Data sheet
6EP4135-0GB00-0AY0
SITOP UPS1100/BATTERY MODULE/24V/12AH
SITOP UPS1100 Battery module
with warning not closed Lead
batteries for SITOP DC-USV
Modules; DC 24 V 12 Ah
Charging current charging voltage
end-of-charge voltage at DC
● at -10 °C recommended
28 V
● at 0 °C recommended
28 V
● at 10 °C recommended
27.8 V
● at 20 °C recommended
27.3 V
● at 30 °C recommended
26.8 V
● at 40 °C recommended
26.6 V
● at 50 °C recommended
26.3 V
Output
Rated current value Iout rated
40 A
Permissible charging current, max.
3A
Rated voltage Vout DC
24 V
Safety
Short-circuit protection
Battery fuse 2x 25 A/32 V (solid-state circuitry blade-type fuse +
support)
design of the overload protection
Valve control
Status display
LED green: Battery OK; LED flashing green: Error or warning; OFF: No
communication
Safety
Protection class
Class III
Degree of protection (EN 60529)
IP20
Approvals
CE mark
Yes
UL/cUL (CSA) approval
cURus-Recognized (UL 1778, CSA C22.2 No. 107.1), File E219627
Explosion protection
IECEx Ex nA nC IIC T4 Gc; cCSAus (CSA C22.2 No. 213-M1987,
ANSI/ISA-12.12.01-2013) Class I, Div. 2, Group ABCD, T4
Approvals
Yes
Marine approval
DNV GL, ABS
environmental conditions
Operating data note
6EP41350GB000AY0
Page 1/2
For storage, mounting and operation of lead-acid batteries, the relevant
DIN/VDE regulations or country-specific regulations (e.g. VDE 0510 Part
2/EN 50272-2) must be observed. You must ensure that the battery site
is sufficiently ventilated. Possible sources of ignition must be at least 50
cm away.
12.18.2020
Subject to change without notice
© Copyright Siemens
ambient temperature
● during operation
-15 ... +50 °C
● during transport
-20 ... +50 °C
● during storage
-20 ... +50 °C
relative temporary capacity loss at 20 °C in a month
typical
3%
Service life
service life of energy storage
● typical note
capacity falls to 80 % of original capacity (according to EUROBAT)
● at 20 °C typical
4y
● at 30 °C typical
2y
● at 40 °C typical
1y
● at 50 °C typical
0.5 y
ambient temperature during storage note
Along with the storage and operating temperature, other factors such as
the duration of the storage period and the charge status during storage
have a decisive influence on the possible useful life. Batteries should
therefore be stored as briefly as possible, always fully charged, and
within the temperature range 0 to +20 °C.
Mechanics
Connection technology
screw-type terminals
Connection for power supply unit
1 screw terminal each for 0.5 ... 16 mm² for + BAT and - BAT
type of electrical connection for control circuit and status
message
1 screw terminal each for 0.14 ... 4 mm²
product component included
Accessories pack with solid-state circuitry fuse 25 A
width of the enclosure
253 mm
height of the enclosure
186 mm
depth of the enclosure
110 mm
installation width
253 mm
Installation height
201 mm
Weight, approx.
9.8 kg
Installation
can be screwed onto flat surface (keyhole mounting for hooking in to M4
screws)
number of cells
12
Battery
12 A·h
other information
Specifications at rated input voltage and ambient temperature +25 °C
(unless otherwise specified)
6EP41350GB000AY0
Page 2/2
12.18.2020
Subject to change without notice
© Copyright Siemens
很抱歉,暂时无法提供与“6EP41350GB000AY0”相匹配的价格&库存,您可以联系我们找货