EXPLOSION PROOF SWITCHES
Explosion proof switches
Honeywell explosion proof switches are designed specifically for use in
hazardous locations. To comply with explosion proof requirements, the flame
path within the housing is designed to contain and cool the escaping hot
gases that otherwise could cause an explosion outside the switch.
Switches are available with UL/CSA for North America. See information below
and product pages for details. In Europe, the usage is governed under the
European Directive on Equipment and Protective Systems Intended for Use in
Potentially Explosive Atmospheres (94/9/EC) commonly referred to as the
ATEX Directive.
The BX, CX and GXE product families comply to the following ATEX Directive:
EExd IIC T6 Category II 2 GD
The 14CE100 product family complies to the following ATEX Directive:
EExd IIC T6 Category II 2 G
NEMA TYPE 7, CLASS I FLAMMABLE GASES OR VAPORS
Type 7 enclosures are for use indoors in locations classified as Class I,
Groups B, C, or D by the National Electrical Code.
Group B — (only switches so noted in the order guides include this listing).
Atmospheres containing hydrogen or manufactured gas.
Group C — atmospheres containing diethyl ether, ethylene, or cyclopropane.
Group D — Atmospheres containing gasoline, hexane, butane, naptha,
propane, acetone, toluene or isoprene.
Division 1
Locations in which hazardous agents are present under normal operating
conditions.
Division 2
Locations in which hazardous agents may be present only in case of
accidental rupture or breakdown.
All Honeywell listings covered in Division 1 are also covered in the same
groups in Division 2.
NEMA TYPE 9, CLASS II COMBUSTIBLE DUSTS
Type 9 enclosures are for use in indoor locations classified as Class II,
Groups E, F or G, as defined in the National Electrical Code.
Group E — Atmospheres containing metal dust.
Group F — Atmospheres containing carbon black, coal dust or coke dust.
Group G — Atmospheres containing flour, starch or grain dust.
ATEX EExd
EExd
Flameproof
enclosure
II
c
T6
Category II 2
Places with potentially
explosive
atmospheres, other
than mines susceptible
to fire damp
Atmosphere may
contain gases
from groups A, B
or C from table in
EN50014, Annex A
Maximum
surface
temperature of
85 °C (185 °F)
Areas in which an explosion
proof atmosphere is likely to
occur
www.honeywell.com/sensing
G
Gas
could be
present
D
Dust
could be
present
57
EXPLOSION PROOF SWITCHES
14CE100 Series
Miniature Enclosed,
Explosion Proof
X
ATEoved
Switches
r
p
ap
The 14CE100 Series has been designed for use in explosive environments. It is approved to meet the
requirements of the Low Voltage directive and is CE marked. The prewired construction allows for ease of
installation where space is at a premium and external operating conditions can be difficult.
Mechanical life:
Sealing:
10 million
IP65, NEMA 1, 3
IP67 , NEMA 1, 3, 4 12, 13
0 °C to 70 °C (32 °F to 158 °F)
CE, PTB 98 ATEX 1064 X EExd IIC T6 Category II 2 G
AC14 D300
DC13 R300
11,8 N max.
1,8 mm (0.71 in) max.
3,0 mm (0.118 in) min.
0,1mm (0.004 in) max.
Standard
Silver
-*G
Gold
Harmonised CENELEC 4 x 0,75 mm2 cable
Standard
Boot sealed
Operating temperature:
Approvals:
Operating force (OF):
Pretravel (PT):
Overtravel (OT):
Differential travel (DT):
Contacts:
Connection:
Switching options:
SPDT
Single Pole, Double Throw
Snap action contacts (1NC/1NO)
Actuators
S.P.D.T
BROWN
2
GREEN/YELLOW
BLUE
1
3
BLACK
Top pin plunger
40,0 Max.
1,57
25,0
1.00
M4 ground
screw
15,7 OP
0.62
Top roller plunger, parallel
16,0 Max.
0.63
1,8 PT
0.07
M4 ground
screw
Top roller plunger, perpendicular
40,0 Max.
1,57
25,0
1.00
M4 ground
screw
Ø 10,0 (0.39)
Stainless steel
plunger
(2) Ø 5,1 (0.20)
Mounting holes
49,0 Max.
1.93
31,4
1.24
1,8 PT
0.07
Ø 12,0 (0.47) x 5,0 (0.20)
Hardened steel roller
REFERENCE
14CE101-1
14CE101-2
14CE101-3
14CE101-4
14CE101-5
14CE101-6
14CE101-10
Boot sealed
1,80 Max.
(0.07) PT
72,0
2,83
31,4
1.24
49,0 Max.
1.93
CABLE LENGTH
1 m (3.3 ft)
3 m (9.9 ft)
3 m (9.9 ft)
Gold contacts
5 m (16.5 ft)
6 m (19.8 ft)
6 m (19.8 ft)
Gold contacts
8 m (26.4 ft)
12 m (39.6 ft)
15 m (49.5 ft)
31,4
1.24
49,0 Max.
1.93
7,6
0.30
"L"
REFERENCE
14CE102-1
14CE102-3
14CE102-3G
14CE102-5
14CE102-6
14CE102-6G
14CE102-8
14CE102-12
14CE102-15
Ø 7,1 (0.28)
Stainless steel
plunger
Neoprene boot seal
58
14,0
0.55
72,0
2,83
7,6
0.30
24,9
(0.98)
OP
CABLE LENGTH
1 m (3.3 ft)
6 m (19.8 ft)
10 m (33.0 ft)
(2) Ø 5,1 (0.20)
Mounting holes
28,5 OP
1.11
"L"
CABLE LENGTH
1 m (3.3 ft)
2 m (6.6 ft)
3 m (9.9 ft)
4 m (13.2 ft)
5 m (16.5 ft)
6 m (19.8 ft)
10 m (33.0 ft)
1,8 PT
0.07
(2) Ø 5,1 (0.20)
Mounting holes
7,6
0.30
"L"
16,0 Max.
0.63
16,0 Max.
0.63
28,5 OP
1.11
59,0
2.32
40,0 Max.
1,57
25,0
1.00
REFERENCE
14CE118-1
14CE118-6
14CE118-10
www.honeywell.com/sensing
CABLE LENGTH
1 m (3.3 ft)
3 m (9.9 ft)
REFERENCE
14CE103-1
14CE103-3
EXPLOSION PROOF SWITCHES
GXE Series
Explosion Proof
Limit Switches
The GXE Series explosion proof limit switches are designed specifically for use in hazardous applications.
The GXE enclosure is fully potted and has sealing protection of IP66/67 as per IEC/EN 60529. The entire
GXE Series complies with the European Directive on Equipment and Protective Systems Intended for Use
in Potentially Explosive Atmospheres (94/9/EC) commonly referred to as the ATEX Directive.
Mechanical life:
Sealing:
Operating temperature:
Approvals:
2 million
IP66/67, EN 60529
-20 °C to 75 °C (-4 °F to 167 °F)
CE, EN 50014, EN 50018, EN 50281-1-1
KEMA 00 ATEX 2103 X EExd IIC T6 Category II 2 GD
AC15
DC13
Silver
5 metre, HO5VV-F, 3 x 0,75 mm2 cable
X
ATEoved
r
app
Contacts:
Connection:
Switching options:
SPDT
Single Pole, Double Throw
Snap action contacts (1NC/1NO)
BLUE
BLACK
BROWN
Actuators
OPTIONS
GXE Series
Side rotary roller lever
Top roller plunger, parallel
Overtravel min. (OT):
6,0 mm (0.0.236 in)
Differential travel max. (DT): 0,5mm (0.020 in)
Operating position max. (OP): 2,0 mm (0.079 in)
Overtravel min. (OT):
Differential travel max. (DT):
Operating position max. (OP):
49°
8°
26°
REFERENCE
GXE51C
REFERENCE
GXE51A1B
Operating force max. (OF):
16 N (3.6 lb)
Top pin plunger
Overtravel min. (OT):
6,0 mm (0.0.236 in)
Differential travel max. (DT): 0,5mm (0.020 in)
Operating position max. (OP): 2,0 mm (0.079 in)
REFERENCE
GXE51B
www.honeywell.com/sensing
59
EXPLOSION PROOF SWITCHES
The EX Series features the smallest UL listed housings available for use in
hazardous locations. Flame paths within the housing cool exploding gases
below the kindling temperature before they reach the explosive gases
surrounding the housing.
EX Series
Standard
Explosion
Proof
Switches
Options available include single or double conduit connection.
These switches are not sealed against liquids and should not be used where
there will be liquid splash. If a weather sealed explosion proof switch is
required please select from the CX or LSX/BX series.
Actuators
Sealing:
Operating temperature:
Approvals:
Conduit:
Contacts:
Electrical ratings:
A
NEMA 1, 7 (Class I, Division I, Groups C, D)
9, (Class II, Division I, Groups E, F, G)
Standard
-40 °C to 71 °C (-40 °F to 160 °F)
High
100 hr @ 400 °F
UL, CSA
½ in - 14NPT
Silver
UL/CSA Rating:
15 A, 125, 250 or 480 Vac;
/8 Hp, 125 Vac; ¼ Hp, 250 Vac;
½ A, 125 Vdc; ¼ A, 250 Vdc.
1
B
UL/CSA Rating:
20 A, 125, 250 or 480 Vac;
10 A, 125 Vac “L”;
1 Hp, 125 Vac; 2 Hp, 250 Vac;
½ A, 125 Vdc; ¼ A, 250 Vdc.
C
UL/CSA Rating:
D
UL/CSA Rating:
10 A, 125 or 250 Vac;
0.3 A, 125 Vdc; 0.15 A, 250 Vdc
.
10 A, 125, 250 or 480 Vac;
½ A, 125 Vdc; ¼ A, 250 Vdc.
E
UL Rating:
Switching options:
SPDT
Single Pole, Double Throw
Snap action contacts (1NC/1NO)
1 A, 125 Vac.
DPDT
Double Pole, Double Throw
Snap action contacts (2NC/2NO)
Side rotary actuated switches
OPTIONS
No lever
Note: Levers are ordered separately
(see pages 71-73 for details)
Operating force max. (OF):
Electrical rating A
Electrical rating B
Pretravel max. (PT):
Overtravel max. (OT):
Electrical rating A
Electrical rating B
Differential travel max. (DT):
Electrical rating A
Electrical rating B
ACTUATION
CW
CCW
CW
60
www.honeywell.com/sensing
CONTACT
SPDT
SPDT
SPDT
0,22 N m (31.25 in oz)
3,34 N to 8,90 N (0.75 lb to 2.0 lb)
5,56 mm (0.219 in) 8°
90°
25°
0,18 mm (0.007 in) 0.25°
0,3 mm (0.012 in) 4°
ELECTRICAL RATING
A
A
B
REFERENCE
EX-AR20
EX-AR230
EXA-AR20
EXPLOSION PROOF SWITCHES
Roller lever
DPDT, Preleaded with 0,91 m (3 ft) leadwire
Operating force max. (OF):
Clockwise (CW)
Counter clockwise (CCW)
Pretravel max. (PT):
Overtravel max. (OT):
Differential travel max. (DT):
Sealing:
ACTUATION
CW
CCW
Roller material:
Operating force max. (OF):
Electrical rating A
Clockwise (CW)
Counter clockwise (CCW)
Electrical rating B
Pretravel max. (PT):
Electrical rating A, B
Clockwise (CW)
Counter clockwise (CCW)
Overtravel max. (OT):
Electrical rating A
Clockwise (CW)
Counter clockwise (CCW)
Electrical rating B
Differential travel max. (DT):
Electrical rating A
Electrical rating B
ACTUATION
CW
CCW
CW/Class 1 Group B
CCW/Class 1 Group B
CW/High temperature
CW
CW/No mounting bracket
CW/Nylon roller
CW/No mounting bracket
CONTACT
SPDT
SPDT
SPDT
SPDT
SPDT
SPDT
SPDT
SPDT
SPDT
CONTACT
DPDT
DPDT
2,22 N to 6,67 N (0.5 lb to 1.5 lb)
12,2 N (2.75 lb)
6,35 mm (0.250 in)
25°
2,77 mm (0.109 in) 4°
NEMA Class 1 Group B
ELECTRICAL RATING
C
C
REFERENCE
EXD-AR-3
EXD-AR30-3
Bronze
Hermetically sealed
2,22 N to 5,56 N (0.5 lb to 1.25 lb)
11,1 N (2.5 lb)
3,34 N to 8,90 N (0.75 lb to 2.0 lb)
5,56 mm (0.219 in) 8°
1,65 mm (0.065 in) 3.5°
90°
25°
25°
Operating force max. (OF):
Clockwise (CW)
Counter clockwise (CCW)
Pretravel max. (PT):
Clockwise (CW)
Counter clockwise (CCW)
Overtravel max. (OT):
Differential travel max. (DT):
Sealing:
ACTUATION
CW/3,2 m (10.5 ft) leadwire
CCW/0,91 m (3 ft) leadwire
CW/0,91 m (3 ft) leadwire
CONTACT
SPDT
SPDT
SPDT
2,22 N to 6,67 N (0.5 lb to 1.5 lb)
11,1 N (2.5 lb)
5,56 mm (0.219 in) 8°
1,65 N (0.065 in) 3.5°
25°
0,64 mm (0.025 in)
NEMA Class 1 Group B
ELECTRICAL RATING
E
E
E
REFERENCE
EXH-AR3
EXH-AR33
EXH-AR7
0,18 mm (0.007 in) 0.25°
0,3 mm (0.012 in) 4°
ELECTRICAL RATING
A
A
A
A
A
B
B
A
A
REFERENCE
EX-AR
EX-AR30
EX-AR800
EX-AR830
EX-AR400
EXA-AR
EXA-AR62
EX-AR182
EX-AR141
2 Conduit openings
CW or CCW actuation, no return spring, low operating
force
Operating force max. (OF):
ACTUATION
CW/CCW/No mounting bracket
CONTACT
SPDT
0,56 N (2 oz)
ELECTRICAL RATING
A
REFERENCE
EX-AR16
Maintained contact
Operating force max. (OF):
Pretravel max. (PT):
Overtravel max. (OT):
ACTUATION
CW
CONTACT
SPDT
3,34 N (0.75 lb)
5,56 mm (0.219 in) 8°
90°
ELECTRICAL RATING
A
REFERENCE
EX-XR3
Operating force max. (OF):
Electrical rating A
Electrical rating B
Electrical rating C
Pretravel max. (PT):
Electrical rating A, B
Electrical rating C
Overtravel max. (OT):
Electrical rating A
Electrical rating B, C
Differential travel max. (DT):
Electrical rating A
Electrical rating B
Electrical rating C
CONTACT
DPDT
SPDT
SPDT
www.honeywell.com/sensing
2,22 N to 5,56 N (0.5 lb to 1.25 lb)
3,61 N to 8,90 N (0.8 lb to 2 lb)
2,22 N to 6,67 N (0.5 lb to 1.5 lb)
5,56 mm (0.219 in) 8°
6,35 mm (0.250 in)
90°
25°
0,18 mm (0.007 in) 0.25°
0,3 mm (0.012 in) 0.5°
2,77 mm (0.109 in) 4°
ELECTRICAL RATING
C
B
A
REFERENCE
4EX1-3
2EX1
1EX1
61
EXPLOSION PROOF SWITCHES
EX Series
Side rotary actuated switches (continued)
Overtravel plunger actuated switches
Cross roller lever, rotated 90°
Top pin plunger
Operating force max. (OF):
Pretravel max. (PT):
Overtravel max. (OT
Differential travel max. (DT):
CW
CONTACT
SPDT
2,22 N to 5,56 N (0.5 lb to 1.25 lb)
5,56 mm (0.219 in) 8°
90°
0,18 mm (0.007 in) 0.25°
ELECTRICAL RATING
A
REFERENCE
EX-CR
Rod lever
OPTIONS
Operating force max. (OF):
Electrical rating A, C
Electrical rating B
Pretravel max. (PT):
Electrical rating A
Electrical rating B
Electrical rating C
Overtravel min. (OT):
Electrical rating A
Electrical rating B
Electrical rating C
Differential travel max. (DT):
Electrical rating A
Electrical rating B
Electrical rating C
No mounting bracket
High temperature
Low OF
Operating force max. (OF):
Pretravel max. (PT):
Overtravel min. (OT):
CW/No mounting bracket
62
CONTACT
SPDT
0,56 N (2 oz)
18°
40°
ELECTRICAL RATING
A
REFERENCE
EX-AR1613
13,34 N (3.0 lb)
8,90 N (2 lb)
1,98 mm (0.078 in)
1,27 mm (0.050 in)
3,96 mm (0.156 in)
4,78 mm (0.188 in)
3,18 mm (0.125 in)
3,48 mm (0.141 in)
0,10 mm (0.004 in)
0,23 mm (0.009 in)
1,52 mm (0.060 in)
CONTACT
SPDT
SPDT
SPDT
SPDT
ELECTRICAL RATING
A
A
A
B
REFERENCE
EX-Q
EX-Q62
EX-Q400
EXA-Q
Sealing NEMA Class 1 Group B
Preleaded with 0,91 m (3 ft) leadwire
www.honeywell.com/sensing
CONTACT
SPDT
DPDT
ELECTRICAL RATING
A
C
REFERENCE
EX-Q800
EXD-Q-3
EXPLOSION PROOF SWITCHES
Boot sealed
Operating force max. (OF):
Electrical rating D
Electrical rating B
Pretravel max. (PT):
Electrical rating D
Electrical rating B
Overtravel min. (OT):
Electrical rating D
Electrical rating B
Differential travel max. (DT):
Electrical rating D
Electrical rating B
Class 1 Group B
CONTACT
SPDT
SPDT
13,34 N (3.0 lb)
15,57 N (3.5 lb)
1,98 mm (0.078 in)
2,77 mm (0.109 in)
4,78 mm (0.188 in)
3,18 mm (0.125 in)
0,10 mm (0.004 in)
0,23 mm (0.009 in)
ELECTRICAL RATING
D
B
REFERENCE
EX-N15
EXA-N
ELECTRICAL RATING
A
REFERENCE
EX-AR50
Manually actuated
Operating force max. (OF):
CONTACT
SPDT
11,1 N (2.5 lb)
www.honeywell.com/sensing
63
EXPLOSION PROOF SWITCHES
CX Series
Weather Sealed
Explosion Proof
Switches
X
ATEoved
r
app
CX switches, as are the LSX/BX Series, are built especially for outdoor use in hazardous atmospheres.
These enclosures are constructed to withstand the pressure of an internal explosion.
O-ring seals make the enclosure weatherproof but are outside of required flame paths so explosion proof
requirements are maintained.
As factory assembled, all basic switches operate on clockwise and counterclockwise rotation. The
actuating mechanism can be field adjusted for CW or CCW operation only.
Analog output, 4 mA to 20 mA, is available.
Basic switches operate nearly simultaneously in multiple switch devices.
Shafts of devices without shaft restoring force can be rotated through 360°.
Sealing:
NEMA
UL listed
1, 3, 4, 4X, 6, 6P, 7, 9 and 13
Class I, Div. 1, Groups B (16CX, 24CX, 26CX, and 84CX only),
C and D; and Class II, Div. 1, Groups E, F and G
Class I, Div. 1, Groups B (16CX, 24CX, 26CX, and 84CX only),
C and D; and Class II, Groups E, F and G
–25 °C to 85 °C (–13 °F to 185 °F)
UL, CSA
CX-E only
ATEX EExd IIC T6 Category II 2 GD
Aluminium
80CX
Bronze
¾ in - 14NPT
A, C, D
Silver
F
Gold
CSA certified
Operating temperature:
Approvals:
Housing:
Conduit:
Contacts:
Actuators
Electrical Ratings:
A
UL/CSA Rating: L96
15 A, 120, 240 or 480 Vac, ind. and res
1
/8 Hp, 120 Vac; ¼ Hp, 240 Vac
0.5 A, 125 Vdc, 0.25 A, 250 Vdc, res
C
UL/CSA Rating: L59
10 A, 120 or 240 Vax, ind. and res
0.3 A, 125 Vdc, 0.15 A, 250 Vdc, res
D
UL/CSA Rating: L22
1 A, 120 Vax, ind. and res
F
UL/CSA Rating: L22
1 A, 125 Vac
G
Analog Current Output (4 mA to 20 mA)
12.5 Vdc to 40 Vdc
Switching options:
SPDT
Single Pole, Double Throw
Snap action contacts (1NC/1NO)
DPDT
Double Pole, Double Throw
Snap action contacts (2NC/2NO)
Analog position sensing specifications (Electrical rating “G”)
Current output:
Voltage compliance range:
Maximum load resistance:
Current signal output:
Span:
Null:
64
www.honeywell.com/sensing
4 mA to 20 mA
12.5 Vdc to 40 Vdc
RL, Max., –V Supply - 12.5
20 mA
4 mA to 20 mA
Adjustable from 15° to 90° of angular rotation
4 mA position may be set at any angular position
EXPLOSION PROOF SWITCHES
Operating characteristics
Basic Switch Type
BZ
BA
DT
Pretravel (max.)*
15°
15°
30°
Differential Travel (max.)
10°
10°
25°
Overtravel (min.)*
90°
90°
75°
Operating Torque (max.)
11.1 in lb/1,25 N m
* May be modified in field to suit application requirements.
Note: Levers are ordered separately
(see pages 71-73 for details)
HS
30°
20°
75°
Notes:
Add the letter “A” to listings with side mounting holes tapped 5/16 (8).
Example: 11CX2A
Add the letter “B” to listings with thru mounting holes tapped 3/8-24 (4).
Example: 11CX2B
Add the letter “C” to listings for low temperature (-40 °C/°F) applications.
Example: 11CX2C
Add “D01” to specify a “direct-couple” listing with 3/8 in. dia by 3/4 in. long
flatted shaft.
Example: 11CX2-D01
Add the letter “E” to listings for European Atex approvals.
Example: 11CX2E
For Replacement Basic Switch Assemblies, change the first number in the
listing to “9”.
Example: 11CX2 becomes 91CX2
Short housing
OPTIONS
HOUSING
SIZE
Short
Short
Short
Short
Short
Short
BASIC
SWITCHES
BZ (2)
BZ (2)
BZ (2)
BZ (2)
BZ (2)
BZ (2)
CONTACT
SPDT
SPDT
SPDT
SPDT
SPDT
SPDT
ELECTRICAL
RATING
A
A
A
A
F
F
SHAFT RESTORING
FORCE TO CENTRE
With
Without
With
Without
With
Without
Standard
Standard
BZ (4)
BZ (4)
REFERENCE
11CX2
11CX12
11CX2E
11CX12E
1172CX2
1172CX12
SPDT
SPDT
A
A
With
Without
21CX4
21CX14
UL listed for Class I, Group B (hydrogen atmospheres)
Standard housing
HOUSING
SIZE
Standard
Standard
Short
Short
Standard
BASIC
SWITCHES
DT (2)
DT (2)
HS (2)
HS (2)
HS (4)
CONTACT
DPDT
DPDT
SPDT
SPDT
SPDT
ELECTRICAL
RATING
C
C
D
D
D
SHAFT RESTORING
FORCE TO CENTRE
With
Without
With
Without
With
REFERENCE
24CX2
24CX12
16CX2
16CX12
26CX4
Analog output, 4 mA to 20 mA
HOUSING
SIZE
Short
Short
Short
Standard
Standard
BASIC
SWITCHES
None
None
None
BZ (2)
BZ (2)
CONTACT
N/A
N/A
N/A
SPDT
SPDT
ELECTRICAL
RATING
G
G
G
A, G
A, G
SHAFT RESTORING
FORCE TO CENTRE
With
Without
Without
With
Without
REFERENCE
18CX0
18CX10
18CX10E
281CX2
281CX12
Bronze housing for use in corrosive
environments
80CX switches have rugged bronze housings which are resistant to salt water
and other corrosive environments. They comply with the NEMA 4X
requirement for protection against corrosion, in addition to NEMA enclosure
standards met by other CX switches. O-ring seals make the enclosure weatherproof, but are outside of required flame paths, maintaining explosion-proof
requirements.
HOUSING
SIZE
Standard
Standard
Standard
Standard
BASIC
SWITCHES
BZ (2)
BZ (4)
BZ (4)
DT (2)
www.honeywell.com/sensing
CONTACT
SPDT
SPDT
SPDT
DPDT
ELECTRICAL
RATING
A
A
A
C
SHAFT RESTORING
FORCE TO CENTRE
With
With
Without
With
REFERENCE
81CX2
81CX4
81CX14
84CX2
65
EXPLOSION PROOF SWITCHES
LSX/BX Series weather sealed, explosion proof limit switches are for use either
indoor or outdoors in hazardous atmospheres. They are completely sealed
and designed for use in explosive gas/dust environments.
LSX/BX Series
Weather sealed
explosion proof
switches
BX X
ATE
LSX/BX products meet the sealing standards of NEMA 1, 3, 4, 6, 7, 9 and 13.
BX products are also sealed to IP67 standard and are ATEX approved (see
specifications below).
All heads are field adjustable at 90° increments. Heads with side rotary
actuators can be adjusted for clockwise and counter clockwise operation.
d
rove
app
Actuators
Sealing:
LSX
NEMA 1, 3, 4, 6, 7 (Class 1, Division 1, Groups B, C, D),
9 (Class 2, Division 1, Groups E, F, G), 13
IP67, NEMA 1, 3, 4, 6, 7 (Class 1, Division 1, Groups B, C, D),
9 (Class 2, Division 1, Groups E, F, G), 13
BX
Rotary actuated switches
Approvals:
LSX/BX
UL, CSA*
BX only
EExd IIC T6 category II 2 GD, SIRA 00ATEX 1037X
Contacts:
Electrical ratings A, B
Silver
Electrical rating C
Gold
Switching options:
SPDT
DPDT
Single Pole, Double Throw
Double Pole, Double Throw
Snap action contacts (1NC/1NO)
Snap action contacts (2NC/2NO)
Operating torque max.:
Standard
Low
Standard
Low
Standard
Low
0,45 N m (4.0 in lb)
0,19 Nm (1.7 in lb)
15°
9°
60°
66°
Differential travel max. (DT):
Standard SPDT
Standard DPDT
Low SPDT
Low DPDT
5°
7°
3°
4°
Pretravel max. (PT):
SPDT Double Break
DPDT Double Break
* Applies only to listings with ½ in NPT or ¾ in NPT
Electrical ratings
10 amps continuous carry. Circuits on any one pole must be the same polarity.
ac Volts
Pilot duty: 600 Vac, 720 VA
A
SPDT
NEMA
A600
B
DPDT
NEMA
B600
C
SPDT/DPDT
Amps at 0.35 Power Factor
Vac
Make
Break
120
60
6
240
30
3
480
15
1.5
600
12
1.2
120
30
3
240
15
1.5
480
7.5
0.75
600
6
0.60
250 Vac or 60 Vdc, 0.050 amp max.
Overtravel min. (OT):
Note: Levers are ordered separately
(see pages 71-73 for details)
dc Volts
Pilot duty: 240 Vdc, 30 watts
A
SPDT
B
DPDT
C
SPDT/DPDT
66
Make and Break Amps
Vdc
Inductive
Resistive
120
0.25
0.8
240
0.15
0.4
120
0.25
0.8
240
0.15
0.4
250 Vac or 60 Vdc, 0.050 amp max.
www.honeywell.com/sensing
EXPLOSION PROOF SWITCHES
OPTIONS
Side rotary
Maintained contact
39,6
1.56
50,8
2.00
Operating torque max.:
Pretravel max. (PT):
Overtravel min. (OT):
Differential travel max. (DT):
19,0
0.75
25,4
1.00
31,9
1.25
LSX
Operating temperature:
49,3
1.94
Maintained
Maintained
Maintained
CONTACT
SPDT
DPDT
DPDT
-1 °C to 121 °C (30 °F to 250 °F)
CONDUIT
½ in - 14NPT
¾ in - 14NPT
½ in - 14NPT
ELECTRICAL RATING
A
B
B
REFERENCE
LSXN3K
LSXN4L
LSXN7L
BX (ATEX approved)
LSX
Operating temperature:
Low DT
SPDT
DPDT
0,45 N m (4.0 in lb)
65°
20°
30°
35°
CONTACT
SPDT
SPDT
SPDT
SPDT
DPDT
DPDT
DPDT
SPDT
-12 °C to 121 °C (10 °F to 250 °F)
CONDUIT
½ in - 14NPT
20 mm
¾ in - 14NPT
½ in - 14NPT
¾ in - 14NPT
20 mm
½ in - 14NPT
½ in - 14NPT
ELECTRICAL RATING
A
A
A
C
B
B
B
A
CONDUIT
½ in - 14NPT
20 mm
¾ in - 14NPT
ELECTRICAL RATING
A
A
B
REFERENCE
LSXA3K
LSX4A3K
LSXA4K
LSXA3E
LSXA4L
LSX4A4L
LSXA7L
LSXP3K
Operating temperature:
Maintained
Maintained
CONTACT
SPDT
DPDT
-40 °C to 70 °C [ -40 °F to 158 °F]
CONDUIT
½ in - 14NPT
¾ in - 14NPT
ELECTRICAL RATING
A
B
REFERENCE
BXN3K
BXN4L
Top rotary
BX (ATEX approved)
Operating temperature:
CONTACT
SPDT
SPDT
DPDT
-40 °C to 70 °C [ -40 °F to 158 °F]
REFERENCE
BXA3K
BX4A3K
BXA4L
LSX
Operating temperature:
Low
Low
Low
Low
DT/Low torque
DT/Low torque
torque
torque
CONTACT
SPDT
DPDT
SPDT
DPDT
-1 °C to 121 °C (30 °F to 250 °F)
CONDUIT
½ in - 14NPT
¾ in - 14NPT
½ in - 14NPT
¾ in - 14NPT
ELECTRICAL RATING
A
B
A
B
REFERENCE
LSXH3K
LSXH4L
LSXR3K
LSXR4L
Operating temperature:
CONTACT
SPDT
SPDT
DPDT
SPDT
DPDT
-40 °C to 70 °C [ -40 °F to 158 °F]
CONDUIT
½ in - 14NPT
½ in - 14NPT
¾ in - 14NPT
ELECTRICAL RATING
A
C
C
REFERENCE
BXR3K
BXR3E
BXR4S
0,28 N m (2.5 in lb)
25°
100°
10°
12°
LSX
Operating temperature:
BX (ATEX approved)
Low torque
Low torque
Low torque
Operating torque max.:
Pretravel max. (PT):
Overtravel min. (OT):
Differential travel max. (DT):
CONTACT
SPDT
DPDT
-1 °C to 121 °C (30 °F to 250 °F)
CONDUIT
½ in - 14NPT
¾ in - 14NPT
ELECTRICAL RATING
A
B
REFERENCE
LSXB3K
LSXB4L
Centre neutral
Operating torque max. :
Pretravel max. (PT):
Overtravel min. (OT):
Differential travel max. (DT):
0,45 N m (4.0 in lb)
18°
57°
10°
LSX
Operating temperature:
CONTACT
DPDT
DPDT
-1 °C to 121 °C (30 °F to 250 °F)
CONDUIT
¾ in - 14NPT
20 mm
ELECTRICAL RATING
B
B
REFERENCE
LSXM4N
LSX4M4N
www.honeywell.com/sensing
67
EXPLOSION PROOF SWITCHES
LSX/BX Series (continued)
Plunger actuated switches
BX X
d
ATpE
rove
ap
Top plungers
Operating force max. (OF):
Pretravel max. (PT):
Overtravel min. (OT):
Differential travel max. (DT):
SPDT
DPDT
17,79 N (4 lb)
1,78 mm (0.07 in)
4,83 mm (0.19 in)
0,38 mm (0.015 in)
0,51 mm (0.02 in)
OPTIONS
Top pin plunger
Top roller plunger
Head can be set at 90° increments for cam or slide actuation
Operating point:
58,5 mm ± 0,76 mm
(2.305 in ± 0.03 in)
LSX
Operating temperature:
CONTACT
SPDT
SPDT
DPDT
CONDUIT
½ in - 14NPT
20 mm
¾ in - 14NPT
-12 °C to 93 °C (10 °F to 200 °F)
ELECTRICAL RATING
A
A
B
REFERENCE
LSXC3K
LSX4C3K
LSXC4L
Operating temperature:
-40 °C to 70 °C [ -40 °F to 158 °F]
CONTACT
SPDT
DPDT
DPDT
REFERENCE
BX4C3K
BXC4L
BX4C4L
ELECTRICAL RATING
A
B
B
Operating temperature:
CONDUIT
½ in - 14NPT
20 mm
¾ in - 14NPT
-40 °C to 70 °C [ -40 °F to 158 °F]
CONTACT
SPDT
REFERENCE
BX4D3K
CONDUIT
20 mm
Min.
operating point
Max.
65,7
operating point (2,59)
72,0
(2,83)
65,66 mm to 72,01 mm
(2.585 in to 2.835 in)
LSX
Operating temperature:
CONTACT
SPDT
68
CONDUIT
½ in - 14NPT
ELECTRICAL RATING
A
-12 °C to 93 °C (10 °F to 200 °F)
REFERENCE
LSXD3K
LSX4D3K
LSXD4L
Operating temperature:
21,6
(0.85)
Operating point:
ELECTRICAL RATING
A
A
B
BX (ATEX approved)
Top pin plunger, adjustable
7,9
(0.31)
68,6 mm ± 1.00 mm (2.700 in ± 0.04 in)
LSX
CONTACT
SPDT
SPDT
DPDT
BX (ATEX approved)
CONDUIT
20 mm
¾ in - 14NPT
20 mm
Operating point:
-12 °C to 93 °C (10 °F to 200 °F)
REFERENCE
LSXV3K
www.honeywell.com/sensing
ELECTRICAL RATING
A
EXPLOSION PROOF SWITCHES
Wobble actuated switches
OPTIONS
Side plungers
Plastic rod
Operating force max. (OF):
Pretravel max. (PT):
Overtravel min. (OT):
Differential travel max. (DT):
26,69 N (6 lb)
2,54 mm (0.10 in)
4,83 mm (0.19 in)
1,14 mm (0.045)
OPTIONS
Side pin plunger
39,6
1.56
50,8
2.00
19,0
0.75
25,4
1.00
49,3
1.94
Operating point:
33,0 mm (1.30 in)
LSX
Operating temperature:
CONTACT
SPDT
DPDT
CONDUIT
½ in - 14NPT
¾ in - 14NPT
ELECTRICAL RATING
A
B
-12 °C to 93 °C (10 °F to 200 °F)
REFERENCE
LSXE3K
LSXE4L
Operating force max. (OF):
Pretravel max. (PT):
2,78 N (10 oz)
25,4 mm (1.0 in)
LSX
Operating temperature:
CONTACT
SPDT
DPDT
Side roller plunger
CONDUIT
½ in - 14NPT
¾ in - 14NPT
ELECTRICAL RATING
A
B
-12 °C to 93 °C (10 °F to 200 °F)
REFERENCE
LSXJ3K-7A
LSXJ4L-7A
Roller may be set in vertical or horizontal position for cam or slide actuation
Cat whisker
Operating point:
44,1 mm (1.735 in)
LSX
Operating temperature:
CONTACT
SPDT
CONDUIT
½ in - 14NPT
ELECTRICAL RATING
A
-12 °C to 93 °C (10 °F to 200 °F)
REFERENCE
LSXF3K
Operating force max. (OF):
Pretravel max. (PT):
BX (ATEX approved)
Operating temperature:
-40 °C to 70 °C [ -40 °F to 158 °F]
LSX
CONTACT
SPDT
REFERENCE
BXF3K
Operating temperature:
CONDUIT
½ in - 14NPT
ELECTRICAL RATING
A
CONTACT
SPDT
CONDUIT
½ in - 14NPT
www.honeywell.com/sensing
ELECTRICAL RATING
A
1,39 N (5 oz)
50,8 mm (2.0 in)
-12 °C to 93 °C (10 °F to 200 °F)
REFERENCE
LSXK3K-8A
69
70
www.honeywell.com/sensing
LEVERS
Levers
REFERENCE
Separate levers must be ordered with side rotary
types. The table provides a cross reference
between product families and the lever order/
reference numbers. The following pages describe
the levers. Illustrations are for reference only.
Exact mounting drawings and dimensions are
available from your local sales office or from the
website below.
Levers lock in any position, 360° around the shaft.
Rollers may be mounted on the front or back of the
lever.
All levers are supplied with cap screws.
Explosion proof switches
Because of explosion proof requirements, only
nylon rollers or other non sparking material should
be selected. BX/LSX, CX and EX plunger and cat
whisker types are of non sparking material. Do not
mix or substitute.
Specification (unless stated
otherwise)
Lever radius/length:
Roller Diameter:
Roller Width:
-EX
1.5 in (38,1 mm)
0.75 in (19,1 mm)
0.25 in (6,35 mm)
0.312 in (7,92 mm)
Note:
Not all levers are compatible with
all switches
6PA57
6PA63
6PA69
6PA80
6PA82
6PA102
6PA144
GLZ51A
GLZ51B
GLZ52A
GLZ52B
GLZ54J
GLZ55B
LSZ51
LSZ51A
LSZ51B
LSZ51C
LSZ51D
LSZ51W
LSZ51Y
LSZ52
LSZ52A
LSZ52B
LSZ52C
LSZ52D
LSZ52J
LSZ52K
LSZ52M
LSZ52N
LSZ52W
LSZ52Y
LSZ53A
LSZ53B
LSZ53D
LSZ53E
LSZ53P
LSZ53S
LSZ53U
LSZ54
LSZ54M
LSZ54N
LSZ54R
LSZ54V
LSZ55
LSZ55A
LSZ55B
LSZ55C
LSZ55D
LSZ55W
LSZ55Y
LSZ61
LSZ67AA
LSZ68
6PA5-EX
6PA127-EX
6PA130-EX
6PA131-EX
6PA136-EX
6PA138-EX
6PA142-EX
6PA204-EX
ROLLER
MATERIAL
Aluminium
Stainless steel
Spring rod
Steel
Steel
Nylon
Ball bearing
Nylon
Steel
Nylon
Steel
Aluminium
Steel
N/A
Nylon
Steel
Nylon
Steel
Rubber
Rubber
N/A
Nylon
Steel
Nylon
Steel
Nylon
Nylon
Nylon
Nylon
Rubber
Rubber
Nylon
Steel
Steel
Nylon
Steel
Nylon
Steel
N/A
Aluminium
Stainless steel
Spring wire
Cable
N/A
Nylon
Steel
Nylon
Steel
Rubber
Rubber
Nylatron
Rubber
Delrin
Bronze
Nylon
Bronze
Bronze
Aluminium
Nylon
Bronze
Nylon
GLA
LIMIT SWITCH SERIES
HDLS
LS2
LS
EXPLOSION PROOF SERIES
BX/LSX
CX
EX
!
!
!
!
!
!
!
!
!
!
!
!
!
!
!
!
!
!
!
!
!
!
!
!
!
!
!
!
!
!
!
!
!
!
!
!
!
!
!
!
!
!
!
!
!
!
!
!
!
!
!
!
!
!
!
!
!
!
!
!
!
!
!
!
!
!
!
!
!
!
!
!
!
!
!
!
!
!
!
!
!
!
!
!
!
!
!
!
!
!
!
!
!
!
!
!
!
Stainless steel
levers
LS2Z51A
LS2Z51B
LS2Z52A
LS2Z52B
LS2Z54N
Nylon
Steel
Nylon
Steel
Steel
!
!
!
!
!
www.honeywell.com/sensing
!
!
!
!
!
!
!
71
LEVERS
OPTIONS * denotes lever suitable for Explosion Proof Series switches
One way roller lever
Standard fixed lever
MOUNTED ON
REFERENCE
LSZ51*
Nylon roller
Metal roller
Front
Front
LSZ51A*
LSZ51B
Nylon roller
Metal roller
Back
Back
LSZ51C*
LSZ51D
Nylon roller
Metal roller
Front
Front
GLZ51A
GLZ51B
Bronze roller
Nylon roller
Front
Front
6PA5-EX*
6PA127-EX*
Ball bearing roller
Front
6PA144
Without roller
Adjustable rod
RADIUS/LENGTH
Hub only
Bronze roller, clockwise
RADIUS/LENGTH REFERENCE
1.56 in (39,6 mm) 6PA130-EX*
Bronze roller, counter clockwise 1.56 in (39,6 mm) 6PA142-EX*
Perpendicular (cross) roller lever
Offset fixed lever
REFERENCE
LSZ54*
Aluminium rod
5.5 in (139,7 mm) LSZ54M*
Stainless steel rod
13.0 in (330,2 mm) LSZ54N
Aluminium, spring only
12.0 in (305 mm)
LSZ54R
Aluminium, flexible cable
4.8 in (122 mm)
LSZ54V
Aluminium rod
7.9 in (200 mm)
GLZ54J
Stainless steel rod
13.0 in (330,2 mm) 6PA63
Aluminium rod
5.3 in (134,1 mm) 6PA136-EX*
Adjustable rod, nylon roller
MOUNTED ON
REFERENCE
LSZ55*
Nylon roller
Metal roller
Back
Back
LSZ55A*
LSZ55B
Nylon roller
Metal roller
Front
Front
LSZ55C*
LSZ55D
Metal roller
Front
GLZ55B
Without roller
RADIUS/LENGTH REFERENCE
1.81 in (46,0 mm) 6PA131-EX*
Bronze roller
Yoke lever
Aluminium rod, nylon roler
RADIUS/LENGTH REFERENCE
12.5 in (317,5 mm) 6PA204-EX*
Adjustable lever
Spring rod
Operating radius/length:
-EX
1.5 in to 3.5 in
(38,1 mm to 88,9 mm)
1.69 in to 3.0 in
(42,9 mm to 76,2 mm)
Adjustable lever, without roller
MOUNTED ON REFERENCE
LSZ52
Nylon roller
Metal roller
Back
Back
LSZ52A*
LSZ52B
Nylon roller
Metal roller
Nylon roller,
Ø 1.0 in (25,4) x 0.5 in (12,7 mm)
Nylon roller, Ø 1.5 in (38,1)
Nylon roller, Ø 2.0 in (50,8)
Nylon roller, 0.5 in wide (12,7 mm)
Front
Front
LSZ52C*
LSZ52D
Front
Front
Front
Front
LSZ52J*
LSZ52K*
LSZ52M*
LSZ52N*
Nylon roller
Metal roller
Back
Back
GLZ52A
GLZ52B
Nylon roller,
Ø 1.0 in (25,4) x 0.5 in (12,7 mm) Front
Nylon roller
Metal roller
MOUNTED ON
Front/Back
Front/Back
REFERENCE
LSZ53A
LSZ53B
Metal roller
Front/Front
LSZ53D
Nylon roller
Back/Front
LSZ53E*
Metal roller
Nylon roller
Back/Back
Back/Back
LSZ53P
LSZ53S*
Metal roller
Back/Front
LSZ53U
Metal roller
Metal roller
Nylon roller
Front/Back
Front/Front
Front/Front
6PA80
6PA82
6PA102
RADIUS/LENGTH
12.0 in (305 mm)
REFERENCE
LSZ68
Ø 0.17 in (4,32 mm)
7.4 in (188 mm)
6PA69
6PA138-EX*
Note:
72
Ø 0.25 in (6,35 mm)
Not all levers are compatible with all switches
www.honeywell.com/sensing
LEVERS
* denotes lever suitable for Explosion Proof Series switches
Stainless steel levers
**Large rubber roller, adjustable
lever
Flexible loop
Roller Diameter:
Roller Width:
0.75 in (19,1 mm)
0.25 in (6,35 mm)
OPTIONS
Standard fixed lever
Flexible loop
RADIUS/LENGTH
6.0 in (152 mm)
REFERENCE
LSZ61
REFERENCE
LSZ52W
Ø 1.6 in X 0.50 in wide roller
(40,6 mm X 12,7 mm)
Hand operated button
Ø 2 in X 0.50 in wide roller
(50,8 mm X 12,7 mm)
LSZ52Y
Operating radius/length:
1.5 in (38,1 mm)
Nylon roller
MOUNTED ON
Front
REFERENCE
LS2Z51A*
Stainless steel roller
Front
LS2Z51B
**Conveyor roller arm
Adjustable lever
Ø 1.5 in (38,1 mm)
REFERENCE
6PA57
**Large rubber roller, fixed lever
Operating radius/length:
Plastic roller, 1.5 in Ø X 3.8 in long
(38,1 mm X 96,5 mm)
6.78 in (172,2 mm)
REFERENCE
LSZ67AA
NOTICE **
Ø 1.6 in X 0.50 in wide roller
(40,6 mm X 12,7 mm)
Ø 2 in X 0.50 in wide roller
(50,8 mm X 12,7 mm)
REFERENCE
LSZ51W
LSZ51Y
Large rubber rollers and conveyor roller arm
Because of the lever’s mass, the limit switch should be
mounted with the lever facing down. This will enable
gravity to help restore the switch to the free position.
Operating radius/length:
1.5 in to 3.5 in
(38,1 mm to 88,9 mm)
Nylon roller
MOUNTED ON
Back
REFERENCE
LS2Z52A*
Stainless steel roller
Back
LS2Z52B
Adjustable rod
**Large rubber roller, fixed offset
lever
Operating radius/length:
Ø 1.6 in X 0.50 in wide roller
(40,6 mm X 12,7 mm)
Ø 2 in X 0.50 in wide roller
(50,8 mm X 12,7 mm)
13 in (330,2 mm)
REFERENCE
LS2Z54N
REFERENCE
LSZ55W
LSZ55Y
Note:
Not all levers are compatible with all switches
www.honeywell.com/sensing
73
POWER RELAYS
Solder/Plug-In Terminal, DPDT
2,6
[0.10]
SZR-MY
Series Power
Relay
8 - O 1,2 [0.05] x 3 Holes
Current rating (SZR-MY2):
Current rating (SZR-MY4):
Contact resistance:
Contact material:
Agency approvals:
Operate time:
Release time:
Ambient temperature:
Ambient humidity:
Switching options:
5A
3A
50 mOhm max.
Fine silver
UL, CE, CSA
20 ms max.
20 ms max.
-25 °C to 75 °C (-13 °F to 167 °F)
45% RH to 85% RH
DPDT, 4PDT
6,3
[0.25]
SZR-MY Series relays have a small package design for multiple application
needs. Relays are available in two configurations: DPDT with a 5 A load and
4PDT with a 3 A load. One standard and three options are available: LED
indicator, internal surge protection diode, and LED indicator/diode protection.
0,5
[0.02]
Max. 36,0 [1.42]
Max. 28,0 [1.10]
0,5
[0.02]
SZR-MY Series general-purpose power relays are designed for a wide range
of applications including power, as well as logic control, for factory machines
and control panels.
Max. 21,5
[0.85]
6,0
[0.24]
Standard
COIL INPUT VOLTAGE
110/120 Vac
220 Vac
12 Vdc
24 Vdc
MAX. CONTACT RATING
250 Vac/5 amp
250 Vac/5 amp
125 Vdc/1 amp
125 Vdc/1 amp
REFERENCE
SZR-MY2-1-AC110-120V
SZR-MY2-1-AC220V
SZR-MY2-1-DC12V
SZR-MY2-1-DC24V
MAX. CONTACT RATING
250 Vac/5 amp
250 Vac/5 amp
125 Vdc/1 amp
125 Vdc/1 amp
REFERENCE
SZR-MY2-N1-AC110-120V
SZR-MY2-N1-AC220V
SZR-MY2-N1-DC12V
SZR-MY2-N1-DC24V
MAX. CONTACT RATING
125 Vdc/1 amp
REFERENCE
SZR-MY2-D1-DC24V
LED Indicator
COIL INPUT VOLTAGE
110/120 Vac
220 Vac
12 Vdc
24 Vdc
Diode Protection
MY2 Series
COIL INPUT VOLTAGE
24 Vdc
OPTIONS
LED Indicator/Diode Protection
COIL INPUT VOLTAGE
24 Vdc
3,3
[0.13]
1,0
[0.04]
Standard, PCB Terminal, DPDT
6,3
[0.25]
0,5
[0.02]
Max. 36,0 [1.42]
COIL INPUT VOLTAGE
110/120 Vac
220/240 Vac
24 Vdc
74
Max. 28,0
[1.10]
0,5
[0.02]
3,5
[0.14]
Max. 21,5
[0.85]
6,0
[0.24]
MAX. CONTACT RATING
250 Vac/5 amp
250 Vac/5 amp
125 Vdc/1 amp
REFERENCE
SZR-MY2-1P-AC110-120V
SZR-MY2-1P-AC220V-240V
SZR-MY2-1P-DC24V
www.honeywell.com/sensing
MAX. CONTACT RATING
125 Vdc/1 amp
REFERENCE
SZR-MY2-X1-DC24V
POWER RELAYS
Solder/Plug-In Terminal, 4PDT
MY4 Series
2,6
[0.10]
OPTIONS
14 - O 1.2 [0.05] x 3 Holes
Max. 28,0
[1.10]
6,3
[0.25]
0,5
[0.02]
6,3
[0.25]
3,5
[0.14]
0,5
[0.02]
Max. 36,0 [1.42]
COIL INPUT VOLTAGE
110/120 Vac
220/240 Vac
24 Vdc
Max. 21,5
[0.85]
6,0
[0.24]
Standard
5,0
[0.20]
MAX. CONTACT RATING
250 Vac/3 amp
250 Vac/3 amp
125 Vdc/0.6 amp
Max. 21,5
[0.85]
0,5
[0.02]
Max. 36,0 [1.42]
Max. 28,0
[1.10]
0,5
[0.02]
3,3
[0.13]
1,0
[0.04]
Standard, PCB Terminal, 4PDT
REFERENCE
SZR-MY4-1P-AC110-120V
SZR-MY4-1P-AC220V-240V
SZR-MY4-1P-DC24V
COIL INPUT VOLTAGE
110/120 Vac
220 Vac
12 Vdc
24 Vdc
MAX. CONTACT RATING
250 Vac/3 amp
250 Vac/3 amp
125 Vdc/0.6 amp
125 Vdc/0.6 amp
REFERENCE
SZR-MY4-1-AC110-120V
SZR-MY4-1-AC220V
SZR-MY4-1-DC12V
SZR-MY4-1-DC24V
MAX. CONTACT RATING
250 Vac/3 amp
250 Vac/3 amp
125 Vdc/0.6 amp
125 Vdc/0.6 amp
REFERENCE
SZR-MY4-N1-AC110-120V
SZR-MY4-N1-AC220V
SZR-MY4-N1-DC12V
SZR-MY4-N1-DC24V
MAX. CONTACT RATING
125 Vdc/0.6 amp
REFERENCE
SZR-MY4-D1-DC24V
LED Indicator
COIL INPUT VOLTAGE
110/120 Vac
220 Vac
12 Vdc
24 Vdc
Diode Protection
COIL INPUT VOLTAGE
24 Vdc
LED Indicator/Diode Protection
COIL INPUT VOLTAGE
24 Vdc
www.honeywell.com/sensing
MAX. CONTACT RATING
125 Vdc/0.6 amp
REFERENCE
SZR-MY4-X1-DC24V
75
POWER RELAYS
SZR-LY Series Power Relay
LY2 Series
OPTIONS
Operate time:
Release time:
Ambient temperature:
Ambient humidity:
Switching options:
10 A
50 mOhm max.
Silver cadium oxide
UL, CE, CSA
18,000 operations/hour (mechanical)
1,800 operations/hour (electrical)
25 ms max.
25 ms max.
-25 °C to 70 °C (-13 °F to 158 °F)
45% RH to 85% RH
DPDT, 4PDT
Max. 28,0 [1.10]
REFERENCE
SZR-LY2-1P-AC110-120V
SZR-LY2-1P-DC24V
Solder/Plug-In Terminal, DPDT
14 - O 3,0 [0.12]
3,0 [0.12]
Max. 36,0 [1.42]
6,4 [0.26]
Max. 21,5
[0.85]
Standard
COIL INPUT VOLTAGE
110/120 Vac
220 Vac
12 Vdc
24 Vdc
MAX. CONTACT RATING
250 Vac/10 amp
250 Vac/10 amp
125 Vdc/2 amp
125 Vdc/2 amp
REFERENCE
SZR-LY2-1-AC110-120V
SZR-LY2-1-AC220V
SZR-LY2-1-DC12V
SZR-LY2-1-DC24V
MAX. CONTACT RATING
250 Vac/10 amp
250 Vac/10 amp
125 Vdc/2 amp
125 Vdc/2 amp
REFERENCE
SZR-LY2-N1-AC110-120V
SZR-LY2-N1-AC220V
SZR-LY2-N1-DC12V
SZR-LY2-N1-DC24V
MAX. CONTACT RATING
125 Vdc/2 amp
REFERENCE
SZR-LY2-D1-DC24V
LED Indicator
COIL INPUT VOLTAGE
110/120 Vac
220 Vac
12 Vdc
24 Vdc
Diode Protection
COIL INPUT VOLTAGE
24 Vdc
LED Indicator/Diode Protection
COIL INPUT VOLTAGE
24 Vdc
76
www.honeywell.com/sensing
MAX. CONTACT RATING
125 Vdc/ 2 amp
REFERENCE
SZR-LY2-X1-DC24V
Max. 28,0 [1.10]
Current rating:
Contact resistance:
Contact material:
Agency approvals:
Operating frequency:
MAX. CONTACT RATING
250 Vac/10 amp
125 Vdc/2 amp
5,75
[0.23]
One standard and three options are available: LED indicator, internal surge
protection diode, and LED indicator/diode protection.
COIL INPUT VOLTAGE
110/120 Vac
24 Vdc
Max. 21,5 [0.85]
4,5
[0.18]
5,0
[0.20]
SZR-LY Series relays break 10 A loads are ideal for control panels that require
stable and reliable relays.
1,0
[0.04]
Max. 36,0 [1.42]
0,5
[0.02]
SZR-LY Series general-purpose power relays are designed for a wide range of
applications including power, as well as logic control, for factory machines
and control panels.
5,75
[0.23]
2,0
[0.08]
0,5
[0.02]
Standard, PCB Terminal, DPDT
POWER RELAYS
LY4 Series
OPTIONS
Solder/Plug-In Terminal, 4PDT
Max. 41,5 [1.63]
4,5
[0.18]
Max. 28,0 [1.10]
14 - O 3.0 Holes
5,0
[0.20]
Max. 28,0 [1.10]
2,0
[0.08]
1,0
[0.04]
Max. 36,0 [1.42]
0,5
[0.02]
0,5
[0.02]
Standard, PCB Terminal, 4PDT
Max. 36,0 [1.42]
3,0
[0.12]
6,4 [0.25]
Max. 41,5 [1.63]
Standard
COIL INPUT VOLTAGE
110/120 Vac
220/240 Vac
24 Vdc
MAX. CONTACT RATING
250 Vac/10 amp
250 Vac/10 amp
125 Vdc/2 amp
REFERENCE
SZR-LY4-1P-AC110-120V
SZR-LY4-1P-AC220V-240V
SZR-LY4-1P-DC24V
COIL INPUT VOLTAGE
110/120 Vac
220 Vac
12 Vdc
24 Vdc
MAX. CONTACT RATING
250 Vac/10 amp
250 Vac/10 amp
125 Vdc/2 amp
125 Vdc/2 amp
REFERENCE
SZR-LY4-1-AC110-120V
SZR-LY4-1-AC220V
SZR-LY4-1-DC12V
SZR-LY4-1-DC24V
MAX. CONTACT RATING
250 Vac/10 amp
250 Vac/10 amp
125 Vdc/2 amp
125 Vdc/2 amp
REFERENCE
SZR-LY4-N1-AC110-120V
SZR-LY4-N1-AC220V
SZR-LY4-N1-DC12V
SZR-LY4-N1-DC24V
MAX. CONTACT RATING
125 Vdc/2 amp
REFERENCE
SZR-LY4-D1-DC24V
LED Indicator
COIL INPUT VOLTAGE
110/120 Vac
220 Vac
12 Vdc
24 Vdc
Diode Protection
COIL INPUT VOLTAGE
24 Vdc
LED Indicator/Diode Protection
COIL INPUT VOLTAGE
24 Vdc
www.honeywell.com/sensing
MAX. CONTACT RATING
125 Vdc/2 amp
REFERENCE
SZR-LY4-X1-DC24V
77
POWER RELAYS
MY2 Series Socket
LY2 Series Socket
22,0 [0.87]
30,0 [1.18]
25,0 [0.99]
47,0
[1.85]
2 - M4
2 - O 4,5 [0.18] Holes
2,5
[0.10]
18,0
[0.70]
26,0
[1.02]
14,5
[0.57]
30,0 [1.18]
25,0 [0.99]
Max. 61,0 [2.40]
Max. 61,0 [2.40]
POLES
2
REFERENCE
SZX-SMF-08N
2 - O 4,5 [0.18] Holes
14-M3.5x8
18,0
[0.70]
26,0 [1.02]
2-M4
36,0 ± 0,2
[1.42 ± 0.008]
8,0
[0.31]
Max. 45,5
[1.79]
25,0 [0.99]
30,0 [1.18]
3,4 [0.13]
68,0 [2.68]
62,0 ± 0,1 [2.44 ± .004]
2-M3 or 2-M4
2 - O 6,0 [0.24] 7,0
[0.28]
69,0 ± 0,3
[2.72 ± 0.01]
4,5
[0.18]
26,0
[1.02]
35,2 [1.39]
15,6
[0.61]
45,0 [1.77]
3,9
[0.15]
4,2
[0.17]
REFERENCE
SZX-SLF-08N
LY4 Series Socket
6,0
[0.24]
62,0 [2.44]
POLES
2
35,5 [1.40]
MY4 Series Socket
TYPE
Rail socket
Max. 78,5 [3.09]
TYPE
Rail socket
3,0
[0.12]
25,0 ± 0,2
[0.99 ± .008]
4,2
[0.17]
62,0 ± 0,1
[2.44 ± .004]
45,0
[1.77]
15,6
[0.61]
3,0
[0.12]
2-M3 or 2-M4
2 - O 4,5 [0.18] Holes
26,0 [1.02]
19,0
[0.75]
8,0
[0.31]
26,0
[1.02]
35,2
[1.39]
62,0 [2.44]
4,2
[0.17]
3,9
[0.15]
67,0 [2.64]
6,0
[0.24]
Max. 61,0 [2.40]
Max. 66,0 [2.60]
Max. 30,0 [1.18]
TYPE
Rail socket
78
POLES
4
REFERENCE
SZX-SMF-14N
TYPE
Rail socket
www.honeywell.com/sensing
POLES
4
REFERENCE
SZX-SLF-14
SAFETY SWITCHES
Electromechanical Safety
Switches
Honeywell is a worldwide leader in advanced switching and sensing
technology - especially in the area of industrial safety. We offer both
electromechanical safety switches and electronic safety sensors as well as
safety control modules for safety applications in all categories of risk.
Customers can count on our diverse product line to meet all of their machine
safety applications.
Honeywell products meet or exceed European machine safety standards and
have been approved (CE, BG, INRS) for use in Europe for more than 25 years.
As North America moves toward harmonizing with global standards, machine
builders and users can confidently turn to Honeywell for compliant machine
safety solutions. Our products are designed to meet all applicable OSHA and
ANSI standards.
Refer to pages 8 and 9 for more information about degrees of protection and
electrical ratings.
Protective Guarding
Cable Pull Switches
Protective guarding around a dangerous machine can be achieved with
tamper-resistant safety switches. Safety switches incorporate positive opening
operation such that even a welded contact will be mechanically broken and a
stop signaled. These switches monitor the position of moveable guards and
doors, which are used to safeguard access to equipment and provide
protection from ejected pieces, chips, projectiles or oil. These safeguards
require a relatively low investment and provide reliable protection if they are
regularly checked and maintained.
Cable-pull limit switches serve as a readily accessible means of emergency
stop for applications. These cable-pull devices are visible, accessible and easy
to use and they immediately open the emergency stop circuit when activated.
WARNING
!
IMPROPER INSTALLATION
• Consult with local safety agencies and their requirements
•
when designing a machine-control link, interface and all
control elements that affect safety.
Strictly adhere to all installation instructions.
Failure to comply with these instructions could result in
death or serious injury.
www.honeywell.com/sensing
79
SAFETY SWITCHES
Selection Guide for Electromechanical Safety Switches
Approvals
Housing Material
Sealing
Dimensions
Electrical
Rating
Actuator
Operating
Temperature
CSA
UL
CE
Metal
BG
From
Plastic
IEC
IP
NEMA
(USA)
HeightxWidthxDepth
mm
(in)
˚C
(˚F)
GSC
GKM
Series
67
1, 12, 13
66
1, 4, 12,
13
69,4 x 34,0 x 16,0
(2.73 x 1.34 x 0.63)
To
Straight or 90˚
key
AC15, DC13
A300
-25
(-13)
85
(185)
-25
(-13)
85
(185)
AC15, DC13
A300
GSD
66
1, 12, 13
GSE
66
1, 4, 12,
13
83,0 x 65,0 x 30,0
(3.27 x 2.56 x 1.18)
GK
67
1, 4, 12,
13
121,6 x 42,0 x 42,6
(4.79 x 1.65 x 1.68)
Straight, 90˚, Spring
key
AC15, DC13
A600
-25
(-13)
85
(185)
GKL/R
67
1, 4, 6P,
12, 13
149,0 x 110,0 x 48,8
(5.85 x 4.33 x 1.92)
Straight, 90˚, Spring
key
AC15, DC13
A600
-25
(-13)
85
(185)
1CPS
67
1, 4, 12,
13
99,1 x 276,2 x 65,2
(3.9 x 10.87 x 2.57)
Linear
AC15, DC13
A600
-25
(-13)
85
(185)
2CPS
GSS
83,0 x 30,5 x 30,0
(3.27 x 1.2 x 1.18)
67
1, 4, 12,
13
165,1 x 325,9 x 79,8
(6.5 x 12.75 x 3.14)
Left and/or Right
AC15, DC13
A600
-40
(-40)
85
(185)
Hinge
Straight or 90˚
AC15, DC13
A600
AC15, DC13
A300
GK
GKM
GSS
80
www.honeywell.com/sensing
SAFETY SWITCHES
Switching Options
1NC/ 2NC/ 1NC/ 2NC/
1NC 2NC
1NO 2NO 1NO 2NO
Slow Action
Make
Break Before Make
Before
Break
1NC/
1NO
1NC/ 2NC/ 2NC/ 3NC/
4NC
1NO 1NO 2NO 1NO
Special Features
Page Number
Snap Action
Termination
Gold
Contacts
(Low
Energy
Options)
M12 or Cable Daisy chain capability
82
85
Conduit
85
86
Standard
Conduit
87
Conduit
89
Conduit
Integral LED option
93
Conduit
High intensity
multi-cluster LED
95
2CPS
GKL/GKR
1CPS
www.honeywell.com/sensing
81
SAFETY SWITCHES
GKM Series
Global Miniature
Safety Key
Operated Switch
Used alone as Category 1 safety components or, in conjunction with other safety switches and our
complete range of safety relays, it is possible to construct comprehensive protection schemes with
Category 2, 3 or 4 compliance.
The preleaded versions allow rapid fit, easy cable routing and function testing which cut costs
dramatically in OEM applications. Simple upgrade guarding solution for End User applications.
Low energy basic switches are rated as follows:
Operating Voltage Ue
1 Vdc to 60 Vdc or 1 Vac to 125 Vac
Operating Current Ie
1 mA to 50 mA
Example of catalog listing using a low energy basic switch - GKMA19
Mechanical life:
Sealing:
Operating temperature:
Approvals:
> 1 million
IP66/67, EN 60529, NEMA 1, 12, 13
-25 °C to 85 °C (-13 °F to 185 °F)
CE, UL, CSA
AC15 B300
DC13 Q300
Contacts:
Silver
Low energy
Gold plated
Switching options:
Slow action contacts
1 Normally Closed/1 Normally Open, Break Before Make
1NC/1NO, BBM - GKMF
1NC/1NO, BBM, low energy - GKMA, B, C, D
3
4
1 Brown
Blue 3
2
1
White 2
3
2
4 Black
1
4
2 Normally Closed
2NC - GKMF
2NC, low energy - GKMA, B, C, D
3
2
4
3 2
1 Brown
Blue 3
1
White 2
4 Black
1 4
Electrical ratings:
Designation & Utilization
Category
AC15
AC15
AC15
AC14
A600
A300
B300
D300
DC13
DC13
Q300
R300
IEC 60947-5-1/EN 60947-5-1
Rated operational current le (A)
at rated operational voltage Ue
120 V 240 V 380 V 480 V 500 V 600 V
6
3
1,9
1,5
1,4
1,2
6
3
3
1.5
0,6
0,3
125 V 250 V
0,55
0,27
0,22
0,1
Of key slot
90˚ - Key shown in optional
actuating positions
16 max. /
0.63
Body style 'B'
17,2 /
0.67
1,6 /
0.058
12,8 /
0.504
Key
slot
22,0 /
0.866
10 max. /
0.30
2 X mounting holes
for M4 or #8 screws.
Counter bored both sides
08,3 X 4,5 deep.
0.366 0.177
82
www.honeywell.com/sensing
32 max. /
1.26
37,4 /
1.47
2,3 /
0.69
34 max. /
0.34
VA
rating
Make
Break
7200
720
7200
720
3600
360
432
72
69
28
69
28
SAFETY SWITCHES
KEY STYLE
OPTIONS
Side exit cable
Side exit M12 dc micro-change
connector
Straight key
45 /
1.77
2 + max. /
0.945
3,5 /
0.138
12,8 /
0.504
2,5 /
0.093
CABLE LENGTH
1m
1m
2m
2m
2m
2m
3m
3m
3m
3m
CONTACT
2NC, low energy
1NC/1NO, BBM, low energy
1NC/1NO, BBM
2NC
2NC, low energy
1NC/1NO, BBM, low energy
1NC/1NO, BBM
2NC
2NC, low energy
1NC/1NO, BBM, low energy
REFERENCE
GKMA17
GKMA19
GKMA23
GKMA26
GKMA27
GKMA29
GKMA33
GKMA36
GKMA37
GKMA39
Face 'A'
21,3 /
0.638
CONTACT
1NC/1NO, BBM
2NC
2NC, low energy
1NC/1NO, BBM, low energy
REFERENCE
GKMC03
GKMC06
GKMC07
GKMC09
15 /
0.59
6,4 min. /
0.252
22 /
0.866
2 holes for M4
or #8 screws
REFERENCE
GKZ51M
Stainless steel
Bottom exit M12 dc micro-change
connector
90° key
Bottom exit cable
2 holes for M4
or #8 screws with
45˚ C' SK X 2,1 deep
0.083
14 max. /
0.55
Face 'A'
CONTACT
1NC/1NO, BBM
2NC, low energy
1NC/1NO, BBM, low energy
CABLE LENGTH
1m
1m
1m
1m
2m
2m
2m
2m
3m
3m
3m
3m
CONTACT
1NC/1NO, BBM
2NC
2NC, low energy
1NC/1NO, BBM, low energy
1NC/1NO, BBM
2NC
2NC, low energy
1NC/1NO, BBM, low energy
1NC/1NO, BBM
2NC
2NC, low energy
1NC/1NO, BBM, low energy
REFERENCE
GKMB13
GKMB16
GKMB17
GKMB19
GKMB23
GKMB26
GKMB27
GKMB29
GKMB33
GKMB36
GKMB37
GKMB39
REFERENCE
GKMD03
GKMD07
GKMD09
22 /
0.866
6,4 min. /
0.252
Dual exit M12 dc micro-change
connector
24 max. /
0.945
Stainless steel
CONTACT
1NC/1NO, BBM
2NC
2NC, low energy
1NC/1NO, BBM, low energy
12,8 /
0.504
32 max. /
1.25
REFERENCE
GKZ52M
REFERENCE
GKMF03
GKMF06
GKMF07
GKMF09
www.honeywell.com/sensing
83
SAFETY SWITCHES
GSS Series
Hinge Mount Safety
Limit Switch
The Hinge Mount Safety Limit Switch is designed for use on machine access doors as an alternative solution
to key operated interlocks and safety limit switches. When the access door is opened, a follower pin (not
supplied) slides down the slot in the actuator lever, forcing the actuator lever to rotate and positively open the
NC safety circuit to shut off the machine. Closing the access door rotates the actuator lever to the reset
position, closing the NC safety contacts.
The Hinge Mount Safety Limit Switch minimizes alignment problems because it may be offset-mounted from
the hinge point of the door. The tamper-resistant design and the positive opening contacts provide a higher
level of safety than the conventional spring-driven limit switches often used to monitor door position.
Low Energy Switching
In today’s demanding age of low energy controls, electromechanical switches are frequently used to interface
directly with safety relays, PLCs and other low energy devices. To accommodate this requirement GSS offers
a new gold plated contact version of the standard basic switch. This improves reliability of switching at low
currents and voltages by protecting the contact surfaces from contamination during operation or storage
prior to use.
Standard silver contacts have a disadvantage in that the contact surface may tarnish under certain
environmental conditions, e.g. in the presence of moisture.
Low energy basic switches are rated as follows:
Operating Voltage Ue
1 Vdc to 60 Vdc or 1 Vac to 125 Vac
1 mA to 50 mA
Operating Current Ie
Example of catalog listing using a low energy basic switch - GSCB33S2.
Switching options:
GSC/D
Snap action contacts (1NC/1NO)
13
14
21
22 Zb
Slow action contacts (1NC/1NO) BBM
GSE
Slow action contacts (4NC)
12
21
22
31
32 4Y
41
42
Slow action contacts (2NC/2NO) BBM
11
12
21
22
22
21
11
2Y, 2X
Zb
13
14
Slow action contacts (2NC)
11
34
44
Slow action contacts (3NC/1NO) BBM
12
2Y
21
33
43
11
12
21
22
31
32
43
44
3Y, 1X
22
Electrical ratings:
Designation & Utilization
Category
84
AC15
AC15
AC15
AC14
A600
A300
B300
D300
DC13
DC13
Q300
R300
IEC 60947-5-1/EN 60947-5-1
Rated operational current le (A)
at rated operational voltage Ue
120 V 240 V 380 V 480 V 500 V 600 V
6
3
1,9
1,5
1,4
1,2
6
3
3
1.5
0,6
0,3
125 V 250 V
0,55
0,27
0,22
0,1
www.honeywell.com/sensing
VA
rating
Make
Break
7200
720
7200
720
3600
360
432
72
69
28
69
28
SAFETY SWITCHES
ACTUATED SWITCHES
GSC Metal body
GSD Plastic body
EN 50047
Safety Standard
Rotated 90° to the left
from center
22 /
0.87
20 /
0.78
24,75 /
0.97
Rotated 90° to the right
from center
104 /
4.09
70 /
2.76
45 /
1.77
3/
0.12
180
MIN
R 2,15 /
0.08
55 /
2.16
GSC - Metal body
GSC - Metal body
30,5 /
1.20
14,5 /
0.57
3,5 /
0.138
30 /
1.18
CONTACT
1NC/1NO
1NC/1NO, BBM
2NC
2NC, low energy
CONDUIT
½ in NPT
½ in NPT
½ in NPT
20 mm
REFERENCE
GSCA01S1
GSCA03S1
GSCA06S1
GSCC36S1
GSD - Plastic body
conduit
thread
19,8 /
0.78
ø 23 /
ø 0.9
Mechanical life:
Sealing:
(GSC)
(GSD)
Operating temperature:
Approvals:
up to 1 million
IP 66
NEMA 1, 4, 12, 13
NEMA 1, 12, 13
-25 °C to 85 °C
(-13 °F to 185 °F)
IEC/EN 60947-5-1
AC15 A300
DC13 Q300
UL, CSA, BG
CONTACT
1NC/1NO, BBM
2NC
1NC/1NO, BBM
2NC
1NC/1NO
CONDUIT
½ in NPT
½ in NPT
PG 13,5
PG 13,5
20 mm
REFERENCE
GSDA03S1
GSDA06S1
GSDB03S1
GSDB06S1
GSDC01S1
CONTACT
1NC/1NO
1NC/1NO, BBM
2NC
2NC, low energy
CONDUIT
½ in NPT
½ in NPT
½ in NPT
PG 13,5
REFERENCE
GSCA01S3
GSCA03S3
GSCA06S3
GSCB36S3
GSD - Plastic body
CONTACT
1NC/1NO, BBM
2NC
1NC/1NO, BBM
2NC
1NC/1NO
CONDUIT
½ in NPT
½ in NPT
PG 13,5
PG 13,5
20 mm
REFERENCE
GSDA03S3
GSDA06S3
GSDB03S3
GSDB06S3
GSDC01S3
Rotated 90° either direction from
center
5,1 /
0.20
11,5 /
0.45
2/
0.08
45 /
1.77
70 /
2.76
90 min.
90 min.
12,5 /
0.49
28 /
24,8 /
0.97
GSC - Metal body
CONTACT
1NC/1NO
1NC/1NO, BBM
2NC
2NC, low energy
CONDUIT
½ in NPT
½ in NPT
½ in NPT
PG 13,5
REFERENCE
GSCA01S2
GSCA03S2
GSCA06S2
GSCB36S2
GSD - Plastic body
CONTACT
1NC/1NO, BBM
2NC
1NC/1NO, BBM
2NC
1NC/1NO
CONDUIT
½ in NPT
½ in NPT
PG 13,5
PG 13,5
20 mm
REFERENCE
GSDA03S2
GSDA06S2
GSDB03S2
GSDB06S2
GSDC01S2
www.honeywell.com/sensing
85
SAFETY SWITCHES
GSE EN 50047 Compatible
Safety 3 Conduit Metal
Standard
12,5 /
0.49
ACTUATED SWITCHES
Rotated 90° to the left
from center
42 /
1.65
40 /
1.57
22 /
0.87
20 /
0.79
24,75 /
0.97
104 /
4.09
70 /
2.76
45 /
1.77
3/
0.12
R 2,15 /
0.08
60 /
2.37
13,75 /
0.54
12 /
0.47
30 /
1.18
2,5 /
0.1
52 /
2.05
57 /
2.24
4/
0.16
CONTACT
2NC/2NO, BBM
3NC/1NO, BBM
4NC, low energy
65 /
2.56
conduit
thread
CONDUIT
½ in NPT
½ in NPT
20 mm
REFERENCE
GSEA44S1
GSEA46S1
GSEC41S1
23,8 /
0.94
ø 23 /
ø 0.9
Mechanical life:
up to 1 million
Sealing:
IP 66, NEMA/UL 1, 4, 12, 13
Operating temperature:
-25 °C to 85 °C
(-13 °F to 185 °F)
Approvals:
IEC/EN 60947-5-1
AC15 A300
DC13 Q300
UL, CSA, BG
Rotated 90° either direction from
center
5,1 /
0.20
11,5 /
0.45
2/
0.08
45 /
1.77
70 /
2.76
90 min.
90 min.
12,5 /
0.49
28 /
CONTACT
2NC/2NO, BBM
CONDUIT
½ in NPT
24,8 /
0.97
REFERENCE
GSEA44S2
Rotated 90° to the right
from center
180
CONTACT
2NC/2NO, BBM
86
MIN
CONDUIT
½ in NPT
REFERENCE
GSEA44S3
www.honeywell.com/sensing
SAFETY SWITCHES
GK Series
Dual Entry Key
Operated Safety
Interlock Switch
The GK Series is designed specifically for use on machines where key removal brings the machine to an
immediate safe condition. It provides enhanced operator safety when added to hinged or sliding guard
doors, screens and protective covers on enclosures. The GK Series is especially well suited for large door
applications, typically in the automotive plant floor environment. Its heavy duty construction withstands
harsh industrial environments where rugged, long-term durability is required.
Nearly 1000 options are available in a simple to understand part number tree.
A safety lockout device is also available for use with the GK Series. The lockout device (GKZL2) is specifically
designed to prevent a key from being inserted either manually, or by the access door being closed while
maintenance personnel are working on the machine. When inserted, the lockout device can accommodate
up to four padlocks to prevent unauthorised removal of the device.
Mechanical life:
up to 15 million
Sealing:
IP 67, NEMA/UL type 1, 4, 12,13
Operating temperature:
-25 °C to 85 °C (-13 °F to 185 °F)
Approvals:
CE, CSA, UL
AC15 A300/A600
DC13 Q300
Contacts:
Silver
Low energy
Gold
Switching options:
Snap action contacts (1NC/1NO)
Snap action contacts (2NC/2NO)
13
Zb
21
13
14
11
12
23
24
21
22
14
22
Slow action contacts (1NC/1NO), BBM
22
21
Slow action contacts (2NC)
21
22
11
12
2Y
Zb
13
14
Slow action contacts (2NC/2NO), BBM
Slow action contacts (3NC/1NO)
11
12
11
12
21
22
21
22
31
32
2y,2x
13
14
23
24
3y,1x
43
44
Slow action contacts (4NC)
11
12
21
22
31
32
41
42
4y
Electrical ratings:
Designation & Utilization
Category
AC15
AC15
AC15
AC14
A600
A300
B300
D300
DC13
DC13
Q300
R300
IEC 60947-5-1/EN 60947-5-1
Rated operational current le (A)
at rated operational voltage Ue
120 V 240 V 380 V 480 V 500 V 600 V
6
3
1,9
1,5
1,4
1,2
6
3
3
1.5
0,6
0,3
125 V 250 V
0,55
0,27
0,22
0,1
www.honeywell.com/sensing
VA
rating
Make
Break
7200
720
7200
720
3600
360
432
72
69
28
69
28
87
SAFETY SWITCHES
GK Series (continued)
Head orientation
OPTIONS
Opening to front and top
42 /
1.65
32 /
1.26
8/
0.32
9/
0.35
31 /
1.22
45,7
1.80
121,6 /
4.79
Opening to right and top
35 /
1.38
60 /
2.36
82 /
3.23
75,9 /
2.99
42,6 /
1.68
ø 5,3 /
0.21
7,3 /
0.29
30 /
1.18
5,3 /
0.21
Standard
CONDUIT
1/2 NPT
1/2 NPT
1/2 NPT
1/2 NPT
1/2 NPT
1/2 NPT
1/2 NPT
1/2 NPT
1/2 NPT
1/2 NPT
1/2 NPT
1/2 NPT
1/2 NPT
1/2 NPT
PG 13,5
PG 13,5
PG 13,5
20 mm
20 mm
20 mm
20 mm
20 mm
20 mm
20 mm
20 mm
CONTACT
1NC/1NO
1NC/1NO
1NC/1NO
4NC
2NC/2NO, BBM
2NC/2NO, BBM
3NC/1NO, BBM
3NC/1NO, BBM
2NC/NO
4NC, low energy
3NC/1NO, BBM, low energy
1NC/1NO, BBM
1NC/1NO, BBM
2NC
2NC/2NO, BBM
1NC/1NO, BBM
2NC
2NC/2NO, BBM
1NC/1NO
1NC/1NO
1NC/1NO
2NC/NO
4NC, low energy
3NC/1NO, BBM, low energy
2NC
Single LED indicator
KEY
90°
Up-down
None
90°
Straight
90°
Straight
90°
Straight
None
None
Straight
90°
None
Straight
90°
90°
90°
Straight
90°
None
None
None
None
None
REFERENCE
GKBA1L7
GKBA1L8-F11*
GKBA1LX
GKBA10L7
GKBA14L6
GKBA14L7
GKBA16L6
GKBA16L7
GKBA2L6
GKBA30LX
GKBA36LX
GKBA3L6
GKBA3L7
GKBA6LX
GKBB14L6
GKBB3L7
GKBB6L7
GKBC14L7
GKBC1L6
GKBC1L7
GKBC1LX
GKBC2LX
GKBC30LX
GKBC36LX
GKBC6LX
Single LED indicator
CONDUIT CONTACT
1/2 NPT 2NC/2NO, BBM
1/2 NPT 1NC/1NO
KEY
Straight
90°
None
None
Straight
Straight
90°
Side-side
None
None
None
None
None
None
REFERENCE
GKCA1L6
GKCA1L7
GKCA1LX
GKCA6LX
GKCA10L6
GKCA14L6
GKCA14L7
GKCA14L9
GKCA30LX
GKCA36LX
GKCC1LX
GKCC6LX
GKCC30LX
GKCC36LX
KEY
90°
REFERENCE
GKDA14L7
Double LED indicator
CONDUIT CONTACT
1/2 NPT 2NC/2NO, BBM
www.honeywell.com/sensing
REFERENCE
GKCA14M6
22 /
0.87
Single LED indicator
CONTACT
1NC/1NO
1NC/1NO
1NC/1NO
2NC
4NC
2NC/2NO, BBM
2NC/2NO, BBM
2NC/2NO, BBM
4NC, low energy
3NC/1NO, BBM, low energy
1NC/1NO
2NC
4NC, low energy
3NC/1NO, BBM, low energy
KEY
straight
Opening to left and top
* fluorocarbon seal
CONDUIT
1/2 NPT
1/2 NPT
1/2 NPT
1/2 NPT
1/2 NPT
1/2 NPT
1/2 NPT
1/2 NPT
1/2 NPT
1/2 NPT
20 mm
20 mm
20 mm
20 mm
88
CONDUIT CONTACT
1/2 NPT 2NC/2NO, BBM
KEY
Straight
90°
REFERENCE
GKCA14P6
GKCA1P7
Double LED indicator
CONDUIT CONTACT
1/2 NPT 2NC/2NO, BBM
KEY
90°
REFERENCE
GKDA14P7
SAFETY SWITCHES
GKL/GKR Series
Dual Entry Solenoid
Key Operated Safety
Interlock Switch
The GKR (head to the right) and GKL (head to the left) products offer the user an unrivalled range of standard
options.
The GKR/GKL product is a key actuated device incorporating a key trapping mechanism. The switch is used
on machinery where instant stop and access to the machinery is either impossible (due to the momentum of
the machine) or impractical (due to tool or machine damage or scrapped product if the current machine
cycle is interrupted).
The switch incorporates an optional manual override feature which allows removal of the key for emergency
access.
Over 1000 options are available in a simple to understand part number tree.
A safety lockout device is also available for use with the GKR/GKL Series. The lockout device (GKZL2) is
specifically designed to prevent a key from being inserted either manually, or by the access door being
closed while maintenance personnel are working on the machine. When inserted, the lockout device can
accommodate up to four padlocks to prevent unauthorised removal of the device.
Mechanical life:
up to 1 million
Sealing:
IP 68, NEMA/UL type 1, 4, 6P, 12,13
Operating temperature:
-25 °C to 40 °C (-13 °F to 104 °F)
Approvals:
CE, CSA, UL
AC15 A300/A600
DC13 Q300
Contacts:
Silver
Low energy
Gold-plated
Switching options:
Snap Action
Type 11NC/1NO Direct Opening
13
14
21
22 Zb
Slow Acting
Type 3
1NC/1NO, Break before make (BBM)
21
Type 14/15
2NC/2NO, Break before make (BBM)
11
12
21
22
22
2Y, 2X
Zb
13
14
33
34
43
44
2 Slow Acting
Type 36
3NC/1NO, Break before make (BBM),low energy
Type 40
4NC
11
12
21
22
21
22
31
32
31
32 4Y
41
42
43
44
11
3Y, 1X
Type 44
2NC/2NO, Break before make (BBM)
11
12
21
22
2Y,2X
33
34
43
44
12
Type 46
3NC/1NO, Break before make (BBM)
11
12
21
22
31
32
43
44
3Y,1X
www.honeywell.com/sensing
89
SAFETY SWITCHES
GKL/GKR Series (continued)
Key:
Type 6
Type 9
Type X
Straight
Side - side, spring loaded
No key
Latching mechanism:
Type A
Mechanical (solenoid unlock with
screwdriver)
Mechanical (without override)
Electrical (solenoid unlock with
screwdriver)
Type B
Type S
OPTIONS
Opening to front and top
9/
0.35
Solenoid voltage:
Type 2
Type 4
24 Vdc
120 Vac
Electrical ratings:
Designation & Utilization
Category
AC15
AC15
AC15
AC14
A600
A300
B300
D300
DC13
DC13
Q300
R300
IEC 60947-5-1/EN 60947-5-1
Rated operational current le (A)
at rated operational voltage Ue
120 V 240 V 380 V 480 V 500 V 600 V
6
3
1,9
1,5
1,4
1,2
6
3
3
1.5
0,6
0,3
125 V 250 V
0,55
0,27
0,22
0,1
VA
rating
Make
Break
7200
720
7200
720
3600
360
432
72
69
28
69
28
Left
1/2 in - NPT buna-n seals
CONTACT
TYPE
3 (1NC/1NO, BBM)
40 (4NC)
46 (3NC, BBM)
KEY
None
None
None
LATCHING
TYPE
A
A
A
SOLENOID
VOLTAGE
24 Vdc
24 Vdc
24 Vdc
REFERENCE
SOLENOID
VOLTAGE
24 Vdc
24 Vdc
REFERENCE
GKLE3LXA2
GKLE40LXA2
GKLE46LXA2
Right
1/2 in - NPT buna-n seals
32,5 /
1.28
19 /
0.75
33 /
1.30
CONTACT
TYPE
40 (4NC)
46 (3NC, BBM)
31 /
1.22
43,7 / 2 x 7,3 /
1.72
0.29
2 x ø 5,3 /
0.21
75 /
2.95
2 x 5,3 /
0.21
100 /
3.94
105,3 /
4.13
110 /
4.33
20 /
0.79
90
43 /
1.69
48,8 /
1.92
65 /
2.56 100 /
3.94
110 /
4.33
www.honeywell.com/sensing
KEY
None
None
LATCHING
TYPE
A
A
GKRE40LXA2
GKRE46LXA2
SAFETY SWITCHES
Opening to left and top
Opening to right and top
26 /
1.02
12 /
0.47
Left
1/2 in - NPT buna-n seals
Right
1/2 in - NPT buna-n seals
CONTACT
TYPE
3 (1NC/1NO, BBM)
3 (1NC/1NO, BBM)
3 (1NC/1NO, BBM)
3 (1NC/1NO, BBM)
36 (3NC/1NO, BBM, low energy)
36 (3NC/1NO, BBM, low energy)
36 (3NC/1NO, BBM, low energy)
KEY
None
None
None
None
None
None
None
LATCHING
TYPE
A
A
S
S
A
A
S
SOLENOID
VOLTAGE
24 Vdc
120 Vac
24 Vdc
120 Vac
24 Vdc
120 Vac
24 Vdc
LATCHING
TYPE
A
A
S
S
A
A
A
S
S
SOLENOID
VOLTAGE
24 Vdc
120 Vac
24 Vdc
120 Vac
24 Vdc
24 Vdc
120 Vac
24 Vdc
120 Vac
REFERENCE
GKRE3MXA2
GKRE3MXA4
GKRE3MXS2
GKRE3MXS4
GKRE36MXA2
GKRE36MXA4
GKRE36MXS2
20 mm - buna-n seals
CONTACT
TYPE
1 (1NC/1NO)
1 (1NC/1NO)
1 (1NC/1NO)
1 (1NC/1NO)
3 (1NC/1NO, BBM)
36 (3NC/1NO, BBM, low energy)
36 (3NC/1NO, BBM, low energy)
36 (3NC/1NO, BBM, low energy)
36 (3NC/1NO, BBM, low energy)
KEY
None
None
None
None
None
None
None
None
None
CONTACT
TYPE
3 (1NC/1NO, BBM)
3 (1NC/1NO, BBM)
3 (1NC/1NO, BBM)
3 (1NC/1NO, BBM)
36 (3NC/1NO, BBM, low energy)
36 (3NC/1NO, BBM, low energy)
36 (3NC/1NO, BBM, low energy)
36 (3NC/1NO, BBM, low energy)
KEY
None
None
None
None
None
None
None
None
LATCHING
TYPE
A
A
S
S
A
A
S
S
SOLENOID
VOLTAGE
24 Vdc
120 Vac
24 Vdc
120 Vac
24 Vdc
120 Vac
24 Vdc
120 Vac
LATCHING
TYPE
A
A
S
S
S
A
A
S
S
B
SOLENOID
VOLTAGE
24 Vdc
120 Vac
24 Vdc
120 Vac
24 Vdc
24 Vdc
120 Vac
24 Vdc
120 Vac
24 Vdc
REFERENCE
GKLE3PXA2
GKLE3PXA4
GKLE3PXS2
GKLE3PXS4
GKLE36PXA2
GKLE36PXA4
GKLE36PXS2
GKLE36PXS4
20 mm - buna-n seals
REFERENCE
GKRG1MXA2
GKRG1MXA4
GKRG1MXS2
GKRG1MXS4
GKRG3MXA2
GKRG36MXA2
GKRG36MXA4
GKRG36MXS2
GKRG36MXS4
CONTACT
TYPE
1 (1NC/1NO)
1 (1NC/1NO)
1 (1NC/1NO)
1 (1NC/1NO)
3 (1NC/1NO, BBM)
36 (3NC/1NO, BBM, low energy)
36 (3NC/1NO, BBM, low energy)
36 (3NC/1NO, BBM, low energy)
36 (3NC/1NO, BBM, low energy)
44 (2NC/2NO, BBM)
www.honeywell.com/sensing
KEY
Non
None
None
None
None
None
None
None
None
None
REFERENCE
GKLG1PXA2
GKLG1PXA4
GKLG1PXS2
GKLG1PXS4
GKLG3PXS2
GKLG36PXA2
GKLG36PXA4
GKLG36PXS2
GKLG36PXS4
GKLG44PXB2
91
SAFETY SWITCHES
Keys for GK and
GKL/GKR switches
Straight key
49,8 /
1.96
8,5 /
0.33
Locking slider bolt
with actuating key
77 /
3.03
20 /
0.79
2x ø 5,3 /
0.21
14 /
0.55
15 /
0.59
3x HOLE PROVIDED
FOR LOCKOUT
19,0 /
.75
3/
0.12
REFERENCE
GKZ56
90° key
8,5 /
0.33
14 /
0.55
49,8 /
1.96
2 x ø 5,3 /
0.21
40 /
1.57
52 /
2.05
7,0 ±,7 /
.28 ±.03
REFERENCE
GKZ57
4x ø 5,1 /
.20
4,93 /
.194
26,97 / 36,8 /
1.062 1.45
14,0 /
.55
41,81 ±,76 /
1.646 ±.030
Spring-loaded key: up/down
115,87 /
4.562
140,0 ±,7 /
5.51 ±.03
12,04 /
.474
13,5 /
0.53
18,5 /
0.73
17,8 /
0.70
37,10 ±1,52 /
1.460 ±.060 26,77 ±1,52 /
1.054 ±.060
8,5 /
0.33
0°key rotation
REFERENCE
GKZ71
180° key rotation
REFERENCE
GKZ73
90° key rotation
REFERENCE
GKZ72
270° key rotation
REFERENCE
GKZ74
2 X ø 5,3 /
0.21
84,9 /
3.34
40 /
30 /
1.57
1.18
14 /
0.55
REFERENCE
GKZ58
Spring-loaded key: left/right
8,5 /
0.33
84,9 /
3.34
2 X ø 5,3 /
14 /
0.55
0.21
20,5 /
0.81
18,5 /
0.73
13,5 /
0.53
30 /
1.18
40 /
1.57
REFERENCE
GKZ59
92
www.honeywell.com/sensing
SAFETY SWITCHES
CPS Series
Cable Pull Safety
Switch
CPS Series Cable Pull Safety Switches provide a readily accessible emergency stop signal. This is a costeffective means compared to using multiple emergency stop push-buttons. (Cable Pull Safety Switches are
not, however, to be used as a means of personnel safeguarding. They may be used to prevent further injury
or damage to equipment when used for emergency stop signaling.)
The CPS Series Cable Pull Safety switch is designed to provide emergency stop protection for exposed
conveyor and assembly lines. The internal mechanism latches on both slackened cable (push) and pulled
cable. This capability also enhances productivity by eliminating nuisance stops due to variations in temperature,
stretch of cable over time, and other application variables.
The 1CPS is intended for use in applications where the cable span is 76 m (250 ft) or shorter. It is an
economical solution for shorter runs or zone protection typical to automated systems. The 2CPS series is
intended for use in very long cable runs of 152 m (500 ft) or shorter, such as long conveyor lines found in
warehouses.
The CPS complies with: Low Voltage Directive 73/23/EEC, as amended by directive 93/68/EEC; Machinery
Directive 98/37/EEC only as the directives relate to the components being used in a safety function; IEC/EN
60947-1; IEC/EN 60947-5-1; IEC/EN 60947-5-5.
Mechanical life:
1 000 000
Sealing:
IP67, NEMA 1, 4, 12,13
Operating temperature:
1CPS
-25 °C to 80 °C (-13 °F to 176 °F)
2CPS
-40 °C to 80 °C (-40 °F to 176 °F)
Approvals:
AC15 A300
DC13 Q300
1CPS
UL, CSA
2CPS
UL, CSA, BG
Contacts:
1CPS
Silver
1CPS, Low energy
Gold plated
2CPS
Gold plate over silver
Switching options:
1CPS
2CPS
1NC/1NO
21
22
13
14
N/A
2NC/2NO
21
22
21
22
21
22
21
22
13
14
13
14
13
14
13
14
21
22
11
12
21
22
11
12
13
14
21
22
13
14
21
22
11
12
11
12
11
12
11
12
21
22
21
22
21
22
21
22
3NC/1NO
4NC
2CPS contact block mounting:
1
2
1
To housing
Removable with heavy duty terminals
2
I
I
1CPS indicator Light Code:
2CPS indicator Light Code:
No letter
A
B
No letter
A
B
www.honeywell.com/sensing
No indicator provided
24 Vdc red LED
120 Vac red LED
No indicator provided
24 Vdc red multi-cluster LED
120 Vac red multi-cluster LED
93
SAFETY SWITCHES
CPS Series (continued)
1CPS
6,35
[0.25]
B
152,4
[6.0]
81,28
[3.2]
1CPS
Cable Pull
Switch
SLACK
88,9
[3.5]
TENSIONED
33,02
[1.3]
RUN
RESET
OFF
99,06
[3.9]
172,72
[6.8]
76,2
[3.0]
4X Ø 7,11
Ø 0.28
50,8
[2.1]
12,7
[0.5]
117,42
[4.623]
A
65,20
[2.567]
56,79
[2.236] 50,83
[2.001]
3X 25,4
[1.0]
2X 26,67
[1.050]
A
B
C
D
25,4
[1.00]
C
25,4
[1.00]
D
Fully extended
Optional indicator
Conduit thread (3 total)
Mounting pad (4 total)
OPTIONS
Cable maintained
1/2 in NPT
CONTACT
1NC/1NO
1NC/1NO
1NC/1NO
2NC/2NO
2NC/2NO
2NC/2NO
3NC/1NO
3NC/1NO
3NC/1NO
4NC
1NC/1NO, low energy
2NC/2NO, low energy
2NC/2NO, low energy
2NC/2NO, low energy
3NC/1NO, low energy
4NC, low energy
94
20 mm
INDICATOR
None
24 V
120 V
None
24 V
120 V
None
24 V
120 V
None
None
None
24 V
120 V
None
None
REFERENCE
1CPSA1
1CPSA1A
1CPSA1B
1CPSA2
1CPSA2A
1CPSA2B
1CPSA3
1CPSA3A
1CPSA3B
1CPSA4
1CPSA5
1CPSA6
1CPSA6A
1CPSA6B
1CPSA7
1CPSA8
CONTACT
1NC/1NO
1NC/1NO
2NC/2NO
2NC/2NO
2NC/2NO
3NC/1NO
3NC/1NO
4NC
1NC/1NO, low energy
2NC/2NO, low energy
2NC/2NO, low energy
3NC/1NO, low energy
4NC, low energy
www.honeywell.com/sensing
INDICATOR
None
24 V
None
24 V
120 V
None
24 V
None
None
None
24 V
None
None
REFERENCE
1CPSC1
1CPSC1A
1CPSC2
1CPSC2A
1CPSC2B
1CPSC3
1CPSC3A
1CPSC4
1CPSC5
1CPSC6
1CPSC6A
1CPSC7
1CPSC8
SAFETY SWITCHES
2CPS
40,4
(1.60)
67,8
(2.63)
79,8
(3.14)
92,9
(3.66)
325,9 A
(12.75)
152,4
(6.00)
52,1
(2.05)
12,7
(0.50)
18,3
(0.72)
SLACK
RUN
OFF
TENSIONED
34,9
(1.38)
SLACK
TENSIONED
21,1
(0.75)
152,4
(6.00)
2X D
2X
2X
8,9
(0.35)
81,3
(3.20)
40,5
(1.60)
6,9
(0.27)
104,8
(4.13)
2X C
B
6,4
(0.25)
2X 31,75
(1.25)
57,2
(2.25)
12,7
(0.50)
2X D
C
2X 6,9
(0.27)
3X 21,5
(0.85)
139,7
(5.50)
OFF
Cable maintained both sides
1/2 in NPT
CONTACT
2NC/2NO
2NC/2NO
2NC/2NO
3NC/1NO
3NC/1NO
3NC/1NO
2NC/2NO
2NC/2NO
2NC/2NO
3NC/1NO
3NC/1NO
3NC/1NO
CONTACT BLOCK
MOUNTING
1
1
1
1
1
1
2
2
2
2
2
2
INDICATOR
REFERENCE
CONTACT
None
24 Vdc
120 Vac
None
24 Vdc
120 Vac
None
24 Vdc
120 Vac
None
24 Vdc
120 Vac
2CPSA1A1
2CPSA1A1A
2CPSA1A1B
2CPSA1B1
2CPSA1B1A
2CPSA1B1B
2CPSA2A1
2CPSA2A1A
2CPSA2A1B
2CPSA2B1
2CPSA2B1A
2CPSA2B1B
2NC/2NO
2NC/2NO
2NC/2NO
3NC/1NO
3NC/1NO
3NC/1NO
2NC/2NO
2NC/2NO
2NC/2NO
2NC/2NO
2NC/2NO
4NC
Fully extended
Optional indicator
C
Conduit thread (3 total)
D
Mounting pad (4 total)
INDICATOR
REFERENCE
None
24 Vdc
24 Vdc
2CPSC1A1
2CPSC1A1A
2CPSC1D1A
CONTACT BLOCK
MOUNTING
1
1
1
1
1
1
2
2
2
INDICATOR
REFERENCE
None
24 Vdc
120 Vac
None
24 Vdc
120 Vac
None
24 Vdc
120 Vac
2CPSA1A2
2CPSA1A2A
2CPSA1A2B
2CPSA1B2
2CPSA1B2A
2CPSA1B2B
2CPSA2A2
2CPSA2A2A
2CPSA2A2B
INDICATOR
REFERENCE
None
24 Vdc
2CPSC1A2
2CPSC1A2A
20 mm
CONTACT
CONTACT BLOCK
MOUNTING
1
1
1
A
B
No actuation right side, cable maintained left side
1/2 in NPT
20 mm
CONTACT
SLACK
RUN
TENSIONED
SLACK
TENSIONED
244,6 A
(9.63)
2NC/2NO
2NC/2NO
CONTACT BLOCK
MOUNTING
1
1
No actuation left side, cable maintained right side
1/2 in NPT
CONTACT
2NC/2NO
2NC/2NO
2NC/2NO
3NC/1NO
3NC/1NO
3NC/1NO
2NC/2NO
2NC/2NO
2NC/2NO
CONTACT BLOCK
MOUNTING
1
1
1
1
1
1
2
2
2
INDICATOR
REFERENCE
None
24 Vdc
120 Vac
None
24 Vdc
120 Vac
None
24 Vdc
120 Vac
2CPSA1A3
2CPSA1A3A
2CPSA1A3B
2CPSA1B3
2CPSA1B3A
2CPSA1B3B
2CPSA2A3
2CPSA2A3A
2CPSA2A3B
INDICATOR
REFERENCE
None
24 Vdc
2CPSC1A3
2CPSC1A3A
20 mm
CONTACT
2NC/2NO
2NC/2NO
CONTACT BLOCK
MOUNTING
1
1
www.honeywell.com/sensing
95
SAFETY SWITCHES
CPS Series (continued)
Hardware packets (order separately)
CPS LED
31,75
[1.25]
71,88 ±2,54
[2.83 ±0.10]
11,43
[0.45]
C
B
D
A
207,01 ±1,27
[8.15 ±0.05]
227,33 ±12,7
[8.95 ±0.50]
CPS Bracket
ACCESSORY
REFERENCE
ACCESSORY
REFERENCE
Cable - 7,6 m (25 ft) length
CLSZC1
(1) Draw-bar Endspring
CPSZ1S
Cable - 15,2 m (50 ft) length
CLSZC2
CPSZK1
Cable - 30,5 m (100 ft) length
CLSZC3
Cable - 45,7 m (150 ft) length
CLSZC4
(1) J-hook Turnbuckle with Lock Nuts
(2) Thimbles
(2) Low-profile Duplex Cable Clamps
(16) Sets of Cable Supports ((16) 1/4-20 Eye Bolts,
(32) 1/4-20 Nuts, (32) Flat Washers, (16) Lock Washers)
Cable - 61 m (200 ft) length
CLSZC5
Multicluster LED Accessory - 24 Vdc (conduit mount)
CPSLED24
Cable - 76,2 m (250 ft) length
CLSZC7
Multicluster LED Accessory - 120 Vdc (conduit mount)
CPSLED120
(2) Thimbles
(2) Low-profile Duplex Cable Clamps
CLSZTC
Mounting bracket (to be used with 1CPS or 2CPS)
CPS-BRACKET
J-hook turnbuckle with lock nuts (included with 2CPS)
CPSZTB
96
www.honeywell.com/sensing