Electrical Sector Solutions
Volume 9 OEM
Eaton Corporation
Electrical Sector
1111 Superior Ave.
Cleveland, OH 44114
United States
877-ETN-CARE (877-386-2273)
Eaton.com
© 2011 Eaton Corporation
All other trademarks are property
of their respective owners.
All Rights Reserved
Printed in USA
Publication No. CA08100011E / MSC
January 2011
Volume 9:
OEM
Volume 9—OEM Product Guide
Tab 1—Circuit Protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . V9-T1-1
Tab 2—Motor Control and Protection . . . . . . . . . . . . . . . . . . V9-T2-1
Tab 3—Logic Devices . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . V9-T3-1
Tab 4—Operator Interface . . . . . . . . . . . . . . . . . . . . . . . . . . . . V9-T4-1
Tab 5—Sensors and Limit Switches . . . . . . . . . . . . . . . . . . . V9-T5-1
Tab 6—Machine Integration . . . . . . . . . . . . . . . . . . . . . . . . . . V9-T6-1
Appendix 1—Eaton Terms & Conditions . . . . . . . . . . . . . . . . V9-A1-1
9
Copyright
Dimensions, Weights and Ratings
Dimensions, weights and ratings given in this catalog are approximate and should not
be used for construction purposes. Drawings containing exact dimensions are available
upon request. All listed product specifications and ratings are subject to change without
notice. Photographs are representative of production units.
Terms and Conditions
All prices and discounts are subject to change without notice. When price changes
occur, they are published in Eaton’s Price and Availability Digest (PAD). All orders
accepted by Eaton’s electrical sector are subject to the general terms and conditions
as set forth in Appendix 1—Eaton Terms & Conditions.
Technical and Descriptive Publications
This catalog contains brief technical data for proper selection of products. Further
information is available in the form of technical information publications and illustrated
brochures. If additional product information is required, contact your local Eaton
Products Distributor, call 1-800-525-2000 or visit our website at www.eaton.com.
Compliance with Nuclear Regulation 10 CFR 21
Eaton products are sold as commercial grade products not intended for application in
facilities or activities licensed by the United States Nuclear Regulatory Commission
for atomic purposes, under 10 CFR 21. Further certification will be required for use of
these products in a safety-related application in any nuclear facility licensed by the
U.S. Nuclear Regulatory Commission.
WARNING
The installation and use of Eaton products should be in accordance with the provisions
of the U.S. National Electrical Code® and/or other local codes or industry standards that
are pertinent to the particular end use. Installation or use not in accordance with these
codes and standards could be hazardous to personnel and/or equipment.
These catalog pages do not purport to cover all details or variations in equipment, nor to provide for
every possible contingency to be met in connection with installation, operation or maintenance.
Should further information be desired or should particular problems arise which are not covered
sufficiently for the purchaser’s purposes, the matter should be referred to the local Eaton Products
Distributor or Sales Office. The contents of this catalog shall not become part of or modify any prior
or existing agreement, commitment or relationship. The sales contract contains the entire
obligation of Eaton’s electrical sector. The warranty contained in the contract between the parties
is the sole warranty of Eaton. Any statements contained herein do not create new warranties or
modify the existing warranty.
Copyright ©2013 Eaton, All Rights Reserved.
Introduction
Eaton Corporation is a global leader in power distribution, power quality,
control and automation, and monitoring products.
At Eaton, we believe a reliable, efficient and safe power system is the foundation of every
successful enterprise. Through innovative technologies, cutting-edge products and our highly
skilled services team, we empower businesses around the world to achieve a powerful advantage.
In addition, Eaton is committed to creating and maintaining powerful customer relationships built
on a foundation of excellence. From the products we manufacture to our dedicated customer
service and support, we know what’s important to you.
Solutions
Eaton takes the complexity out of power systems management with a holistic and strategic
approach, leveraging our industry-leading technology, solutions and services. We focus on
the following three areas in all we do:
●
Reliability—maintain the
appropriate level of power
continuity without
disruption or unexpected
downtime
●
Efficiency—minimize
energy usage, operating
costs, equipment footprint
and environmental impact
●
Safety—identify and
mitigate electrical hazards
to protect what you value
most
Using the Eaton Catalog Library
As we grow, it becomes increasingly difficult to include all products in one or two comprehensive
catalogs. Knowing that each user has their specific needs, we have created a library of catalogs for our
products that when complete, will contain 15 volumes. Since the volumes will continuously be a work
in progress and updated, each volume will stand alone. Refer to our volume directory, MZ08100001E,
for a quick glance of where to look for the products you need. The 15 volumes include:
●
●
●
●
●
●
Volume 1—Residential
and Light Commercial
(CA08100002E)
Volume 2—Commercial
Distribution (CA08100003E)
Volume 3—Power
Distribution and Control
Assemblies (CA08100004E)
Volume 4—Circuit
Protection (CA08100005E)
Volume 5—Motor Control
and Protection
(CA08100006E)
Volume 6—Solid-State
Motor Control
(CA08100007E)
●
●
●
●
●
Volume 7—Logic Control,
Operator Interface and
Connectivity Solutions
(CA08100008E)
Volume 8—Sensing
Solutions (CA08100010E)
Volume 9—Original
Equipment Manufacturer
(CA08100011E)
Volume 10—Enclosed
Control (CA08100012E)
Volume 11—Vehicle and
Commercial Controls
(CA08100013E)
●
●
●
●
Volume 12—Aftermarket,
Renewal Parts and Life
Extension Solutions
(CA08105001E)
Volume 13—Counters,
Timers and Tachometers
(CA08100015E)—Available
in electronic format only
Volume 14—Fuses
(CA08100016E)—Available
in electronic format only
Volume 15—Solar Inverters
and Electrical Balance of
System (CA08100018E)
These volumes are not all-inclusive of every product, but they are meant to be an overview
of our product lines. For our full range of product solutions and additional product information,
consult Eaton.com/electrical and other catalogs and product guides in our literature library.
These references include:
●
The Consulting Application
Guide (CA08104001E)
●
The Eaton Power Quality
Product Guide (COR01FYA)
If you don’t have the volume that contains the product or information that you are looking for,
not to worry. You can access every volume of the catalog library at Eaton.com/electrical in the
Literature Library.
By installing our Automatic Tab Updater (ATU), you can be sure you always have the most recent
version of each volume and tab.
Volume 9—OEM—Original Equipment Manufacturer CA08100011E—March 2013
www.eaton.com
i
Circuit Protection
Circuit Breakers
1.1
Circuit Breakers
Product Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Series G Molded Case Circuit Breakers . . . . . . . . . . . . . . . . . . . . . . . .
Series G Motor Circuit Protectors. . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Series G Motor Protector Breakers . . . . . . . . . . . . . . . . . . . . . . . . . . .
Universal Molded Case Circuit Breakers . . . . . . . . . . . . . . . . . . . . . . .
QUICKLAG Type QC Miniature Circuit Breakers—
Cable-In/Cable-Out Type QC . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
WMZ UL 489 Miniature Circuit Breakers . . . . . . . . . . . . . . . . . . . . . . .
WMZS UL 1077 Miniature Circuit Breakers—
Supplementary Protectors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Series NRX Low Voltage Power Breakers . . . . . . . . . . . . . . . . . . . . . .
Magnum Low Voltage Power Breakers . . . . . . . . . . . . . . . . . . . . . . . .
Fuse Blocks and Fuse Holders
1.2
1.3
V9-T1-5
V9-T1-8
V9-T1-10
1
1
1
V9-T1-19
1
V9-T1-25
V9-T1-27
V9-T1-29
V9-T1-32
V9-T1-40
V9-T1-41
Rotary Disconnect Switches
Open Rotary Disconnects . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Enclosed Rotary Disconnects . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1
V9-T1-13
Fuse Blocks and Fuse Holders
Product Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
C350 Series . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Rotary Disconnect Switches
V9-T1-2
V9-T1-42
V9-T1-58
1
1
1
1
1
1
1
1
For our complete product offering, see Volume 4—Circuit Protection, CA08100005E and
Volume 5—Motor Control and Protection, CA08100006E.
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
Volume 9—OEM—Original Equipment Manufacturer CA08100011E—March 2013 www.eaton.com
V9-T1-1
1.1
1
1
Circuit Protection
Circuit Breakers
Product Overview
Circuit Breaker Selection Guide
1
1
1
1
Description
1
General Applications
1
1
1
Series G
Molded Case Circuit Breaker
Universal
Molded Case Circuit Breakers
QUICKLAG® Type QC
Miniature Circuit Breakers
Page V9-T1-5
Page V9-T1-13
Page V9-T1-19
Line protection—molded case switch, motor circuit
protection (combination tested with Eaton starters
and contactors) thermal-magnetic and electronic
trip units.
Line protection—feeder and branch thermalmagnetic trip unit.
Used to provide branch circuit protection in
cable-in/out panel or DIN-Rail mount
applications.
Technical Data
Maximum current rating
2500A
600A
100A
Maximum voltage—AC
690 Vac
480 Vac
240 Vac
Maximum voltage—DC
250 Vdc
250 Vdc
80 Vdc
Poles
1, 2, 3, 4
1, 2, 3
QC = 1, 2, 3, 4
QCD = 1, 2, 3
QCR/QCF = 1, 2, 3
1
Max. interrupting capacities
Three-pole at 240V
E = 200 kA
J = 200 kA
L = 200 kA
Three-pole at 480V
E = 100 kA
J = 200 kA
L = 200 kA
Three-pole at 240V
G = 25 kA (480/277)
F = 25 kA
J = 35 kA
K = 35 kA
L = 35 kA
Three-pole at 480V
GI = 14 kA (480/277)
GD = 22 kA
F = 14 kA
J = 20 kA
K = 20 kA
L = 20 kA
65 kA at 240 Vac
5 kA at 80 Vdc
1
See individual catalogs for
limitations and back-up
protection requirements.
UL® 489
IEC 60947-2
CE
CSA®
KEMA-KEUR
CCC
UL 489CE
IEC 60947-2
CE
CSA
UL 489
CSA 22.2
1
1
1
1
Approvals
1
1
Environmental Data
Humidity
Non-condensing 100% relative humidity
Non-condensing 100% relative humidity
—
1
Shock
—
—
—
Vibration
—
—
—
1
Operating temperature
–20° to 70°C (–4° to 158°F) derating applies
–20° to 70°C (–4° to 158°F) derating applies
40°C (104°F)
Dielectric strength
Below 250A 6 kV
Above 250A 8 kV
Below 250A 6 kV
Above 250A 8 kV
1960 Vac (acc. to UL 489)
1
1
1
Insulation resistance
750 Vac
750 Vac
—
Endurance/life
250A: EG, JG = 8,000 operations
630A: LG = 6,000 operations
250A: Gi = 10,000 operations
Fi = 8,000 operations
400A: Ji, Ki, Li = 6,000 operations
>10,000 operations
Approximate weight
E Three-pole—2.88 lbs (1.04 kg)
J Three-pole—5.06 lbs (2.30 kg)
L Three-pole—12.36 lbs (5.61 kg)
G Three-pole—2.10 lbs (0.95 kg)
F Three-pole—4.5 lbs (2.0 kg)
J Three-pole—12.50 lbs (5.7 kg)
K Three-pole—11.50 lbs (5.2 kg)
QC
Mounting configuration
Backpan, plug-in adapter, DIN-rail (E)
Backpan, DIN-rail (G)
Panel mount, front mount, 35 mm DIN-rail
mountable
1
1
1
1
1
1
Single-pole—0.36 lbs (162.8 g)
Two-pole—0.61 lbs (274.9 g)
Three-pole—1.14 lbs (518.3 g)
QCD Single-pole—0.43 lbs (195.3 g)
Two-pole—0.89 lbs (401.9 g)
Three-pole—1.34 lbs (605.6 g)
QCR Single-pole—0.22 lbs (97.9 g)
Two-pole—0.48 lbs (215.8 g)
Three-pole—0.70 lbs (315.6 g)
QCF Single-pole—0.24 lbs (109.9 g)
Two-pole—0.50 lbs (225.2 g)
Three-pole—0.74 lbs (335.1 g)
For our complete product offering, see Volume 4—Circuit Protection, CA08100005E.
1
V9-T1-2
Volume 9—OEM—Original Equipment Manufacturer CA08100011E—March 2013 www.eaton.com
Circuit Protection
Circuit Breakers
1.1
Circuit Breaker Selection Guide, continued
1
1
1
1
Description
WMZ UL 489
Miniature Circuit Breakers
WMZS UL 1077
Miniature Circuit Breakers—
Supplementary Protectors
1
Page V9-T1-25
Page V9-T1-27
1
Used to provide branch circuit protection in cablein/out DIN-Rail mount applications.
Used to provide overcurrent protection where
branch protection (for example UL 489 MCCB) is
already provided or not required. Replacement for
fuses used as supplementary protectors.
40A
63A
General Applications
1
1
1
Technical Data
Maximum current rating
Maximum voltage—AC
480/277 Vac (240/415 Vac IEC)
480/277 Vac
Maximum voltage—DC
48 Vdc
65 Vac Single-pole
130 Vac Two-pole
Poles
1, 2, 3
1, 2, 3
Max. interrupting capacities
10 kA UL/CSA;
15 kA IEC/EN 60947-2
IEC
240/415V 10 kA
UL/CSA 120V 10 kA
240V 10 kA
277V 6 kA
480V 6 kA
See individual catalogs for limitations
and back-up protection requirements.
1
1
1
1
1
Approvals
UL 489
CE; IEC/EN 60947-2
CSA 22.2
UL 1077
CE; IEC/EN 60947-2; IEC/EN 60898
CSA 22.2 235
Humidity
Acc. IEC 60068-2 (25° to 55°C/
77° to 131°F, 90–95% RH)
—
Shock
Acc. IEC 60068-2-27
(40g half sine wave for 10 ms—3 axes)
(15g half sine wave for 20 ms—3 axes)
—
Vibration
Acc. to IEC 60068-2-6
5–100 Hz/1.0 mm/0.7g (3 axes)
—
1
Operating temperature
30°C (86°F)
—
Dielectric strength
1960 Vac (acc. to UL 489)
—
1
1
1
Environmental Data
Insulation resistance
100M ohms at 500 Vdc
—
Endurance/life
>20,000 operations
—
Approximate weight
Single-pole—0.27 lbs (121.0g)
Two-pole—0.53 lbs (242.0g)
Three-pole—0.80 lbs (363.0g)
Single-pole—0.26 lbs (120.0g)
Two-pole—0.54 lbs (244.9g)
Three-pole—0.83 lbs (376.5g)
Mounting contribution
35 mm DIN rail mountable
35 mm DIN rail mountable
1
1
1
1
1
1
For our complete product offering, see Volume 4—Circuit Protection, CA08100005E.
1
1
1
1
1
1
Volume 9—OEM—Original Equipment Manufacturer CA08100011E—March 2013 www.eaton.com
V9-T1-3
1.1
1
Circuit Protection
Circuit Breakers
Circuit Breaker Selection Guide, continued
1
1
1
1
1
1
Description
Magnum
Low Voltage Power Breakers
Page V9-T1-29
Page V9-T1-32
Solution for where space is at a premium or when
equipment dimensions are critical when upgrading
or retrofitting current systems. Offering the power
and performance of a power breaker in the compact
size of a molded case breaker. With its reduced
weight and compact dimensions, you can mount
two times as many feeder breakers and reduce the
overall enclosure density up to 50%.
Enables comprehensive solutions to meet and
exceed the unique and wide-ranging requirements
of today’s global power distribution systems.
Designed and engineered for ultimate custom
configuration and application flexibility in metal
enclosed switchgear and power distribution
enclosures.
General Applications
1
1
1
1
Series NRX
Low Voltage Power Breakers
Technical Data
Maximum current rating
630–1600A
800–6300A
1
Maximum voltage—AC
220–690 Vac
Up to 690 Vac
Maximum voltage—DC
—
—
1
Poles
3, 4
3, 4
Max. interrupting capacities
65 kAIC at 480 Vac
Max. withstand capacities 42 kAIC
200 kA at 480 Vac
Max. withstand capacities
100 kAIC
CL fuseless 200 kA at 635 Vac with integral limiters
UL 1006 Component
UL 489 Component
IEC 60947-2
UL 1066
IEC 60947-2
KEMA
1
See individual catalogs for limitations
and back-up protection requirements.
1
Approvals
1
1
1
1
1
1
1
Environmental Data
Humidity
—
—
Shock
—
—
Vibration
—
—
Operating temperature
–25° to 70°C
–25° to 70°C
Dielectric strength
—
—
Insulation resistance
—
—
Endurance/life
10,000 electrical operations
20,000 mechanical operations
—
Approximate weight
Three-pole breaker + cassette—85 lbs (39 kg)
Three-pole breaker—53 lbs (24 kg)
Four-pole breaker + cassette—104 lbs (47 kg)
Four-pole breaker—67 lbs (30 kg)
—
Mounting configuration
Rear-connected, front-connected,
surface mounting, mounting bracket,
fixed, drawout breaker with cassette
Fixed or drawout with cassette rear-connected, frontconnected
1
1
1
1
For our complete product offering, see Volume 4—Circuit Protection, CA08100005E.
1
1
1
1
V9-T1-4
Volume 9—OEM—Original Equipment Manufacturer CA08100011E—March 2013 www.eaton.com
Circuit Protection
Circuit Breakers
1.1
Features
Series G Molded Case Circuit Breakers
●
●
●
●
●
●
1
Field-fit accessories
Common accessories through 630A
Space-saving footprint
High-performance current limiting designs up to
200 kAIC at 480V
Global ready: UL, CSA, CE, IEC, KEMA-KEUR listings
Complete breaker includes frame, trip unit, standard
terminals and mounting hardware
1
1
1
1
1
1
1
1
Catalog Number Selection
Series G® Molded Case Circuit Breakers
1
EG Frame
1
1
E G H 3 015 FF G
Frame
E
Number of Poles
Standard/Application
G = IEC/CE/UL/CSA
B
E
S
H
C
K
Performance
600Y/347
480
415
—
18
18
18
25
25
22
35
40
25
65
70
35
100
100
Molded case switch 1
240
25
35
85
100
200
1 = One
2 = Two
3 = Three
4 = Four—Neutral 0% Protected
7 = Four—Neutral 100% Protected
Amperes
016 2
015
020
025
030
032 2
035
040
045
050
060
063 2
070
080
090
100
110
125
1
Terminations/Hardware
Terminals
Mounting Hardware
M = Metric end caps
Metric
E = Imperial end caps
Imperial
G = Line/load standard
Metric
B = Bolt-on
—
1
1
1
Trip Unit
FF = Fixed fixed
AF = Adjustable thermal
fixed magnetic
KS = Molded case switch
1
1
1
1
1
1
Notes
1 Available only as 125 and 160A sizes.
2 Is not UL rated.
1
1
1
1
1
1
1
1
Volume 9—OEM—Original Equipment Manufacturer CA08100011E—March 2013 www.eaton.com
V9-T1-5
1.1
1
Circuit Protection
Circuit Breakers
JG Frame
J G S 3 250 FA G C
1
1
Frame
Rating
Blank = 80% rated
C = 100% rated
J
1
Standard/Application
G = IEC/CE/UL/CSA
1
1
E
S
H
C
U
X
K
1
1
1
Performance
600
480
415
18
25
25
18
35
40
25
65
70
35
100
100
50
150
150
50
200
200
Molded case switch
Number of Poles
240
65
85
100
200
200
200
2 = Two
3 = Three
4 = Four—Neutral 0% protected
8 = Four—Neutral 0–60% protected
9 = Four—Neutral 100% protected
Amperes
050
070
080
090
100
125
150
160
175
200
225
250
1
1
1
L G S 3 600 FA G C
1
Frame
1
Rating
Blank = 80% rated
C = 100% rated
L
1
Standard/Application
G = IEC/CE/UL/CSA
1
1
E
S
H
C
U
X
K
1
1
1
Performance
600
480
415
18
35
35
25
50
50
35
65
70
50
100
100
65
150
150
65
200
200
Molded case switch
Number of Poles
240
65
85
100
200
200
200
3 = Three
4 = Four—Neutral 0% protected
6 = Four—Neutral 60% protected
7 = Four—Neutral 100% protected
8 = Four—Neutral 0–60% protected
9 = Four—Neutral 0–100 protected
1
1
1
Trip Unit
AA = Adjustable thermal
Adjustable magnetic
FA = Fixed thermal
Adjustable magnetic
KS = Molded case switch
33 = 310+ electronic LS
32 = 310+ electronic LSI
35 = 310+ electronic LSG
36 = 310+ electronic LSIG
NN = Frame only (no trip)
LG Frame
1
1
Terminations/Hardware
Terminals
Mounting Hardware
M = Metric end caps
Metric
E = Imperial end caps
Imperial
G = Line/load standard
Metric
Amperes
250
300
350
400
500
600
630
Terminations/Hardware
Terminals
Mounting Hardware
M = Metric end caps
Metric
Imperial
E = Imperial end caps
G = Line/load standard
Metric
W = Without terminals
—
Trip Unit 1
AA = Adjustable thermal
Adjustable magnetic
FA = Fixed thermal
Adjustable magnetic
KS = Molded case switch
33 = 310+ electronic LS
32 = 310+ electronic LSI
35 = 310+ electronic LSG
36 = 310+ electronic LSIG
38 = 310+ electronic ALSI
39 = 310+ electronic ALSIG
NN = Frame only (no trip)
Note
1 A = Arc reduction, L = Long, S = Short, I = Instantaneous, G = Ground.
1
1
1
1
1
V9-T1-6
Volume 9—OEM—Original Equipment Manufacturer CA08100011E—March 2013 www.eaton.com
Circuit Protection
Circuit Breakers
1.1
Product Selection
1
Series G Molded Case Circuit Breakers
1
Approximate Dimensions are in Inches
1
EG Frame
Maximum
Continuous
Amperes at 40°C 1
Three-Pole 3 W x 5.5 H x 2.99 D
Fixed Thermal
Fixed Magnetic
IC Rating: 25 kAIC at 415 and 480 Vac
Maximum
Continuous
Amperes at 40°C
Three-Pole 3 W x 5.5 H x 2.99 D
1
Fixed Thermal
Fixed Magnetic
1
IC Rating: 70 kAIC at 415 Vac, 65 kAIC at 480 Vac
15
EGE3015FFG
15
EGH3015FFG
20
EGE3020FFG
20
EGH3020FFG
25
EGE3025FFG
25
EGH3025FFG
30
EGE3030FFG
30
EGH3030FFG
35
EGE3035FFG
35
EGH3035FFG
40
EGE3040FFG
40
EGH3040FFG
45
EGE3045FFG
45
EGH3045FFG
50
EGE3050FFG
50
EGH3050FFG
60
EGE3060FFG
60
EGH3060FFG
70
EGE3070FFG
70
EGH3070FFG
80
EGE3080FFG
80
EGH3080FFG
90
EGE3090FFG
90
EGH3090FFG
100
EGE3100FFG
100
EGH3100FFG
125
EGE3125FFG
125
EGH3125FFG
1
1
1
1
1
1
1
1
1
JG Frame
Maximum
Continuous
Amperes
Three-Pole 4.13 W x 7 H x 3.57 D
Magnetic
Range
Fixed Thermal
Adjustable Magnetic
IC Rating: 25 kAIC at 415 and 480 Vac
Maximum
Continuous
Amperes
1
Three-Pole 4.13 W x 7 H x 3.57 D
Magnetic
Range
Fixed Thermal
Adjustable Magnetic
1
IC Rating: 70 kAIC at 415 Vac, 65 kAIC at 480 Vac
70
350–00
JGE3070FAG
70
350–700
JGH3070FAG
90
450–900
JGE3090FAG
90
450–900
JGH3090FAG
100
500–1000
JGE3100FAG
100
500–1000
JGH3100FAG
125
625–1250
JGE3125FAG
125
625–1250
JGH3125FAG
150
750–1550
JGE3150FAG
150
750–1550
JGH3150FAG
175
875–1750
JGE3175FAG
175
875–1750
JGH3175FAG
200
1000–2000
JGE3200FAG
200
1000–2000
JGH3200FAG
225
1125–2250
JGE3225FAG
225
1125–2250
JGH3225FAG
250
1250–2500
JGE3250FAG
250
1250–2500
JGH3250FAG
1
1
1
1
1
1
LG Frame
Ampere
Rating
Fixed Thermal
Adjustable Magnetic
Ampere
Rating
IC Rating: 35 kAIC at 415 and 480 Vac
1
Fixed Thermal
Adjustable Magnetic
1
IC Rating: 70 kAIC at 415 Vac, 65 kAIC at 480 Vac
LGE3250FAG
250
LGH3250FAG
300
LGE3300FAG
300
LGH3300FAG
350
LGE3350FAG
350
LGH3350FAG
400
LGE3400FAG
400
LGH3400FAG
500
LGE3500FAG
500
LGH3500FAG
600
LGE3600FAG
600
LGH3600FAG
250
1
Three-Pole 3 W x 5.5 H x 2.99 D
Three-Pole 5.48 W x 10.13 H x 4.09 D
1
1
1
1
Note
1 16, 32, 63A are not UL listed ratings.
1
Volume 9—OEM—Original Equipment Manufacturer CA08100011E—March 2013 www.eaton.com
V9-T1-7
1.1
1
Circuit Protection
Circuit Breakers
Features
Series G Motor Circuit Protector
●
1
●
●
1
●
Instantaneous only protector
Designed for use in combination with motor starters
Adjustable to motor FLA
UL recognized component, File E7819 motor circuit protectors
1
1
1
1
1
1
Product Selection
1
Series G Motor Circuit Protectors
1
EG Frame—480 Vac, 600Y/347 Vac Maximum
1
1
Continuous
Amperes
3
Cam
Setting
Motor Full Load
Current Amperes 1
MCP Trip
Setting 2
MCP
Catalog Number
Continuous
Amperes
Cam
Setting
Motor Full Load
Current Amperes 1
MCP Trip
Setting 2
MCP
Catalog Number
A
0.69–0.91
9
HMCPE003A0C
50
A
11.5–15.2
150
HMCPE050K2C
B
1.1–1.3
15
B
19.2–22.9
250
1
C
1.6–1.7
21
C
26.9–30.6
350
D
2.0–2.2
27
D
34.6–38.3
450
1
E
2.3–2.5
30
E
38.4–42.1
500
F
2.6–2.8
33
F
42.2–43.5
550
A
1.5–2.0
21
A
16.1–30.6
210
B
2.6–3.1
35
B
26.9–32.2
350
1
7
1
1
HMCPE007C0C
70
C
3.7–3.9
49
C
37.6–42.9
490
D
4.8–5.2
63
D
48.4–53.7
630
E
5.3–5.7
70
E
53.8–59.1
700
F
5.8–6.1
77
F
59.2–60.9
770
A
3.4–4.5
45
A
23.0–30.6
300
1
B
5.7–6.8
75
B
38.4–46.0
500
C
8.0–9.1
105
C
53.8–61.4
700
1
D
10.4–11.4
135
D
69.2–76.8
900
E
11.5–12.6
150
E
76.9–84.5
1000
1
F
12.7–13.0
165
F
84.6–87.0
1100
A
3.9–9.1
90
A
38.4–46.0
500
B
11.5–13.7
150
B
57.6–65.2
750
1
C
16.1–18.3
210
C
76.9–84.5
1000
D
20.7–22.9
270
D
3
1250
1
E
23.0–25.2
300
E
3
1375
F
25.3–26.1
330
F
3
1500
1
1
1
1
1
15
30
HMCPE015E0C
HMCPE030H1C
100
100
HMCPE070M2C
HMCPE100R3C
HMCPE100T3C
Notes
1 Motor FLA ranges are typical. The corresponding trip setting is at 13 times the minimum FLA value shown. Where a 13 times setting is required for an intermediate FLA value,
alternate cam settings and/or MCP ratings should be used.
2 For DC applications, actual trip levels are approximately 40% higher than values shown.
3 Settings above 10 x I are for special applications, where the ampere rating of the disconnecting means cannot be less than 115% of the motor full load ampere rating.
n
1
1
V9-T1-8
Volume 9—OEM—Original Equipment Manufacturer CA08100011E—March 2013 www.eaton.com
Circuit Protection
Circuit Breakers
1.1
JG Frame—600 Vac Maximum, 250 Vdc Maximum
Continuous
Amperes
MCP Trip Range
Amperes
MCP
Catalog Number
250
500–1000
HMCPJ250D5L
625–1250
HMCPJ250F5L
750–1500
HMCPJ250G5L
875–1750
HMCPJ250J5L
1000–2000
HMCPJ250K5L
1125–2250
HMCPJ250L5L
1250–2500
HMCPJ250W5L
1
1
1
1
1
1
LG Frame—600 Vac Maximum, 250 Vdc Maximum
1
Continuous
Amperes
MCP Trip Range
Amperes
MCP
Catalog Number
1
600
1250–2500
HMCPL600L6G
1500–3000
HMCPL600N6G
1
1750–3500
HMCPL600R6G
2000–4000
HMCPL600X6G
2250–4500
HMCPL600Y6G
2500–5000
HMCPL600P6G
3000–6000
HMCPL600M6G
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
Volume 9—OEM—Original Equipment Manufacturer CA08100011E—March 2013 www.eaton.com
V9-T1-9
1.1
1
Circuit Protection
Circuit Breakers
Features
Series G Motor Protector Breakers
●
1
●
1
●
1
1
●
●
1
●
Eliminates need for separate overload relay
Can be used with contactor to eliminate need for overload
relay and still create manual motor control
Meets requirement for motor branch protection, including:
●
Disconnecting means
●
Branch circuit short circuit protection
●
Overload protection
UL 489 listed, IEC60947-02 rated
Phase unbalance, phase loss protection and high load alarm
Optional pre-detection trip relay
1
1
1
1
Product Selection
Series G Motor Protector Breakers
1
For pre-trip alarm option, order Style Number 5721B31G02.
1
JG Frame Motor Protector Circuit Breakers,
250A Maximum Rated Current
1
Continuous
Amperes
35 kAIC
Catalog Number
65 kAIC
Catalog Number
1
50
JGMPS050G
JGMPH050G
100
JGMPS100G
JGMPH100G
1
160
JGMPS160G
JGMPH160G
250
JGMPS250G
JGMPH250G
1
1
1
1
1
1
1
LG Frame Motor Protector Circuit Breakers,
630A Maximum Rated Current
Continuous
Amperes
50 kAIC
Catalog Number
65 kAIC
Catalog Number
250
LGMPS250G
LGMPH250G
400
LGMPS400G
LGMPH400G
600
LGMPS600G
LGMPH600G
630 1
LGMPS630G
LGMPH630G
Note
1 630A is not a UL listed rating. 600A is the maximum UL or CSA rating for LG breaker.
1
1
1
1
1
1
1
1
V9-T1-10
Volume 9—OEM—Original Equipment Manufacturer CA08100011E—March 2013 www.eaton.com
1.1
Circuit Protection
Circuit Breakers
Accessories
1
Field Fit Kit Catalog Numbers
Description
Alarm Lockout
Pole Location
Terminal Shields
Frame—
EG, JG and LG
Alarm Lockout
Auxiliary Switch
Line
3
EG
EFTS3K
Right
ALM1M1BEPK 1
Line
4
EG
EFTS4K
2 make/2 break
Right
ALM2M2BEPK 2
Line or load
2, 3
JG
FJTS3K
Line or load
4
JG
FJTS4K
1
Right
AUX1A1BPK
Number of Poles
Frame
Catalog Number
2A, 2B
Right
AUX2A2BPK
3 or 4
EG
EIPBK
3
JG
FJIPBK
4
JG
FJIPBK4
3 or 4
LG
IPB3
1
1
Flex Shaft Handles
120 Vac
Left
SNT120CPK 4
240 Vac
Left
SNT120CPK 4
1
Flex Shaft Handle Mechanisms
Flexible Shaft Length in ft (m)
Breaker Frame
4 (1.2)
Catalog Number
7 (2.1)
Catalog Number
12 Vdc
Left
SNT012CPK
24 Vdc
Left
SNT060CPK
EG
EHMFS04
EHMFS07
JHMFS04
JHMFS07
LHMFS04
LHMFS07
48 Vdc
Left
SNT060CPK
JG
380–600 Vac
Left
SNT480CPK 5
LG
1
1
Left
UVR120APK
208–240 Vac
Left
UVR240APK
24 Vac
Left
UVR024APK
24 Vdc
Left
UVR024DPK
48–60 Vdc
Left
UVR048DPK
12 Vac/Vdc
Left
UVR012CPK
48–60 Vac
Left
UVR048APK
120 Vdc
Left
UVR125DPK
220–250 Vdc
Left
UVR250DPK
Frame
380–500 Vac
Left
UVR480APK
Black Handle Color
525–600 Vac
Left
UVR600APK
EG
EHMCCBI
EHMCCB
JG
JHMCCBI
JHMCCB
LG
LHMCCBI
LHMCCB
Multiwire Connectors Ordering Information (Package of 3)
High SCCR ratings are available for Power Distribution blocks
with Series G MCCBs. See Tab 63.
Maximum
Amperes
Wires per
Terminal
Wire Size Range
AWG Cu
Frame
Kit
Catalog Number
125
3
14–2
EG
3TA125E3K
125
6
14–6
EG
3TA125E6K
250
3
14–2
JG
3TA250FJ3
250
6
14–6
JG
3TA250FJ6
1
1
Undervoltage Release Mechanism
110–127 Vac
1
1
AUXALRMEPK 3
Shunt Trip—Standard
1
1
1A, 1B
Right
1
1
Interphase Barriers (Package of 2)
Auxiliary Switch
—
Undervoltage Release
Mechanism
Frame
IP30 Protection
Catalog Number
Make/break
Auxiliary Switch/Alarm Lockout
Shunt Trip
Location
Number
of Poles
1
1
1
Universal Direct
Handle Mechanism
Universal Direct Handle Mechanisms
With Interlock
Catalog Number
Without Interlock
Catalog Number
EHMCCRI
EHMCCR
JG
JHMCCRI
JHMCCR
LG
LHMCCRI
LHMCCR
1
1
1
1
Red Handle Color
EG
1
1
1
1
Notes
1 Part number for JG and LG is ALM1M1BJPK.
2 Part number for JG and LG is ALM2M2BJPK.
3 Part number for JG and LG is AUXALRMJPK.
4 110–125 Vdc, 50/60 Hz.
5 380–600 Vdc, 50/60 Hz.
1
1
1
1
Volume 9—OEM—Original Equipment Manufacturer CA08100011E—March 2013 www.eaton.com
V9-T1-11
1.1
1
Rotary Handle
Mechanisms
1
Circuit Protection
Circuit Breakers
High Performance Rotary Handle Mechanisms (Complete Kit Includes Handle, Shaft and Mechanism)
Color
Rating Type
UL
IP
EG Frame 1
Catalog Number
JG Frame
Catalog Number
LG Frame
Catalog Number
Black/blue
1/12/3R
20/54/55
EGHMVD06B
JGHMVD06B
LGHMVD06B
EGHMVD12B
JGHMVD12B
LGHMVD12B
EGHMVD24B
JGHMVD24B
LGHMVD24B
EGHMVD06R
JGHMVD06R
LGHMVD06R
EGHMVD12R
JGHMVD12R
LGHMVD12R
EGHMVD24R
JGHMVD24R
LGHMVD24R
EGHMVD06BX
JGHMVD06BX
LGHMVD06BX
EGHMVD12BX
JGHMVD12BX
LGHMVD12BX
EGHMVD24BX
JGHMVD24BX
LGHMVD24BX
EGHMVD06RX
JGHMVD06RX
LGHMVD06RX
EGHMVD12RX
JGHMVD12RX
LGHMVD12RX
EGHMVD24RX
JGHMVD24RX
LGHMVD24RX
1
1
Red/yellow
1/12/3R
20/54/55
1
Black/blue
1
1
Red/yellow
4/4X
4/4X
66
66
1
1
1
1
1
1
External Accessories
1
Description
Fit Type
Frame
EG
JG
LG
Non-padlockable handle block
Field
EFHB
—
—
1
Padlockable handle block
Field
EFPHB
—
—
Padlockable handle block off-only
Field
EFPHBOFF
FJPHBOFF
LBHPOFF
1
Padlockable handle lock hasp
Field
EFPHL
FJPHL
LPHL
Padlockable handle lock hasp off-only
Field
EFPHLOFF
FJPHLOFF
LPHLOFF
Kirk key interlock kit 23
Field
—
KYKJG
KYKLG
1
Castell key interlock kit 34
Field
—
CTKJG
CTKLG
Slide bar interlock 5
Field
EFSBI
FJSBI
LGSBI
1
Walking beam interlock
1
Electrical operator
1
1
1
1
1
1
Three-pole
EG3WBI
JG3WBI
LG3WBI
Four-pole
EG4WBI
JG4WBI
LG4WBI
120/240 Vac
MOPEG240C
MOPJG240C
MOPLG240C
125 Vdc
MOPEG240C
MOPJG240C
MOPLG240C
Plug-in adapters
Three-pole
PAD3E
PAD3J
PAD3L
Four-pole
PAD4E
PAD4J
PAD4L
Rear connecting studs
Field
EFRCSDL
FJRCSDL
3P–LRCS3WK
EFRCSDS
FJRCSDS
4P–LRCS4WK
EFRCSWL
FJRCSWL
—
EFRCSWS
FJRCSWS
—
Notes
1 Compatible with three-pole and four-pole EG breakers only.
2 Provision only.
3 See Volume 4—Circuit Protection, CA08100005E, Tab 25, for bolt projection dimensions.
4 Castell bolt mounting hole must be 10 mm.
5 Requires two breakers.
1
1
1
1
1
V9-T1-12
Volume 9—OEM—Original Equipment Manufacturer CA08100011E—March 2013 www.eaton.com
Circuit Protection
Circuit Breakers
1.1
Features
Universal Molded Case Circuit Breakers
●
●
●
●
●
1
Universal design for both NEMA® (UL 489) and
IEC (IEC 947-2) standards
Suitable for 50°C application
Factory-sealed thermal magnetic trip unit
Standard interrupting ratings
Includes mounting hardware and terminals
1
1
1
1
1
1
1
1
Catalog Number Selection
Universal Molded Case Circuit Breakers
1
Universal Molded Case
1
Gi 2 070
Frame Size
Gi = Gi Frame
Fi = Fi Frame
Ji = Ji Frame
Ki = Ki Frame
Li = Li Frame
1
1
1
Number of Poles
Gi Frame
Fi Frame
Ji Frame
Ki Frame
Li Frame
1 = Single-pole 2 = Two-pole 3 = Three-pole 3 = Three-pole 3 = Three-pole
2 = Two-pole
3 = Three-pole
3 = Three-pole
Gi Frame
015 = 15 amp
020 = 20 amp
030 = 30 amp
040 = 40 amp
050 = 50 amp
060 = 60 amp
070 = 70 amp
080 = 80 amp
100 = 100 amp
125 = 125 amp
Fi Frame
015 = 15 amp
020 = 20 amp
030 = 30 amp
040 = 40 amp
050 = 50 amp
060 = 60 amp
070 = 70 amp
080 = 80 amp
100 = 100 amp
125 = 125 amp
150 = 150 amp
160 = 160 amp
175 = 175 amp
200 = 200 amp
225 = 225 amp
Ampere Rating
Ji Frame
Ki Frame
250 = 250 amp 300 = 300 amp
350 = 350 amp
400 = 400 amp
Li Frame
500 = 500 amp
600 = 600 amp
630 = 630 amp
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
Volume 9—OEM—Original Equipment Manufacturer CA08100011E—March 2013 www.eaton.com
V9-T1-13
1.1
1
1
Circuit Protection
Circuit Breakers
Product Selection
Universal Molded Case Circuit Breakers
Three-Pole
1
Approximate Dimensions are in Inches
1
Universal G Frame
1
1
1
1
Universal J Frame
Description
Amperes
Catalog
Number 1
3 W x 4-7/8 H x 2-13/16 D (optional DIN-Rail kit available
catalog number GDIN, package of ten)
15
Gi3015
20
Gi3020
25
Gi3025
Voltage
Interrupting Rating
Description
4-1/8 W x 10 H x 4-1/16 D
Voltage
Interrupting Rating
30
Gi3030
415
25/13K
380–415
18/5K
35
Gi3035
480
20K
480/277
14K
40
Gi3040
45
Gi3045
50
Gi3050
60
Gi3060
1
1
1
Universal F Frame
1
Description
Amperes
Catalog
Number 1
4-1/8 W x 6 H x 3-3/8 D
15
Fi3015L
20
Fi3020L
1
5-1/2 W x 10-1/8 H x 4-1/16 D
Voltage
Interrupting Rating
415
25/13K
480
20K
Voltage
Interrupting Rating
30
Fi3030L
415
18/9K
35
Fi3035L
20K
40
Fi3040L
50
Fi3050L
1
60
Fi3060L
70
Fi3070L
Description
1
80
Fi3080L
8-1/4 W x 10-3/4 H x 4.37 D
90
Fi3090L
100
Fi3100L
Voltage
Interrupting Rating
1
125
Fi3125L
415
25/13K
150
Fi3150L
480
20K
1
175
Fi3175L
200
Fi3200L
225
Fi3225L
1
1
480
1
1
225
Ji3225L
250
Ji3250L
Amperes
Catalog
Number 1
300
Ki3300L
350
Ki3350L
400
Ki3400L
Amperes
Catalog
Number 1
500
Li3500
600
Li3600
Universal L Frame
Note
1 Metric mounting hardware.
1
1
1
1
1
1
1
1
V9-T1-14
Catalog
Number 1
Universal K Frame
Description
1
Amperes
Volume 9—OEM—Original Equipment Manufacturer CA08100011E—March 2013 www.eaton.com
1.1
Circuit Protection
Circuit Breakers
Accessories
1
Internal Accessories
Auxiliary Switch (Right-Pole Mounted)
Bell Alarm (Right-Pole Mounted)
Shunt Trip (Left-Pole Mounted)
1
UVR (Left-Pole Mounted)
1
1
Add This Suffix to
Catalog Number
Configuration
Add This Suffix to
Catalog Number
1NO/1NC
A3
1 make/1 break
B3
2NO/2NC
A6
Configuration
Voltage Range
Add This Suffix to
Catalog Number
Voltage Range
Add This Suffix to
Catalog Number
Universal G Frame
If both an auxiliary switch and bell alarm are required, add B13 to
the catalog number (right-pole mounted). Auxiliary switch and
bell alarm are 240V rated.
1NO/1NC
A06
A13
1 make/1 break
B06
If both an auxiliary switch and bell alarm are required, add C05 to
the catalog number (right-pole mounted). Auxiliary switch and
bell alarm are 600V rated.
24 Vac
S7
24 Vac 50/60 Hz
T2
S1
48 Vac 50/60 Hz
T3
240 Vac
S2
60 Vac 50/60 Hz
T4
12 Vdc
S3
120 Vac 50/60 Hz
T1
24 Vdc
S4
240 Vac 50/60 Hz
T8
220 Vac 50 Hz
T7
440 Vac 50 Hz
T11
480 Vac 60 Hz
T12
1
1
1
1
1
1
12–24 Vac/Vdc
S02
12 Vac
U02
48–127 Vac or
48–60 Vdc
S06
24 Vac
U06
48 Vac/Vdc
U38
208–380 Vac or
110–127 Vdc
S10
110–127 Vac
U14
208–240 Vac
U18
415–600 Vac or
220–250 Vdc
S14
380–480 Vac
U22
525–600 Vac
U26
12 Vdc
U30
24 Vdc
U34
125 Vdc
U42
220–250 Vdc
U46
1
1
1
1
1
1
1
Universal J Frame
1NO/1NC
A06
2 NO/2NC
A13
1 make/1 break
If both an auxiliary switch and bell alarm are required, add CO5 to
the catalog number (right-pole mounted). Auxiliary switch and
bell alarm are 600V rated.
B06
1
120 Vac
Universal F Frame
2NO/2NC
1
12–24 Vac/Vdc
S42
12 Vac
U06
48–60 Vac/Vdc
S50
24 Vac
U10
110–240 Vac or
110–125 Vdc
S10
48–60 Vac
U14
110–127 Vac
U18
380–440 Vac or
220–50 Vdc
S14
208–240 Vac
U22
380–480 Vac
U26
480–600 Vac
S18
12 Vdc
T02
24 Vdc
T06
48–60 Vdc
T10
110–125 Vdc
T14
220–250 Vdc
T18
1
1
1
1
1
1
1
1
1
1
1
Volume 9—OEM—Original Equipment Manufacturer CA08100011E—March 2013 www.eaton.com
V9-T1-15
1.1
1
Circuit Protection
Circuit Breakers
Internal Accessories, continued
Auxiliary Switch (Right-Pole Mounted)
Bell Alarm (Right-Pole Mounted)
Shunt Trip (Left-Pole Mounted)
UVR (Left-Pole Mounted)
1
1
1
Configuration
Add This Suffix to
Catalog Number
Configuration
Add This Suffix to
Catalog Number
1 make/1 break
B06
1
Universal K Frame
1
1NO/1NC
A06
2NO/2NC
A13
1
1
If both an auxiliary switch and bell alarm are required, add CO5 to
the catalog number (right-pole mounted). Auxiliary switch and
bell alarm are 600V rated.
1
Voltage Range
Add This Suffix to
Catalog Number
12–24 Vac/Vdc
S42
12 Vac
U06
S50
24 Vac
U10
110–240 Vac or
110–125 Vdc
S10
48–60 Vac
U14
110–127 Vac
U18
380–440 Vac or
220–250 Vdc
S14
208–240 Vac
U22
380–480 Vac
U26
480–600 Vac
S18
12 Vdc
T02
24 Vdc
T06
48–60 Vdc
T10
110–125 Vdc
T14
220–250 Vdc
T18
1
Universal L Frame
1
1NO/1NC
A06
2NO/2NC
A13
1
1
1 make/1 break
If both an auxiliary switch and bell alarm are required, add CO5 to
the catalog number (right-pole mounted). Auxiliary switch and
bell alarm are 600V rated.
1
1
1
1
B06
12–24 Vac/Vdc
S02
12 Vac
U06
48–60 Vdc
S06
24 Vac
U10
48–60 Vac
S86
48–60 Vac
U14
110–240 Vac
S10
110–127 Vac
U18
110–125 Vdc
S42
208–240 Vac
U22
380–440 Vac or
220–250 Vdc
S14
380–480 Vac
U26
12 Vdc
T02
480–600 Vac
S18
24 Vdc
T06
48–60 Vdc
T10
110–125 Vdc
T14
220–250 Vdc
T18
1
1
1
1
1
1
1
1
1
1
1
V9-T1-16
Add This Suffix to
Catalog Number
48–60 Vac/Vdc
1
1
Voltage Range
Volume 9—OEM—Original Equipment Manufacturer CA08100011E—March 2013 www.eaton.com
Circuit Protection
Circuit Breakers
Handle Mechanisms
1.1
Handle Mechanisms
1
Type 1/12 Universal Rotary
Ordering Information
1
Shaft Length
in Inches (mm)
Handle
Color
Complete
Catalog Number
Flange Flex Shaft
Type 1, 3R, 12 Versions
6 (152.4)
Black
GHMVD06B
3-ft length; order F0S03C
12 (304.8)
Black
GHMVD12B
4-ft length; order F0S04C
6 (152.4)
Red
GHMVD06R
5-ft length; order F0S05C
12 (304.8)
Red
GHMVD12R
6-ft length; order F0S06C
6 (152.4)
Black
FHMVD06B
3-ft length; order F1S03C
12 (304.8)
Black
FHMVD12B
4-ft length; order F1S04C
6 (152.4)
Red
FHMVD06R
5-ft length; order F1S05C
12 (304.8)
Red
FHMVD12R
6-ft length; order F1S06C
1
1
Universal G Frame
1
1
1
Universal F Frame
1
1
1
7-ft length; order F1S07C
8-ft length; order F1S08C
1
9-ft length; order F1S09C
10-ft length; order F1S10C
1
1
Universal J Frame
6 (152.4)
Black
JHMVD06B
3-ft length; order F2S03C
12 (304.8)
Black
JHMVD12B
4-ft length; order F2S04C
6 (152.4)
Red
JHMVD06R
5-ft length; order F2S05C
12 (304.8)
Red
JHMVD12R
6-ft length; order F2S06C
1
1
7-ft length; order F2S07C
8-ft length; order F2S08C
1
9-ft length; order F2S09C
10-ft length; order F2S10C
1
1
Universal K Frame
6 (152.4)
Black
KHMVD06B
3-ft length; order F3S03C
12 (304.8)
Black
KHMVD12B
4-ft length; order F3S04C
6 (152.4)
Red
KHMVD06R
5-ft length; order F3S05C
12 (304.8)
Red
KHMVD12R
6-ft length; order F3S06C
1
1
7-ft length; order F3S07C
1
8-ft length; order F3S08C
9-ft length; order F3S09C
1
10-ft length; order F3S10C
1
Note
1 Only available as complete handle mechanism. Parts not sold separately.
1
1
1
1
1
1
1
1
Volume 9—OEM—Original Equipment Manufacturer CA08100011E—March 2013 www.eaton.com
V9-T1-17
1.1
1
1
Circuit Protection
Circuit Breakers
Terminals and Termination Accessory Devices
Terminal/Termination
Devices
1
1
Universal G Frame
Terminals (Included with Breaker)
Optional Multiwire Lugs (Load End Only)
15–20 A
25–100A
Three-Hole Version
Six-Hole Version
14–2 AWG Cu/Al
10–1/0 AWG Cu/Al
2.5–4 mm2 Cu/Al
4–50 mm2 Cu/Al
(3) 14–2 AWG
Order 3TA100G3K
(6) 14–6 AWG
Order 3TA100G6K
1
1
1
1
1
Universal F Frame
1
Terminals (Included with Breaker)
10–20A
25–100A
110–225A
Three-Hole Version
Six-Hole Version
1
14–10 AWG Cu/Al
14–1/0 AWG Cu/Al
4–4/0 AWG Cu/Al
2.5–4 mm2 Cu/Al
2.5–50 mm2 Cu/Al
25–95 mm2 Cu/Al
(3) 14–2 AWG
Order 3TA150F3K
(6) 14–6 AWG
Order 3TA150F6K
1
1
Optional Multiwire Lugs (Load End Only)
Universal J Frame
1
1
Terminals (Included with Breaker)
Optional Multiwire Lugs (Load End Only)
70–250A
Three-Hole Version
Six-Hole Version
4–350 MCM AWG Cu/Al
(3) 14–2 AWG
Order 3TA250J3K
(6) 14–6 AWG
Order 3TA250J6K
25–150 mm2 Cu/Al
1
1
Universal K Frame
Terminals (Included with Breaker)
Optional Multiwire Lugs (Load End Only)
1
300–350A
400A
Three-Hole Version
Six-Hole Version
250–500 MCM AWG Cu/Al
3/0–200 (2) AWG Cu/Al
1
120–240 mm2 Cu/Al
95–120 mm2 Cu/Al
(3) 12–2/0 AWG
Order 3TA400K3K
(6) 14–2/0 AWG
Order 3TA400K6K
1
Universal L Frame
1
1
1
Terminals (Included with Breaker)
Optional Multiwire Lugs (Load End Only)
500A
600A
Three-Hole Version
Six-Hole Version
(2) 250–300 MCM Cu/Al
(2) 400–500 MCM Cu/Al
—
—
120–150 mm2 Cu/Al
185–250 mm2 Cu/Al
1
1
1
1
1
1
1
V9-T1-18
Volume 9—OEM—Original Equipment Manufacturer CA08100011E—March 2013 www.eaton.com
Circuit Protection
Circuit Breakers
1.1
Features
QUICKLAG Type QC Miniature Circuit Breakers—Cable-In/Cable-Out Type QC
1
For Cable-In/Cable-Out Panel Mount Applications
●
●
●
●
1
Single-, two-, three- and four-pole options
Built and listed to UL 489
All products UL and CSA listed
All products 10–100A are HACR rated
1
1
1
1
1
1
1
Catalog Number Selection
QUICKLAG Type QC Miniature Circuit Breakers—Cable-In/Cable-Out Type QC
1
Type QC Miniature Circuit Breakers
1
1
QC 3 020 H
Ampere Rating
QC = QC breaker
Number of Poles
1 = Single-pole
2 = Two-pole
3 = Three-pole
4 = Four-pole
010
015
020
025
030
035
040
045
Ampere Rating
= 10 amp
050 = 50 amp
= 15 amp
055 = 55 amp
= 20 amp
060 = 60 amp
= 25 amp
070 = 70 amp
= 30 amp
080 = 80 amp
= 35 amp
090 = 90 amp
= 40 amp
100 = 100 amp
= 45 amp
1
Construction
H = 240V (two-, threeand four-pole only)
1
1
1
1
1
Product Selection
1
QUICKLAG Type QC 10,000 Ampere I.C. Thermal-Magnetic Breakers
Note: For non-automatic switches, see Volume 4—Circuit Protection, CA08100005E, Tab 24.
Continuous Ampere
Rating at 40ºC
Single-Pole, 120/240 Vac
Catalog Number
Two-Pole, 120/240 Vac
Catalog Number
Three-Pole, 240 Vac
Catalog Number
10
QC1010
QC2010
—
15
QC1015 12
QC2015
QC3015H
20
QC1020 12
QC2020
QC3020H
30
QC1030
QC2030
QC3030H
40
QC1040
QC2040
QC3040H
50
QC1050
QC2050
QC3050H
60
—
QC2060
QC3060H
70
—
QC2070
QC3070H
100
QC1100
QC2100
QC3100H
1
1
1
1
1
1
1
Notes
1 Switching duty rated for 120 Vac fluorescent light applications only.
2 For special low-magnetic breaker, order QC1015L1 or QC1020L1.
1
1
1
1
Volume 9—OEM—Original Equipment Manufacturer CA08100011E—March 2013 www.eaton.com
V9-T1-19
1.1
1
Circuit Protection
Circuit Breakers
Features
QUICKLAG Type QC Miniature Circuit Breakers—Cable-In/Cable-Out Type QCD
For Cable-In/Cable-Out DIN-Rail Mount HVAC Applications
1
●
●
1
●
1
●
1
●
●
Single-, two- and three-pole options
Modular construction
DIN mounted (symmetrical rail 35 in x 7.5 in DIN/EN 50 022)
Flexible power feed connection: wire size, position
Same breaker size for entire rating range
Field-mountable accessories: finger-shroud proof, quick
connect terminals, jumper units
1
1
1
1
1
Catalog Number Selection
QUICKLAG Type QC Miniature Circuit Breakers—Cable-In/Cable-Out Type QCD
1
QCD 3 020 H
1
Breaker Type
QCD = QCD breaker
1
1
Number of Poles
1 = Single-pole
2 = Two-pole
3 = Three-pole
1
1
1
1
010
015
020
025
030
035
040
045
Ampere Rating
= 10 amp
050 = 50 amp
= 15 amp
055 = 55 amp
= 20 amp
060 = 60 amp
= 25 amp
070 = 70 amp
= 30 amp
080 = 80 amp
= 35 amp
090 = 90 amp
= 40 amp
100 = 100 amp
= 45 amp
Product Selection
QUICKLAG Type QCD 10,000 Ampere I.C. Thermal-Magnetic Breakers
1
Continuous Ampere
Rating at 40ºC
Single-Pole, 120/240 Vac
Catalog Number
Two-Pole, 120/240 Vac
Catalog Number
Three-Pole, 240 Vac
Catalog Number
1
10
QCD1010
QCD2010
—
15
QCD1015
QCD2015
QCD3015H
1
20
QCD1020
QCD2020
QCD3020H
1
30
QCD1030
QCD2030
QCD3030H
40
QCD1040
QCD2040
QCD3040H
1
50
QCD1050
QCD2050
QCD3050H
60
QCD1060
QCD2060
QCD3060H
1
70
—
QCD2070
QCD3070H
100
—
QCD2100
QCD3100H
1
Construction
H = 240V (two- and
three-pole only)
1
1
1
1
1
V9-T1-20
Volume 9—OEM—Original Equipment Manufacturer CA08100011E—March 2013 www.eaton.com
1.1
Circuit Protection
Circuit Breakers
Features
QUICKLAG Type QC Miniature Circuit Breakers—Cable-In/Cable-Out
1/2-Inch Wide Types QCR, QCF
1
When Space is at a Premium
●
●
●
●
●
●
●
●
QCR: For DIN-rail mount cable-in/cable-out applications
QCF: For front-mount through-the-door cable-in/cable-out
applications
1/2 in (12.7 mm) wide per pole
Three-position handle: ON, tripped (center), OFF
Thermal-magnetic protection
Single-, two- and three-pole
10 kAIC at 120/240 Vac, 10–60A
10 kAIC at 240 Vac, 10–30A
1
1
1
1
1
1
1
1
Catalog Number Selection
1
QUICKLAG Type QC Miniature Circuit Breakers—Cable-In/Cable-Out 1/2-Inch Wide Types QCR, QCF
1
QCR 1 020 T
1
Breaker Type
QCR = QCD Breaker (rear mount)
QCF = QCF Breaker (front mount)
Number of Poles
1 = Single-pole
2 = Two-pole
3 = Three-pole
010
015
020
025
= 10 amp
= 15 amp
= 20 amp
= 25 amp
Ampere Rating
030 = 30 amp
035 = 35 amp
040 = 40 amp
045 = 45 amp
050 = 50 amp
055 = 55 amp
060 = 60 amp
Construction/Terminals
H = 240V (two- and three-pole only)
T = Ring or spade terminals
(10–30A only)
1
1
1
Product Selection
QUICKLAG Type QCR Breakers 10 kAIC
Interrupting Ratings 1234
1
QUICKLAG Type QCF Breakers 10 kAIC
Interrupting Ratings 123
Continuous
Ampere Rating
at 40ºC
Single-Pole
120/240 Vac
Catalog Number
Two-Pole
120/240 Vac
Catalog Number
Three-Pole
240 Vac
Catalog Number
Continuous
Ampere Rating
at 40ºC
Single-Pole
120/240 Vac
Catalog Number
Two-Pole
120/240 Vac
Catalog Number
Three-Pole
240 Vac
Catalog Number
10
QCR1010
QCR2010
—
10
QCF1010
QCF2010
—
QCR1010T
QCR2010T
—
QCF1010T
QCF2010T
—
QCR1015 5
QCR2015
QCR3015H
QCF1015 5
QCF2015
QCF3015H
QCR1015T 5
QCR2015T
QCR3015HT
—
—
QCF3015HT
QCR1020 5
QCR2020
QCR3020H
QCF1020 5
QCF2020
QCF3020H
QCR1020T 5
QCR2020T
QCR3020HT
—
—
QCF3020HT
15
20
25
QCR1025
QCR2025
QCR3025H
—
—
QCR3025HT
15
20
25
QCF1025
QCF2025
QCF3025H
—
—
QCF3025HT
QCR1030
QCR2030
QCR3030H
—
—
QCR3030HT
35
QCR1035
QCR2035
—
40
40
QCR1040
QCR2040
—
50
QCF1050
QCF2050
—
45
QCR1045
QCR2045
—
60 6
QCF1060
QCF2060
—
50
QCR1050
QCR2050
—
55
QCR1055
—
—
60 6
QCR1060
QCR2060
—
30
30
QCF1030
QCF2030
QCF3030H
—
—
QCF3030HT
QCF1040
QCF2040
—
1
1
1
1
1
1
1
1
1
1
Notes
1 Standard breaker terminals are box type lugs.
2 Breakers with “T” catalog number suffix are suitable for line and load side ring terminal connection (#10-32 plus/minus terminal screw provided).
3 Breakers with “P” catalog number suffix are suitable for terminating two 10 AWG quick-connect type terminals per phase on breaker load side.
4 Breakers with shunt trip (extra pole required on breaker right-hand side) are available on single-, two- and three-pole.
5 All 15 and 20A single-pole breakers are SWD (switching duty) rated for fluorescent lighting applications.
6 60/75°C Cu/Al wire on all ratings except 60A, which requires Cu only conductor.
Volume 9—OEM—Original Equipment Manufacturer CA08100011E—March 2013 www.eaton.com
1
1
1
1
V9-T1-21
1.1
1
Circuit Protection
Circuit Breakers
Accessories
Type QCR and QCF
1
Description
Catalog Number
1
Steel mounting clip mounts QCR breaker if individual mounting is required. Quantity two
required for single- and two-pole and four required for three-pole breakers.
QCRMTGFT
1
Removable padlock device for single-pole QCR or QCF breaker.
QCRFPL1P
Removable padlock device for multi-pole QCR or QCF breaker.
QCRFPLMP
1
Padlock bracket assembly for QCR or QCF single- or multi-pole breakers (OFF only).
QCRFLOFF
Padlock bracket for QCR, lock-off only.
QCRPLOFF
QUICKLAG Type C
Spacer
QUICKLAG Type C Spacer
QCRSPACER
QCR and QCF Ring or
Spade Lug Terminals
QCR and QCF ring or spade lug terminals (10–30A ratings only). Factory installed line and load
side terminals each equipped with a #10-32 screw suitable for terminating one 10 AWG wire
with insulated ring or spade type terminal as shown.
Suffix “T”
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
V9-T1-22
Volume 9—OEM—Original Equipment Manufacturer CA08100011E—March 2013 www.eaton.com
Circuit Protection
Circuit Breakers
1.1
Features
QUICKLAG Type QC Miniature Circuit Breakers—Cable-In/Cable-Out
1/2-Inch Wide Types QCGF, QCGFEP
1
For Cable-In/Cable-Out Panel-Mount Applications
●
●
●
●
●
QUICKLAG ground fault circuit breakers, Class A GFCI:
Built and tested to UL 943
5 mA trip sensitivity
QUICKLAG ground fault equipment protectors:
●
Built and tested to UL 1053
●
30 mA trip sensitivity
All products UL and CSA listed
1
1
1
1
1
1
1
1
Catalog Number Selection
1
QUICKLAG Type QC Miniature Circuit Breakers—
Cable-In/Cable-Out Ground Fault and Equipment Protector Types QCGF, QCGFEP
1
QCGFEP 1 020
Breaker Type
QCGF = QC ground fault circuit protector
QCGFEP = QC ground fault equipment protector
Number of Poles
1 = Single-pole
2 = Two-pole
1
1
Ampere Rating
015 = 15 amp
030 = 30 amp
020 = 20 amp
040 = 40 amp
025 = 25 amp
050 = 50 amp
1
1
Product Selection
1
Types QCGF and QCGFEP Thermal-Magnetic Breakers
Continuous Ampere
Rating at 40ºC
Single-Pole, 120/240 Vac
Catalog Number
1
Two-Pole, 120/240 Vac
Catalog Number
1
Ground Fault Circuit Breakers—5 mA Sensitivity
QUICKLAG Type: QCGF 10,000 Ampere I.C.
15
QCGF1015
QCGF2015
20
QCGF1020
QCGF2020
30
QCGF1030
QCGF2030
40
QCGF1040
QCGF2040
50
—
QCGF2050
1
1
1
1
Ground Fault Equipment Protectors—30 mA Sensitivity
QUICKLAG Type: QCGFEP 10,000 Ampere I.C.
15
QCGFEP1015
QCGFEP2015
20
QCGFEP1020
QCGFEP2020
30
QCGFEP1030
QCGFEP2030
40
QCGFEP1040
QCGFEP2040
50
—
QCGFEP2050
1
1
1
1
1
1
1
1
Volume 9—OEM—Original Equipment Manufacturer CA08100011E—March 2013 www.eaton.com
V9-T1-23
1.1
1
Circuit Breakers
Accessories
Type QC Miniature Circuit Breakers
1
1
Circuit Protection
Handle Locks
1
Accessory 1
Description
Catalog Number
Handle locks:
Non-padlockable 2
QUICKLAG type P, B, C—single-pole
QL1NPL
QUICKLAG type P, B, C—two-, three-pole
QL23NPL
Handle locks:
Padlockable
QUICKLAG type P, B, C—single-pole
QL1PL
QUICKLAG type C—single-, two-, three-pole
QC123PL
QUICKLAG type C—single-, two-, three-pole (off only)
QCD123PLOFF
1
1
1
1
1
Handle Tie
Handle tie
1
QUICKLAG handle tie—single-pole
QL1HT
QUICKLAG handle tie—three-pole
QL3HT
1
1
1
Hardware
QUICKLAG type C face mounting clip
QCFCLIP
QUICKLAG type C face mounting plate—single-pole
QC1FP
QUICKLAG type C face mounting plate —two-pole
QC2FP
1
QUICKLAG type C face mounting plate —three-pole
QC3FP
QUICKLAG type C face mounting plate and lock-off (off only)—two-pole 3
QC2FPLOFF
1
QUICKLAG type C face mounting plate and lock-off (off only)—three-pole
QC3FPLOFF
QUICKLAG type C base mounting clamp
QCBCLIP
QUICKLAG base mounting plate—six poles total
QC6BP
QUICKLAG type C base mounting plate, six-poles total—
heavy-duty screw-secured
QC6BPS
QUICKLAG type C (QCD) two-way jumper unit with cover
QCDJ2
QUICKLAG type C (QCD) four-way jumper unit with cover
QCDJ4
1
QUICKLAG type C (QCD) six-way jumper unit with cover
QCDJ6
QUICKLAG type C (QCD) two-way jumper unit, no cover
QCDJ2T
1
QUICKLAG type C (QCD) four-way jumper unit, no cover
QCDJ4T
QUICKLAG type C (QCD) six-way jumper unit, no cover
QCDJ6T
QUICKLAG type QCD finger protection attachment
QCDFP
QUICKLAG type C DIN-rail adapter
QCDINADAPT
1
1
1
1
1
1
Mounting hardware
1
1
Notes
1 See Page V9-T1-22 for QCR and QCF accessories.
2 Can lock in ON or OFF position.
3 Suitable for ground fault breakers.
1
1
1
1
1
V9-T1-24
Volume 9—OEM—Original Equipment Manufacturer CA08100011E—March 2013 www.eaton.com
1.1
Circuit Protection
Circuit Breakers
Features
WMZ UL 489 Miniature Circuit Breakers
●
●
●
●
●
UL 489 listed DIN-rail mounted miniature circuit breakers
up to 40A current rating
Current limiting design provides fast short circuit interruption
that reduces let-through energy
Thermal-magnetic overcurrent protection available with
C and D curve level of protection
●
C curve—5–10X In—for medium inrush startup currents
●
D curve—10–20X In—provides a magnetic range to allow
for high inrush levels
1
1
1
1
1
1
Ring-tongue terminals available
Complete line of accessories
1
1
1
Catalog Number Selection
WMZ UL 489 Miniature Circuit Breakers
1
WMZ UL 489
1
1
WMZ T 1 C 16 T
Breaker Type
WMZ = WMZ UL 489
circuit breaker
Breaker Type
T = 10 kAIC
H = 14 kAIC
D = 10 kAIC/DC
Number of Poles
1 = Single-pole
2 = Two-pole
3 = Three-pole
Protective Curve
C = C curve (5–10X In)
D = D curve (10–20X In)
Ampere Rating
X0 = 0.5A
10 = 10A
01 = 1A
13 = 13A
X1 = 1.5A
15 = 15A
02 = 2A
16 = 16A
03 = 3A
20 = 20A
04 = 4A
25 = 25A
05 = 5A
30 = 30A
06 = 6A
32 = 32A
07 = 7A
40 = 40A
08 = 8A
1
Terminal
T = Ring terminals
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
Volume 9—OEM—Original Equipment Manufacturer CA08100011E—March 2013 www.eaton.com
V9-T1-25
1.1
1
1
Circuit Protection
Circuit Breakers
Product Selection
WMZT UL 489 Circuit Breakers
Ampere
Rating
C Curve (5–10X In Current Rating)
Single-Pole 1
Two-Pole 1
Catalog Number
Catalog Number
Three-Pole 1
Catalog Number
D Curve (10–20X In Current Rating)
Single-Pole 1
Two-Pole 1
Catalog Number
Catalog Number
Three-Pole 1
Catalog Number
0.5
WMZT1CX0
WMZT2CX0
WMZT3CX0
WMZT1DX0
WMZT2DX0
WMZT3DX0
1
WMZT1C01
WMZT2C01
WMZT3C01
WMZT1D01
WMZT2D01
WMZT3D01
1
1.5
WMZT1CX1
WMZT2CX1
WMZT3CX1
WMZT1DX1
WMZT2DX1
WMZT3DX1
2
WMZT1C02
WMZT2C02
WMZT3C02
WMZT1D02
WMZT2D02
WMZT3D02
1
3
WMZT1C03
WMZT2C03
WMZT3C03
WMZT1D03
WMZT2D03
WMZT3D03
4
WMZT1C04
WMZT2C00
WMZT3C04
WMZT1D04
WMZT2D04
WMZT3D04
1
5
WMZT1C05
WMZT2C05
WMZT3C05
WMZT1D05
WMZT2D05
WMZT3D05
6
WMZT1C06
WMZT2C06
WMZT3C06
WMZT1D06
WMZT2D06
WMZT3D06
1
7
WMZT1C07
WMZT2C07
WMZT3C07
WMZT1D07
WMZT2D07
WMZT3D07
8
WMZT1C08
WMZT2C08
WMZT3C08
WMZT1D08
WMZT2D08
WMZT3D08
10
WMZT1C10
WMZT2C10
WMZT3C10
WMZT1D10
WMZT2D10
WMZT3D10
1
13
WMZT1C13
WMZT2C13
WMZT3C13
WMZT1D13
WMZT2D13
WMZT3D13
15
WMZT1C15
WMZT2C15
WMZT3C15
WMZT1D15
WMZT2D15
WMZT3D15
1
16
WMZT1C16
WMZT2C16
WMZT3C16
WMZT1D16
WMZT2D16
WMZT3D16
20
WMZT1C20
WMZT2C20
WMZT3C20
WMZT1D20
WMZT2D20
WMZT3D20
1
25
WMZT1C25
WMZT2C25
WMZT3C25
WMZT1D25
WMZT2D25
WMZT3D25
30
WMZT1C30
WMZT2C30
WMZT3C30
WMZT1D30
WMZT2D30
WMZT3D30
1
32
WMZT1C32
WMZT2C32
WMZT3C32
WMZT1D32
WMZT2D32
WMZT3D32
40
WMZT1C40
WMZT2C40
WMZT3C40
WMZT1D40
WMZT2D40
WMZT3D40
1
1
1
1
1
1
1
WMZH UL 489 Circuit Breakers—14 kAIC
Amperes
Single-Pole
Catalog Number
WMZD UL 489 Circuit Breakers—10 kAIC at 125 Vdc per Pole
Two-Pole
Catalog Number
Three-Pole
Catalog Number
C Curve (5–10X In Current Rating)
Amperes
Single-Pole
Catalog Number
Two-Pole
Catalog Number
C Curve (5–10X In Current Rating)
15
WMZH1C15
WMZH2C15
WMZH3C15
2
WMZD1C02
WMZD2C02
1
16
WMZH1C16
WMZH2C16
WMZH3C16
3
WMZD1C03
WMZD2C03
20
WMZH1C20
WMZH2C20
WMZH3C20
4
WMZD1C04
WMZD2C04
1
25
WMZH1C25
WMZH2C25
WMZH3C25
5
WMZD1C05
WMZD2C05
6
WMZD1C06
WMZD2C06
1
13
WMZH1D13
WMZH2D13
WMZH3D13
7
WMZD1C07
WMZD2C07
15
WMZH1D15
WMZH2D15
WMZH3D15
8
WMZD1C08
WMZD2C08
16
WMZH1D16
WMZH2D16
WMZH3D16
10
WMZD1C10
WMZD2C10
20
WMZH1D20
WMZH2D20
WMZH3D20
13
WMZD1C13
WMZD2C13
15
WMZD1C15
WMZD2C15
16
WMZD1C16
WMZD2C16
20
WMZD1C20
WMZD2C20
25
WMZD1C25
WMZD2C25
30
WMZD1C30
WMZD2C30
32
WMZD1C32
WMZD2C32
40
WMZD1C40
WMZD2C40
1
1
1
1
1
D Curve (10–20X In Current Rating)
WMZH UL 489 Circuit Breakers with Ring-Tongue Terminals
Amperes
Single-Pole
Catalog Number
Two-Pole
Catalog Number
Three-Pole
Catalog Number
C Curve (5–10X In Current Rating)
15
WMZH1C15T
WMZH2C15T
WMZH3C15T
1
16
WMZH1C16T
WMZH2C16T
WMZH3C16T
20
WMZH1C20T
WMZH2C20T
WMZH3C20T
1
25
WMZH1C25T
WMZH2C25T
WMZH3C25T
1
13
WMZH1D13T
WMZH2D13T
WMZH3D13T
15
WMZH1D15T
WMZH2D15T
WMZH3D15T
16
WMZH1D16T
WMZH2D16T
WMZH3D16T
20
WMZH1D20T
WMZH2D20T
WMZH3D20T
1
1
Note
1 For ring-tongue terminals, ADD suffix “T” to above catalog number.
D Curve (10–20X In Current Rating)
V9-T1-26
Volume 9—OEM—Original Equipment Manufacturer CA08100011E—March 2013 www.eaton.com
1.1
Circuit Protection
Circuit Breakers
Features
WMZS UL 1077 Miniature Circuit Breakers—Supplementary Protectors
●
●
●
●
●
UL 1077 recognized DIN-rail mounted supplemental
protectors up to 63A
Current limiting design provides fast short circuit interruption
that reduces let-through energy
Thermal-magnetic overcurrent protection available with
B, C and D curve levels of protection
●
B curve—3–5X In—for maximum protection of control
circuit wiring from low-level short circuit faults
●
C curve—5–10X In—for medium inrush startup currents
●
D curve—10–20X In—provides a magnetic range to allow
for high inrush levels
Ideal replacement for fuses that are applied as supplemental
protection
Complete line of accessories
1
1
1
1
1
1
1
1
1
Catalog Number Selection
WMZS UL 1077 Miniature Circuit Breakers—Supplementary Protectors
1
WMZS UL 1077 Miniature Circuit Breakers
1
WMZS 1 B 10
Breaker Family
WMZS = Supplementary protector
Number of Poles
1 = Single-pole
2 = Two-pole
3 = Three-pole
Protective Curve
B = B curve (3–5X In)
C = C curve (5–10X In)
D = D curve (10–20X In)
1
00 = 0.5A
01 = 1A
02 = 2A
03 = 3A
04 = 4A
Ampere Rating
05 = 5A
13 = 13A
06 = 6A
15 = 15A
07 = 7A
16 = 16A
08 = 8A
20 = 20A
10 = 10A
25 = 25A
1
30 = 30A
32 = 32A
40 = 40A
50 = 50A
63 = 63A
1
1
1
Product Selection
1
WMZS UL 1077 Supplementary Protectors
Ampere
Rating
B Curve (3–5X In Current Rating)
Single-Pole
Two-Pole
Three-Pole
Catalog Number Catalog Number Catalog Number
C Curve (5–10X In Current Rating)
Single-Pole
Two-Pole
Three-Pole
Catalog Number Catalog Number Catalog Number
D Curve (10–20X In Current Rating)
Single-Pole
Two-Pole
Three-Pole
Catalog Number Catalog Number Catalog Number
0.5
—
—
—
WMZS1C00
WMZS2C00
WMZS3C00
WMZS1D00
WMZS2D00
WMZS3D00
1
—
—
—
WMZS1C01
WMZS2C01
WMZS3C01
WMZS1D01
WMZS2D01
WMZS3D01
2
—
—
—
WMZS1C02
WMZS2C02
WMZS3C02
WMZS1D02
WMZS2D02
WMZS3D02
3
—
—
—
WMZS1C03
WMZS2C03
WMZS3C03
WMZS1D03
WMZS2D03
WMZS3D03
4
—
—
—
WMZS1C04
WMZS2C04
WMZS3C04
WMZS1D04
WMZS2D04
WMZS3D04
5
—
—
—
WMZS1C05
WMZS2C05
WMZS3C05
WMZS1D05
WMZS2D05
WMZS3D05
6
WMZS1B06
WMZS2B06
WMZS3B06
WMZS1C06
WMZS2C06
WMZS3C06
WMZS1D06
WMZS2D06
WMZS3D06
7
WMZS1B07
WMZS2B07
WMZS3B07
WMZS1C07
WMZS2C07
WMZS3C07
WMZS1D07
WMZS2D07
WMZS3D07
8
WMZS1B08
WMZS2B08
WMZS3B08
WMZS1C08
WMZS2C08
WMZS3C08
WMZS1D08
WMZS2D08
WMZS3D08
10
WMZS1B10
WMZS2B10
WMZS3B10
WMZS1C10
WMZS2C10
WMZS3C10
WMZS1D10
WMZS2D10
WMZS3D10
13
WMZS1B13
WMZS2B13
WMZS3B13
WMZS1C13
WMZS2C13
WMZS3C13
WMZS1D13
WMZS2D13
WMZS3D13
15
WMZS1B15
WMZS2B15
WMZS3B15
WMZS1C15
WMZS2C15
WMZS3C15
WMZS1D15
WMZS2D15
WMZS3D15
16
WMZS1B16
WMZS2B16
WMZS3B16
WMZS1C16
WMZS2C16
WMZS3C16
WMZS1D16
WMZS2D16
WMZS3D16
20
WMZS1B20
WMZS2B20
WMZS3B20
WMZS1C20
WMZS2C20
WMZS3C20
WMZS1D20
WMZS2D20
WMZS3D20
25
WMZS1B25
WMZS2B25
WMZS3B25
WMZS1C25
WMZS2C25
WMZS3C25
WMZS1D25
WMZS2D25
WMZS3D25
30
WMZS1B30
WMZS2B30
WMZS3B30
WMZS1C30
WMZS2C30
WMZS3C30
WMZS1D30
WMZS2D30
WMZS3D30
32
WMZS1B32
WMZS2B32
WMZS3B32
WMZS1C32
WMZS2C32
WMZS3C32
WMZS1D32
WMZS2D32
WMZS3D32
40
WMZS1B40
WMZS2B40
WMZS3B40
WMZS1C40
WMZS2C40
WMZS3C40
WMZS1D40
WMZS2D40
WMZS3D40
50
WMZS1B50
WMZS2B50
WMZS3B50
WMZS1C50
WMZS2C50
WMZS3C50
—
—
—
63
WMZS1B63
WMZS2B63
WMZS3B63
WMZS1C63
WMZS2C63
WMZS3C63
—
—
—
Volume 9—OEM—Original Equipment Manufacturer CA08100011E—March 2013 www.eaton.com
1
1
1
1
1
1
1
1
1
1
1
1
1
V9-T1-27
1.1
Circuit Protection
Circuit Breakers
1
Accessories
1
WMZT UL 489
Description
Catalog Number
Description
Rating
Catalog Number
1
Two-pole contact or auxiliary contact/trip indicating contact
WMZSAUXTRIP
Auxiliary contact—1 NO/1 NC
230 Vac
WMZSAUX
Auxiliary contact
WMZTAUX
230 Vac
WMZSAUXTRIP
Shunt trip 110–415 Vac
WMZTST415
Two-pole contact or auxiliary contact/
trip indicating contact
Shunt trip 12–110 Vac
WMZTST110
1
1
1
1
1
1
WMZT UL 489
Undervoltage release
WMZPLK
Padlock hasp
Busbar—single-pole 6 terminals
Busbar—single-pole 12 terminals
WMZT1P6T
WMZT1P12T
Busbar—single-pole 18 terminals
WMZT1P18T
Busbar—two-pole 6 terminals
WMZT2P6T
Busbar—two-pole 12 terminals
WMZT2P12T
Busbar—two-pole 18 terminals
WMZT2P18T
Busbar—three-pole 6 terminals
WMZT3P6T
Shunt trip
115 Vac
WMZSUVR115
230 Vac
WMZSUVR230
400 Vac
WMZSUVR400
110–415 Vac
WMZSST415
110–230 Vdc
Shunt trip
12–110 Vac
WMZSST110
12–60 Vdc
Without Auxiliary Contacts
Busbar—Single-pole 57 terminals
80A
WMZS1P57T
Busbar—Two-pole 56 terminals
80A
WMZS2P56T
Busbar—Three-pole 57 terminals
80A
WMZS3P57T
Busbar—Single-pole 57 terminals
100A
WMZS1P57T25
Busbar—Two-pole 56 terminals
100A
WMZS2P56T25
Busbar—Three-pole 57 terminals
100A
WMZS3P57T25
Busbar— Single-pole 37 terminals
80A
WMZS1P37TAUX
1
Busbar— Two-pole 46 terminals
80A
WMZS2P46TAUX
Busbar— Three-pole 48 terminals
80A
WMZS3P48TAUX
1
Busbar— Single-pole 37 terminals
100A
WMZS1P37T25AUX
Busbar— Two-pole 46 terminals
100A
WMZS2P46T25AUX
1
Busbar— Three-pole 48 terminals
100A
WMZS3P48T25AUX
Pin type incoming supply terminals
25 mm2 (~AWG 4)
—
WMZSBCON
Bus incoming supply terminals
50 mm2 (14-1 AWG)
—
WMZS50EXT
Busbar terminals cover
—
WMZSBBTC
Padlock hasp
—
WMZPLK
Fork connector—Two- and three-pole
—
WMZS3CAP
Fork connector—Single-pole
—
WMZS1CAP
1
1
1
Busbar—three-pole 12 terminals
Busbar—three-pole 18 terminals
WMZT3P12T
WMZT3P18T
WMZT3PSHROUD
Three-pole busbar shroud
Extension terminal—35 mm (2–14 AWG)
Bus connector—conductors up to 50 mm2 (~1/0 AWG)
WMZT35EXT
WMZTBCON
Auxiliary/Trip Indicating Contacts
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
V9-T1-28
Volume 9—OEM—Original Equipment Manufacturer CA08100011E—March 2013 www.eaton.com
Circuit Protection
Circuit Breakers
1.1
Features
Series NRX Low Voltage Power Breakers
●
●
●
●
●
Rogowski coil does not saturate like iron core sensors, and
one sensor accommodates 200–1600A range. Never change
a sensor, and NO CTs are required
Tension clamp secondary terminals—10A continuous rating at
600V meets UL/CSA/RoHS and UL-94 V0. Mounted directly to
fixed breaker or drawout cassette they reduce wiring and
provide clean, organized wiring schemes
Breaker mounted communication modules for INCOM™,
Modbus® and PROFIBUS® mount directly to the cassette,
reducing the space and room required for communication
capability
With the patent pending simple design of the fold-up
cassette, all items in a cassette are replaceable without
removing the cassette from the cell
Plug-and-play accessories—no special tools needed.
Accessories come with plug and wires ready to install
1
1
1
1
1
1
1
1
1
Series NRX™ Low Voltage Power Breakers
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
Volume 9—OEM—Original Equipment Manufacturer CA08100011E—March 2013 www.eaton.com
V9-T1-29
1.1
Circuit Protection
Circuit Breakers
1
Catalog Number Selection
1
Series NRX Power Breakers (Exclusionary Rules Apply)
N S S6 08 3 W 52 8 A B A N 4 X N D X
1
1
1
1
1
1
1
1
1
1
Breaker Frame Size
N = Type NF, 630–1600A,
(70 mm pole spacing)
Standard, Mechanism, Device
S = UL 1066, stored energy,
power breaker
X = UL 489, stored energy,
insulated case breaker
E = IEC 60947-2, stored
energy, air breaker
Frame Rating (Amperes)
12 = 1200 (UL only)
07 = 630 (IEC only)
13 = 1250 (IEC only)
08 = 800
16 = 1600 (On NF: IEC only)
10 = 1000 (IEC only)
Poles, Phasing
3 = Three-pole, ABC
4 = Four-pole, NABC
1
Mounting Configuration
W = Drawout
B = Fixed mount rear connect, mounting bracket,
with secondary terminal row
R = Fixed mount rear connect, surface mount,
with secondary terminal row
T = Fixed mount front connect, surface mount,
cable connect, with secondary terminal row
F = Fixed mount front connect, mounting bracket,
bus connect, with secondary terminal row
S = Fixed mount front connect, surface mount,
bus connect, with secondary terminal row
1
1
1
1
1
Trip Unit
1
52
53
5G
5H
M2
M3
MA
MB
MG
MH
R2
1
1
1
1
R3
1
RA
1
RB
RG
1
RH
1
1
1
2
3
4
5
6
Fault Current Rating
S4 = 42 kA at 480 Vac UL or 415 Vac IEC
S5 = 50 kA at 480 Vac UL or 415 Vac IEC
S6 = 65 kA at 480 Vac UL or 415 Vac IEC
1
1
Future Use
X = All product
SW
= 520 LSI, no ZSI
= 520 LSI, with ZSI
= 520 LSIG, no ZSI
= 520 LSIG, with ZSI
= 520M LSI, no ZSI, 24 Vdc
= 520M LSI, with ZSI, 24 Vdc
= 520M LSIA, no ZSI, 24 Vdc
= 520M LSIA, with ZSI, 24 Vdc
= 520M LSIG, no ZSI, 24 Vdc
= 520M LSIG, with ZSI, 24 Vdc
= 520M LSI, no ZSI, 24 Vdc, with
Arcflash Reduction Maintenance System™
= 520M LSI, with ZSI, 24 Vdc, with
Arcflash Reduction Maintenance System
= 520M LSIA, no ZSI, 24 Vdc, with
Arcflash Reduction Maintenance System
= 520M LSIA, with ZSI, 24 Vdc, with
Arcflash Reduction Maintenance System
= 520M LSIG, no ZSI, 24 Vdc, with
Arcflash Reduction Maintenance System
= 520M LSIG, with ZSI, 24 Vdc, with
Arcflash Reduction Maintenance System
= Non-auto switch
Drawout Breaker Shipping,
Fixed Breaker Terminals, Door Frame Kit
D = Drawout (or parent) breaker shipping alone,
without door frame kit
C = Drawout breaker in cassette, no shutters,
no terminals, with door frame kit
K = Fixed breaker, no adapters, rear connector,
with door frame kit, with mounting feet,
with door frame kit
A = Terminal adapters for rear connect,
short vertical/horizontal, with door frame kit
E = Terminal adapters for rear connect,
long vertical/horizontal, with door frame kit
F = Terminal adapters for rear connect,
with mounting feet, short vertical/horizontal,
with door frame kit
H = Terminal adapters for rear connect, with
mounting feet, long vertical/horizontal,
with door frame kit
1 = Drawout breaker in cassette, no shutters,
short vertical/horizontal, with door frame kit
2 = Drawout breaker in cassette, no shutters,
long vertical/horizontal, with door frame kit
4 = Drawout breaker in cassette, with shutters,
short vertical/horizontal, with door frame kit
5 = Drawout breaker in cassette, with shutters,
long vertical/horizontal, with door frame kit
9 = Drawout breaker in cassette, with shutters,
no terminals, with door frame kit
Rating Plug
(Amperes)
= 200
7 = 630
= 250
8 = 800
= 300
A = 1000
= 400
B = 1200
= 500
C = 1250
= 600
D = 1600
Shunt Trip 1
N = No shunt trip
A = 110–127 Vac/Vdc
R = 208–240 Vac/Vdc
L = 24 Vdc
H = 48 Vdc
Motor Operator 1
M = Manually operated
B = 110–125 Vac
W = 110–125 Vdc
T = 208–250 Vac
P = 220–250 Vdc
L = 24 Vdc
H = 48 Vdc
Spring Release,
Latch Check Switch 1
N = No spring release, no LCS
A = 110–127 Vac/Vdc, no LCS
R = 208–240 Vac/Vdc, no LCS
UVR, Second Shunt Trip 1
N = None
A = 110–125 Vac/Vdc UVR
R = 220–250 Vac/Vdc UVR
1 = 110–127 Vac/Vdc second shunt trip
2 = 208–240 Vac/Vdc second shunt trip
Padlock Provisions, Key Lock
Provisions, Operations Counter 1
N = No PB covers, none, no counter
N =
X =
Z =
Auxiliary, Switches,
Label Language 1
E = No auxiliary switches,
no label (parent)
2 = 2 Form C, English
4 = 4 Form C, English
M=
Y =
1 =
2 =
3 =
4 =
5 =
Trip Indicator and Bell Alarm/OTS,
Secondary Terminal Blocks 1
No indicator, no OTS, secondary terminal blocks
per breaker options
Trip indicator provided, no OTS, secondary
terminal blocks per breaker options
Trip indicator provided, 2 Form C OTS, secondary
terminal blocks per breaker options
Interlock trip indicator provided, no OTS,
secondary terminal blocks per breaker options
Trip indicator provided, 2 Form C OTS, secondary
terminal blocks per breaker options
No indicator, no OTS, full complement secondary
terminal blocks
Trip indicator, no OTS, full complement secondary
terminal blocks
Trip indicator provided, 2 Form C OTS, full
complement secondary terminal blocks
Interlock trip indicator provided, no OTS, full
complement secondary terminal blocks
Interlock trip indicator provided, 2 Form C, full
complement secondary terminal blocks
Note
1 Contact Eaton for available voltages. Not all voltages are currently available.
V9-T1-30
Volume 9—OEM—Original Equipment Manufacturer CA08100011E—March 2013 www.eaton.com
1.1
Circuit Protection
Circuit Breakers
Catalog Number Selection
1
Series NRX Cassettes
1
NX 12 3 F A B N S N N N C
1
Cassette Family and Breaker Frame
NS = UL 1066 N Frame
NX = UL 489 N Frame
NE = IEC N Frame
Cassette Shipping
C = Cassette only
B = Breaker shipped in cassette
Arc Hood
A = Arc hood installed (default)
N
B
F
C
TOC Switches
(Truck Operated Cell)
N = Not included (default)
Load Terminal Connections
= With flat tapped pads only
= With vertical/horizontal bus adapter kit (short style)
= With front-connected kit
= No cassette stabs (interunit only)
1
Future
N = None
Door Frame Gasket and Rejection Kits
B = Door kit included (default), with rejection kit
Poles and Phasing
(Facing Front of Breaker)
3 = Three-pole ABC
4 = Four-pole NABC
F
G
H
N
1
Future
N = None
Continuous Ampere Range
08 = 800A (UL 1066)
12 = 800–1200A (UL 489)
16 = 630–1600A (IEC)
1
1
Secondary Contact Terminals Installed
= None
= Breaker defined, when breaker ships in cassette
= Full complement
= Common options when cassette ships alone
Shutters
N = Not included (default)
S = Included
1
1
1
1
1
Product Selection
1
Series NRX Low Voltage Power Breakers
1
Breaker
Frame
Industry
Standard
Fault Current
Rating (kAIC)
Frame Rating
in Amperes
Poles
Mounting
Trip Unit
Rating Plug
Part Number
N
UL 1066
42
800
3
Drawout 1
520 LSI (No ZSI)
800
NSS4083W528
N
UL 1066
42
800
4
Fixed
520 LSI (No ZSI)
800
NSS4084B528
520 LSI (No ZSI)
800
NSS5083W528
520 LSI (No ZSI)
800
NSS5084B528
N
UL 1066
50
800
3
Drawout
N
UL 1066
50
800
4
Fixed
N
UL 1066
65
800
3
Drawout
N
UL 1066
65
800
3
Fixed
1
1
2
520 LSI (No ZSI)
800
NSS6083W528
520 LSI (No ZSI)
800
NSS6083B528
N
UL 1066
65
800
4
Drawout 1
520 LSI (No ZSI)
800
NSS6084W528
N
UL 1066
65
800
4
Fixed
520 LSI (No ZSI)
800
NSS6084B528
N
UL 489
42
800
3
Drawout 1
520 LSI (No ZSI)
800
NXS4083W528
N
UL 489
42
1200
4
Drawout 1
520 LSI (No ZSI)
1200
NXS4124W52B
N
UL 489
50
800
3
Fixed
520 LSI (No ZSI)
800
NXS5083B528
N
UL 489
50
1200
4
Fixed
520 LSI (No ZSI)
1200
NXS5124B528
N
UL 489
65
800
3
Drawout 1
520 LSI (No ZSI)
800
NXS6083W528
N
UL 489
65
800
4
Fixed
520 LSI (No ZSI)
800
NSS6084B528
N
UL 489
65
1200
3
Drawout 1
520 LSI (No ZSI)
1200
NXS6123W52B
N
UL 489
65
1200
4
Fixed
520 LSI (No ZSI)
1200
NXS6124B52B
N
IEC
42
630
3
Drawout 1
520 LSI (No ZSI)
630
NES4073W527
N
IEC
42
1600
4
Drawout 1
520 LSI (No ZSI)
1600
NES4164W52D
N
IEC
50
630
3
Fixed
520 LSI (No ZSI)
630
NES5073B527
N
IEC
50
1600
4
Fixed
520 LSI (No ZSI)
1600
NES5164B52D
N
IEC
65
630
3
Drawout 1
520 LSI (No ZSI)
630
NES6073W527
N
IEC
65
800
4
Fixed
520 LSI (No ZSI)
800
NES6084B528
N
IEC
65
1250
3
Fixed
520 LSI (No ZSI)
1250
NES6133B52C
N
IEC
65
1600
4
Drawout 1
520 LSI (No ZSI)
1600
NES6164W52D
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
Notes
1 See Page V9-T1-30 for cassette selection for drawout breakers.
2 See selection above for accessories in positions 12–20.
Volume 9—OEM—Original Equipment Manufacturer CA08100011E—March 2013 www.eaton.com
1
V9-T1-31
1.1
1
Circuit Protection
Circuit Breakers
Magnum Low Voltage Power Breakers
Features
●
1
●
1
●
1
1
●
1
●
1
Rated up to 6300A with interrupting ratings up to 200 kAIC
and withstand ratings up to 100 kAIC
Magnum® DS is UL 1066 listed for one-half second short-time
withstand rating, and rated for 30 cycles. It is a switchgear
class product to meet UL 1558 switchgear standards
Magnum SB is a UL 1066 listed product with one-half second
short-time withstand rating at three cycles to meet
switchboard class product specifications, such as UL 891
Magnum DS MDDX is the highest interrupting performance in
a non-current limiting breaker construction rated up to
200 kAIC with 100 kAIC short-time withstand
The Magnum DS, Magnum SB and Magnum IEC lines all offer
the smallest double narrow 4000A frame available
1
1
Magnum Low Voltage Power Breakers
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
V9-T1-32
Volume 9—OEM—Original Equipment Manufacturer CA08100011E—March 2013 www.eaton.com
1.1
Circuit Protection
Circuit Breakers
Catalog Number Selection
1
Magnum ANSI/UL Low Voltage Power Breakers
1
MD S 4 12 3 V E A 06 MU A W C H N E H K L A X
1
Frame Use
X = All breakers
Breaker Type
MD = Magnum DS
SB = Magnum
switchboard
Frame Type
S = Standard or double
N = Narrow
D = Double (MDDX only)
Interrupting/
Withstand Rating
4 = 42
5 = 50
6 = 65
8 = 85
C = 100
E = 150 (DSE)
X = 200 (DSX)
L = 200 (DSL)
Continuous Amperes and
Phasing (Facing Front of
Breaker)
08 = 800 ABC
12 = 1200 ABC
16 = 1600 ABC
20 = 2000 ABC
25 = 2500 ABC
30 = 3000 ABC
32 = 3200 ABC or ABCABC
3N = 3200 AABBCC
4N = 4000 AABBCC
5N = 5000 AABBCC
6N = 6000 AABBCC
40 = 4000 ABCABC
50 = 5000 ABCABC
60 = 6000 ABCABC
Poles and Neutral
(Facing Front of Breaker)
3 = Three-pole
4 = Four-pole, neutral left
Mounting Configuration
and Load Terminals
H = Fixed horizontal
V = Fixed vertical
L = Drawout (MDN)
W = Drawout (MDS)
Nameplate Language
E = English
A = Spanish
Current Limiter Selection
A = Non-DSL
H = MA800
(no limiter)
K = MB1200
D = MA250
L = MB1600
E = MA300
M = MB2000
F = MA400
N = MD2500
G = MA600
P = MD3000
Sensor and
Rating Plug Rating
NN = None 13 = 1250
01 = 100
16 = 1600
02 = 200
20 = 2000
05 = 250
25 = 2500
03 = 300
30 = 3000
04 = 400
32 = 3200
06 = 600
40 = 4000
08 = 800
50 = 5000
10 = 1000 60 = 6000
12 = 1200
Breaker Shipping Options
and Instructions
A = Fixed breaker alone with
door kit
F = Fixed breaker alone without
door kit
A = Drawout breaker alone
without door frame kit
C = Drawout breaker in cassette
(unwired)
P = Drawout breaker in cassette
(prewired)
S = Drawout breaker in cassette
(shutters)
W = Drawout breaker in cassette
(prewired and shutters)
Double frame drawout breakers
ship without cassette drawout.
ACBs ship in narrow and
universal cassettes only.
Shunt Trip (ST)
N = None
A = 110–127 Vac/Vdc
R = 208–240 Vac/Vdc
C = 24 Vdc
H = 48 Vdc
Trip Unit and Protection
(and External Control
Voltage When Required)
NN = Non-automatic (no trip unit)
22 = 220 + LI
52 = 520 LSI
5G = 520 LSIG
M2 = 520M LSI
MT = 520M LSI (24/48 Vdc)
MU = 520M LSI (120 Vac)
MV = 520M LSI (240 Vac)
MQ = 520M LSI (125 Vac)
MG = 520M LSIG
MH = 520M LSIG (24/48 Vdc)
MM = 520M LSIG (120 Vac)
MN = 520 LSIG (240 Vac)
MX = 520M LSIG (125 Vac)
ME = 520M LSIA (24/48 Vdc)
MC = 520 LSIA (120 Vac)
MF = 520M LSIA (240 Vac)
MZ = 520M LSIA (125 Vac)
CT = 520MC LSI (24/48 Vdc)
CU = 520MC LSI (120 Vac)
CV = 520MC LSI (240 Vac)
CQ = 520MC LSI (125 Vac)
CH = 520MC LSIG (24/48 Vdc)
CM = 520MC LSIG (120 Vac)
CN = 520MC LSIG (240 Vac)
CX = 520MC LSIG (125 Vac)
CE = 520MC LSIA (24/48 Vdc)
CC = 520MC LSIA (120 Vac)
CF = 520MC LSIA (240 Vac)
CY = 520MC LSIA (125 Vac)
1A = 1150 LSI (24/48 Vdc)
1C = 1150 LSI (120 Vac)
1E = 1150 LSI (240 Vac)
1Q = 1150 LSI (125 Vac)
1F = 1150 LSIG (24/48 Vdc)
1G = 1150 LSIG (120 Vac)
1H = 1150 LSIG (240 Vac)
1X = 1150 LSIG (125 Vac)
1J = 1150 LSIA (24/48 Vdc)
1K = 1150 LSIA (120 Vac)
1M = 1150 LSIA (240 Vac)
1Y = 1150 LSIA (125 Vac)
Motor Operator
M = Manual operated
N = 110–125 Vac
W = 110–125 Vdc
T = 220–250 Vdc
P = 220–240 Vac
L = 24 Vdc
K = 48 Vdc
Spring Release
Device (SRD)
N = None
A = 110–127 Vac/Vdc
R = 208–240 Vac/Vdc
C = 24 Vdc
H = 48 Vdc
N
A
R
C
H
E
F
J
K
1
2
3
4
Undervoltage
Release (UVR) or
2nd Shunt Trip (ST)
= None
= UVR (110–127 Vac)
= UVR (208–240 Vac)
= UVR (24 Vdc)
= UVR (48 Vdc)
= UVR (110–125 Vdc)
= UVR (220–250 Vdc)
= UVR (480 Vac)
= UVR (600 Vac)
= 2nd ST (110–127 Vac/Vdc)
= 2nd ST (208–240 Vac/Vdc)
= 2nd ST (24 Vdc)
= 2nd ST (48 Vdc)
Auxiliary Switch
N = None
2 = 2A/2B
4 = 4A/4B
6 = 6A/6B
Bell Alarms Switch (OTS)
with 2a/2b Contacts and/or
Mechanical Trip Indicator
OTS 2a/2b Trip Indicator
E = No OTS
No indicator
N = No OTS
With indicator
Y = With OTS
With indicator
N=
M=
L =
Y=
C=
D=
Latch Check Switch/Trip Unit
Metering Voltage Connection
for Digitrip 1150 Trip Unit
Latch Check
1150 Voltage
Switch
Connection
None
Upper terminals
None
Lower terminals
LCS wired to SRD
Upper terminals
LCS wired to SRD
Lower terminals
LCS wired external Upper terminals
LCS wired external Lower terminals
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
N
K
C
R
A
Y
L
H
Operations Counter and/or
Keylock Provisions
Keylock
Counter
Provisions
= No counter No lock
= No counter Kirk lock
= No counter Castell lock
= No counter Ronis lock
= Counter
No lock
= Counter
Kirk lock
= Counter
Castell lock
= Counter
Ronis lock
Padlock Provisions for Blocking
Close and/or Open ACB Manual
Pushbuttons
N = None
M = Metal (block close and open)
P = Plastic (block close and open)
C = Metal (block close only)
H = Plastic (block close only)
S = Metal swbd lock-off (block close,
depress open)
Volume 9—OEM—Original Equipment Manufacturer CA08100011E—March 2013 www.eaton.com
1
1
1
1
1
1
1
1
1
1
1
V9-T1-33
1.1
1
Circuit Protection
Circuit Breakers
Magnum ANSI/UL Low Voltage Air Circuit Breaker Cassettes
M E 32 3 C A DN N NNN W C
1
1
Cassette Shipping
CA = Cassette only
BA = Breaker shipped in cassette
Cassette Family
M = Standard or double frame
L = Narrow frame
S = SB standard or double frame
T = SB narrow frame
1
1
Future Use
E = SB cassette (150 kAIC)
N = Cassettes (up to 100 kA)
L = MDSL cassettes (200 kA)
X = MDSX cassettes (200 kA)
D = MDDX breaker
1
1
1
Continuous Amperes
16 = Up to 1600A
20 = Up to 2000A
32 = 2500 to 3200A
40 = 4000A
50 = 5000A
1
1
1
Poles
3 = Three-pole
4 = Four-pole
1
Cassette Frame and Rear Terminals
P = Basic cassette
(without vertical bus stabs)
C = Basic cassette with stabs
(with vertical bus stab kit)
H = Narrow frame cassette
(with horizontal terminal pads)
U = Universal cassette
(with universal terminal pads)
Cassette Wiring
N = Unwired
W = Cassettes wired
Future Use
NNN = All cassettes
Shutters
N = No shutters
S = Shutters installed
Arc Hood
A = Arc hood installed
Door Frame and Gasket Kit
DN = Door frame and gasket kit included
XN = Door frame and gasket kit not included
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
V9-T1-34
Volume 9—OEM—Original Equipment Manufacturer CA08100011E—March 2013 www.eaton.com
1.1
Circuit Protection
Circuit Breakers
Magnum IEC Low Voltage Air Circuit Breakers
1
MW I 4 08 3 H E A – 02 22 A M A A 2 E M K L A X
Breaker Frame
I = Standard
or double
N = Narrow
K = Special
1100 Vac ACB
Interrupting ICU
4
5
6
8
C
2
= 40 kA
= 50 kA
= 65 kA
= 85 kA
= 100 kA
= 25 kA
(1100 Vac MWK)
Continuous Amperes
and Phasing (Facing
Front of Breaker)
08 = 800 ABC
10 = 1000 ABC
12 = 1250 ABC
16 = 1600 ABC
20 = 2000 ABC
25 = 2500 ABC
32 = 3200 ABC
4N = 4000 AABBCC
5N = 5000 AABBCC
6N = 6300 AABBCC
40 = 4000 ABCABC
50 = 5000 ABCABC
60 = 6300 ABCABC
Poles and Neutral
(Facing Front of Breaker)
3 = Three
4 = Four (neutral left)
R = Four (reserved for neutral right)
Sensor and Rating Plug Rating
NN = None
13 = 1250
02 = 200
16 = 1600
05 = 250
20 = 2000
03 = 300
25 = 2500
04 = 400
30 = 3000
06 = 600
32 = 3200
07 = 630
40 = 4000
08 = 800
50 = 5000
10 = 1000
63 = 6300
12 = 1200
1
Future Use
X = All ACBs
Trip Unit Protection,
(and External Control
Voltage When Required)
NN = Non-automatic (no trip unit)
22 = 220 LI
52 = 520 LSI
5W = 520i LSIG
M2 = 520M LSI
MT = 520M LSI (24–48 Vdc)
MU = 520M LSI (120 Vac)
MV = 520M LSI (240 Vac)
MW = 520Mi LSIG
MJ = 520Mi LSIG (24–48 Vdc)
MK = 520Mi LSIG (120 Vac)
ML = 520Mi LSIG (240 Vac)
ME = 520M LSIA (24–48 Vdc)
MC = 520M LSIA (120 Vac)
MF = 520M LSIA (240 Vac)
CT = 520MC LSI
CU = 520MC LSI
CV = 520MC LSI
CE = 520MC LSIA
CC = 520MC LSIA
CF = 520MC LSIA
CJ = 520MCi LSIG
CK = 520MCi LSIG
CL = 520MCi LSIG
1W = 1150i LSI (24–48 Vdc)
1N = 1150i LSI (120 Vac)
1P = 1150i LSI (240 Vac)
1R = 1150i LSIG/A (24–48 Vdc)
1S = 1150i LSIG/A (120 Vac)
1T = 1150i LSIG/A (240 Vac)
Mounting Configuration
and Load Terminals
H = Fixed horizontal
V = Fixed vertical
L = Drawout horizontal
Nameplate Language
E = English
A = Spanish
1
Auxiliary Switch
N = None
2 = 2A/2B
4 = 4A/4B
6 = 6A/6B
ACB Shipping Instructions
A = Fixed ACB with door kit
F = Fixed ACB without door kit
A = D/O ACB only without
door kit
C = D/O ACB in cassette
(unwired)
P = D/O ACB in cassette
(prewired)
S = D/O ACB in cassette
(shutters)
W = D/O ACB in cassette
(prewired and shutters)
Double frame D/O ACBs ship
without cassette
Shunt Trip
Attachment (STA)
N = None
A = 110–127 Vac
R = 208–240 Vac
C = 24 Vdc
H = 48 Vdc
Motor Operator
M = Manual operated
N = 110–125 Vac
W = 110–125 Vdc
T = 220–250 Vdc
P = 220–250 Vac
L = 24 Vdc
K = 48 Vdc
Latch Checking Switch/Trip Unit
Metering Voltage Connection
for Digitrip 1150 Trip Unit
Latch Check
1150 Voltage
Switch
Connection
N = None
Upper terminals
M = None
Lower terminals
L = LCS wired to SRD Upper terminals
Y = LCS wired to SRD Lower terminals
C = LCS wired external Upper terminals
D = LCS wired external Lower terminals
Spring Release
Device (SRD)
N = None
A = 110–127 Vac/Vdc
R = 208–240 Vac/Vdc
C = 24 Vdc
H = 48 Vdc
Undervoltage Release (UVR) or
2nd Shunt Trip Attachment
(STA)
N = None
A = 110–127 Vac
R = 208–240 Vac
C = 24 Vdc
H = 48 Vdc
E = 110–125 Vdc
F = 220–250 Vdc
G = 32 Vdc
X = 380–415 Vac
J = 480 Vac
K = 600 Vac
1 = 2nd STA (110–127 Vac/Vdc)
2 = 2nd STA (208–250 Vac/Vdc)
3 = 2nd STA (24 Vdc)
4 = 2nd STA (48 Vdc)
N
K
C
R
A
T
L
H
=
=
=
=
=
=
=
=
Operations Counter and/or
Keylock Provisions
Keylock
Provisions
Counter
No counter No lock
No counter Kirk lock
No counter Castell lock
No counter Ronis lock
Counter
No lock
Counter
Kirk lock
Counter
Castell lock
Counter
Ronis lock
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
Padlock Provisions for Blocking Close
and/or Open ACB Manual Pushbuttons
N = None
M = Metal (block close and open)
P = Plastic (block close and open)
C = Metal (block close only)
H = Plastic (block close only)
Bell Alarms Switch (OTS) with 2a/2b
Contacts and/or Mechanical Trip Indicator
OTS 2a/2b
Trip Indicator
E = No OTS
No indicator
N = No OTS
With indicator
Y = With OT
With indicator
1
1
1
1
1
1
1
1
1
1
Volume 9—OEM—Original Equipment Manufacturer CA08100011E—March 2013 www.eaton.com
V9-T1-35
1.1
1
Circuit Protection
Circuit Breakers
Magnum IEC Low Voltage Air Circuit Breaker Cassettes
E N 20 3 H A N N N N N N N C
1
1
Cassette Family
E = Standard or double frame IEC
(690 and 1100 Vac)
N = Narrow frame IEC
1
1
Cassette Wiring
C = Cassette only
Cassette Wiring
N = Unwired
W = Cassette wired
Future Use
N = All cassettes
1
Door Frame and Gasket Kit
X = Door frame and gasket kit
included
D = Door frame and gasket kit
not included
Continuous Amperes
20 = Up to 2000A
32 = 2500–3000A
40 = 4000A
63 = 5000–6300A
1
1
1
Future Use
N = All cassettes
Poles
3 = Three-pole
4 = Four-pole
1
1
Future Use
N = All cassettes
Rear Terminals
H = Horizontal stabs (upper
and lower terminals)
1
1
Arc Hood
A = Arc hood for 690 Vac
K = Arc hood for 1100 Vac
1
1
Shutters
N = No shutters
S = Shutters installed
Future Use
N = All cassettes
Future Use
N = All cassettes
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
V9-T1-36
Volume 9—OEM—Original Equipment Manufacturer CA08100011E—March 2013 www.eaton.com
1.1
Circuit Protection
Circuit Breakers
Product Selection
1
Magnum DS Switchgear Class UL 1066 Low Voltage Power Circuit Breakers
Frame
Type
Narrow
Standard
Narrow
Standard
Narrow
Standard
RMS Symmetrical Current Ratings kA 50/60 Hz 1
Interrupting at 254 Vac
Interrupting at 508 Vac
Interrupting at 635 Vac
1
Short Time
Current Rating
Frame
Amperes
Breaker Type 2
800
MDN-408
42
42
42
42
50
50
50
50
MDN-508
65
65
65
65
MDN-608
100
100
65
20
42
42
42
42
65
65
65
65
MDS-608
85
85
85
85
MDS-808
100
100
100
85
MDS-C08
200
200
200
—
MDS-L08 3
200
200
4
30
MDS-X08 56
42
42
42
42
50
50
50
50
MDN-516
65
65
65
65
MDN-616
100
100
65
30
65
65
65
65
85
85
85
85
MDS-816
100
100
100
85
MDS-C16
200
200
200
—
MDS-L16 3
200
200
4
30
MDS-X16 5
65
65
65
65
100
100
65
35
65
65
65
65
85
85
85
85
MDS-820
100
100
100
85
MDS-C20
1
MDN-C08
800
1600
1
MDS-408
1
1
MDN-C16
1600
2000
MDS-616
1
1
MDS-620
1
200
200
—
MDS-L20 3
4
30
MDS-X20 5
65
65
65
65
85
85
85
85
MDS-832
100
100
100
85
MDS-C32
3200
200
200
50
3200
MDS-X32
85
85
4
85
4000
MDN-840
100
100
4
100
85
85
85
85
100
100
100
100
MDS-C40
200
200
4
50
MDS-X40 5
5
1
MDS-840
200
4
100
4000
MDD-X40
85
85
85
5000
MDS-850
100
100
100
100
MDS-C50
200
200
4
50
MDS-X50 57
200
200
4
100
MDD-X50
100
6000
MDS-C60
1
1
200
100
1
MDN-C40
4000
85
100
1
1
Double (N)
4
1
MDS-632
Double
200
1
MDN-C20
2000
200
100
1
MDN-620
200
200
1
1
200
100
1
MDN-416
4
Double
1
1
1
7
1
MDD-X60
Notes
1 Interrupting ratings shown based on breaker equipped with integral Digitrip RMS trip unit. Interruption ratings for non-automatic breakers are equal to the published short time current rating. These
interruption ratings are based on the standard duty cycle consisting of an open operation, a 15-second interval and a close-open operation, in succession, with delayed tripping in case of short-delay
devices. The standard duty cycle for short time ratings consists of maintaining the rated current for two periods of 1/2 seconds each, with a 15-second interval of zero current between the two periods.
2 See Page V9-T1-36 for selection of trip unit and accessories. See Page V9-T1-36 for cassette selection for drawout breakers.
3 Magnum MDSL current limiting power circuit breaker with integral current limiters. Current limiter selected determines short time and maximum instantaneous trip rating.
Maximum voltage rating is 600 Vac.
4 Product to be tested. Contact Eaton for product rating.
5 Magnum MDSX current limiting power circuit breaker with fast opening contacts.
6 Contact Eaton for availability.
7 Breaker applied in a tested fan-cooled enclosure.
Volume 9—OEM—Original Equipment Manufacturer CA08100011E—March 2013 www.eaton.com
V9-T1-37
1
1
1
1
1
1.1
1
1
Frame
Type
Narrow
Standard
1
1
Narrow
1
1
1
Standard
Narrow
Interrupting at 508 Vac
Interrupting at 635 Vac
Short Time
Current Rating
Frame
Amperes
Breaker Type 2
800
SBN-508
50
50
35
20
65
65
42
20
SBN-608
100
100
65
20
SBN-C08
800
SBS-608
65
65
65
20
100
100
85
20
SBS-C08
200
150
2
30
SBS-E08 3
1200
SBN-512
50
50
35
25
65
65
42
25
100
100
65
25
65
65
65
25
100
100
85
25
SBS-C12
150
2
30
SBS-E12 3
SBN-612
SBN-C12
1200
SBN-516
50
50
35
30
65
42
30
100
100
65
30
65
65
65
30
100
100
85
30
SBS-C16
200
150
2
30
SBS-E16 3
65
65
65
35
100
100
65
35
65
65
65
35
100
100
85
35
SBS-C20
200
150
2
30
SBS-E20 3
65
65
65
45
100
100
85
45
SBS-C25
Double
200
150
2
50
SBS-E25 3
Standard
65
65
65
50
Standard
1
Narrow
1
Standard
1
1
1
1600
SBS-612
65
1
1
RMS Symmetrical Current Ratings kA 50/60 Hz 1
Interrupting at 254 Vac
200
1
1
Circuit Breakers
Magnum SB Switchboard Class UL 1066 Insulated Case Low Voltage Power Circuit Breakers
1
1
Circuit Protection
SBN-616
SBN-C16
1600
2000
SBS-616
SBN-620
SBN-C20
2000
2500
3000
SBS-620
SBS-625
SBS-630
100
100
85
50
SBS-C30
Double
200
150
2
50
SBS-E30 3
Double (N)
85
85
3
85
100
100
3
100
SBN-C40
85
85
85
85
SBS-840
1
100
100
100
100
SBS-C40
200
150
2
50
1
85
85
85
85
100
100
100
100
SBS-C50
200
150
2
50
SBS-E50 34
100
100
100
100
1
1
Double
1
1
1
1
1
4000
SBS-E40 3
5000
6000
Notes
1 Interrupting ratings shown based on breaker equipped with integral Digitrip RMS trip unit. Interruption ratings for non-automatic breakers are equal to the
published short time current rating. These interruption ratings are based on the standard duty cycle consisting of an open operation, a 15-second interval
and a close-open operation, in succession, with delayed tripping in case of short-delay devices. The standard duty cycle for short time ratings consists of
maintaining the rated current for two periods of 1/2 seconds each, with a 15-second interval of zero current between the two periods.
2 Product to be tested. Contact Eaton for product rating.
3 Magnum SBSE current limiting power circuit breaker with fast opening contacts.
4 Breaker applied in a tested fan-cooled enclosure.
1
1
1
V9-T1-38
SBN-840
Volume 9—OEM—Original Equipment Manufacturer CA08100011E—March 2013 www.eaton.com
SBS-850
SBS-C60 4
Circuit Protection
Circuit Breakers
1.1
Magnum IEC 60947-2 Rated Low Voltage Air Circuit Breakers
rms Symmetrical Current Ratings kA 1
200, 250, 300, 400, 630, 800
Breaker
Type
800
MWN-408
Narrow
40
40
40
40/—
—
MWN-508
Narrow
50
50
50
50/—
—
1250
1600
2000
2500
3200
Interrupting at
240 Vac ICU = ICS
Available Current Sensor and Rating
Plugs for Digitrip RMS Trip Unit
(Establishes Breaker In Rating)
Frame
Amperes
1000
Frame
Type
Fixed
Internal
Inst. Trip
Interrupting at
440 Vac ICU = ICS
Interrupting at
690 Vac ICU = ICS
Withstand Rating
ICW 1-Sec/3-Sec
MWN-608
Narrow
65
65
65
65/40
—
MWI-608
Standard
65
65
65
65/—
—
MWI-808
Standard
85
85
85
85/65
—
MWI-C08
Standard
100
100
85
85/65
85
MWN-410
Narrow
40
40
40
40/—
—
MWN-510
Narrow
50
50
50
50/—
—
MWN-610
Narrow
65
65
65
65/40
—
MWI-610
Standard
65
65
65
65/—
—
MWI-810
Standard
85
85
85
85/65
—
MWI-C10
Standard
100
100
85
85/65
85
MWN-412
Narrow
40
40
40
40/—
—
MWN-512
Narrow
50
50
50
50/—
—
MWN-612
Narrow
65
65
65
65/40
—
MWI-612
Standard
65
65
65
65/—
—
MWI-812
Standard
85
85
85
85/65
—
MWI-C12
Standard
100
100
85
85/65
85
MWN-516
Narrow
50
50
50
50/—
—
MWN-616
Narrow
65
65
65
65/40
—
MWI-616
Standard
65
65
65
65/—
—
MWI-816
Standard
85
85
85
85/65
—
MWI-C16
Standard
100
100
85
85/65
85
MWN-520
Narrow
50
50
50
50/30
—
MWN-620
Narrow
65
65
65
65/40
—
MWI-620
Standard
65
65
65
65/50
—
MWI-820
Standard
85
85
85
85/65
—
MWI-C20
Standard
100
100
85
85/65
85
MWI-625
Standard
65
65
65
65/—
—
MWI-825
Standard
85
85
85
85/65
—
MWI-C25
Standard
100
100
85
85/65
85
MWI-632
Standard
65
65
65
65/50
—
MWI-832
Standard
85
85
85
85/65
—
MWI-C32
Standard
100
100
85
85/65
85
MWI-64N
Double
65
65
65
65/—
—
MWI-84N
Double
85
85
85
85/—
—
MWI-C4N
Double
100
100
100
100/—
—
5000
MWI-85N
Double
85
85
85
85/—
—
MWI-C5N
Double
100
100
100
100/—
—
6300
MWI-86N
Double
85
85
85
85/—
—
MWI-C6N
Double
100
100
100
100/—
—
4000
1
1
1
1
1
200, 250, 300, 400, 630, 800, 1000
1
1
1
1
200, 250, 300, 400, 630, 800, 1000, 1250
1
1
1
200, 250, 300, 400, 630, 800, 1000, 1250,
1600
1
1
1
200, 250, 300, 400, 630, 800, 1000, 1250,
1600, 2000
1
1
1
200, 250, 300, 400, 630, 800, 1000, 1250,
1600, 2000, 2500
1
1
200, 250, 300, 400, 630, 800, 1000, 1250,
1600, 2000, 2500, 3200
1
1
2000, 2500, 3200, 4000
1
2500, 3200, 4000, 5000
1
3200, 4000, 5000, 6300
1
1
Note
1 Interrupting ratings shown based on breaker equipped with integral Digitrip RMS trip unit. Interruption ratings for non-automatic breakers are
equal to the published breaker Icw rating.
1
1
1
1
Volume 9—OEM—Original Equipment Manufacturer CA08100011E—March 2013 www.eaton.com
V9-T1-39
1.2
1
1
Circuit Protection
Fuse Blocks and Fuse Holders
Product Overview
Fuse Blocks and Fuse Holders
1
1
1
1
1
1
1
Description
C350 Series
Page V9-T1-41
Technical Data
Number of poles
Up to 3
Mounting
35 mm flat or 32 mm asymmetrical DIN rail
(with optional adapter)
Terminal ratings
600V, 30A
Housing construction
Thermoplastic UL 94VO flammability rating
1
Clip/terminal construction
Tin-plated copper alloy
Screw/pressure plate construction
Zinc-plated steel
1
Dielectric strength
1200V
Approvals
1
1
UL, CSA
For our complete product offering, see Volume 4—Circuit
Protection, CA08100005E.
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
V9-T1-40
Volume 9—OEM—Original Equipment Manufacturer CA08100011E—March 2013 www.eaton.com
1.2
Circuit Protection
Fuse Blocks and Fuse Holders
Features
C350 Series Fuse Blocks and Fuse Holders
●
●
●
1
Space-saving design
Rated 600V, 30A
UL approved for motor loads
1
1
1
1
1
1
1
1
Product Selection
C350 Series
1
Fuse Blocks and Fuse Holders
1
250V
Wire Termination
Number
of Poles
30A
Catalog Number
600V
Carton
Qty.
60A
Catalog Number
Carton
Qty.
30A
Catalog Number
Carton
Qty.
60A
Catalog Number
Carton
Qty.
Class H Fuse Holders
Single collar (box lug)—sized to ampere
rating
Combination of double quick-connect,
20A max., and pressure plate screw,
#10 max., Cu only
Combination of double quick-connect,
20A max., and binding head screw,
#10 max., Cu/Al
Combination of double quick-connect,
20A max., and pressure plate screw,
#10 max., Cu only
W231HA
10
W261HA
10
W631HA
10
W661HA
1
W232HA
5
W262HA
5
W632HA
5
W662HA
1
3
W233HA
5
W263HA
5
W633HA
1
W663HA
2
1
1
—
—
—
—
WM631F
10
—
—
1
2
—
—
—
—
WM632F
8
—
—
3
—
—
—
—
WM633F
6
—
—
1
—
—
—
—
WM631G
10
—
—
2
—
—
—
—
WM632G
8
—
—
3
—
—
—
—
WM633G
6
—
—
1
WR231HA
10
—
—
WR631HA
10
—
—
2
—
—
—
—
WR632HA
5
—
—
3
WR233HA
5
WR263HA
1
WR633HA
5
WR663HA
5
1
—
—
—
—
—
—
—
—
2
—
—
—
—
WMR632F
1
—
—
3
—
—
—
—
WMR633F
6
—
—
1
—
—
—
—
WMR631G
10
—
—
3
—
—
—
—
WMR633G
6
—
—
—
—
WRR633G
6
—
—
3
—
—
1
1
1
1
1
1
1
1
1
Class R Fuse Holder, Type WRR Control Transformer Fuse Block
Combination of double quick-connect,
20A max., and pressure plate screw,
#14–#10 Cu only
1
1
Class R Fuse Holders
Single collar (box lug)—sized to ampere
rating
1
2
Class M Fuse Holders
Combination of double quick-connect,
20A max., and binding head screw,
#10 max., Cu/Al
1
1
1
1
1
1
Volume 9—OEM—Original Equipment Manufacturer CA08100011E—March 2013 www.eaton.com
V9-T1-41
1.3
1
1
1
Circuit Protection
Rotary Disconnect Switches
Open Rotary Disconnects
Product Overview
Rotary Disconnect Switch Selection Guide
1
1
1
1
Description
1
1
R9 Series
Non-Fusible 30–100A Compact
R9 Series
Non-Fusible 100–1200A
Page V9-T1-44
Page V9-T1-46
Page V9-T1-48
R5 Series (UL 508 listed) products are manually
operated modular switches. Load break switching
and isolation provide safety solutions for any low
voltage circuit, particularly for machine and control
circuits. The R5 Series products are manual motor
controllers suitable as motor disconnect.
The R9 Series (UL 98 listed) non-fusible 30–100A
compact range ensures making or breaking on
load and safety isolation for low voltage electrical
circuits, particularly for machine control circuits
up to 600V.
The R9 Series (UL 98 listed) non-fusible 100–1200A
are manually operated multipole load-break switches.
Quick-make, quick-break design provides safety
isolation for any low voltage circuit.
UL 508 listed, Guide NLRV, File E165150
CSA C22.2 No.14, File 217736
IEC 60947-3, EN 60947-3
CCC
UL 98, File E222859
CSA 22.2 No. 4, File 217736
IEC 60947-3
EN 60947-3
UL 98, File E222859
CSA 22.2 No. 4, File 217736
IEC 60947-3
EN 60947-3
R9 Series
Fusible 30–800A
R9 Series
DC Rated Disconnects
Manual Transfer Switches
Page V9-T1-50
Page V9-T1-55
Page V9-T1-56
R9 Series (UL 98 listed) Fusible 30–800A manual
operated multi-pole fusible disconnect switches
use double break contacts per pole that ensure
complete isolation of the fuse when the switch
is in the OFF position.
UL listed disconnect switches 600 Vdc for
photovoltaic applications 100 to 400A
R9 Series (UL 98 listed) non-fusible disconnects are
heavy-duty manual transfer switches, they transfer
load manually between two low voltage circuits and
provide safety disconnection.
Product Description
1
1
1
R5 Series
Non-Fusible 16–80A
Approvals
1
1
1
1
1
1
1
1
Description
1
Product Description
1
1
When installed with fuses, they provide protection
for low voltage electrical installations against short
circuit and overload.
1
1
These switches are extremely durable and are tested
and approved for use in the most demanding
applications as resistive load or total system
applications.
Approvals
UL 98, File E222859 for 30 to 800A ratings
UL 489, File E305341 for H Frame switches
CSA 22.2 No. 4, File 217736
CSA 22.2 No. 5, File 217736, H Frame only
IEC 60947-1, EN 60947-1
IEC 60947-3, EN 60947-3
CE mark
NFPA® 79
1
1
1
1
R9 Series (UL 98 listed) DC rated disconnects are
manually operated multi-pole load break switches.
They provide safety isolation for any low voltage
circuit in a photovoltaic application.
UL 98, cULus®, File E222859
CSA 22.2 No. 4, File 217736 1
IEC 60947-3
EN 60947-3
IEC 60-364-7-712 (Rules for the installations and
sites special—photovoltaic applications)
UL 98, cULus, File E222859
UL 1008 (2011)
CSA 22.2 No. 4, File 217736
IEC 60947-3
EN 60947-3
Note
1 Q4 2010
1
V9-T1-42
Volume 9—OEM—Original Equipment Manufacturer CA08100011E—March 2013 www.eaton.com
Circuit Protection
Rotary Disconnect Switches
1.3
Catalog Number Selection
1
Disconnects
1
R5 A 3 016 U
UL Listing
R5 = UL 508
R9 = UL 98
R4 = UL 489
A
B
C
V
D
E
F
G
H
I
J
K
L
M
N
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
Frame Designation
UL 508 (16–40A)
UL 508 (60–80A)
UL 98 Non-fusible (30–100A modular)
UL 98 Non-fusible (60–100A visible blade)
UL 98 Non-fusible (100–200A)
UL 98 Non-fusible (400A)
UL 98 Non-fusible (600A)
UL 98 Non-fusible (800–1200A)
UL 489 Fusible (30A compact)
UL 98 Fusible (30A)
UL 98 Fusible (30–60A)
UL 98 Fusible (60–100A)
UL 98 Fusible (200A)
UL 98 Fusible (400A)
UL 98 Fusible (600–800A)
Phase
2 = Two-pole
3 = Three-pole
4 = Four-pole
Ampere Rating
016 = 16A
025 = 25A
030 = 30A
040 = 40A
060 = 60A
080 = 80A
100 = 100A
200 = 200A
400 = 400A
600 = 600A
800 = 800A
1000 = 1000A
1200 = 1200A
1
Fuse Type Accepted
CC = Class CC
J = Class J
L = Class L
Blank = Non-fusible device
1
1
1
1
Protection
U = Non-fusible
F = Fusible
1
1
1
1
1
External Handles
1
SH B 00 4X F
1
Handle Type
SH = Selector handle
PH = Pistol handle
Color
B = Black/blue
R = Red/yellow
Size
(Smallest to Largest)
00 = Size 00
0 = Size 0
1 = Size 1
2 = Size 2
3 = Size 3
4 = Size 4
NEMA Type Rating
12 = Type 1, 3R, 12
4X = Type 4, 4X
Additional Features 1
T = Test position function
Blank = No test function
1
1
1
Operation
F = Front
S = Right side
Blank = Front or right side
1
1
1
Shafts
SF 150 SH 5X5
Product Type
SF = Shaft
1
1
Additional Features 2
55
90
150
200
320
400
500
Length
= 55 mm
= 90 mm
= 150 mm
= 200 mm
= 320 mm
= 400 mm
= 500 mm
Applicable
Handle Type
SH = Selector handle
PH = Pistol handle
Shaft Cross Section
5x5 = 5 mm x 5 mm
6x6 = 6 mm x 6 mm
10x10 = 10 mm x 10 mm
12x12 = 12 mm x 12 mm
15x12 = 15 mm x 12 mm
1
1
1
1
Notes
1 HV at the end of some catalog numbers indicates use with H and V switches only. Not all handles are designed to go with all disconnects.
Consult specific section of the catalog for available options.
2 H at the end of some catalog numbers indicates use with H Frame switches only. Not all shafts are designed to go with all disconnects.
Consult specific section of the catalog for available options.
1
1
1
1
Volume 9—OEM—Original Equipment Manufacturer CA08100011E—March 2013 www.eaton.com
V9-T1-43
1.3
1
Circuit Protection
Rotary Disconnect Switches
Features
R5 Series Non-Fusible 16–80A
●
1
●
1
●
●
●
1
●
●
Up to 65 kAIC short-circuit rating
Direct or external operation
Compact footprint
DIN rail or base mount
Wide range of accessories
Modular design
Padlockable design (direct, toggle and external handles)
1
1
1
1
1
R5 Series Non-Fusible 16–80A
1
6
1
1
5
1
1
1
1
1
4
2
1
1
3
1
1
1
Product Identification
1
2
3
1
4
1
6
5
External front handle
Shaft extension for external handle
Direct handle
Auxiliary contacts
Switched fourth-pole module
Terminal shroud
Note: For further details, please see the installation instructions supplied with each device.
1
1
1
1
1
1
1
V9-T1-44
Volume 9—OEM—Original Equipment Manufacturer CA08100011E—March 2013 www.eaton.com
1.3
Circuit Protection
Rotary Disconnect Switches
Product Selection
1
Direct Operation
External Operation
+
Switch body
+
+
Direct handle
Switch body
+
1
+
Shaft
+
1
1
External handle
1
R5 Series
1
1
1
Ampere
Rating
Three-Pole Toggle
Switch Only 1
Three-Pole Rotary
Switch Only
Direct
Handle
16
—
R5A3016U
DHR5
25
—
R5A3025U
30
T5A3030U
R5A3030U
40
T5A3040U
R5A3040U
60
T5B3060U
R5B3060U
80
T5B3080U
R5B3080U
1
Front and Right
External Handle SH00
(Choose One)
Front and Right
External Handle SH0
(Choose One)
Three-Position Front
External Handle
SH00 (Black) 2
Shaft for SH0 and
SH00—5 x 5 mm—
In (mm)
SH00
Black
3R, 12
SHB00N12
SH0
Black
3R, 12
SHB0N12
SH00
4, 4X
I–0–II
Open transition
SHB00MTSOT
2.20 (55.5)
SF55SH5X5
3.50 (90.0)
SF90SH5X5
SH00
Red
3R, 12
SHR00N12
SH0
Red
3R, 12
SHR0N12
1
5.90 (150.0)
SF150SH5X5
1
SH00
Black
4, 4X
SHB00N4X
SH0
Black
4, 4X
SHB0N4X
SH00
4, 4X
I–I+II–II
Closed transition
SHB00MTSCT
7.90 (200.0)
SF200SH5X5
1
12.60 (320.0)
SF320SH5X5
1
SH00
Red
4, 4X
SHR00N4X
SH0
Red
4, 4X
SHR0N4X
1
1
1
1
1
Accessories
1
1
1
Ampere
Rating
Switched Fourth-Pole
Module
Unswitched Neutral
Module
Auxiliary Contacts
(Choose One)
Terminal
Shrouds
Conversion Kit
(Choose One) 2
Door
Mounting Kit 3
16
S4PR516
UNMR5A
S4PR525
1NO + 1NC
AC1NON
1P
TS1R5A
6/8 pole
CKR568
DMK
25
30
S4PR530
3P
TS3R5A
Changeover switch
Open transition
I–0–II
MTSCKR5OT
40
S4PR540
60
S4PR560 2
80
S4PR580 2
2NO
AC2N
UNMR5B
1P
TS1R5B
3P
TS3R5B
1
1
1
1
1
Changeover switch
Closed transition
I–I+II–II
MTSCKR5CT
1
Notes
1 Toggle version includes direct handle.
2 Available Q2 2011.
3 Includes shaft and accessory cap.
1
1
1
Volume 9—OEM—Original Equipment Manufacturer CA08100011E—March 2013 www.eaton.com
V9-T1-45
1.3
1
Circuit Protection
Rotary Disconnect Switches
Features
Non-Fusible 30–100A Compact
●
1
●
1
●
●
Rating three-pole from 30A to 100A
Direct or external operation handle (padlockable in
ON position)
Double breaking per phase
Small footprint
1
1
1
1
1
1
R9 Series Non-Fusible 30–100A Compact
1
1
4
1
1
1
1
1
5
6
1
7
1
1
8
1
1
1
1
3
1
1
1
2
Product Identification
1
1
1
1
1
2
3
4
5
6
7
8
Direct handle
Door interlocked external handle
Shaft extension
Terminal shrouds
Unswitched neutral pole
Switch body
Switched fourth-pole module
Modular type auxiliary contacts
Note: For further details, please see the installation instructions supplied with each device.
1
V9-T1-46
Volume 9—OEM—Original Equipment Manufacturer CA08100011E—March 2013 www.eaton.com
Circuit Protection
Rotary Disconnect Switches
1.3
Product Selection
1
Direct Operation
External Operation
+
Switch body
+
+
Direct handle
Switch body
+
1
+
Shaft
+
1
1
External handle
1
R9 Series 30–100A
1
1
1
Ampere
Rating
(Frame)
Number
of Poles
Switch Body
Only
Direct
Handle
30
(C Frame)
3
R9C3030U
DHR9
60
(C Frame)
3
R9C3060U
100
(C Frame)
3
R9C3100U
Front and
Right External
Handle SH00
(Choose One)
Front and
Right External
Handle SH0
(Choose One)
SH00
Black
3R, 12
SHB00N12
SH0
Black
3R, 12
SHB0N12
SH00
Red
3R, 12
SHR00N12
SH0
Red
3R, 12
SHR0N12
SH00
Black
4, 4X
SHB00N4X
SH0
Black
4, 4X
SHB0N4X
SH00
Red
4 4X
SHR00N4X
SH0
Red
4 4X
SHR0N4X
Shaft for SH0
and SH00
Handles—
In (mm)
(Choose One)
2.20 (55.5)
SF55SH5X5
3.50 (90.0)
SF90SH5X5
1
Switched
Fourth-Pole
Module
Unswitched
Neutral
Module
Auxiliary
Contacts
(Choose One)
Terminal Shrouds
(Choose One)
S4PR930
Neutral
UNMR9C
1NO + 1NC
AC1NONC
1P
TS1R9
2NO
AC2N
3P
TS3R9CV
S4PR960
1
1
1
1
S4PR9100
5.91 (150.0)
SF150SH5X5
1
7.87 (200.0)
SF200SH5X5
1
12.60 (320.0)
SF320SH5X5
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
Volume 9—OEM—Original Equipment Manufacturer CA08100011E—March 2013 www.eaton.com
V9-T1-47
1.3
1
Circuit Protection
Rotary Disconnect Switches
Features
Non-Fusible 100–1200A
●
1
●
●
High thermal and dynamic withstand ratings
Arduous categories of applications
High electrical and mechanical endurances
1
1
1
1
1
1
1
R9 Series Non-Fusible 100–1200A
1
4
1
1
1
2
1
1
1
1
1
3
1
1
1
Product Identification
1
2
1
1
3
4
External front handle
Shaft extensions for external handle
Configurable U-type ACs, for pre-break and signalling or TEST
Terminal Screens
Note: For further details, please see the installation instructions supplied with each device.
1
1
1
1
1
1
1
1
V9-T1-48
Volume 9—OEM—Original Equipment Manufacturer CA08100011E—March 2013 www.eaton.com
Circuit Protection
Rotary Disconnect Switches
1.3
Product Selection
1
Direct Operation
External Operation
+
Switch body
+
1
+
Direct handle
Switch body
+
1
+
Shaft
+
1
External handle
1
R9 Series Non-Fusible 100–1200A
1
1
1
1
Ampere Rating
(Frame)
Number
of Poles
Switch
Body Only
Direct
Handle
100
(D Frame)
3
R9D3100U
DHR9DE
4
R9D4100U
200
(D Frame)
400
(E Frame)
3
R9D3200U
4
R9D4200U
3
R9E3400U
4
R9E4400U
Door Interlocked
External Pistol Handle
(Choose One)
Size 2, Black
1, 3R, 12
Defeatable
PHB2N12F
Size 2, Red
1, 3R, 12
Defeatable
PHR2N12F
Size 2, Black
4, 4X
Defeatable
PHB2N4XF
Terminal Screens
(Choose One)
Terminal
Lugs 3
7.90 (200.0)
SF200PH10X10
3-pole, Line side only
TS3R9DT
LK3R9DL
12.60 (320.0)
SF320PH10X10
15.70 (400.0)
SF400PH10X10
1NO + 1NC
AC1N0NCDE
AC1N0NCDELL
2NO + 2NC
AC2N0NCDE
AC2N0NCDELL
3
R9F3600U
4
R9F4600U
3
R9G3800U
4
R9G4800U
1000
(G Frame)
3
R9G31000U
4
R9G41000U
1200
(G Frame)
3
R9G31200U
4
R9G41200U
800
(G Frame)
DHR9FG
Size 3, Black
4, 4X
Defeatable
PHB3N4XF
Size 3, Red
4, 4X
Defeatable
PHR3N4XF
Size 4, Black
4, 4X
Defeatable
PHB4N4XF
3-pole, Load side only
TS3R9DB
1
1
LK4R9DL
LK3R9DL
1
LK4R9DL
4-pole, Line or load side
TS4R9DTB
3-pole, Line side only
TS3R9ET
19.70 (500.0)
SF500PH10X10
Size 2, Red
4, 4X
Defeatable
PHR2N4XF
600
(F Frame)
1
Shaft Extensions for
External Handle—
In (mm)
Auxiliary
(Choose One)
Contacts
1
LK3R9EM
1
LK4R9EM
3-pole, Load side only
TS3R9EB
1
4-pole, Line or load side
TS4R9ETB
1
1
7.90 (200.0)
SF200PH15X12
1NO AC U Type
AC1N0R9 2
12.60 (320.0)
SF320PH15X12
1NC AC U Type
AC1NCR9 2
1
LK3R9FN
TS4R9F 1
LK4R9FN
TS3R9G 1
LK6R9G
LK8R9G
TS3R9F
TS4R9G 1
1
1
1
1.70 (400.0)
SF400PH15X12
1
19.7 (500.0)
SF500PH15X12
1
1
Size 4, Red
4, 4X
Defeatable
PHR4N4XF
1
1
Notes
1 Top (line side) supplied as standard.
2 Auxiliary contact requires holder (catalog number ACHFG) when used on F and G Frame switches (non-fusible 600–1200A).
3 Each catalog number is for line or load side. For both line and load, please order two sets.
1
1
1
1
Volume 9—OEM—Original Equipment Manufacturer CA08100011E—March 2013 www.eaton.com
V9-T1-49
1.3
1
Circuit Protection
Rotary Disconnect Switches
Features
Fusible 30–800A
●
1
●
●
1
●
●
1
●
1
●
●
1
Load break functionality
Double break contacts
Up to 200 kA short-circuit rating with Class CC, J or L fuses
Compact footprints
Defeatable pistol handles automatically re-latch when the
panel door is closed
Front or right side operation
NFPA 79 compliant kits
Two-, three- and four-pole devices
1
1
1
1
1
R9 Series Fusible 30–800A
R9 Fusible 30A/J–800A/L (I–N Frames)—
Direct and External Operation
R9 Fusible 30A/CC and 30A/J (H Frame)—
Direct and External Operation
7
1
1
3
1
6
1
2
1
4
4
1
2
1
4
1
1
5
1
1
1
Product Identification
1
2
3
4
3
External front handles
Direct handle
Shaft extensions for external handles
Configurable U Type ACs, for pre-break and signaling or TEST
1
Product Identification
1
1
2
1
3
4
1
5
6
7
1
External front handles
External right side handle (not applicable for N Frame 600/800A)
Direct handle
Shaft extensions for external handles
Configurable U Type ACs, for pre-break and signaling or TEST
Side auxiliary contacts
Terminal shrouds
1
1
1
1
V9-T1-50
Volume 9—OEM—Original Equipment Manufacturer CA08100011E—March 2013 www.eaton.com
1.3
Circuit Protection
Rotary Disconnect Switches
Product Selection
1
Direct Operation
External Operation
+
Switch body
+
+
Direct handle
Switch body
+
1
+
Shaft
+
1
1
External handle
1
Front and Right Side Operation
1
1
1
Ampere Rating
(Frame)
(Fuse Class)
Number
of Poles
Switch
Body Only
Direct
Handle
30
Compact
(H Frame) (CC)
3
R4H3030FCC
DHR9HC
30
(H Frame) (CC)
3 + switched neutral
R4H3030FCCSN
30
Compact
(H Frame) (J)
3
R4H3030FJ
30
(H Frame) (J)
3 + switched neutral
DHR9HJ
External Selector
Handle
(Choose One)
Shaft Extension for
Selector Handle Only
(Choose One)
Black
1,3R,12
SHB0N12HV
Red
1,3R,12
SHR0N12HV
External Front
Pistol Handle
External Right
Side Pistol Handle
7.90 (200.0)
SF200SH5X5H
Black
1,3R,12
PHB1N12F
—
12.60 320.0)
SF320SH5X5H
Red
1,3R,12
PHR1N12F
15.70 (400.0)
SF400SH5X5H
Black
4,4X
SHB0N4XHV
R4H3030FJSN
30
(I Frame) (CC)
30
(J Frame) (J)
60 1
(J Frame) (J)
3
R9I3030FCC
4
R9I4030FCC
2
R9J2030FJ
3
R9J3030FJ
4
R9J4030FJ
2
R9J2060FJ
3
R9J3060FJ
4
R9J4060FJ
DHR9J2M
—
1
1
1
1
Black
4,4X
PHB1N4XF
Red
4,4X
SHR0N4XHV
—
1
1
Red
4,4X
PHR1N4XF
Black
4,4X
(w/ TEST Position)
PHB1N4XFT
Red
4,4X
(w/ TEST Position)
PHR1N4XFT
1
1
1
Black
4, 4X
PHB1N4XS
1
Red
4, 4X
PHR1N4XS
1
1
Note
1 100 kA short-circuit rating.
1
1
1
1
1
1
1
1
1
1
Volume 9—OEM—Original Equipment Manufacturer CA08100011E—March 2013 www.eaton.com
V9-T1-51
1.3
1
Circuit Protection
Rotary Disconnect Switches
Front and Right Side Operation, continued
1
1
1
1
1
1
1
1
1
1
1
1
1
Ampere Rating
(Frame)
(Fuse Class)
Number
of Poles
Switch
Body Only
30
Compact
(H Frame) (CC)
3
R4H3030FCC
30
(H Frame) (CC)
3 + switched neutral
R4H3030FCCSN
12.60 (320.0)
SF320PH5X5
30
Compact
(H Frame) (J)
3
R4H3030FJ
15.70 (400.0)
SF400PH5X5
30
(H Frame) (J)
3 + switched neutral
R4H3030FJSN
30
(I Frame) (CC)
3
R9I3030FCC
4
R9I4030FCC
2
R9J2030FJ
3
R9J3030FJ
4
R9J4030FJ
2
R9J2060FJ
3
R9J3060FJ
4
R9J4060FJ
30
(J Frame) (J)
60 1
(J Frame) (J)
1
7.90 (200.0)
SF200PH5X5
7.90 (200.0)
SF200PH10X10
12.60 (320.0)
SF320PH10X10
15.70 (400.0)
SF400PH10X10
19.70 (500.0)
SF500PH10X10
NFPA79H
Auxiliary
Contacts
(Choose One)
S Type Auxiliary
Contacts
(Choose One)
Terminal
Shrouds
1 AC
NO
AC1NOR9
—
Integral to switch
1 AC
NC
AC1NCR
NFPA79JKL
1 AC
NO + NC
AC1NO1NCJ2N
2 AC
NO + NC
AC2NO2NCJ2N
1 AC
NO + NC
w/ TEST
AC1NO1NCJ2NT
2 AC
NO + NC
w/ TEST
AC2NO2NCJ2NT
1
1
Shaft Extensions for
Pistol Handle Only
In (mm)
NFPA
(Choose One)
79 Kit
Note
1 100 kA short-circuit rating.
1
1
1
1
1
1
1
1
1
1
1
1
1
V9-T1-52
Volume 9—OEM—Original Equipment Manufacturer CA08100011E—March 2013 www.eaton.com
Circuit Protection
Rotary Disconnect Switches
1.3
Front and Right Side Operation, continued
1
1
1
1
Ampere Rating
(Frame)
(Fuse Class)
60 1
(K Frame) (J)
100
(K Frame) (J)
200
(L Frame) (J)
400
(M Frame) (J)
Number
of Poles
Switch
Body Only
Direct Handle
(Black)
2
R9K2060FJ
DHR9J2M
3
R9K3060FJ
4
R9K4060FJ
2
R9K2100FJ
3
R9K3100FJ
4
R9K4100FJ
2
R9L2200FJ
3
R9L3200FJ
4
R9L4200FJ
3
R9M3400FJ
4
R9M4400FJ
External Front
Pistol Handle
(Choose One)
External Right Side
Pistol Handle (Choose One)
Black
1,3R,12
PHB2N12F
Black
4, 4X
PHB2N4XS
Red
1,3R,12
PHR2N12F
Red
4, 4X
PHR2N4XS
1
1
1
1
1
Black
4,4X
PHB2N4XF
Red
4,4X
PHR2N4XF
1
1
—
1
Black
4,4X
(w/ TEST Position)
PHB2N4XFT
1
1
Red
4,4X
(w/ TEST Position)
PHR2N4XFT
600
(N Frame) (J)
800
(N Frame) (L)
2
R9N2600FJ
3
R9N3600FJ
4
R9N4600FJ
2
R9N2800FL
3
R9N3800FL
4
R9N4800FL
DHR9N
1
Black
4, 4X
PHB3N4XF
1
1
Red
4,4X
PHR3N4XF
1
1
Note
1 200 kA short-circuit rating.
1
1
1
1
1
1
1
1
1
1
1
Volume 9—OEM—Original Equipment Manufacturer CA08100011E—March 2013 www.eaton.com
V9-T1-53
1.3
1
Circuit Protection
Rotary Disconnect Switches
Front and Right Side Operation, continued
1
1
1
1
1
1
1
Ampere Rating
(Frame)
(Fuse Class)
2
R9K2060FJ
3
R9K3060FJ
4
R9K4060FJ
100
(K Frame) (J)
2
R9K2100FJ
3
R9K3100FJ
4
R9K4100FJ
2
R9L2200FJ
3
R9L3200FJ
200
(L Frame) (J)
1
1
1
4
R9L4200FJ
400
(M Frame) (J)
3
R9M3400FJ
4
R9M4400FJ
600
(N Frame) (J)
2
R9N2600FJ
3
R9N3600FJ
4
R9N4600FJ
800
(N Frame) (L)
2
R9N2800FL
1
1
1
3
R9N3800FL
4
R9N4800FL
1
Shaft Extensions
for External Handle
In (mm) (Choose One)
7.90 (200.0)
Pistol
SF200PH10X10
NFPA
79 Kit
NFPA79JKL
12.60 (320.0)
Pistol
SF320PH10X10
15.70 (400.0)
Pistol
SF400PH10X10
Auxiliary
Contacts
(Choose One)
1 AC
NO
AC1NOR9
1 AC
NO + NC
AC1NO1NCJ2N
1 AC
NC
AC1NCR9
2 AC
NO + NC
AC2NO2NCJ2N
1 AC
NO + NC
w/ TEST
AC1NO1NCJ2NT
19.70 (500.0)
Pistol
SF500PH10X10
7.90 (200.0)
Pistol
SF200PH12X12
Auxiliary
Contacts
(Choose One)
2 AC
NO + NC
w/ TEST
AC2NO2NCJ2NT
NFPA79N
1 AC
NO + NC
AC1NO1NCJ2N
2 AC
NO + NC
AC2NO2NCJ2N
15.70 (400.0)
Pistol
SF400PH12X12
Note
1 200 kA short-circuit rating.
1
1
1
1
1
1
1
1
1
1
1
V9-T1-54
Terminal
Shrouds
Integral to switch
TSR9L2
TSR9L3
TSR9L4
TSR9M3
TSR9M4
TSR9N2
TSR9N3
TSR9N4
12.60 (320.0)
Pistol
SF320PH12X12
19.70 (500.0)
Pistol
SF500PH12X12
1
1
Switch
Body Only
60 1
(K Frame) (J)
1
1
Number
of Poles
Volume 9—OEM—Original Equipment Manufacturer CA08100011E—March 2013 www.eaton.com
TSR9N2
TSR9N3
TSR9N4
Circuit Protection
Rotary Disconnect Switches
1.3
Features
DC Rated Disconnects
●
●
●
1
Switching technology
Up to 600 Vdc according to UL 98/CSA
Up to 1000 Vdc according to IEC 947-3
1
1
1
1
1
1
1
1
R9 Series DC Rated Disconnects
1
Product Selection
+
Switch body
+
+
Direct handle
Switch body
+
1
+
Shaft
+
1
1
External handle
1
Front Operation—Three- and Four-Pole
1
1
1
Ampere Number Switch
Rating of Poles Body
100
200
3
R9D3100UDC
4
R9D4100UDC
3
R9D3200UDC
4
R9D4200UDC
Direct Handle
DHR9DE
Shaft for External
External Handle Handle
Auxiliary Contacts
(Choose One)
In (mm) (Choose One) (Choose One)
S2 Type
Black
1, 3R, 12 1
PHB2N12F
Red/Yellow
1, 3R, 12 1
PHR2N12F
7.90 (200.0)
SF200PH10X10
12.60 (320.0)
SF320PH10X10
15.7 0 (400.0)
SF400PH10X10
C Type
1st Contact
NO+NC
AC1NONCDE
C Type
2nd Contact
NO+NC
AC2NONCDE
Terminals
Shroud
Terminal Lugs
3P 2
TS3R9DT
3P 4
LK3R9DL
2 pieces
DCJUMPD2
1
3P 3
TS3R9DB
4P 4
LK4R9DL
3 pieces
DCJUMPD3
1
400
3
R9E3400UDC
4
R9E4400UDC
1
1
4P 4
TS4R9DTB
1
Black
4, 4X 1
PHB2N4XF
Red/Yellow
4, 4X 1
PHR2N4XF
1
Jumpers for
Connecting
Poles in Series
1
3P 2
TS3R9ET
3
3P
TS3R9EB
4
2 pieces
DCJUMPE2
1
4
3 pieces
DCJUMPE3
1
3P
LK3R9EM
4P
LK4R9EM
1
4P 4
TS4R9ETB
1
Notes
1 Defeatable handle.
2 Top (line side).
3 Bottom (load side).
4 Top or bottom (line or load side).
1
1
Volume 9—OEM—Original Equipment Manufacturer CA08100011E—March 2013 www.eaton.com
V9-T1-55
1.3
1
Circuit Protection
Rotary Disconnect Switches
Features
Manual Transfer Switches
●
1
●
●
1
●
●
Three load break positions (I, 0, II)
On load switching
Direct or external handle
480 Vac total system
600 Vac resistive load
1
1
1
1
1
1
Manual Transfer Switches
1
5
1
1
4
1
3
1
1
1
2
1
1
1
1
1
Product Identification
1
2
1
1
3
4
5
External front handle
Direct handle
Shaft extension for external handle
Pre-break ACs (standard on 600–1200A)
Terminal Screen
1
1
1
1
1
1
1
1
V9-T1-56
Volume 9—OEM—Original Equipment Manufacturer CA08100011E—March 2013 www.eaton.com
1.3
Circuit Protection
Rotary Disconnect Switches
Product Selection
1
Direct Operation
External Operation
+
Switch body
+
+
Direct handle
Switch body
+
1
+
Shaft
+
1
1
External handle
1
Manual Transfer Switches—UL 98 Standard 1
1
1
1
Ampere
Rating
Number Switch
of Poles Body Only 1
100
3
RMTS3100U
4
RMTS4100U
3
RMTS3200U
4
RMTS4200U
200
400
3
RMTS3400U
4
RMTS4400U
Direct
Handle (Black)
DHMTSSL
External ThreePosition Handle
(Choose One)
Size 2, Black
I–0–II
Type 4/4X
PHB2N4X3P
Size 2, Red
I–0–II
Type 4/4X
PHR2N4X3P
Size 3, Black
I–0–II
Type 4/4X
PHB3N4X3P
Size 3, Red
I–0–II
Type 4/4X
PHR3N4X3P
600
800
1200
3
RMTS3600U
4
RMTS4600U
3
RMTS3800U
4
RMTS4800U
3
RMTS31200U
4
RMTS41200U
DHMTSDL
DHMTSDLM
Size 4, Black
I–0–II
Type 4/4X
PHB4N4X3P
Size 4, Red
I–0–II
Type 4/4X
PHR4N4X3P
1
Shaft Extensions for
External Handle
In (mm)
(Choose One)
Bridging
Bars
Auxiliary
Contacts
Terminal
Screens 2
7.90 (200.6)
SF200PH10X10
3P
BB3P200
NO/NC
AC1NONCMTS400
3P
TS3MTS200TB
12.60 (320.0)
SF320PH10X10
4P
BB4P200
4P
Low level
AC1NONCMTS400LL 3 TS4MTS200TB
1
15.70 (398.8)
SF400PH10X10
1
1
1
1
7.90 (200.6)
SF200PH15X12
3P
BB3P400
3P
TS3MTS400TB
1
12.60 (320.0)
SF320PH15X12
4P
BB4P400
4P
TS4MTS400TB
1
1
15.70 (398.8)
SF400PH15X12
3P
BB3P600
NO/NC
contact
standard
1
3P
TS3MTS600
4P
BB4P600
4P
TS4MTS600
3P
BB3P1200
3P
TS3MTS1200
4P
BB4P1200
4P
TS4MTS1200
1
1
1
1
Notes
1 All ratings, 100–1200A, are UL 98 listed. Switches are to be UL 1008 listed in 2011.
2 Line or load (top or bottom); for both line and load, order two kits.
3 Low level auxiliary contact—gold plated for minimal resistance—for PLC applications.
1
1
1
1
1
1
1
1
Volume 9—OEM—Original Equipment Manufacturer CA08100011E—March 2013 www.eaton.com
V9-T1-57
1.3
1
Circuit Protection
Rotary Disconnect Switches
Features
Enclosed Rotary Disconnects
●
1
●
1
●
1
●
●
●
1
●
●
1
●
Padlockable in the OFF position (up to three padlocks) to meet
OSHA lockout requirements
Available in 16–80A ratings
600 Vac, three- and four-pole non-fusible device
Rated for making and breaking loads
Accepts auxiliary contacts; capability to signal PLC controllers
Ground lug connection provided
Possibility of adding one power pole and one auxiliary contact
NEMA Type 1, 3R, 12, 4, 4X
65kAIC rating when applied downstream from appropriate
fusing
1
1
1
1
1
1
1
Enclosed Rotary Disconnects
Provide users with the ability
to lock directly wired motor
loads in the OFF position to
comply with OSHA lockout/
tagout regulations. Also for
machine applications that
require compact, economical
disconnect switches.
1
Enclosed rotary disconnect
switches allow safe control
and safe disconnect of any
motor application.
Open rotary disconnects can
be found on Pages V9-T1-42
to V9-T1-57 and full
information in Volume 5,
Motor Control and Protection,
CA08100006E, Tab 34.
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
V9-T1-58
Volume 9—OEM—Original Equipment Manufacturer CA08100011E—March 2013 www.eaton.com
1.3
Circuit Protection
Rotary Disconnect Switches
Product Selection
1
1
Enclosed Rotary Non-Fusible
NEMA 1 1
Enclosure
Indoor
NEMA 12 1 2
Enclosure
Dust-Tight/
Rainproof
NEMA 4X 1
Enclosure
Corrosion-Resistant,
Stainless Steel
NEMA 4X 1
Enclosure
Corrosion-Resistant,
Non-Metallic
NEMA 4X
Enclosure
PolycarbonateNon-Metallic
Maximum Horsepower Ratings
Ampere
Rating
Three-Phase AC
208V
240V
480V
600V
Catalog Number
Catalog Number
Catalog Number
Catalog Number
Catalog Number
1
1
1
Three-Pole, 600 Vac
16
3
5
10
10
ER53016UG
ER53016UD
ER53016UW
ER53016UX
—
25
7-1/2
7-1/2
15
20
ER53025UG
ER53025UD
ER53025UW
ER53025UX
—
1
30
7-1/2
7-1/2
15
20
ER53030UG
ER53030UD
ER53030UW
ER53030UX
ER53030UPYR 34
40
7-1/2
7-1/2
20
25
ER53040UG
ER53040UD
ER53040UW
ER53040UX
—
60
15
15
30
30
ER53060UG
ER53060UD
ER53060UW
ER53060UX
ER53060UPYR 34
80
15
20
40
40
ER53080UG
ER53080UD
ER53080UW
ER53080UX
—
1
1
1
Four-Pole, 600 Vac
16
3
5
10
10
ER54016UG
ER54016UD
ER54016UW
ER54016UX
—
25
7-1/2
7-1/2
15
20
ER54025UG
ER54025UD
ER54025UW
ER54025UX
—
30
7-1/2
7-1/2
20
25
ER54030UG
ER54030UD
ER54030UW
ER54030UX
—
40
7-1/2
7-1/2
20
25
ER54040UG
ER54040UD
ER54040UW
ER54040UX
—
1
1
1
1
Accessories for Enclosed Rotary Disconnects 56
Disconnect
Ampere Rating
Switched
Fourth Pole
Unswitched
Neutral Pole
Auxiliary Contacts
(Choose One)
Terminal
Shrouds
16
S4PR516
UNMR5A
25
S4PR525
1NO + 1NC
AC1NONC
Single-pole
TS1R5A
30
S4PR530
40
S4PR540
2NC
AC2NC
Three-pole
TS3R5A
7
60
S4PR560
80
S4PR580 7
UNMR5B
7
1
1
1
Single-pole
TS1R5B
1
Three-pole
TS3R5B
1
Notes
1 For CSA listed switches, add prefix letter “C” to the front of the catalog number.
2 NEMA Type 12 enclosures (16–80A) can be field modified to meet NEMA Type 3R rainproof requirements when a factory-provided drain hole is opened.
3 YR suffix indicates Yellow cover with Red handle. For Gray cover with Black handle, replace “YR” with “GB.” For Gray cover with Red handle, replace “YR” with “GR.”
4 cULus only.
5 Ordered and shipped as separate components—not integral to enclosed device.
6 Enclosed disconnects can accept one power pole, neutral or up to two auxiliary contacts (one mounted on either side of switch).
7 Available 2011.
1
1
1
1
Contact the Safety Switch Flex Center (1-888-329-9272) for factory-installed accessories or other special modifications.
1
1
1
1
1
1
1
1
Volume 9—OEM—Original Equipment Manufacturer CA08100011E—March 2013 www.eaton.com
V9-T1-59
Motor Control and Protection
Contactors
2.1
Contactors
Product Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Compact Definite Purpose Contactors . . . . . . . . . . . . . . . . . . . . . . . .
50 mm C25 Definite Purpose Contactors . . . . . . . . . . . . . . . . . . . . . .
XT IEC Miniature Contactors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
XT IEC Contactors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2.2
2.3
2.4
2.5
V9-T2-7
V9-T2-9
V9-T2-15
V9-T2-17
V9-T2-19
V9-T2-22
V9-T2-23
V9-T2-26
V9-T2-32
V9-T2-36
V9-T2-37
V9-T2-41
Soft Starters
Product Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
DS7 Soft Start Controller . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
DS6 Soft Start Controller . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
S611 Soft Starter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
S801+ Soft Starter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
S811+ Soft Starter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Soft Starters
V9-T2-5
Manual Motor Protectors and Controllers
Product Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
XT IEC Manual Motor Protectors . . . . . . . . . . . . . . . . . . . . . . . . . . . .
XT IEC Manual and Combination Motor Controllers . . . . . . . . . . . . . .
Manual Motor Protectors
and Controllers
V9-T2-3
Motor Protection and Monitoring Relays
Product Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
D65 Series Monitoring Relays . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
D65C Series Monitoring Relays . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
XT IEC Miniature Overload Relays . . . . . . . . . . . . . . . . . . . . . . . . . . . .
XTOB, XTOT Thermal Overload Relays . . . . . . . . . . . . . . . . . . . . . . . .
XT Electronic Overload Relays . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Motor Insight Overload and Monitoring Relays . . . . . . . . . . . . . . . . . .
Motor Protection and
Monitoring Relays
V9-T2-2
V9-T2-47
V9-T2-48
V9-T2-50
V9-T2-51
V9-T2-55
V9-T2-58
Drives
Product Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
M-Max Machinery Drive . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
SVX9000 Drives . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
V9-T2-65
V9-T2-66
V9-T2-68
For our complete product offering, see Volume 5—Motor Control and Protection, CA08100006E
and Volume 6—Solid-State Motor Control, CA08100007E.
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
Drives
2
2
2
2
2
2
Volume 9—OEM—Original Equipment Manufacturer CA08100011E—March 2013 www.eaton.com
V9-T2-1
2.1
2
2
Motor Control and Protection
Contactors
Product Overview
Contactors Selection Guide
2
2
2
2
2
Description
2
Type
2
Approvals
2
Definite Purpose Contactors
XT IEC Miniature Contactors
XT IEC Contactors
Page V9-T2-3
Page V9-T2-7
Page V9-T2-9
Definite purpose
IEC
IEC
UL® Recognized, CSA®, CE, ARI, RoHS
UL, IEC EN 60947, CE, CSA, RoHS
UL, IEC EN 60947, CE, CSA, RoHS
Technical Data
2
Pole configurations
1P, 2P, 3P, 4P
3P, 4P
3P, 4P
Inductive Amp ratings
To 360A
To 8.8A (AC-3)
To 1600A (AC-3)
2
Resistive Amp ratings
To 360A
To 20A (AC-1)
To 3185A (AC-1)
Typical electrical operations
To 300,000
To 750,000
To 1,400,000
2
For our complete product offering, see Volume 5—Motor Control and Protection, CA08100006E.
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
V9-T2-2
Volume 9—OEM—Original Equipment Manufacturer CA08100011E—March 2013 www.eaton.com
Motor Control and Protection
Contactors
2.1
Features
Compact Definite Purpose Contactors
●
●
●
●
2
Insulation voltage: 690V
Current rated and hp/kW rated
Magnet coil: Class F, 155°C
Contact arc covers are standard on all contactors
2
2
2
2
2
2
2
2
Product Selection
Compact Definite Purpose Contactors—Open Type
2
Ampere Ratings 1
2
2
Resistive
Locked Rotor
240–277V
Catalog Number 2
30
40
150
C25ANB130_
40
50
240
C25ANB140_
2
2
Inductive Full Load
2
Single-Pole
Single-Pole with Shunt
30
40
150
C25CNB130_
40
50
240
C25CNB140_
2
25
35
150
C25BNB225_
2
30
40
150
C25BNB230_
40
50
240
C25BNB240_
Two-Pole
Magnet Coil Selection
AC Coil Voltage
50/60 Hz
Coil Suffix
24
T
110–120
A
208–240
B
2
2
Notes
1 Rating per pole.
2 Replace underscore (_) in catalog
number with coil suffix letter from table
at left.
2
2
2
2
2
2
2
2
2
2
2
Volume 9—OEM—Original Equipment Manufacturer CA08100011E—March 2013 www.eaton.com
V9-T2-3
2.1
2
2
Motor Control and Protection
Contactors
Catalog Number Selection
Definite Purpose Contactors
Definite Purpose Contactors
2
C 25 D N A 2 15 A A
2
2
2
Model
C = Contactor
A = Three-phase starter
B = Single-phase starter
2
Type
25 = Non-reversing contactors
27 = Non-reversing starters
29 = Non-reversing starters
65 = Reversing contactors
2
2
2
Contactor Frame Size
A = Compact, single-pole
B = Compact, two-pole
C = Compact, single-pole w/shunt
D = 15–50A, two- and three-pole
E = 25–40A, four-pole
F = 60–75A, two- and three-pole
G = 90A, two- and three-pole
H = 120A, two- and three-pole
K = 200 and 300A, three-pole
L = 360A, three-pole
For Starters Only
C = Common control wiring
S = Separate control wiring
2
2
2
2
2
2
Enclosure Type
N = Open with metal mounting plate
R = Open with DIN rail mounting adapter
(two- and three-pole, 15–50A contactors only)
G = NEMA Type 1 Enclosed
2
2
2
2
2
2
2
Auxiliary Contacts (Side Mount)
A = 1NO pressure plate
B = 1NC pressure plate
C = 1NO-1NC pressure plate
L = 1NO-1NC snap switch QC only
M = 2NO-2NC snap switch QC only
Coil Selection
A = 110–120 Vac, 50/60 Hz
R = 12 Vac, 50/60 Hz
B = 208–240 Vac, 50/60 Hz
T = 24 Vac, 50/60 Hz
C = 440–480 Vac, 50/60 Hz
1R = 12 Vdc
D = 550–600 Vac, 50/50 Hz
1T = 24 Vdc
H = 277 Vac, 60 Hz
1W = 48 Vdc
J = 220–240 Vac, 50/60 Hz
1A = 120 Vdc
L = 380–415 Vac, 50 Hz
Number of Poles
1 = Single-pole
2 = Two-pole
3 = Three-pole
4 = Four-pole
15 = 15A
25 = 25A
30 = 30A
40 = 40A
Power Terminals
A = Binding head screw
B = Binding head screw and quick connect terminals (side-by-side)
C = Screw/pressure plate 1
D = Screw/pressure plate and quick connect terminals (side-by-side) 1
E = Box lugs (posidrive setscrew)
F = Box lugs (posidrive setscrew) and quick connect terminals (side-by-side)
G = Binding head screw and quick connect terminals (vertical in-line)
H = Screw/pressure plate and quick connect ZZ terminals (vertical in-line) 1
J = Box lugs (posidrive setscrew) and quick connect terminals (vertical in-line)
K = Box lugs (hex socket allen head setscrew)
L = Box lugs (hex socket allen head setscrew) and quick connect terminals (side-by-side)
M = Box lugs (hex socket allen head setscrew) and quick connect terminals (vertical in-line)
Note
1 Not available on 50A devices.
2
2
2
2
2
2
2
V9-T2-4
Current Rating
50 = 50A
120 = 120A
60 = 60A
200 = 200A
75 = 75A
300 = 300A
90 = 90A
360 = 360A
Volume 9—OEM—Original Equipment Manufacturer CA08100011E—March 2013 www.eaton.com
Motor Control and Protection
Contactors
2.1
Features
50 mm C25 Definite Purpose Contactors
●
●
●
●
Contactors are dual-rated with inductive and resistive ratings,
as well as horsepower and kilowatt ratings
Contactors rated 15–50A are available with DIN rail mount as
a factory installed option
Magnet coil: Class B (C25E, F, G, H and K), 130°C
Ambient temperature: 150°F (65°C) maximum
2
2
2
2
2
2
2
2
2
Product Selection
2
50 mm C25 Definite Purpose Contactors
2
C25 Contactors—Open Type
Rating, Amperes
Resistive
Inductive Full Load per Pole
15
20
25
35
30
40
40
50
50
65
60
75
75
90
Line Voltage
C25DND315_
C25DRD315_
2
90
2
3
75
—
5
575
60
—
5
230
150
3
7-1/2
C25DND325_
460
125
—
10
C25END425_
575
100
—
10
230
180
5
10
C25DND330_
460
150
—
15
C25END430_
575
120
—
15
230
240
7-1/2
10
C25DNF340_
460
200
—
20
C25ENF440_
575
160
—
20
230
300
10
15
460
250
—
30
575
200
—
30
230
360
10
20
460
300
—
40
575
240
—
40
230
450
15
20
460
375
—
50
575
300
—
50
Coil
Suffix
24 4
24
T
110–120 5
110–120 5
A
208–240 5
208–240
B
AC
2
230
50 Hz
3
Maximum Motor Horsepower
Single-Phase
Three-Phase
Open Type with
DIN Rail Adapter
Catalog Number 12
460
Magnet Coil Selection
Voltage
60 Hz
Locked Rotor
Open Type with
Metal Mounting Plate
Catalog Number 12
Notes
1 Replace underscore (_) in catalog
number with magnet coil suffix from
table at left.
2 Carton quantities including 20
individually packaged units are available
for two- and three-pole units through
60A inductive.
2
C25DRD325_
2
2
C25DRD330_
2
2
C25DRF3340_
2
C25DNJ350_
C25DRJ350_
C25FNF360_
—
2
2
2
C25FNF375_
2
—
2
2
3
4
5
Class H AC coils available as option for
15–50A contactor. Add 2 before AC coil
suffix letter.
Available through 120A.
104–120V 50/60 Hz for 60A, 75A and all
four-pole contactors (25–40A).
6
Contactors with DC coils (only available
up to 75A) include an early break NC
auxiliary contact, C320KGD1.
2
2
2
DC 6
24
2
1T
2
Volume 9—OEM—Original Equipment Manufacturer CA08100011E—March 2013 www.eaton.com
V9-T2-5
2.1
2
Motor Control and Protection
Contactors
Reversing and Two-Speed Contactors—Open Type—Unwired, Mechanically Interlocked Only
2
Rating, Amperes
Inductive Full Load
Resistive
per Pole
2
15
20
2
25
35
2
2
30
40
2
2
40
50
2
2
50
65
2
2
2
2
2
Magnet Coil Selection
Voltage
60 Hz
Coil
Suffix 2
50 Hz
24
24
T
110–120 3
110–120 3
A
208–240 4
208–240
B
Line
Voltage
Locked
Rotor
Maximum Motor Horsepower
Open Type with
Metal Mounting Plate
Single-Phase
Three-Phase
Catalog Number 1
C65DND315_
230
90
2
3
460
75
—
5
575
60
—
5
230
150
3
7-1/2
460
125
—
10
575
100
—
10
230
180
5
10
460
150
—
15
15
575
120
—
230
240
7-1/2
10
460
200
—
20
575
160
—
20
230
300
10
15
460
250
—
30
575
200
—
30
C65DND325_
C65DND330_
C65DNF340_
C65DNJ350_
Notes
1 Replace underscore (_) with magnet coil
suffix from table at left.
2 Class H AC coils available as option for
15–50A contactor. Add 2 before AC coil
suffix letter.
3 104–120V 50/60 Hz for 60A, 75A.
4 Available through 50A.
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
V9-T2-6
Volume 9—OEM—Original Equipment Manufacturer CA08100011E—March 2013 www.eaton.com
2.1
Motor Control and Protection
Contactors
Features
XT IEC Miniature Contactors
2
Reversing or non-reversing
Three- and four-pole configurations
●
Three-pole XTMC
●
Four-pole XTMF
Panel or DIN rail mounting
IP20 finger and back-of-hand proof
Direct mount with XTOM miniature overload relays
●
●
●
●
●
2
2
2
2
2
2
2
2
Catalog Number Selection
XT IEC Miniature Contactors
2
Miniature Contactors
2
2
XT MC 6 A 10 A
Designation
XT = XT IEC power control
Type
MC = Three-pole FVNR
mini IEC contactor
Current Rating, AC-3
XTMC
6 = 6.6A
9 = 8.8A
Frame Size
A = 45 mm mini
Integral
Auxiliary Contact
01 = 1NC
10 = 1NO
A
B
T
TD
=
=
=
=
2
Coil Codes
110V 50 Hz, 120V 60 Hz
220V 50 Hz, 240V 60 Hz
24V 50/60 Hz
24 Vdc
2
2
2
Product Selection
2
Full Voltage Non-Reversing Miniature Contactors
Operational
Current AC-3
Amp Rating
380/400V
Conventional
Free Air Thermal
Current AC-1
at 50°C
Maximum kW Ratings AC-3
Maximum Three-Phase Motor Ratings
Three-Phase Motors, 50–60 Hz
Single-Phase hp Ratings
220–240V 380–400V 550V 660/690V 115V
200V
230V
200V
230V
460V
575V
Number
of Power Auxiliary Catalog Number—
Poles
Contacts Screw Terminals 1
6.6
20
1.5
3
3
3
1/4
3/4
1
1-1/2
2
3
3
3
1NO
XTMC6A10_
6.6
20
1.5
3
3
3
1/4
3/4
1
1-1/2
2
3
3
3
1NC
XTMC6A01_
8.8
20
2.2
4
4
4
1/2
1
1-1/2
2
3
5
5
3
1NO
XTMC9A10_
8.8
20
2.2
4
4
4
1/2
1
1-1/2
2
3
5
5
3
1NC
XTMC9A01_
8.8
20
2.2
4
4
4
1/2
1
1-1/2
2
3
5
5
4
—
XTMF9A00_
Magnet Coil Suffix
Coil Voltage
Suffix Code
110V 50 Hz, 120V 60 Hz
A
220V 50 Hz, 240V 60 Hz
B
24V 50/60 Hz
T
24 Vdc
TD
415V 50 Hz, 480V 60 Hz
C
550V 50 Hz, 600V 60 Hz
D
208V 60 Hz
E
IEC Utilization Categories
AC-1: Non-inductive or
slightly inductive loads.
AC-3: Squirrel cage motors—
starting, switching of motors
during running.
Three-Phase hp Ratings
2
2
2
2
2
2
Notes
1 Underscore (_) indicates magnet coil
suffix required. See table at left.
2 With DC operation: Integrated diode
resistor combination, coil rating 2.6W.
2
2
2
2
AC-4: Squirrel cage motors—
starting, plugging, inching.
2
2
2
2
Volume 9—OEM—Original Equipment Manufacturer CA08100011E—March 2013 www.eaton.com
V9-T2-7
2.1
Motor Control and Protection
Contactors
2
Accessories
2
Front Mount Auxiliary Contacts 1
2
2
Conventional Free
Air Thermal Current,
Ith = Ie, AC-1 in Amps
Contact
Contact
Configuration Sequence
Package Catalog Number—
Qty.
Screw Terminals
10
1NO-1NC
5
XTMCXFA11
5
XTMCXFA22
5
XTMCXFA31
5
XTMCXFA40
53 61
54 62
2
10
2NO-2NC
2
2
2
10
3NO-1NC
53 61 71
83
54 62 72
84
53 61 73 83
54 62 74 84
10
4NO
2
53 63 73 83
54 64 74 84
2
2
XT IEC Miniature Contactors
Package
Qty.
Catalog Number
2
Description
Mechanical interlock
5
XTMCXML
2
Reversing link kit—main current wiring for reversing
contactors and starters
1
XTMCXRL 2
2
Connector—for mechanically arranging contactors and
timing relays in combinations
50
XTMCXCN 3
2
Notes
1 For two contactors with AC or DC operated magnet system that are horizontally or vertically
mounted, the distance between contactors is 0 mm, and the mechanical lifespan is 2.5 x 106
operations. The following control cables are integrated as part of the electrical interlock:
K1M: A1—K2M: 21; K1M: 21—K2M: A1.
2 Reversing link kit does not include mechanical interlock.
3 0 mm distance between contactors.
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
V9-T2-8
Volume 9—OEM—Original Equipment Manufacturer CA08100011E—March 2013 www.eaton.com
Motor Control and Protection
Contactors
2.1
Features
XT IEC Contactors
●
●
●
●
●
●
●
●
Reversing or non-reversing contactors
AC-3 contactor ratings to 1600A and AC-1 contactor ratings to
2000A
Panel or DIN rail mounting to 65A
IP20 finger and back-of-hand proof
Built-in NO or NC auxiliary contacts to 32A
Built-in surge suppression on DC coils XTCE Frame B-G and
AC or DC coils on XTCE Frame L-R
Can be used with XT or C396 overload relays
Can be used with XTPR MMPs for manual motor controllers
or UL508 Type F combination motor controllers
2
2
2
2
2
2
2
2
2
Catalog Number Selection
XT IEC Contactors
2
Contactors
2
2
XT CE 007 B 01 A
2
Designation
XT = XT line of IEC control
Coil Codes
See Page V9-T2-12.
Type
CE = Three-pole FVNR IEC contactor
CS = Three-pole FVNR S Series IEC contactor
007 = 7A
009 = 9A
012 = 12A
015 = 15A
018 = 18A
025 = 25A
032 = 32A
040 = 40A
050 = 50A
065 = 65A
072 = 72A
2
2
Built-In Auxiliary Contact
01 = 1NC
00 = 0NO–0NC
10 = 1NO
22 = 2NO–2NC
Current Ratings, AC-3
080 = 80A
570 = 570A
095 = 95A
580 = 580A
115 = 115A
650 = 650A
150 = 150A
750 = 750A
170 = 170A
820 = 820A
185 = 185A
C10 = 1000A
225 = 225A
C14 = 1400A, AC-1
250 = 250A
C16 = 1600A, AC-3
300 = 300A
C20 = 2000A, AC-1
400 = 400A
500 = 500A
2
2
Frame Size Designation
B = 45 mm
L = 140 mm
C = 45 mm
M = 160 mm
D = 55 mm
N = 250 mm
F = 90 mm
P = 260 mm
G = 90 mm
R = 515 mm
H = 140 mm
2
2
2
2
2
2
2
2
2
2
2
2
2
Volume 9—OEM—Original Equipment Manufacturer CA08100011E—March 2013 www.eaton.com
V9-T2-9
2.1
2
2
2
2
Motor Control and Protection
Contactors
Product Selection
Full Voltage Non-Reversing Three-Pole Contactors, Frames B–G
UL/CSA Ratings
UL General
Purpose Amp
Rating
IEC Ratings
Single-Phase hp Ratings Three-Phase hp Ratings
115V
200V
230V
200V
230V
460V
575V
AC-3
Ie (A)
AC-1
(40°C)
Ie = Ith (A)
Maximum kW Ratings AC-3
Three-Phase Motors 50–60 Hz
220/230V 380/400V 415V
Auxiliary
660/690V Contacts
Catalog Number—
Screw Terminals 12
Frame B
2
20
1/4
3/4
1
1-1/2
2
3
5
7
22
2.2
3
4
3.5
1NO
XTCE007B10_
20
1/4
3/4
1
1-1/2
2
3
5
7
22
2.2
3
4
3.5
1NC
XTCE007B01_
2
20
1/2
1
1-1/2
3
3
5
7-1/2
9
22
2.5
4
5.5
4.5
1NO
XTCE009B10_
20
1/2
1
1-1/2
3
3
5
7-1/2
9
22
2.5
4
5.5
4.5
1NC
XTCE009B01_
2
20
1
2
2
3
3
10 3
10
12
22
3.5
5.5
7
6.5
1NO
XTCE012B10_
3
20
1
2
2
3
3
10
10
12
22
3.5
5.5
7
6.5
1NC
XTCE012B01_
20
1
2
3
5
5
10 3
10
15.5
22
4
7.5
8
7
1NO
XTCE015B10_
2
20
1
2
3
5
5
10 3
10
15.5
22
4
7.5
8
7
1NC
XTCE015B01_
2
40
2
2
3
5
5
10 3
15
18
40
5
7.5
10
11
1NO
XTCE018C10_
40
2
2
3
5
5
10 3
15
18
40
5
7.5
10
11
1NC
XTCE018C01_
40
2
3
5
7-1/2
10
15
20
25
45
7.5
11
14.5
14
1NO
XTCE025C10_
2
40
2
3
5
7-1/2
10
15
20
25
45
7.5
11
14.5
14
1NC
XTCE025C01_
40
3
5
5
10
10
20
25
32
45
10
15
18
17
1NO
XTCE032C10_
2
40
3
5
5
10
10
20
25
32
45
10
15
18
17
1NC
XTCE032C01_
63
3
5
7-1/2
10
15
30
40
40
60
12.5
18.5
24
23
—
XTCE040D00_
80
3
7-1/2
10
15
20
40
50
50
80
15.5
22
30
30
—
XTCE050D00_
88
5
10
15
20
25
50
60
65
98
20
30
39
35
—
XTCE065D00_
2
88
5
10
15
20
25
50
60
72
98
22
37
41
35
—
XTCE072D00_
2
125
7-1/2
15
15
25
30
60
75
80
110
25
37
48
63
—
XTCE080F00_
125
7-1/2
15
15
25
40
75
75
95
130
30
45
57
75
—
XTCE095F00_
2
Frame G
160
10
25
25
40
50
100
100
115
160
37
55
70
90
—
XTCE115G00_
180
10
25
30
40
60
125
125
150
190
48
75
91
96
—
XTCE150G00_
225 4
10
25
30
40
60
125
125
170
225
52
90
100
96
—
XTCE170G00_
2
2
2
2
2
2
2
2
2
Frame C
Frame D
Frame F
Notes
The 7–32A XTCE contactors have positively driven contacts between the integrated auxiliary contact and the auxiliary contact module as well as within
the auxiliary contact modules.
The 40–65A XTCE contactors have positively driven contacts within the auxiliary contact module. Six auxiliary contacts are possible with a combination
of side mounted and front mount auxiliary contacts.
DC operated contactors (Frames B–G, 7–150A) have a built-in suppressor circuit.
Frames B–C contactors with 1NC built-in auxiliary are mirror contacts (XTCE…B01_–XTCE…C01_).
1
2
2
2
2
3
4
Underscore (_) indicates magnet coil suffix required. See Page V9-T2-12.
For spring cage terminals, insert C after the fourth digit of the catalog number. Example: XTCE C 007B10A.
For 7–12A XTCEC contactors, the power, auxiliary and coil terminals are spring cage.
For 18–32A XTCEC contactors, the auxiliary and coil terminals are spring cage.
For 40–150A XTCEC contactors, the coil terminals only are spring cage.
For electrical life contactor application data, see Volume 5—Motor Control and Protection, CA08100006E, Tab 27.
For 180–225A, use 2 x 3/0 AWG wire.
2
2
2
2
V9-T2-10
Volume 9—OEM—Original Equipment Manufacturer CA08100011E—March 2013 www.eaton.com
2.1
Motor Control and Protection
Contactors
Full Voltage Non-Reversing Three-Pole Contactors, Frames H–R
UL/CSA Ratings
UL General
Purpose Amp
Rating
2
IEC Ratings
Three-Phase hp Ratings
200V
230V
460V
575V
AC-3
Ie (A)
AC-1
(40°C)
Ie = Ith (A)
Maximum kW Ratings AC-3
Three-Phase Motors 50–60 Hz
220/230V
380/400V
415V
660/690V 1
1000V 1
Auxiliary
Contacts
Catalog Number 2
2
Frame H—Electronic Coil
250
50
60
125
150
185
337
55
90
—
140
108
2NO-2NC
XTCE185H22_
250
60
75
150
200
225
386
70
110
—
215
108
2NO-2NC
XTCE225H22_
2
2
2
Frame L—Standard Coil (110/120V, 230/240 Vac Coil Only)
300
75
100
200
250
250
429
75
132
148
240
108
2NO-2NC
XTCS250L22_
350
100
125
250
300
300
490
90
160
—
195
132
2NO-2NC
XTCS300L22_
2
2
Frame L—Electronic Coil
300
75
100
200
250
250
429
75
132
148
240
108
2NO-2NC
XTCE250L22_
350
100
125
250
300
300
490
90
160
—
195
132
2NO-2NC
XTCE300L22_
2
Frame M—Standard Coil (110/120V, 230/240 Vac Coil Only)
450
125
150
300
400
400
612
125
200
240
344
132
2NO-2NC
XTCS400M22_
550
150
200
400
500
500
857
155
250
300
344
132
2NO-2NC
XTCS500M22_
2
2
Frame M—Electronic Coil
450
125
150
300
400
400
612
125
200
240
344
132
2NO-2NC
XTCE400M22_
550
150
200
400
500
500
857
155
250
300
344
132
2NO-2NC
XTCE500M22_
2
Frame N—Electronic Coil
2
630
200
200
400
600
580
980
185
315
348
560
600
2NO-2NC
XTCE580N22_ 3
700
200
250
500
600
650
1041
205
355
390
630
600
2NO-2NC
XTCE650N22_ 3
800
250
300
600
700
750
1102
240
400
455
720
800
2NO-2NC
XTCE750N22_ 3
850
290
350
700
860
820
1225
260
450
500
750
800
2NO-2NC
XTCE820N22_ 3
1100
350
420
850
980
1000
1225
315
560
610
1000
1000
2NO-2NC
XTCEC10N22_ 3
2
—
—
—
1714
—
—
—
—
—
2NO-2NC
XTCEC14P22_ 3
2
1200
1300
1600
2200
500
900
900
1600
1700
2NO-2NC
XTCEC16R22_ 3
2
2NO-2NC
3
Frame P—Electronic Coil
1400
—
—
Frame R—Electronic Coil
1600
2000
560
—
640
—
—
—
—
2450
—
Contactor Application Data
Catalog Prefix
Electrical Life (Operations) for 10 hp,
480V (14.2A) Applications
XTCE012B
1 million
XTCE015B
1.2 million
XTCE018C
2 million
—
—
—
—
XTCEC20R22_
Full Voltage Non-Reversing Three-Pole Contactors—
Contact Sequence (Circuit Symbols), Standard Offering
Contactor Frame
Auxiliary Contacts
B–C
1NO
Contact Sequence
A2 2 4 6 14
1NC
A1 1 3 5 21
D–G
—
A1 1 3 5
Notes
AC and DC operated contactors have a built-in suppressor circuit (Frames L–R, 185–2000A).
1
2
3
2
2
2
2
A2 2 4 6
2NO-2NC
2
2
A2 2 4 6 22
L–R
2
2
A1 1 3 5 13
B–C
2
A1 1 3 5 13 21 31 43
2
A2 2 4 6 14 22 32 44
2
For 185–500A contactors at 660/690V or 1000V: Do not reverse directly.
Underscore (_) indicates magnet coil suffix required. See Page V9-T2-12.
When operating the 580–2000A XTCE contactors with frequency inverters, the suppressor on
the load side must be removed. The load side suppressor must also be removed when
performing a high-voltage test—see Pub51204, Pub51209.
2
2
2
2
Volume 9—OEM—Original Equipment Manufacturer CA08100011E—March 2013 www.eaton.com
V9-T2-11
2.1
2
Motor Control and Protection
Contactors
Magnet Coil Suffix
Coil Voltage
Suffix Code
Coil Voltage
Suffix Code
2
Frames B–F
110V 50 Hz, 120V 60 Hz
A
100–120V 50/60 Hz
A
2
220V 50 Hz, 240V 60 Hz
B
190–240V 50/60 Hz
B
24V 50/60 Hz
T
480–500V 50/60 Hz
C
24 Vdc
TD
24–27 Vdc
TD
2
415V 50 Hz, 480V 60 Hz
C
Frames L–M, S-Series
550V 50 Hz, 600V 60 Hz
D
110–120V 50/60 Hz
A
2
208V 60 Hz
E
220–240V 50/60 Hz
B
2
100–120V 50/60 Hz
A
110–250V 40–60 Hz/DC
A
2
190–240V 50/60 Hz
B
250–500V 40–60 Hz
C
24V 50/60 Hz
T
24–48 Vdc
TD
2
24–27 Vdc
TD
Frames P–R
480–500V 50/60 Hz
C
220–250V 50–60 Hz/DC
2
Frame H
Frame G
Frame N
B
2
2
XTCR Reversing Contactor Components
Qty.
Frame
B
C
D
F
G
2
Contactor
XTCE…B01_
XTCE…B01_
XTCE…D00_
XTCE…F00_
XTCE…G00_
2
2
Auxiliary contact
XTCEXFAC20
XTCEXFAC20
XTCEXFBG11
XTCEXFBG11
XTCEXFBG11
1
Mechanical interlock
XTCEXMLB
XTCEXMLC
XTCEXMLD
XTCEXMLG
XTCEXMLG
2
1
Reversing link kit
XTCEXRLB
XTCEXRLC
XTCEXRLD
XTCEXRLG
XTCEXRLG
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
V9-T2-12
Volume 9—OEM—Original Equipment Manufacturer CA08100011E—March 2013 www.eaton.com
Motor Control and Protection
Contactors
2.1
Accessories
2
Auxiliary Contacts—Frames B–G
Conventional Thermal
Current, Open at 60°C
Ith = Ie, AC-1 in Amps Poles
Frames B–C
Contact
Configuration
2
Circuit Symbol
Pkg. Qty.
Catalog Number—
Screw Terminals
2
5
XTCEXFAC20
2
5
XTCEXFAC11
5
XTCEXFAC40
5
XTCEXFAC22
Frames B–C—Front (Top) Mount 1
16
2
2NO
16
2
1NO-1NC
53 63
2
54 64
53 61
2
54 62
16
4
4NO
16
4
2NO-2NC
53 6373 83
2
54 6474 84
5361 71 83
2
2
54 62 72 84
Frame B
Frame B—Side Mount 12
16
1
1NO
53
1
2
XTCEXSAB10
2
2
54
16
1
1NC
51
1
2
XTCEXSAB01
2
52
Frame C
2
Frame C—Side Mount 1
10
2
1NO-1NC
13 23 33 43
1
2
XTCEXSCC11 1
14 24 34 44
Frames D–G
2
2
Frames D–G 3
16
2
2NO
13 23
16
2
1NO-1NC
13 21
16
4
4NO-0NC
13 23 33 43
5
XTCEXFBG20
5
XTCEXFBG11
5
XTCEXFBG40
5
XTCEXFBG22
2
14 24
2
2
14 22
2
14 24 34 44
16
4
2NO-2NC
13 21 31 43
2
14 22 32 44
2
Notes
Interlocked opposing contacts, to IEC/EN 60947-5-1 Annex L (positively driven), within the auxiliary contact modules (not NO
[early make] and NC [late break] contacts) and for the built-in auxiliary contacts of the XTCE007_–XTCE032_ Auxiliary break
contact can be used as mirror contact to IEC/EN 60947-4-1 Annex F (not NC [late break] contact). No auxiliary contacts can
be fitted between two contactors.
1
2
3
2
2
Frames B–C cannot use both a side AND a top mount auxiliary contact at the same time.
Can be mounted to the left side of contactor only.
Cannot be used in combination with front (top) mount auxiliary contacts or mechanical interlocks.
For Frame D, six auxiliary contacts maximum (can be a combination of side and top mount units).
2
2
2
2
Volume 9—OEM—Original Equipment Manufacturer CA08100011E—March 2013 www.eaton.com
V9-T2-13
2.1
Contactors
Side Mount Auxiliary Contacts—Frames D–R, 40–2000A
2
Conventional Free Air
Thermal Current,
Ith = Ie, AC-1 in Amps
2
Poles
Contact
Configuration
Circuit Symbol
2
1NO-1NC
13
14
13
14
Pkg. Qty.
Catalog Number—
Screw Terminals
1
XTCEXSBN11
1
XTCEXSBR11
Frame D–R 12
43
22
44
21
32
43
22
31
2
21
31
10
44
Frames D–R
32
2
Motor Control and Protection
2
2
Frames H–R (Screw Mount) 2
Frames H–R
10
2
1NO-1NC
2
2
2
Mechanical Interlock 3
2
2
For Use with …
Package Qty.
Catalog Number
XTCEXMLB
XTCE007B–XTCE015B, XTCF020B
5
XTCEXMLB
XTCEXMLC
XTCE018C–XTCE032C
1
XTCEXMLC
2
2
2
XTCF032C–XTCF045C
2
XTCF063D–XTCF080D
1
XTCEXMLD
XTCE080F–XTCE170G
1
XTCEXMLG 4
XTCE185H–XTCE570M
1
XTCEXMLM
XTCE580N–XTCEC10N
1
XTCEXMLN 4
XTCE500M–XTCE570M with XTCE500N–XTCEC10N
1
XTCEXMLNM 4
For Use with …
Package Qty.
Catalog Number
2
XTCE007B–XTCE015B
1
XTCEXRLB 5
XTCE018C–XTCE032C
1
XTCEXRLC
2
XTCE040D–XTCE065D
1
XTCEXRLD
XTCE080F–XTCE150G
1
XTCEXRLG
XTCE040D–XTCE072D
2
2
XTCF125G–XTCF200G
XTCEXMLM
2
2
2
2
2
Reversing Link Kits
Reversing Link Kits
2
2
Notes
1 For Frame D, six auxiliary contacts maximum (can be a combination of side and top mount units).
2 For Frames F–R, eight auxiliary contacts maximum (can be a combination of side and top mount units).
3 For two contactors with AC or DC operated magnet system which are horizontally or vertically mounted. For B–G frames,
mechanical lifespan is 2.5 x 106 operations and the distance between contactors is 0 mm. For L–N frames, mechanical
lifespan is 5 x 106 operations and no auxiliary contact can be mounted between the mechanical interlock and the
contactor—the distance between contactors is 15 mm.
4 XTCEXMLG, XTCEXMLN and XTCEXMLNM consist of an interlock element and mounting plate.
5 Also includes interlocking bridge (XTCEXLBB). The following control cables are integrated for electrical interlock:
K1M: A1–K2M: 21; K1M: 21–K2M: A1; K1M: A2–K2M: A2.
2
2
2
2
V9-T2-14
Volume 9—OEM—Original Equipment Manufacturer CA08100011E—March 2013 www.eaton.com
Motor Control and Protection
Motor Protection and Monitoring Relays
2.2
Product Overview
2
Monitoring Relays Selection Guide
2
2
2
2
Description
2
D65 Series
D65C Series
Page V9-T2-17
Page V9-T2-19
2
cULus, CE
RoHS, cURus, cULus, CE
2
Various combinations of protection available
Compact cases for easy mounting
LED indicators for quick troubleshooting
Monitors AC single-phase currents from 0.1–10 A
External CT can be used to extend ranges
LED indicates output relay status
Choice of fixed or user-adjustable settings
Configuration
SPDT or DPDT
—
Maximum allowable load
10A
Less than 5 VA
Approvals
Features
2
2
2
Contact Data
2
Material
—
—
Resistance
—
—
Dielectric strength
2000V
—
2
AC
24–480 Vac
—
2
DC
24–120 Vdc
—
VA (Vac)
5 VA
—
Watts (Vdc)
—
—
2
Coil Data
2
Power
2
2
General Data
Ambient temperature
Operational
Maximum pick-up
Maximum release
–4° to 149°F (–20° to 65°C)
Ir = 0.9 x In mot
2
2
2
2
Rated
Uninterrupted
Current—
Iu = Ie (Amps)
Maximum Motor Ratings 1
Maximum hp Rating—P (hp)
UL 508/CSA C 22.2 No. 14
Three-Phase
FLA Adjustment
Range/Overload
Release—Ir (A)
Short Circuit
Release—
Irm (A)
Maximum kW Rating
AC-3—P (kW) Three-Phase
220–240V
380–415V
440V
500V
660–690V
200V
240V
480V
600V
0.1–0.16
2.2
—
—
—
—
0.06
2
2
2
2
XTPBP16BC1
2
2
2
XTPBP25BC1
Screw Terminals—
Catalog Number
Frame B
0.16
2
0.25
0.16–0.25
3.5
—
0.06
0.06
0.06
0.12
2
0.4
0.25–0.4
5.6
0.06
0.09
0.12
0.12
0.18
2
2
2
2
XTPBP40BC1
2
0.63
0.4–0.63
8.8
0.09
0.12
0.18
0.25
0.25
2
2
2
2
XTPBP63BC1
1
0.63–1
14
0.12
0.25
0.25
0.37
0.55
2
2
1/2
1/2
XTPB001BC1
1.6
1–1.6
22
0.25
0.55
0.55
0.75
1.1
2
2
3/4
1
XTPB1P6BC1
2.5
1.6–2.5
35
0.37
0.75
1.1
1.1
1.5
1/2
1/2
1
1-1/2
XTPB2P5BC1
4
2.5–4
56
0.75
1.5
1.5
2.2
3
1
1
2
3
XTPB004BC1
2
6.3
4–6.3
88
1.1
2.2
3
3
4
1-1/2
1-1/2
3
5
XTPB6P3BC1
10
6.3–10
140
2.2
4
4
4
7.5
3
3
7-1/2
10
XTPB010BC1
2
12
8–12
168
3
5.5
5.5
5.5
11
3
3
7-1/2
10
XTPB012BC1
16
10–16
224
4
7.5
9
9
12.5
3
5
10
10
XTPB016BC1
2
20
16–20
280
5.5
9
11
12.5
15
5
5
10
15
XTPB020BC1
25
20–25
350
5.5
12.5
12.5
15
22
5
7-1/2
15
20
XTPB025BC1
2
2
2
2
Notes
1 Select manual motor protectors by full load amperes. Maximum motor ratings (kW, hp) are for reference only.
2 In this range, calculate motor rating according to rated current. Specified values to NEC® 430.6(A)(1).
2
2
2
2
2
2
2
2
2
2
2
2
2
2
V9-T2-38
Volume 9—OEM—Original Equipment Manufacturer CA08100011E—March 2013 www.eaton.com
Motor Control and Protection
Manual Motor Protectors and Controllers
2.3
XTPR Rotary Manual Motor Protectors with Screw Terminals—Global Ratings and North American Ratings
Motor Protective Device with Thermal and Magnetic Trip
2
Note: Service Factor (SF)—Setting Ir of current scale in dependence of load factor:
SF = 1.15 -> Ir = 1 x In mot
SF = 1 -> Ir = 0.9 x In mot
2
Rated
Uninterrupted
Current—
Iu = Ie (Amps)
Maximum Motor Ratings 1
Maximum hp Rating—P (hp)
UL 508/CSA C 22.2 No. 14
Three-Phase
2
FLA Adjustment
Range/Overload
Release—Ir (A)
Short Circuit
Release—
Irm (A)
Maximum kW Rating
AC-3—P (kW) Three-Phase
220–240V
380–415V
440V
500V
660–690V
200V
240V
480V
600V
0.1–0.16
2.2
—
—
—
—
0.06
2
2
2
2
XTPRP16BC1
2
2
2
XTPRP25BC1
2
XTPRP40BC1
Screw Terminals—
Catalog Number 3
Frame B
0.16
2
2
2
0.25
0.16–0.25
3.5
—
0.06
0.06
0.06
0.12
2
0.4
0.25–0.4
5.6
0.06
0.09
0.12
0.12
0.18
2
2
2
0.63
0.4–0.63
8.8
0.09
0.12
0.18
0.25
0.25
2
2
2
2
XTPRP63BC1
1
0.63–1
14
0.12
0.25
0.25
0.37
0.55
2
2
1/2
1/2
XTPR001BC1
1.6
1–1.6
22
0.25
0.55
0.55
0.75
1.1
2
2
3/4
1
XTPR1P6BC1
2.5
1.6–2.5
35
0.37
0.75
1.1
1.1
1.5
1/2
1/2
1
1-1/2
XTPR2P5BC1
4
2.5–4
56
0.75
1.5
1.5
2.2
3
1
1
2
3
XTPR004BC1
6.3
4–6.3
88
1.1
2.2
3
3
4
1-1/2
1-1/2
3
5
XTPR6P3BC1
10
6.3–10
140
2.2
4
4
4
7.5
3
3
7-1/2
10
XTPR010BC1
12
8–12
168
3
5.5
5.5
5.5
11
3
3
7-1/2
10
XTPR012BC1
16
10–16
224
4
7.5
9
9
12.5
3
5
10
10
XTPR016BC1
20
16–20
280
5.5
9
11
12.5
15
5
5
10
15
XTPR020BC1
25
20–25
350
5.5
12.5
12.5
15
22
5
7-1/2
15
20
XTPR025BC1
32
25–32
448
7.5
15
15
22
30
7-1/2
10
25
30
XTPR032BC1
2
10–16
224
4
7.5
9
9
12.5
3
5
10
15
XTPR016DC1
2
25
16–25
350
5.5
12.5
12.5
15
22
7-1/2
7-1/2
20
25
XTPR025DC1
32
25–32
448
7.5
15
17.5
22
22
10
10
25
30
XTPR032DC1
40
32–40
560
11
20
22
24
30
10
15
30
40
XTPR040DC1
50
40–50
700
14
25
30
30
45
10
15
30
40
XTPR050DC1
58
50–58
812
17
30
37
37
55
—
—
40
—
XTPR058DC1
65
55–65
882
18.5
34
37
45
55
—
—
—
—
XTPR063DC1
Frame D
16
Notes
1 Select manual motor protectors by full load amperes. Maximum motor ratings (kW, hp) are for reference only.
2 In this range, calculate motor rating according to rated current. Specified values to NEC 430.6(A)(1).
3 Catalog number shown comes with screw terminals. For Frame B devices up to 16A, spring cage terminals are available.
For spring cage terminals on line and load sides, insert a “C” into the catalog number in the 5th position—Example: XTPRC _BC1.
For spring cage terminals on the load side only, insert an “SC” into the catalog number in the 5th and 6th positions—Example: XTPRSC _BC1.
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
Volume 9—OEM—Original Equipment Manufacturer CA08100011E—March 2013 www.eaton.com
V9-T2-39
2.3
2
2
2
2
2
Motor Control and Protection
Manual Motor Protectors and Controllers
XTPR Manual Self-Protected Motor Starters—North American Ratings, UL 508 Type E 2
Motor Protective Device with Thermal and Magnetic Trip
Note: A UL 508 Type E self-protected manual combination starter (XTPR) consists of a manual motor protector
(XTPR) and a UL listed line side adapter (e.g., XTPAXLSA). The Type E self-protected manual combination
starter alone is a legitimate short-circuit protective device and disconnect means for the downstream motor,
while the contactor has been added to provide remote operation of the motor circuit.
Rated
Uninterrupted
Current—
Iu = Ie (Amps)
Maximum Motor Ratings 1
FLA Adjustment
Range/Overload
Release—Ir (A)
Short Circuit
Release—
Irm (A)
220V
240V
480–277V
600–247V
240V
480–277V
600–247V
Manual Motor
Protector
Line Side Adapter— Screw Terminals—
2
Catalog Number
Catalog Number
Maximum hp Rating—P (hp)
Three-Phase
Rated Short Circuit Breaking
Capacity (kA)
2
Frame B
0.16
0.1–0.16
2.2
3
3
1/2
1/2
50
50
50
XTPAXLSA
XTPRP16BC1
2
0.25
0.16–0.25
3.4
3
3
1/2
1/2
50
50
50
XTPAXLSA
XTPRP25BC1
0.4
0.25–0.4
5.6
3
3
1/2
1/2
50
50
50
XTPAXLSA
XTPRP40BC1
0.63
0.4–0.63
8.8
3
3
1/2
1/2
50
50
50
XTPAXLSA
XTPRP63BC1
3
2
2
1
0.63–1
14
3
1/2
1/2
50
50
50
XTPAXLSA
XTPR001BC1
1.6
1–1.6
22
3
3
3/4
3/4
50
50
50
XTPAXLSA
XTPR1P6BC1
2
2.5
1.6–2.5
35
1/2
1/2
1
1-1/2
50
50
50
XTPAXLSA
XTPR2P5BC1
4
2.5–4
56
3/4
1
2
3
50
50
50
XTPAXLSA
XTPR004BC1
2
6.3
4–6.3
88
1
1-1/2
3
5
50
50
50
XTPAXLSA
XTPR6P3BC1
10
6.3–11
140
3
3
7-1/2
10
50
50
50
XTPAXLSA
XTPR010BC1
12
8–12
168
3
3
7-1/2
—
42
42
—
XTPAXLSA
—
2
16
10–16
224
3
5
10
—
42
42
—
XTPAXLSA
XTPR016BC1
20
16–20
280
5
5
—
—
42
42
—
XTPAXLSA
XTPR020BC1
2
25
20–25
350
5
7-1/2
15
—
18
18
—
XTPAXLSA
XTPR025BC1
32
25–32
448
7-1/2
10
25
—
18
18
—
XTPAXLSA
XTPR032BC1
2
2
Frame D
2
16
10–16
224
3
5
10
10
50
50
50
XTPAXLSAD
XTPR016DC1
25
16–25
350
7-1/2
7-1/2
20
25
50
50
50
XTPAXLSAD
XTPR025DC1
2
32
25–32
448
10
10
25
30
50
50
50
XTPAXLSAD
XTPR032DC1
40
32–40
560
10
10
30
40
50
50
50
XTPAXLSAD
XTPR040DC1
50
40–50
700
10
15
30
—
65
65
—
XTPAXLSAD
XTPR050DC1
58
50–58
812
15
15
40
—
65
65
—
XTPAXLSAD
XTPR058DC1
65
55–65
882
15
15
40
—
65
65
—
XTPAXLSAD
XTPR063DC1
2
2
2
2
Notes
1 Select manual motor protectors by full load amperes. Maximum motor ratings (kW, hp) are for reference only.
2 UL 508 Type E starters are assembled from a standard XTPR and a special incoming terminal line side adapter (XTPAXLSA or XTPAXLSAD).
3 In this range, calculate motor rating according to rated current. Specified values to NEC 430.6(A)(1).
2
2
2
2
2
2
2
2
2
V9-T2-40
Volume 9—OEM—Original Equipment Manufacturer CA08100011E—March 2013 www.eaton.com
Motor Control and Protection
Manual Motor Protectors and Controllers
2.3
Features
XT IEC Manual and Combination Motor Controllers
●
●
●
●
●
●
●
ON/OFF rotary handle with lockout provision
Class 10 overload protection
Adjustment dial for setting motor FLA
Built-in surge suppression on DC coils as standard
Assembled manual motor controllers consist of manual motor
protector, contactor, connector kit and 1NO-1NC auxiliary
contact for MMP
Assembled combination motor controllers consist of manual
motor protector, contactor, connector kit, 1NO-1NC auxiliary
contact for MMP and line side adapter
Combination motor controllers are UL 508 Type F rated, and
provide the following functions in a single device
●
Disconnect, short circuit protection, motor overload
protection, motor controller
2
2
2
2
2
2
2
2
2
Catalog Number Selection
XT IEC Manual and Combination Motor Controllers
2
Manual and Combination Motor Controllers
2
2
XT SC 012 B B A
Design
XT = XT IEC power control
Type
SC = Manual motor controller—
FVNR
FC = Combination motor controller,
UL 508 Type F—FVNR
Rated Current of MMP
Frame B
Frame D
P16 = 0.16A 016 = 16A
P25 = 0.25A 025 = 25A
P40 = 0.40A 032 = 32A
P63 = 0.63A 040 = 40A
001 = 1A
050 = 50A
1P6 = 1.6A
058 = 58A
2P5 = 2.5A
063 = 63A
004 = 4A
6P3 = 6.3A
010 = 10A
012 = 12A
016 = 16A
020 = 20A
025 = 25A
032 = 32A
Frame Size—Contactor
B = 45 mm, 7 to 15A
C = 45 mm, 18 to 32A
D = 55 mm, 40 to 65A
Frame Size—MMP
B = 45 mm, 0.1 to 32A
D = 55 mm, 16 to 63A
A
B
C
D
E
T
TD
Coil Voltage
= 110V 50 Hz, 120V 60 Hz
= 220V 50 Hz, 240V 60 Hz
= 415V 50 Hz, 480V 60 Hz
= 550V 50 Hz, 600V 60 Hz
= 208V 50 Hz
= 24V 50/60 Hz
= 24 Vdc
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
Volume 9—OEM—Original Equipment Manufacturer CA08100011E—March 2013 www.eaton.com
V9-T2-41
2.3
Motor Control and Protection
Manual Motor Protectors and Controllers
2
Product Selection
2
XTSC Manual Motor Controllers (MMC)/Starter Combinations
Factory Assembled Motor Protective Device with Thermal and Magnetic Trip + Contactor
2
Maximum Motor Ratings—P 2
220–240V
380–415V
500V
660–690V
200V
240V
480V
600V
Assembled Manual
Motor Controller 3
Non-Reversing—
Catalog Number
3.2
—
—
—
0.06
4
4
1/2
1/2
XTSCP16BB_
3.5
—
0.06
0.06
0.12
4
4
1/2
1/2
XTSCP25BB_
0.25–0.4
5.6
0.06
0.09
0.12
0.18
4
4
1/2
1/2
XTSCP40BB_
0.4–0.63
8.82
0.09
0.18
0.25
0.25
4
4
1/2
1/2
XTSCP63BB_
4
Short Circuit
Release—
Irm (A)
2
FLA Adjustment
Range (A) 1
2
Frame B MMP + Frame B Contactor
0.1–0.16
2
0.16–0.25
2
Maximum kW Rating
AC-3—P (kW) Three-Phase
Maximum hp Rating—P (hp)
Three-Phase
2
0.63–1
14
0.12
0.25
0.37
0.55
4
1/2
1/2
XTSC001BB_
1–1.6
22.4
0.25
0.55
0.75
1.1
4
4
3/4
1
XTSC1P6BB_
2
1.6–2.5
35
0.37
0.75
1.1
1.5
1/2
1/2
1
1-1/2
XTSC2P5BB_
2.5–4
56
0.75
1.5
2.2
3
1
1
2
3
XTSC004BB_
4–6.3
88.2
1.1
2.2
3
4
1-1/2
1-1/2
3
5
XTSC6P3BB_
2
6.3–10
140
2.2
4
4
7.5
3
3
7-1/2
10
XTSC010BB_
8–12
168
3
5.5
5.5
11
3
3
7-1/2
10
XTSC012BB_
2
10–16
224
4
7.5
9
12.5
3
3
10
10
XTSC016BB_
2
10–16
224
4
7.5
9
12.5
3
3
10
10
XTSC016BC_
16–20
280
5.5
9
12.5
15
5
5
10
15
XTSC020BC_
20–25
350
5.5
11
15
22
5
7-1/2
15
20
XTSC025BC_
2
25–32
448
7.5
15
22
30
7-1/2
10
20
25
XTSC032BC_
2
10–16
224
4
7.5
9
12.5
3
5
10
15
XTSC016DC_
16–25
350
5.5
12.5
12.5
22
7-1/2
7-1/2
20
25
XTSC025DC_
2
25–32
448
7.5
15
17.5
22
10
10
25
30
XTSC032DC_
2
2
2
Frame B MMP + Frame C Contactor
Frame D MMP + Frame C Contactor
Frame D MMP + Frame D Contactor
32–40
560
11
20
22
30
10
—
30
30
XTSC040DD_
2
40–50
700
14
25
30
45
15
15
30
40
XTSC050DD_
50–58
812
17
30
37
55
—
—
40
—
XTSC058DD_
2
55–65
882
18.5
34
37
55
—
—
40
—
XTSC063DD_
2
Notes
The assembled Manual Motor Controller (MMC) consists of an XTPR Manual Motor Protector (MMP) and an XTCE contactor. For Frame B MMP + Frame B
Contactor assemblies, the XTSC can be mounted directly on DIN rail without an adapter. The contactors are supported mechanically with a mechanical
connection element (included in XTPAXTPCB). For 16A and above, the assembly is mounted via a DIN rail adapter plate (XTPAXTPCPC, XTPAXTPCPD) and
the electrical connection is made with electrical contact modules (XTPAXECMC, XTPAXECMD), both included in XTPAXTPCC and XTPAXTPCD.
Service Factor (SF)—Setting Ir of current scale in dependence of load factor:
SF = 1.15 -> Ir = 1 x In mot
SF = 1 -> Ir = 0.9 x In mot
2
2
2
1
2
3
2
4
Overload release—Ir.
Select manual motor protectors by full load amperes. Maximum motor ratings (kW, hp) are for reference only.
Underscore (_) indicates magnet coil suffix required. See Page V9-T2-43.
In this range, calculate motor rating according to rated current. Specified values to NEC 430.6(A)(1).
2
2
2
2
2
V9-T2-42
Volume 9—OEM—Original Equipment Manufacturer CA08100011E—March 2013 www.eaton.com
Motor Control and Protection
Manual Motor Protectors and Controllers
2.3
XTFC Combination Motor Controllers (CMC), UL 508 Type F
Factory Assembled Motor Protective Device with Thermal and Magnetic Trip + Contactor + Required Line Side Adapter
Maximum Motor Ratings—P 2
FLA Adjustment
Range (A) 1
Short Circuit
Release—
Irm (A)
220–240V
380–415V
500V
660–690V
200V
240V
480V
600V
Assembled Manual
Motor Controller 3
Non-Reversing—
Catalog Number
—
—
0.06
4
4
1/2
1/2
XTFCP16BB_
Maximum kW Rating
AC-3—P (kW) Three-Phase
Maximum hp Rating—P (hp)
Three-Phase
2
2
2
2
Frame B MMP + Frame B Contactor
0.1–0.16
2.2
—
0.16–0.25
3.5
—
0.06
0.06
0.12
4
4
1/2
1/2
XTFCP25BB_
0.25–0.4
5.6
0.06
0.09
0.12
0.18
4
4
1/2
1/2
XTFCP40BB_
0.4–0.63
8.82
0.09
0.18
0.25
0.25
4
4
1/2
1/2
XTFCP63BB_
4
1/2
1/2
XTFC001BB_
4
3/4
1
XTFC1P6BB_
0.63–1
14
0.12
0.25
0.37
0.55
4
1–1.6
22.4
0.25
0.55
0.75
1.1
4
1.6–2.5
35
0.37
0.75
1.1
1.5
1/2
1/2
1
1-1/2
XTFC2P5BB_
2.5–4
56
0.75
1.5
2.2
3
1
1
2
3
XTFC004BB_
2
2
2
2
2
4–6.3
88.2
1.1
2.2
3
4
1-1/2
1-1/2
3
5
XTFC6P3BB_
6.3–10
140
2.2
4
4
7.5
3
3
7-1/2
10
XTFC010BB_
8–12
168
3
5.5
5.5
11
3
3
7-1/2
—
XTFC012BB_
10–16
224
4
7.5
9
12.5
3
5
10
—
XTFC016BB_
2
2
2
Frame B MMP + Frame C Contactor
10–16
224
4
7.5
9
12.5
3
5
10
—
XTFC016BC_
16–20
280
5.5
9
12.5
15
5
5
—
—
XTFC020BC_
20–25
350
5.5
11
15
22
5
7-1/2
15
—
XTFC025BC_
25–32
448
7.5
15
22
30
7-1/2
10
20
—
XTFC032BC_
2
2
2
Frame D MMP + Frame C Contactor
10–16
224
4
7.5
9
12.5
3
5
10
10
XTFC016DC_
16–25
350
5.5
12.5
12.5
22
7-1/2
7-1/2
20
25
XTFC025DC_
25–32
448
7.5
15
17.5
22
10
10
25
30
XTFC032DC_
2
2
Frame D MMP + Frame D Contactor
32–40
560
11
20
22
30
10
10
30
40
XTFC040DD_
40–50
700
14
25
30
45
10
15
30
—
XTFC050DD_
50–58
812
17
30
37
55
15
15
40
—
XTFC058DD_
55–65
882
18.5
34
37
55
15
15
40
—
XTFC063DD_
Magnet Coil Suffix
Coil Voltage
Suffix
Code
110V 50 Hz, 120V 60 Hz
A
220V 50 Hz, 240V 60 Hz
B
24V 50/60 Hz
T
24 Vdc
TD 5
415V 50 Hz, 480V 60 Hz
C
550V 50 Hz, 600V 60 Hz
D
208V 60 Hz
E
Notes
The assembled Combination Motor
Controller (CMC) consists of an XTPR
Manual Motor Protector (MMP) and an
XTCE contactor and a required Line Side
Adapter. For Frame B MMP + Frame B
Contactor assemblies, the XTFC and
XTFR can be mounted directly on DIN rail
without an adapter. The contactors are
supported mechanically with a
mechanical connection element
(included in XTPAXTPCB, XTPAXRPCRB).
For 16A and above, the assembly is
mounted via a DIN rail adapter plate
(XTPAXTPCPC, XTPAXTPCPD) and the
electrical connection is made with
electrical contact modules (XTPAXECMC,
XTPAXECMD), both included in
XTPAXTPCC and XTPAXTPCD.
SF = 1.15 -> Ir = 1 x In mot
SF = 1 -> Ir = 0.9 x In mot
1
2
3
4
5
2
2
Overload release—Ir.
Select combination motor controllers by
full load amperes. Maximum motor
ratings (kW, hp) are for reference only.
Underscore (_) indicates magnet coil
suffix required. See table at left.
In this range, calculate motor rating
according to rated current. Specified
values to NEC 430.6(A)(1).
With DC operation: Integrated dioderesistor combination, coil rating 2.6W.
2
2
2
2
2
2
2
2
2
2
2
Volume 9—OEM—Original Equipment Manufacturer CA08100011E—March 2013 www.eaton.com
V9-T2-43
2.3
Motor Control and Protection
Manual Motor Protectors and Controllers
2
Accessories
2
Auxiliary Contacts
2
Contact Configuration
2
1NO-1NC
Contact Sequence
Screw Terminals
Pkg. Qty.
Catalog Number
5
XTPAXSA11
5
XTPAXFA11
Pkg. Qty.
Catalog Number
Side-Mount
2
2
2
Front-Mount
1NO-1NC
2
2
2
Rotary Handle
Mechanism
IP65 Rotary Handle Mechanism 123
Description
Complete Kits—Includes Handle, Shaft and Required Hardware
2
2
2
2
2
Rotary handle mechanism IP65 black—for use on main
switches to IEC/EN 60204.
1
XTPAXRHMB
Rotary handle mechanism IP65 red/yellow—for use on main
switch with emergency-stop function to IEC/EN 60204.
1
XTPAXRHMRY
Rotary handle mechanism IP65 black—for use on main
switches to IEC/EN 60204 where XTPR is mounted 90° from
vertical.
1
XTPAXRHM90B
Rotary handle mechanism IP65 red/yellow—for use on main
switch with emergency-stop function to IEC/EN 60204
where XTPR is mounted 90° from vertical.
1
XTPAXRHM90RY
2
2
Shunt Release
2
2
2
Shunt Release
Pkg. Qty.
Screw Terminals—
Catalog Number
2
XTPAXSR120V60H
2
XTPAXSR240V60H
2
XTPAXSR480V60H
2
XTPAXSR24VDC
2
2
Undervoltage Release
2
2
2
2
Undervoltage Release
Pkg. Qty.
Screw Terminals—
Catalog Number
2
XTPAXUVR120V60H
2
XTPAXUVR240V60H
2
XTPAXUVR480V60H
Notes
1 With ON/OFF switch position and “+” (tripped), lockable with three padlocks, 4–8 mm hasp. Can be locked in the OFF position, if required.
2 Rotary handle mechanisms ship with door interlock disabled. See instruction publication with product for how to enable door interlock.
3 Not for use with XTPAXFAEM20 early-make front-mount auxiliary contact.
2
2
2
2
V9-T2-44
Volume 9—OEM—Original Equipment Manufacturer CA08100011E—March 2013 www.eaton.com
2.3
Motor Control and Protection
Manual Motor Protectors and Controllers
Three-Phase Commoning Links 1
For Use With…
MMP—Frame B
Length of
Link (mm)
Unit
Width (mm)
Pkg. Qty.
Catalog Number
2
90
45
10
XTPAXCLKA2
3
135
45
10
XTPAXCLKA3
4
180
45
10
XTPAXCLKA4
5
225
45
10
XTPAXCLKA5
Frame B
MMP with no side-mounted auxiliaries or voltage releases
MMP—Frame D
2
Qty MMP
2
2
2
2
2
Frame D
MMP with no side-mounted auxiliaries or voltage releases
2
110
55
1
XTPAXCLKA2D
2
3
165
55
1
XTPAXCLKA3D
2
4
220
55
1
XTPAXCLKA4D
2
2
Incoming Terminal
2
Incoming Terminal for Three-Phase Commoning Link 2
For Use With…
Pkg. Qty.
Catalog Number
B Frame XTPR, XTPB
5
XTPAXIT
2
2
2
Line-Side Adapter
Line-Side Adapter 3
For Use With…
Pkg. Qty.
Catalog Number
B Frame XTPR to create a UL 508 type E/F manual
combination starter
5
XTPAXLSA
D Frame XTPR to create a UL 508 type E/F manual
combination starter
1
XTPAXLSAD 4
2
2
2
2
2
Notes
1 Protected against accidental contact. B Frame short circuit proof Ue = 690V, Iu = 63A; D Frame short circuit proof
Ue = 690V, Iu = 128A. Frame B links can be combined by rotating mounting. Frame D links cannot be combined.
2 For three-phase commoning link, protected against accidental contact, Ue = 690V, Iu = 63A; for conductor crosssections: 2.5–25 mm2 stranded; 2.5–16 mm2 flexible with ferrules, AWG 14-6.
3 XTPAXLSA is for three-phase commoning link, finger- and back-of-hand proof, Ue = 690V, Iu = 60A; for conductor
cross sections: 2.5–25 mm2 stranded, 2.5–16 mm2 flexible with ferrule, AWG 14-6.
4 XTPAXLSAD cannot be combined with three-phase commoning links.
2
2
2
2
2
2
2
2
2
2
2
Volume 9—OEM—Original Equipment Manufacturer CA08100011E—March 2013 www.eaton.com
V9-T2-45
2.3
2
Non-Reversing
Starters
2
Motor Control and Protection
Manual Motor Protectors and Controllers
Combination Connection Kits for Connection of XTPR MMP with XTCE Contactor
For Use With…
Std. Pack
Catalog Number
Comprised of:
1
XTPAXTPCB
1
XTPAXTPCC
1
XTPAXTPCD
Non-Reversing Starters
XTPR…B + XTCE…B
2
Mechanical connection element for XTPR…B and contactor
Main current wiring between XTPR…B and contactor in tool-less plug
connection
2
Cable guidance
2
Use contactor auxiliary switch XTCEXFAT_.
Control cable guidance: max. six cables up to 2.5 mm2 external diameter or
four cables up to 3.5 mm2 external diameter.
2
XTPR…B + XTCE…C
XTPR…D + XTCE…D
2
Comprised of:
DIN rail adapter plate
Main current wiring between XTPR and contactor
2
2
Description
Insulated Enclosures
Insulated Enclosures for Surface Mounting
2
Degree of
Protection
2
XTPB Pushbutton Manual Motor Protectors—North American Usage 12
For Use With…
Description
Catalog Number
IP65
NEMA
3R, 4X, 12, 13
XTPB MMP only or with: XTPAXFA_, XTPBXFAEM20,
XTPAXSA_, XTPAXUVR_, XTPAXSR_, XTPAXCL
With actuating diaphragm
XTPBXENAS65
2
IP65
NEMA
3R, 4X, 12, 13
XTPB MMP only or with: XTPAXFA_, XTPBXFAEM20,
XTPAXUVR_, XTPAXSR_, XTPAXCL
With emergency-stop (E-stop) pushbutton
actuator, red/yellow
XTPBXENASES65
2
B Frame (0.1–32A) XTPR Rotary Manual Motor Protectors—North American Usage 3
2
IP55
NEMA
1, 12, 3R
2
D Frame (10–65A) XTPR Rotary Manual Motor Protectors 45
2
IP65
NEMA
1, 12, 3R, 4X
2
2
B Frame XTPR Only or with: XTPAXSA_ and XTPAXFA_,
XTPAXUVR_ and XTPAXFA_, XTPAXSR_ and XTPAXFA_,
XTPAXCL
D Frame XTPR only or with: XTPAXFA_, XTPAXFAEM20,
XTPAXSA_, XTPAXSATR_, XTPAXUVR_, XTPAXSR_,
XTPAXCL
With red/yellow rotary handle for use as
emergency-stop switch to VDE 0113
XTPAXENAS55RY
With red/yellow rotary handle for use as
emergency-stop switches to IEC/EN 60204
XTPAXENCSD65RY
Notes
1 Built-in terminal for PE(N).
2 North American enclosures come with conduit adapters for use with 1/2 NPT.
3 Built-in N and PE terminal, lower part without knockouts.
4 Integrated terminal for PE(N) connection.
5 % Metric knockouts:
Top ÷ bottom: M25/M32
In backplate: M25/M32
Control cable entry: M20
2
2
2
2
2
2
2
2
2
2
2
2
V9-T2-46
Volume 9—OEM—Original Equipment Manufacturer CA08100011E—March 2013 www.eaton.com
Motor Control and Protection
Soft Starters
2.4
Product Overview
2
Soft Starters Selection Guide
2
2
2
2
2
Description
DS7
DS6
S611
S801+
S811+
Page V9-T2-48
Page V9-T2-50
Page V9-T2-51
Page V9-T2-55
Page V9-T2-58
Current range (A)
4–32
41–200
26–414
11–1000
11–1000
Phases
Two-phase control
Two-phase control
Three-phase
Three-phase
Three-phase
2
2
Power
2
Input voltage (line voltage)
0–460V
0–460V
0–600V
0–600V; 690V on V and T Frame
0–600V; 690V on V and T Frame
Horsepower range
460V: 2–20 hp
460V: 30–150 hp
460V: 40–350 hp
460V: 25–800 hp
460V: 25–800 hp
Internal run-bypass
Yes
Yes
Yes
Yes
Yes
Inside-the-delta control
—
—
—
Yes
Yes
2
2
2
Control
User interface
Dials
Dials
LED and keypad
Dials and DIP switches
LCD and keypad
Control voltage
24 Vac/Vdc or 120–240 Vac
24 Vdc
120 Vac
24 Vdc
24 Vdc
2
Communications
—
—
Modbus RTU, EtherNet/IP,
Modbus TCP, PROFIBUS,
DeviceNet
—
Modbus RTU, EtherNet/IP,
Modbus TCP
2
Program relays
—
—
Yes
Yes
Yes
2
Voltage ramp initial current
5–85% LRT
5–85% LRT
5–85% LRT
5–85% LRT
5–85% LRT
2
Voltage ramp time
1–30 sec
1–30 sec
0.5–180 sec
0.5–180 sec
0.5–180 sec
Current limit
—
—
5–85% LRT
5–85% LRT
5–85% LRT
Soft Start
2
2
Current limit time
—
—
0.5–180 sec
0.5–180 sec
0.5–180 sec
Kick start current
—
—
5–85% LRT
5–85% LRT
5–85% LRT
Kick start time
—
—
0–2 sec
0–2 sec
0–2 sec
Jog
—
—
—
Yes
Yes
2
Stop ramp time
0–30 sec
0–30 sec
0–60 sec
0–60 sec
0–60 sec
Pump control
—
—
Optional
Optional
Optional
2
2
Soft Stop
2
Environmental
Operating temperature
0° to 40°C
0° to 40°C
–20° to 50°C
–30° to 50°C
–30° to 50°C
Humidity
0–95% noncondensing
0–95% noncondensing
0–95% noncondensing
0–95% noncondensing
0–95% noncondensing