General-purpose Relay
G2R-@-S (S)
Slim and Space-saving Power Plug-in Relay
■ Reduces wiring work by 60% when combined with the
P2RF-@-PU Push-In Plus Socket
(according to actual OMRON measurements).
■ Lockable test button models available.
■ Built-in mechanical operation indicator.
■ Provided with nameplate.
■ AC type is equipped with a coil-disconnection self-diagnostic
function (LED type).
■ High switching power (1-pole: 10 A).
LR
For the most recent information on models that have been certified for
safety standards, refer to your OMRON website.
Model Number Structure
Model Number Legend
G2R -
-S
(S)
1
2
3
1. Number of Poles
1:1 pole
2:2 poles
4
5
4. Rated Coil Voltage
5. Mechanical operation indicator and Nameplate
(S):Models with mechanical operation indicator and Nameplate
2. Terminals
S:Plug-in
3. Classification
Blank:General-purpose
N:LED indicator
D:Diode
ND:LED indicator and diode
NI:LED indicator with test button
NDI:LED indicator and diode with test button
Note: Contact your OMRON representative for Relays with gold-plated contacts.
Ordering Information
When your order, specify the rated voltage.
List of Models
Classification
General-purpose
LED indicator
LED indicator with test button
Coil ratings
AC 24, 110, 120, 230, 240
DC 6, 12, 24, 48
Diode
LED indicator and diode
LED indicator and diode with test button
DC 6, 12, 24, 48
Contact form
SPDT
G2R-1-S (S)
DPDT
G2R-2-S (S)
G2R-1-SN (S)
G2R-2-SN (S)
G2R-1-SNI (S)
G2R-2-SNI (S)
G2R-1-SD (S)
G2R-2-SD (S)
G2R-1-SND (S)
G2R-2-SND (S)
G2R-1-SNDI (S)
G2R-2-SNDI (S)
Note: 1. The standard models are compliant with UL/CSA and VDE standards. Also, an EC compliance declaration has been made for combinations with the P2RF-@-E, P2RF-@-S and P2RF-@-PU. The Relays bear the CE Marking.
2. Refer to Connecting Sockets, below, for applicable Socket models.
3. When ordering, add the rated coil voltage and "(S)" to the model number. Rated coil voltages are given in the coil ratings table.
Example: G2R-1-S 12 VDC (S)
Rated coil voltage
1
G2R-@-S (S)
Accessories (Order Separately)
Connecting Sockets
Track/surface-mounting Socket
Applicable Relay model
Push-In Plus
Terminal Blocks
No. of poles
Back-mounting Socket
Screw terminals *
Model
PCB terminals
Solder terminals
Models
Model
Models
1 pole
G2R-1-S (S)
P2RF-05-PU
P2RF-05
P2RF-05-E
2 poles
G2R-2-S (S)
P2RF-08-PU
P2RF-08
P2RF-08-E
P2R-05P
P2R-057P
P2R-05A
P2R-08P
P2R-087P
P2R-08A
* The structure of P2RF-@-E models provides finger protection. Round terminals cannot be used. Use forked crimp terminals.
Accessories for Push-In Plus Terminal Block Sockets (P2RF-@-PU)
Short Bars
Pitch
No. of poles
Model *
Colors
2
3
7.75 mm
PYDN-7.75-030@
Red (R)
Blue (S)
Yellow (Y)
4
20
15.5 mm
Minimum order (quantity)
PYDN-7.75-020@
PYDN-7.75-040@
10
PYDN-7.75-200@
8
PYDN-15.5-080@
Note: Use the Short Bars for crossover wiring within one Socket or between Sockets.
* Replace the box (@) in the model number with the code for the covering color.
Labels
Model
Manufacturer
Minimum order (Box)
(quantity per Box)
MG-CPM-04 41390N
Cembre
1680
(35 Sheet/48 Pieces)
Note: PRINTER: MARKINGENIUS MG3 (Ask to your Omron contact for more details on printers)
Mounting Tracks
Applicable Socket
Description
Model
Minimum order
(quantity)
50 cm (l) × 7.3 mm (t): PFP-50N
Mounting track
Track-connecting Socket
1 m (l) × 7.3 mm (t):
PFP-100N
1 m (l) × 16 mm (t):
PFP-100N2
End plate *1
PFP-M
Spacer
PFP-S
Back-connecting Socket Mounting plate *2
P2R-P
---
10
1
*1. When mounting DIN rail, please use End Plate (PFP-M).Use the Short Bars for crossover wiring within one Socket or between Sockets.
*2. Used to mount several P2R-05A and P2R-08A Connecting Sockets side by side.
2
G2R-@-S (S)
Specifications
Coil Ratings
Rated current*
Rated voltage
50 Hz
AC
60 Hz
Armature
OFF
43.5 mA
37.4 mA
253 Ω
0.81
1.55
110 V
9.5 mA
8.2 mA
5,566 Ω
13.33
26.83
120 V
8.6 mA
7.5 mA
7,286 Ω
16.13
32.46
230 V
4.4 mA
3.8 mA
27,172 Ω
72.68
143.90
240 V
4.2 mA
3.7 mA
27,800 Ω
90.58
182.34
Rated current*
Coil
resistance
Coil inductance (H)
(ref. value)
Armature
OFF
Must
operate
voltage
Armature
ON
24 V
Rated voltage
DC
Coil
resistance
Coil inductance (H)
(ref. value)
87.0 mA
69 Ω
0.25
0.48
12 V
43.2 mA
278 Ω
0.98
2.35
24 V
21.6 mA
1,113 Ω
3.60
8.25
48 V
11.4 mA
4,220 Ω
15.2
29.82
Max.
voltage
% of rated voltage
80% max.
30% max.
Must
operate
voltage
Must
release
voltage
Armature
ON
6V
Must
release
voltage
110%
Max.
voltage
% of rated voltage
70% max.
15% min.
110%
Power
consumption
(approx.)
0.9 VA at 60 Hz
Power
consumption
(approx.)
0.53 W
Note: 1. The rated current and coil resistance are measured at a coil temperature of 23°C with tolerances of +15%/-20% for the AC rated current
and ±10% for the DC coil resistance.
2. The AC coil resistance and inductance values are reference values only (at 60 Hz).
3. Operating characteristics were measured at a coil temperature of 23°C.
4. The maximum voltage is the maximum possible value of the voltage that can be applied to the relay coil.
It is not the maximum voltage that can be applied continuously.
Contact Ratings
Number of poles
1 pole
Load
Resistive load
(cosφ = 1)
Inductive load
(cosφ = 0.4; L/R = 7 ms)
Resistive load
(cosφ = 1)
2 poles
Inductive load
(cosφ = 0.4; L/R = 7 ms)
Rated load
10 A at 250 VAC;
10 A at 30 VDC
7.5 A at 250 VAC;
5 A at 30 VDC
5 A at 250 VAC;
5 A at 30 VDC
2 A at 250 VAC; 3 A at
30 VDC
Rated carry current
10 A
5A
Max. switching voltage
440 VAC, 125 VDC
380 VAC, 125 VDC
Max. switching current
10 A
Max. switching power
2,500 VA,
300 W
Failure rate (reference value) *
100 mA at 5 VDC
5A
1,875 VA,
150 W
1,250 VA,
150 W
500 VA,
90 W
10 mA at 5 VDC
Note: P level: λ60 = 0.1 x 10-6/operation
* This value was measured at a switching frequency of 120 operations per minute.
3
G2R-@-S (S)
Characteristics
Item
1 pole
2 poles
Contact configration
SPDT
Contact structure
Single
Contact resistance
100 mΩ max.
Operate (set) time
15 ms max.
Release (reset) time
AC: 10 ms max.; DC: 5 ms max.
(w/built-in diode: 20 ms max.)
Max. operating
frequency
Mechanical:
Electrical:
Insulation resistance
1,000 MΩ min. (at 500 VDC)
Dielectric strength *
5,000 VAC, 50/60 Hz for 1 min between coil and
5,000 VAC, 50/60 Hz for 1 min between coil and contacts;
contacts;
3,000 VAC, 50/60 Hz for 1 min between contacts of different polarity
1,000 VAC, 50/60 Hz for 1 min between contacts of
1,000 VAC, 50/60 Hz for 1 min between contacts of same polarity
same polarity
Vibration resistance
Destruction:
Malfunction:
10 to 55 to 10 Hz, 0.75 mm single amplitude (1.5 mm double amplitude)
10 to 55 to 10 Hz, 0.75 mm single amplitude (1.5 mm double amplitude)
Shock resistance
Destruction:
Malfunction:
1,000 m/s2
200 m/s2 when energized; 100 m/s2 when not energized
Mechanical:
AC coil: 10,000,000 operations min.;
DC coil: 20,000,000 operations min. (at 18,000 operations/hr)
100,000 operations min. (at 1,800 operations/hr under rated load)
Endurance
AC: 15 ms max.; DC: 10 ms max.
(w/built-in diode: 20 ms max.)
18,000 operations/hr
1,800 operations/hr (under rated load)
Electrical:
Ambient temperature
Operating:
–40°C to 70°C (with no icing or condensation)
Ambient humidity
Operating:
5% to 85%
Weight
Approx. 20 g
Note: Values in the above table are the initial values.
* These values are relay only. Prease refer to the “Products Related to Common Sockets and DIN Tracks Data Sheet” for connecting sockets.
Approved Standards
IEC/VDE (Certificate No. 40015012 EN 61810-1)
UL 508 (File No. E41643)
Model
Contact
Coil ratings
form
Contact ratings
Operations
G2R-1-S (S) SPDT
10 A, 30 VDC (resistive)
100 × 103
10 A, 250 VAC (general use)
G2R-2-S (S) DPDT
25 × 103
5 to 110 VDC TV-3 (NO contact only)
6 to 240 VAC 5 A, 30 VDC (resistive)
100 × 103
5 A, 250 VAC (general use)
TV-3 (NO contact only)
25 × 103
CSA 22.2 No.0, No.14
(File No. LR31928)
Model
Contact
Coil ratings
form
Contact ratings
Operations
G2R-1-S (S) SPDT
10 A, 30 VDC (resistive)
100 × 103
10 A, 250 VAC (general use)
G2R-2-S (S) DPDT
25 × 103
5 to 110 VDC TV-3 (NO contact only)
6 to 240 VAC 5 A, 30 VDC (resistive)
100 × 103
5 A, 250 VAC (general use)
25 × 103
Coil ratings
Contact ratings
Operations
1 pole
6, 12, 24, 48 VDC
24, 110, 120, 230,
240 VAC
5 A, 440 VAC (cosφ = 1.0)
10 A, 250 VAC (cosφ = 1.0)
10 A, 30 VDC (0 ms)
100 × 103
2 poles
6, 12, 24, 48 VDC
24, 110, 120, 230,
240 VAC
5 A, 250 VAC (cosφ =1.0)
5 A, 30 VDC (0 ms)
100 × 103
LR
Number
of poles
TV-3 (NO contact only)
4
Contact
form
Coil ratings
Contact ratings
Operations
1 pole
5 to 110 VDC
6 to 240 VDC
10 A, 250 VAC (general use)
7.5 A, 250 VAC (PF0.4)
100 × 103
10 A, 30 VDC (resistive)
5A, 30VDC (L/R=7ms)
2 poles
5 to 110 VDC
6 to 240 VDC
5 A, 250 VAC (general use)
2 A, 250 VAC (PF0.4)
5 A, 30 VDC (resistive)
3A, 30VDC (L/R=7ms)
100 × 103
G2R-@-S (S)
Engineering Data
Maximum Switching Power
G2R-2-S (S)
G2R-1-S (S)
100
Switching current (A)
AC inductive load
(cosφ = 0.4)
AC resistive
load
10
DC resistive
load
DC inductive load
(L/R = 7 ms)
1
0.1
1
10
100
Switching current (A)
100
AC resistive
load
DC resistive
load
1
0.1
1000
AC inductive load
(cosφ = 0.4)
10
DC inductive load
(L/R = 7 ms)
1
Switching voltage (V)
10
100
1000
Switching voltage (V)
Endurance
G2R-2-S (S)
10,000
5,000
1,000
250-VAC/30-VDC
resistive load
500
100
250-VAC inductive load
(cosφ = 0.4)
30-VDC inductive load (L/R = 7ms)
50
Switching current (A)
Endurance (x103 operations)
Endurance (x103 operations)
G2R-1-S (S)
5,000
1,000
500
30-VDC inductive load (L/R = 7ms)
250-VAC/30-VDC
resistive load
100
250-VAC
50 inductive load
(cosφ = 0.4)
Switching current (A)
Maximum voltage (%)
Ambient Temperature vs Maximum Coil Voltage
DC coil
AC coil
Ambient temperature (°C)
5
G2R-@-S (S)
Dimensions
(Unit: mm)
Note: All units are in millimeters unless otherwise indicated.
SPDT Relays
G2R-1-S (S), G2R-1-SN (S), G2R-1-SNI (S)
G2R-1-SD (S), G2R-1-SND (S), G2R-1-SNDI (S)
Terminal Arrangement/Internal Connections
(Bottom View)
G2R-1-SD (S) (DC)
G2R-1-S (S)
29 max.
1
13 max.
1
2
20
35.5 max.
5
4
3
G2R-1-SN (S), G2R-1-SNI (S) (AC)
4.75
2
5
3
4
4
2
5
3
7.5
0.5
1
5
1
24V
3
4
G2R-1-SN (S), G2R-1-SNI (S) (DC)
1
DC
2
5
G2R-1-SND (S), G2R-1-SNDI (S) (DC)
5.2
5.2
17.5
1
2
5
3
4
DPDT Relays
G2R-2-S (S), G2R-2-SN (S), G2R-2-SNI (S)
G2R-2-SD (S), G2R-2-SND (S), G2R-2-SNDI (S)
Terminal Arrangement/Internal Connections
(Bottom View)
G2R-2-S (S)
1
2
3
4
8
7
6
5
13 max.
2.5
7.4
6
35.5 max.
3
4
8
7
6
5
2
3
4
1
2
3
4
8
7
6
5
8
7
6
5
5
19.4
2
1
G2R-2-SND (S), G2R-2-SNDI (S) (DC)
5
1
G2R-2-SN (S), G2R-2-SNI (S) (DC)
8.9
2.4
G2R-2-SN (S), G2R-2-SNI (S) (AC)
6.2
20
29 max.
0.5
G2R-2-SD (S) (DC)
1
2
3
4
8
7
6
5
G2R-@-S (S)
Track/Surface Mounting Sockets
P2RF-05-PU
57.5
Terminal Arrangement/
Internal Connection Diagram
(Top View)
53.1
A2
30.8
28.1
(4.2)
(1)
Mounting Hole
Dimensions
A1
(5)
25.6
Two M3 screw
holes or
two 3.5-dia. holes
108
90
Release lever
35.3
12
(2)
14
(3)
27.35
11
(4)
(4.2)
3.9
15.5
34.3
43
52.1
P2RF-08-PU
Note: Pull out the hooks to
mount the Socket
with screws.
Note: The numbers in
parentheses are
traditionally used
terminal numbers.
25.6
57.5
Terminal Arrangement/
Internal Connection Diagram
(Top View)
53.1
30.8
28.1
(4.2)
A2
(1)
Mounting Hole
Dimensions
A1
(8)
25.6
Two M3 screw
holes or
two 3.5-dia. holes
90
Release lever
35.3
108
12
27.35
(4.2)
3.9
15.5
25.6
34.3
22
(2)
(7)
14
24
(4)
(5)
11
21
(3)
(6)
Note: The numbers in
parentheses are
traditionally used
terminal numbers.
43
52.1
Note: Pull out the hooks to
mount the Socket
with screws.
Accessories for P2RF-@-PU
Short Bars
PYDN-7.75-@@ (7.75 mm)
Application
L
12
For Contact
terminals
(common)
18.5
2.25
1.57
PYDN-15.5-080@ (15.5 mm)
12
For Coil
terminals
7.75 mm
15.5 mm
No. of
poles
L (Length)
2
15.1
3
22.85
4
30.6
20
154.6
8
115.85
Colors
Model *
Maximum
carry current
PYDN-7.75-020@
PYDN-7.75-030@
Red (R)
Blue (S)
Yellow (Y)
PYDN-7.75-040@
20 A
PYDN-7.75-200@
PYDN-15.5-080@
* Replace the box (@) in the model number with the code for the covering color.
3.90
115.85
2.25
Pitch
3.90
18.5
Note: 1. Use the Short Bars for crossover wiring within one Socket or between Sockets.
2. When using short bar to coil terminals of PYF-@@-PU, make sure to use
PYDN-31.0-080@ (31 mm).
When using short bar to coil terminals of P2RF-@@-PU, make sure to use
PYDN-15.5-080@ (15.5 mm).
1.57
7
G2R-@-S (S)
P2RF-05-E
7±0.2
Five, M3.5´7
2
48 max.
Terminal Arrangement
(Top View)
4
(12)
39.5
3
35.5
85.5 max.
Mounting Holes
(for Surface Mounting)
3.2-dia.
hole
(11)
2
(14)
39.5±0.1
3.5-dia.
hole
M3 or
3.5-dia.
hole
5
(A1)
(A2)
4
1
11.5
61 max.
16.0 max.
Note: Pin numbers in parentheses apply to DIN standard.
P2RF-08-E
6 +0.2
−0.1
2
Terminal Arrangement
(Top View)
2
1.5
Eight, M3´8
48.0 max.
Mounting Holes
(for Surface Mounting)
3
39.5
(21)
(22)
(24)
6
3
7
5
2
4
(11)
(12)
(14)
3.2-dia.
hole
35.5
39.5±0.1
85.5
max.
3.5-dia. hole
8
(A1)
(A2)
4
61.0
max.
1
M3 or
3.5-dia.
hole
11.5
16.0 max.
P2RF-05
2
7
Terminal Arrangement
(Top View)
Five, M3.5 x 8
4-dia. holes
Mounting Holes
(for Surface Mounting)
4.2-dia. hole
35.5
71.5 max.
30±0.05
4
19.5
30 max.
19.5 max.
M3 or 3.2-dia.
hole
54 max.
P2RF-08
2
7
Eight, M3.5 x 8
4-dia. holes
Terminal Arrangement
(Top View)
Mounting Holes
(for Surface Mounting)
4.2-dia. hole
35.5
71.5 max.
30±0.05
4
19.5 max.
19.5
30 max.
54 max.
8
M3 or 3.2-dia.
hole
G2R-@-S (S)
Mounting Height of Relay with Track/Surface Mounting Sockets
P2RF-05-PU
P2RF-08-PU
G2R-@-S (S)
Relay
G2R-@-S (S)
Relay
P2RF-05ーPU
Socket
P2RF-08ーPU
Socket
63.6
63.6
28.1
28.1
(3.9)
(3.9)
P2RF-@
P2RF-@-E
G2R-@-S (S)
Relay
G2R-@-S (S)
Relay
P2RF-@-E
Socket
P2RF-@
Socket
67.0 70.5
66.5 62.0
Back-connecting Sockets
P2R-05P (1-pole)
4
1
Terminal Arrangement
(Bottom View)
14.5 max.
7
Mounting Holes
Tolerance: ±0.1
4
6
4.5
6
35.5 max.
15
Five,
1.6-dia.
holes
4.5
1.2
4
15
3.5
4
1.5
(5)
4
7
7
36.5 max.
P2R-08P (2-pole)
4
0.3
14.5 max.
7
Terminal Arrangement
(Bottom View)
Mounting Holes
7.5
Eight, 1.3-dia. holes
5
5
35.5 max.
20
1
5
5
20
2.8
1.5
(4.3)
7.5
Terminal plate thickness: 0.3
36.5 max.
9
G2R-@-S (S)
4.5
P2R-05A (1-pole)
7.5
14.5 max.
1.2
0.3
Terminal Arrangement
(Bottom View)
6.7
3.8
35.5 max.
5
16.7
Panel Cutout
Five, 3 x 1.8-dia. holes
13.6±0.1
6
36.5 max.
Terminal plate thickness: 0.3
30.5±0.2
6.5 7.5
P2R-08A (2-pole)
14.5 max.
1.2
0.3
5
5
35.5 max.
Recommended thickness of
the panel is 1.6 to 2.0 mm
20
2.6
2.8
1.5
Eight, 3 x 1.2-dia. holes
7.5
Terminal plate thickness: 0.3
P2R-057P (1-pole)
0.7
14 max.
8.7
36.5 max.
1
Terminal Arrangement
(Bottom View)
16.4
10.4 3.5
1
Mounting Holes
4±0.1
6
4.5
15
37 max.29.6
1
8.7
Five,
1.6-dia.
holes
6±0.1
4
8.75
4.5±0.1 15±0.1
4±0.1
5
7.4
7±0.1
41 max.
P2R-087P (2-pole)
14 max.
7.5
1
Terminal Arrangement
(Bottom View)
16.4
10.4 3.5
0.3
7.5
5
5
37 max. 29.1
20
1
Eight,
1.3-dia.
holes
5
5
8.1
8.9
Mounting Holes
20
7.4
(8.1)
41 max.
Mounting Height of Relay with Back-connecting Sockets
P2R-@P
P2R-@A
P2R-@7P
G2R-@-S (S) Relay
G2R-@-S (S) Relay
44.5
P2R-@P
Socket
10
38.0
47.5
P2R-@A
Socket
G2R-@-S (S) Relay
P2R-@7P
Socket
G2R-@-S (S)
Mounting Tracks
PFP-100N, PFP-50N
PFP-100N2
16
7.3±0.15
4.5
4.5
15
25
25
25
25
10
15 (5)
10
1,000 (500)
35±0.3 27
27±0.15
35±0.3
15
1
25
25 15
25
25
10
10
24
29.2
1
1.5
1,000
It is recommended to use a panel 1.6 to 2.0 mm thick.
End Plate
Spacer
10
6.2
PFP-M
PFP-S
16
12
5
1.8
1
50
1.8
11.5
10
M4 x 8 pan
head screw
35.5 35.3
34.8
44.3
1.3
4.8
16.5
Mounting Plate
P2R-P
90
R2.25
10-Ellipse hole
4.5
13.6
3.4
49 42±0.1
30.5
18±0.15 18±0.15 18±0.15 18±0.15
Square hole
9±0.1
72±0.2
9±0.1
t=1.6 mm
Safety Precautions
Be sure to read the Common Precautions for All Relay in the website at the following URL:
http://www.ia.omron.com/.
Refer to Products Related to Common Sockets and DIN Tracks for precautions on the applicable Sockets.
Refer to PYF-@@-PU/P2RF-@@-PU for precautions on Push-In Plus Terminal Block Sockets.
Warning Indications
CAUTION
Indicates a potentially hazardous
situation which, if not avoided, may result
in minor or moderate injury or in property
damage.
Cation
• Do not use the test button for any purpose other than testing. Be
sure not to touch the test button accidentally as this will turn the
contacts ON. Before using the test button, confirm that circuits, the
load, and any other connected item will operate safely.
• Check that the test button is released before turning ON relay circuits.
• If the test button is pulled out too forcefully, it may bypass the momentary testing position and go straight into the locked position.
• Use an insulated tool when you operate the test button.
11
OMRON Corporation
Industrial Automation Company
Authorized Distributor:
Kyoto, JAPAN
Contact: www.ia.omron.com
Regional Headquarters
OMRON EUROPE B.V.
Wegalaan 67-69, 2132 JD Hoofddorp
The Netherlands
Tel: (31)2356-81-300/Fax: (31)2356-81-388
OMRON ELECTRONICS LLC
2895 Greenspoint Parkway, Suite 200
Hoffman Estates, IL 60169 U.S.A.
Tel: (1) 847-843-7900/Fax: (1) 847-843-7787
OMRON ASIA PACIFIC PTE. LTD.
No. 438A Alexandra Road # 05-05/08 (Lobby 2),
Alexandra Technopark,
Singapore 119967
Tel: (65) 6835-3011/Fax: (65) 6835-2711
OMRON (CHINA) CO., LTD.
Room 2211, Bank of China Tower,
200 Yin Cheng Zhong Road,
PuDong New Area, Shanghai, 200120, China
Tel: (86) 21-5037-2222/Fax: (86) 21-5037-2200
© OMRON Corporation 2018 All Rights Reserved.
In the interest of product improvement,
specifications are subject to change without notice.
Cat. No. J226-E1-01
1118(1118)