: 2001-04
● for EMC against high frequency fields
IEC 61000-4-3: 2006-02
● for EMC against conducted LF disturbance
variables (industry)
IEC 61000-6-4, Group 1 Klasse A / CISPR11 Gruppe 1 Klasse A
FCC Part 15 Subpart B Class A
● for EMC against conducted disturbance
variables via HF fields
IEC 61000-4-6: 2001-12
● for EMC against magnetic fields with power
engineering frequencies
IEC 61000-4-8: 2001-03
● for EMC against quick, transient electrical
disturbances
IEC 61000-4-4: 2005-07
● for EMC against voltage drops and
interruptions
IEC 61000-4-11: 2004-03
● for EMC against surge voltages
IEC 61000-4-5: 2001-12
● for free fall
IEC 60068-2-32: 1975
● for pulse emitter
according to IEC62053-31
● for cyclic, environmental damp heat check
IEC 60068-2-30
● for environmental coldness check
IEC 60068-2-1
● for environmental dry heat check
IEC 60068-2-2
Relative humidity / at 25 °C / without condensation /
during operation
● minimum
5 %
● maximum
95 %
Ambient temperature
● during operation / minimum
-10 °C
● during operation / maximum
55 °C
● during storage / minimum
-25 °C
● during storage / maximum
70 °C
Certificates
Certificate of suitability
● as EC declaration of conformity
IEC 61010-1: 2001 (2nd Ed.) with Corr. 1, EN 61010-1: 2001 (2nd
Ed.) and DIN EN 61010-1:2002 with "Berichtigung 1"
● as approval for Canada
UL 61010-1, 2nd Ed. CAN/CSA-C22.2 NO. 61010-1-04
● as approval for USA
UL 61010-1, 2nd Ed. CAN/CSA-C22.2 NO. 61010-1-04
Reference code / acc. to DIN EN 61346-2
7KM2112-0BA00-3AA0
Page 6/9
P
06/15/2018
Subject to change without notice
© Copyright Siemens
General Product
Approval
Declaration of
Conformity
other
Confirmation
Metrological Approval
Further information
Information- and Downloadcenter (Catalogs, Brochures,…)
http://www.siemens.com/lowvoltage/catalogs
Industry Mall (Online ordering system)
https://mall.industry.siemens.com/mall/en/en/Catalog/product?mlfb=7KM2112-0BA00-3AA0
Service&Support (Manuals, Certificates, Characteristics, FAQs,...)
https://support.industry.siemens.com/cs/ww/en/ps/7KM2112-0BA00-3AA0
Image database (product images, 2D dimension drawings, 3D models, device circuit diagrams, ...)
http://www.automation.siemens.com/bilddb/cax_en.aspx?mlfb=7KM2112-0BA00-3AA0
CAx-Online-Generator
http://www.siemens.com/cax
Tender specifications
http://www.siemens.com/specifications
7KM2112-0BA00-3AA0
Page 7/9
06/15/2018
Subject to change without notice
© Copyright Siemens
POWER
SENTRON
ZUR
SCHALTTA
UC:
UE:
IE:
SCHRAUB
X/1A
MAX.6
110-34
MESS
OD
M
-X2
V1
V2
V3
VN
L/+
N/-
-X4
FE
DI-
DI+
DO-
DO+
LAN
-P
-X1
IL1/k
IL1/l
IL2/k
IL2/l
IL3/k
-X3
IL3/l
POWER
SENTRON
PANEL
FOR
VAUX:
VIN:
AMPIN:
COMPRES
MAX.6
MEAS
110
MO
X/1
M
POWER
SENTRON
ZUR
SCHALTTA
UC:
UE:
IE:
SCHRAUB
X/1A
MAX.6
110-34
MESS
OD
M
-X2
V1
V2
V3
VN
L/+
N/-
-X4
FE
DI-
DI+
DO-
DO+
LAN
-P
-X1
IL1/k
IL1/l
IL2/k
IL2/l
IL3/k
-X3
IL3/l
POWER
SENTRON
PANEL
FOR
VAUX:
VIN:
AMPIN:
COMPRES
MAX.6
MEAS
110
MO
X/1
M
7KM2112-0BA00-3AA0
Page 8/9
06/15/2018
Subject to change without notice
© Copyright Siemens
7KM2112-0BA00-3AA0
Page 9/9
06/15/2018
Subject to change without notice