Digital Fiber Sensor
FX-300 SERIES
Related Information
LASER
SENSORS
■■General terms and conditions.............. F-7
■■SC-GU1-485............................... P.1009~
■■General precautions.................... P.1458~
■■Sensor selection guide………………… P.3~
■■Glossary of terms........................ P.1455~
■■Korea’s S-mark.............................. P.1506
PHOTOELECTRIC
SENSORS
MICRO
PHOTOELECTRIC
SENSORS
Conforming to
EMC Directive
Recognition
AREA
SENSORS
Certified
LIGHT CURTAINS /
SAFETY
COMPONENTS
PRESSURE /
FLOW
SENSORS
INDUCTIVE
PROXIMITY
SENSORS
NPN output types of
connector type only
* Passed the UL 991 Environment Test
* UL 61010C-1 compatible, Passed the UL 991
Environment Test based on SEMI S2-0200.
[Category applicable for semiconductor
manufacturing: TWW2, Process Equipment]
[Applicable standards: UL 61010C-1]
[Additional test / evaluation standards as per intended
use: UL 991, SEMI S2-0200]
PARTICULAR
USE SENSORS
SENSOR
OPTIONS
SIMPLE
WIRE-SAVING
UNITS
PNP output
type available
WIRE-SAVING
SYSTEMS
panasonic.net/id/pidsx/global
MEASUREMENT
SENSORS
STATIC ELECTRICITY
PREVENTION
DEVICES
LASER
MARKERS
PLC
HUMAN MACHINE
INTERFACES
ENERGY CONSUMPTION
VISUALIZATION
COMPONENTS
FA COMPONENTS
MACHINE VISION
SYSTEMS
UV CURING
SYSTEMS
Selection
Guide
Timer
Interference Light intensity
monitor
prevention
Automatic
sensitivity setting
Constant advances achieving significant
improvement of sensing performance
Stable sensing over long and short periods
FX-301 FX-301-HS FX-305
In addition to a “four-chemical emitting element” which
suppresses changes in the light emitting element over
time so that a stable level of light emission
can
be
•
•
maintained
over
long
periods,
a
“APC
(Auto
Power
•
Control) circuit” has also been adopted afresh. The light
emitting amount can be controlled in minute degrees
so that even changes occurring over very short periods
can be handled, allowing stable sensing performance by
suppressing deviations in light emitting amounts caused
by changes in the ambient environment that could not
previously be suppressed.
Even greater sensing range
All models
Adoption of a “double coupling lens” that increases
emission efficiency to its maximum limits and greatly
increases sensing range. Sensing ranges with small
diameter fibers and ultra-small diameter fibers, which
have become very popular due to the miniaturization of
chip components, have been increased by 50 % over
previous values achieved with other amplifiers.
• Conventional fiber sensors (Without lens)
● Stable sensing comparison
Fiber
Amplifiers
FX-500
FX-100
FX-300
FX-410
FX-311
FX-301-F7/
FX-301-F
Light emitting amount
Fibers
Short-term stability
Disperses the light reduces
emitting efficiency.
Deviation
• Double coupling lens
Long-term stability
Time
FX-301
FX-301-HS
FX-305
Three-chemical emitting element,
Without APC
The lens concentrates the light, greatly
increasing emitting efficiency.
Digital Fiber Sensor
FX-300 SERIES
APPLICATIONS
140
FIBER
SENSORS
Detecting the presence or absence of labels
Detecting the presence or absence of ICs on a tray
The light-emitting amount selection
function can even stabilize detection
of transparent labels that saturate the
light-receiving level.
You can set upper and lower limits for
the threshold values using the window
comparator mode and turn ON / OFF
the incident light intensity
within that limit.
Detecting the passage of small objects
The differential sensing mode will only
detect rapid changes in the amount of
light, which makes it
possible for small
objects to be
detected.
LASER
SENSORS
PHOTOELECTRIC
SENSORS
MICRO
PHOTOELECTRIC
SENSORS
AREA
SENSORS
LIGHT CURTAINS /
SAFETY
COMPONENTS
PRESSURE /
FLOW
SENSORS
INDUCTIVE
PROXIMITY
SENSORS
FX-301 FX-301-HS FX-305
Light-emitting amount selection
If the light receiving level becomes saturated during close-range sensing or when sensing
transparent or minute objects, you can adjust the light emitting amount of the sensor to
stabilize sensing without needing to change the response time. Sensing that previously
required the response time or fibers to be changed can now be set much more easily using
this function.
[Light receiving level saturated]
A
4000
Actual digit difference: C
Upper display limit
B
Saturated digit
difference: D
Light emitting
amount
changed
,
A
,
B
SENSOR
OPTIONS
SIMPLE
WIRE-SAVING
UNITS
Level 4
Level 3
WIRE-SAVING
SYSTEMS
Level 2
MEASUREMENT
SENSORS
Level 1
STATIC ELECTRICITY
PREVENTION
DEVICES
[Stable sensing]
Actual digit difference: C’
PARTICULAR
USE SENSORS
LASER
MARKERS
OFF
Light emitting amount
can be changed
without changing
response time
PLC
HUMAN MACHINE
INTERFACES
ENERGY CONSUMPTION
VISUALIZATION
COMPONENTS
FA COMPONENTS
FX-305
Large display 9999
Large display with 4 digits (9999). With a greater
difference in digit value than previous models, threshold
values can be set in units of 1 digit up to maximum 9999.
Threshold setting can now be done more easily and
accurately.
(During STDF, LONG and U-LG modes)
2.5 times
previous
models
● Digit difference comparison
Example Digit difference between object A and object B
Previous models FX-305
4000
9999
Ultra high-speed
35 µs response
FX-301-HS FX-305
Ultra high-speed 35 µs response. Even small objects
moving at high speeds can be sensed. In addition, at 65
µs the FX-301 standard
4 times as fast
type and FX-305 highas before
function type is also
twice as fast as previous
models.
35 µs
Selection
Guide
Fiber
Amplifiers
Ultra high-speed type FX-301-HS
(H-SP mode)
35 μs
Standard type FX-301, High-function type FX-305
65 μs
Digit difference: Large
UV CURING
SYSTEMS
Fibers
(H-SP mode)
Digit difference: Small
MACHINE VISION
SYSTEMS
Previous model
150 μs
FX-500
FX-100
FX-300
FX-410
FX-311
FX-301-F7/
FX-301-F
FIBER
SENSORS
LASER
SENSORS
PHOTOELECTRIC
SENSORS
MICRO
PHOTOELECTRIC
SENSORS
AREA
SENSORS
Digital Fiber Sensor
FX-300 SERIES
A window comparator mode and
differential sensing mode have
been added. These modes make
it easy to carry out sensing tasks
that previously required multiple
sensors or involved complex
threshold settings.
● Window comparator mode
● Differential sensing mode
LIGHT CURTAINS /
SAFETY
COMPONENTS
PRESSURE /
FLOW
SENSORS
INDUCTIVE
PROXIMITY
SENSORS
PARTICULAR
USE SENSORS
Tray absent
IC present
Tray present
OFF
ON
OFF
SENSOR
OPTIONS
WIRE-SAVING
SYSTEMS
MEASUREMENT
SENSORS
LASER
MARKERS
PLC
HUMAN MACHINE
INTERFACES
ENERGY CONSUMPTION
VISUALIZATION
COMPONENTS
Incident
light
intensity
Upper and lower limits for threshold
values can be set so that the incident light
intensity can turn on and off within those
ranges. Single output is used, so that
only one cable is required, and no PLC
processing is required either.
SIMPLE
WIRE-SAVING
UNITS
STATIC ELECTRICITY
PREVENTION
DEVICES
FX-305
Simplified systems using new operating modes
Lower light amounts due to dust
Incident light intensity
141
Because sensing is not possible at normal
sensitivity settings, sensitivity must be reset.
ON
ON
Sensing of only sudden changes in light amounts
Only the target objects are sensed.
No need to reset the sensitivity.
FX-305
Equipped with 5 types timers
The FX-305 includes the same ON-delay / OFF-delay / ONE SHOT timer
as the FX-301(-HS), as well as an ON-delay • OFF-delay timer and an
ON-delay • ONE SHOT timer. A wide variety of timer control operations
can be carried out by these fiber sensors alone.
Timer period
Output 1: 0.5 to 9,999 ms (variable)
Output 2: 0.5 to 500 ms (variable)
Time chart
ONE SHOT
UV CURING
SYSTEMS
ON-delay •
OFF-delay
ON-delay •
ONE SHOT
Fiber
Amplifiers
FX-500
FX-100
FX-300
FX-410
FX-311
FX-301-F7/
FX-301-F
RUN
TEACH
ADJ
RUN→
RUN
TEACH
ADJ
TEACH→
RUN
TEACH
ADJ
ADJ→
OFF
T1
T1
ON
OFF
T1
ON
T1
OFF
T1
T1
T2
T2
ON
OFF
ON
OFF
All models
Even beginners can quickly learn how to use the MODE NAVI
MODE NAVI uses six
indicators to display the
amplifier’s basic operations.
The current operating mode
can be confirmed at a glance,
so even a first time user can
easily operate the amplifier
without becoming confused.
ON
T1
OFF-delay
MACHINE VISION
SYSTEMS
Fibers
Beamreceived
Beaminterrupted
Sensing
condition
ON-delay
FA COMPONENTS
Selection
Guide
For L-ON
L / D L / D ON→
TIMER This mode allows the selection
of output operation as either
PRO Light-ON or Dark-ON.
This is the sensing mode.
Incident light level is displayed
in the digital display.
L / D TIMER→
TIMER This mode permits the
choice of using or not
PRO using the timer.
This mode is for setting
the threshold value.
L / D PRO→
TIMER This mode allows the selection of further
advanced functions, such as the copying of
PRO individual settings and the memory functions.
In this mode, the threshold
value, once set, may be
fine-tuned.
FX-301 FX-301-HS FX-305
Easy confirming of threshold value settings
The threshold value can be confirmed by turning the jog
switch even during RUN mode.
Jog switch is turned
Left: FX-301(-HS)
Right: Output 2 for
Output 1 for FX-305
FX-305
The threshold value is displayed
Digital Fiber Sensor
FX-300 SERIES
All models
The use of only two switches makes for very simple operations
Only two switches, the large
jog switch and the large MODE
key, are required for operation.
You can operate it simply by
the 3 steps shown on the right.
● Large MODE key
● Large jog switch
1
142
FIBER
SENSORS
LASER
SENSORS
2
3
PHOTOELECTRIC
SENSORS
MICRO
PHOTOELECTRIC
SENSORS
AREA
SENSORS
Pressing the switch selects
or cancels the operating
mode
Moving the switch
from side to side
allows items to be
selected
Pressing the
switch then
confirms the
selected setting
A quick-connection cable saves wiring and
Connector type
work-hours
An optical communication function allows up to *16 sensors
FX-301 FX-305
to be adjusted simultaneously
One unit can be used as either a main unit or sub unit
The optical communication function allows the data that is
currently set to be copied and saved all at once for all amplifiers
connected together from the right side. This greatly reduces
troublesome setup tasks and makes setup much smoother. In
addition, troublesome adjustment operations at times such as
when replacing
sensors can also be
carried out easily
and data can also be
Single copy & save operation for all amplifiers
copied and stored
using the optical
communication
function.
The amplifier unit can be used as either a main unit
or a sub unit. This feature allows for easy mounting in
the side-by-side configuration. The main and sub unit
functions are distinguished only by the proper use of the
main cable and the sub cable.
Moreover, inventory management and maintenance is
simplified.
Identical part numbers eliminate
the need for costly inventory
management labor
* Use the optical communication function for only the same types of sensors. Furthermore,
the FX-301-HS is not equipped with optical communication function capability.
Settings can be entered directly using numerical input All models
Sub cable
FX-305
FX-301(-HS)
FX-301B/G/H
Main cable (4-core)
CN-74-C□
Every function can be directly set merely by the input
of a four digit code (numbers) from the code table. This
convenient feature is easy to set up. In the event that
settings are accidentally changed at the operating site,
merely entering the correct code can restore the original
settings. This results in easy and quick maintenance.
First digit: Settings for response time and hysteresis
Sub cable (2-core)
CN-72-C□
Second digit: Settings for L/D ON and display mode
LIGHT CURTAINS /
SAFETY
COMPONENTS
PRESSURE /
FLOW
SENSORS
INDUCTIVE
PROXIMITY
SENSORS
PARTICULAR
USE SENSORS
SENSOR
OPTIONS
SIMPLE
WIRE-SAVING
UNITS
WIRE-SAVING
SYSTEMS
MEASUREMENT
SENSORS
STATIC ELECTRICITY
PREVENTION
DEVICES
LASER
MARKERS
PLC
HUMAN MACHINE
INTERFACES
ENERGY CONSUMPTION
VISUALIZATION
COMPONENTS
FA COMPONENTS
MACHINE VISION
SYSTEMS
UV CURING
SYSTEMS
Main cable (3-core)
Main cable
CN-73-C□
Sub cable (1-core)
CN-71-C□
Fourth digit: Timer period settings
Third digit: Settings for Adjust lock and timer
Communication unit improves equipment starting up and maintenance
External input unit for digital sensor
FX-CH2
Teaching and changing settings can be performed
by using the PLC and touch panel.
FX-301 FX-305
Upper communication unit for digital sensor SC-GU1-485
We now offer remote maintenance for digital sensors!
Various settings and switching of up to 16 units of
digital fiber sensors can be accomplished at once
without operating the actual sensors themselves, but
via external signals, such as the PLC, touch panel, and
push buttons.
The communication unit enables inputs to the digital fiber
sensors (such as teaching and data bank switching) to
be carried out via a PLC or a personal computer, and
also allows confirming of the incident light intensity an
output status for the fiber sensors. This greatly improves
workability during equipment starting up and maintenance.
• Batch teaching
• Key lock setting
• Batch loading / saving of
the data bank
• Sensor incident light intensity
• Sensor settings verification
• Sensor output status
• Threshold value settings, etc.
FX-301(P)
FX-305(P)
PLC
Refer to our website for details
Compatible with all PLCs equipped
with RS-485 compatible units
SC-GU1-485
RS-485
communication
Refer to SC-GU1-485 pages for details
Selection
Guide
Fibers
Fiber
Amplifiers
FX-500
FX-100
FX-300
FX-410
FX-311
FX-301-F7/
FX-301-F
143
Amplifiers Quick-connection cable is not supplied with the amplifier. Please order it separately.
Type
MICRO
PHOTOELECTRIC
SENSORS
Appearance
Model No.
FX-301
AREA
SENSORS
FX-301B
SENSOR
OPTIONS
SIMPLE
WIRE-SAVING
UNITS
WIRE-SAVING
SYSTEMS
High-speed
type
LASER
MARKERS
Model No.
Length
CN-73-C1
1 m 3.281 ft
CN-73-C2
2 m 6.562 ft
CN-73-C5
5 m 16.404 ft
CN-71-C1
1 m 3.281 ft
CN-71-C2
2 m 6.562 ft
CN-71-C5
5 m 16.404 ft
CN-74-C1
1 m 3.281 ft
CN-74-C2
2 m 6.562 ft
CN-74-C5
5 m 16.404 ft
CN-72-C1
1 m 3.281 ft
CN-72-C2
2 m 6.562 ft
CN-72-C5
5 m 16.404 ft
NPN open-collector transistor
PNP open-collector transistor
NPN open-collector transistor
Blue LED
FX-301BP
PNP open-collector transistor
FX-301G
NPN open-collector transistor
Green LED
FX-301GP
PNP open-collector transistor
FX-301H
NPN open-collector transistor
Infrared LED
MEASUREMENT
SENSORS
STATIC
ELECTRICITY
PREVENTION
DEVICES
Quick-connection cables
Type
Main cable (3-core)
PRESSURE /
FLOW
SENSORS
Standard type
FX-301P
PARTICULAR
USE
SENSORS
Output
Red LED
LIGHT
CURTAINS /
SAFETY
COMPONENTS
INDUCTIVE
PROXIMITY
SENSORS
Emitting element
FX-301HP
PNP open-collector transistor
FX-301-HS
NPN open-collector transistor
Sub cable (1-core)
PHOTOELECTRIC
SENSORS
ORDER GUIDE
Main cable (4-core)
LASER
SENSORS
FX-300 SERIES
Sub cable (2-core)
FIBER
SENSORS
Digital Fiber Sensor
Red LED
FX-301P-HS
PNP open-collector transistor
PLC
HUMAN
MACHINE
INTERFACES
FA
COMPONENTS
MACHINE
VISION
SYSTEMS
UV
CURING
SYSTEMS
Selection
Guide
Fibers
Fiber
Amplifiers
FX-500
FX-100
FX-300
FX-410
FX-311
FX-301-F7/
FX-301-F
FX-305
High-function type
ENERGY
CONSUMPTION
VISUALIZATION
COMPONENTS
NPN open-collector transistor
Red LED
FX-305P
PNP open-collector transistor
Digital Fiber Sensor
FX-300 SERIES
ORDER GUIDE
144
FIBER
SENSORS
Quick-connection cables
LASER
SENSORS
For FX-301(-HS)/B/G/H Quick-connection cable is not supplied with the amplifier. Please order it separately.
Main cable
PHOTOELECTRIC
SENSORS
Type
Main cable
(3-core)
Sub cable
(1-core)
Model No.
CN-73-C1
Description
Length: 1 m 3.281 ft
CN-73-C5
0.2 mm2 3-core cabtyre cable, with connector
Length: 2 m 6.562 ft on one end
Cable outer diameter: ø3.3 mm ø0.130 in
Length: 5 m 16.404 ft
CN-71-C1
Length: 1 m 3.281 ft
CN-73-C2
CN-71-C2
CN-71-C5
MICRO
PHOTOELECTRIC
SENSORS
• CN-73-C□
0.2 mm2 1-core cabtyre cable, with connector
Length: 2 m 6.562 ft on one end
Cable outer diameter: ø3.3 mm ø0.130 in
Length: 5 m 16.404 ft
AREA
SENSORS
LIGHT
CURTAINS /
SAFETY
COMPONENTS
PRESSURE /
FLOW
SENSORS
Sub cable
INDUCTIVE
PROXIMITY
SENSORS
• CN-71-C□
PARTICULAR
USE
SENSORS
SENSOR
OPTIONS
SIMPLE
WIRE-SAVING
UNITS
For FX-305 Quick-connection cable is not supplied with the amplifier. Please order it separately.
Type
Main cable
(4-core)
Sub cable
(2-core)
Model No.
CN-74-C1
Description
CN-74-C5
CN-72-C1
Length: 1 m 3.281 ft
CN-72-C2
CN-72-C5
WIRE-SAVING
SYSTEMS
• CN-74-C□
MEASUREMENT
SENSORS
Length: 1 m 3.281 ft
0.2 mm2 4-core cabtyre cable, with connector
Length: 2 m 6.562 ft on one end
Cable outer diameter: ø3.3 mm ø0.130 in
Length: 5 m 16.404 ft
CN-74-C2
Main cable
0.2 mm2 2-core cabtyre cable, with connector
Length: 2 m 6.562 ft on one end
Cable outer diameter: ø3.3 mm ø0.130 in
Length: 5 m 16.404 ft
STATIC
ELECTRICITY
PREVENTION
DEVICES
LASER
MARKERS
Sub cable
PLC
• CN-72-C□
HUMAN
MACHINE
INTERFACES
ENERGY
CONSUMPTION
VISUALIZATION
COMPONENTS
End plates End plates are not supplied with the amplifier. Please order them separately when the amplifiers are mounted in cascade.
Appearance
Model No.
MS-DIN-E
Description
FA
COMPONENTS
MACHINE
VISION
SYSTEMS
UV
CURING
SYSTEMS
When cascading multiple amplifiers, or when it
moves depending on the way it is installed on a
DIN rail, these end plates clamp amplifiers into
place on both sides. Make sure to use end plates
when cascading multiple amplifiers together.
Two pcs. per set
Selection
Guide
Fibers
OPTIONS
Fiber
Amplifiers
Amplifier mounting bracket
Designation
Model No.
Amplifier
mounting bracket
MS-DIN-2
Mounting bracket for amplifier
FX-MB1
10 sets of 2 communication window seals and 1 connector seal
Communication window seal:
It prevents malfunction due to transmission signal from another
amplifier, as well as, prevents effect on another amplifier.
Connector seal:
It prevents contact of any metal, etc., with the pins of the quickconnection cable.
Fiber amplifier
protection seal
Description
Note: Fiber amplifier protection seals are supplied with the FX-301(P) and FX-305(P).
• MS-DIN-2
FX-500
FX-100
FX-300
FX-410
FX-311
FX-301-F7/
FX-301-F
Fiber amplifier protection seal
• FX-MB1
Communication
window seal
Connector seal
145
FIBER
SENSORS
Digital Fiber Sensor
FX-300 SERIES
LIST OF FIBERS
LASER
SENSORS
FX-301 / FX-305 (Red LED type) sensing range (Note 1)
PHOTOELECTRIC
SENSORS
Thru-beam type (one pair set)
MICRO
PHOTOELECTRIC
SENSORS
AREA
SENSORS
LIGHT
CURTAINS /
SAFETY
COMPONENTS
PRESSURE /
FLOW
SENSORS
INDUCTIVE
PROXIMITY
SENSORS
PARTICULAR
USE
SENSORS
The FX-305 and FX-301(-HS) have different sensing modes.
FX-305: H-SP, FAST, STD, STDF, LONG, U-LG (no S-D mode)
FX-301(-HS): S-D, H-SP (Note 1), FAST, STD, LONG (no STDF or U-LG mode)
Fibers are listed in alphabetic order. Refer to p.5~ “Fiber Selection” for details of each fiber.
Sensing range (mm in) (Note 2)
Model No.
Red LED
U-LG
FT-140
LONG
STDF
STD
Dimensions
FAST
19,600 771.654 (Note 3) 19,600 771.654 (Note 3) 19,600 771.654 (Note 3) 16,000 629.921 16,000 629.921
H-SP
8,700 342.520
S-D
8,700 342.520
P.51
FT-30
450 17.717
310 12.205
210
8.268
150
5.906
110
4.331
60
2.362
60
2.362
P.51
FT-31
440 17.323
290 11.417
200
7.874
142
5.591
105
4.134
58
2.283
49
1.929
P.51
FT-31S
440 17.323
290 11.417
200
7.874
140
5.512
100
3.937
55
2.165
49
1.929
P.51
FT-31W
300 11.811
230
130
5.118
100
3.937
65
2.559
30
1.181
30
1.181
P.51
9.055
FT-40
1,300 51.181
900 35.433
600 23.622
450 17.717
330 12.992
180
7.087
180
7.087
P.51
FT-42
1,100 43.307
800 31.496
550 21.654
400 15.748
285 11.220
160
6.299
150
5.906
P.51
FT-42S
1,100 43.307
800 31.496
550 21.654
400 15.748
285 11.220
160
6.299
150
5.906
P.51
FT-42W
1,000 39.370
710 27.953
460 18.110
330 12.992
240
9.449
130
5.118
130
5.118
P.51
1,900 74.803
1,400 55.118
800 31.496
610 24.016
440 17.323
240
9.449
250
9.843
P.51
FT-45X
1,600 62.992 (Note 3)
1,100 43.307
780 30.709
570 22.441
410 16.142
230
9.055
230
9.055
P.52
STATIC
ELECTRICITY
PREVENTION
DEVICES
FT-A11
3,600 141.732 (Note 3) 3,600 141.732 (Note 3) 3,600 141.732 (Note 3)
2,700 106.299
1,800 70.866
1,100 43.307
1,000 39.370
P.52
FT-A11W
3,600 141.732 (Note 3) 3,600 141.732 (Note 3) 3,600 141.732 (Note 3)
3,100 122.047
2,300 90.551
1,200 47.244
1,200 47.244
P.52
LASER
MARKERS
FT-A32
3,600 141.732 (Note 3) 3,600 141.732 (Note 3) 3,600 141.732 (Note 3) 3,600 141.732 (Note 3) 3,600 141.732 (Note 3)
2,900 114.173
2,900 114.173
P.52
FT-A32W
3,600 141.732 (Note 3) 3,600 141.732 (Note 3) 3,600 141.732 (Note 3) 3,600 141.732 (Note 3) 3,600 141.732 (Note 3)
2,000 78.740
2,100 82.677
P.52
SENSOR
OPTIONS
SIMPLE
WIRE-SAVING
UNITS
WIRE-SAVING
SYSTEMS
MEASUREMENT
SENSORS
PLC
HUMAN
MACHINE
INTERFACES
FT-43
FT-AL05
760 29.921
680 26.772
340 13.386
330 12.992
230
9.055
130
5.118
130
5.118
P.52
FT-E13
20
0.787
13
0.512
9
0.354
6
0.236
5
0.197
2
0.079
2
0.079
P.52
ENERGY
CONSUMPTION
VISUALIZATION
COMPONENTS
FT-E23
95
3.740
65
2.559
42
1.654
31
1.220
22
0.866
12
0.472
12
0.472
P.52
1,200 47.244
880 34.646
550 21.654
440 17.323
300 11.811
150
5.906
155
6.102
P.52
FA
COMPONENTS
FT-H20-J20-S (Note 4)
530 20.866
390 15.354
225
8.858
200
7.874
140
5.512
60
2.362
60
2.362
P.53
FT-H20-J30-S (Note 4)
530 20.866
390 15.354
225
8.858
200
7.874
140
5.512
60
2.362
60
2.362
P.53
FT-H20-J50-S (Note 4)
530 20.866
390 15.354
225
8.858
200
7.874
140
5.512
60
2.362
60
2.362
P.53
FT-H20-M1
750 29.528
550 21.654
320 12.598
280 11.024
200
7.874
85
3.346
90
3.543
P.53
FT-H20-VJ50-S (Note 4)
840 33.071
550 21.654
370 14.567
280 11.024
200
7.874
90
3.543
90
3.543
P.53
FT-H20-VJ80-S (Note 4)
840 33.071
550 21.654
370 14.567
280 11.024
200
7.874
90
3.543
90
3.543
P.53
FT-H20W-M1
420 16.535
310 12.205
180
7.087
140
5.512
100
3.937
40
1.575
50
1.969
P.53
FT-H30-M1V-S (Note 5)
350
250
150
5.906
125
4.921
90
3.543
50
1.969
40
1.575
P.53
FT-H35-M2
750 29.528
550 21.654
330 12.992
280 11.024
200
7.874
85
3.346
90
3.543
P.53
FT-H35-M2S6
750 29.528
550 21.654
330 12.992
280 11.024
200
7.874
85
3.346
90
3.543
P.53
FT-HL80Y
3,500 137.795 (Note 3) 3,500 137.795 (Note 3)
1,800 70.866
1,350 53.150
900 35.433
450 17.717
480 18.898
P.53
FT-KS40
3,600 141.732 (Note 3) 3,600 141.732 (Note 3) 3,600 141.732 (Note 3)
2,700 106.299
1,900 74.803
1,000 39.370
850 33.465
P.54
120
MACHINE
VISION
SYSTEMS
UV
CURING
SYSTEMS
Selection
Guide
Fibers
Fiber
Amplifiers
FX-500
FX-100
FX-300
FX-410
FX-311
FX-301-F7/
FX-301-F
FT-H13-FM2
FT-KV26
13.78
9.843
710 27.953
340 13.386
310 12.205
4.724
P.54
FT-KV40
3,600 141.732 (Note 3) 3,600 141.732 (Note 3)
3,200 125.984
2,500 98.425
1,800 70.866
1,000 39.370
1,000 39.370
P.54
FT-KV40W
3,600 141.732 (Note 3) 3,600 141.732 (Note 3)
3,200 125.984
2,000 78.740
1,400 55.118
790 31.102
810 31.890
P.54
2,000 78.740
1,500 59.055
1,000 39.370
500 19.685
530 20.866
P.54
FT-L80Y
800 31.496
3,500 137.795
3,500 137.795
20
0.787
120
4.724
Notes: 1) Please contact our office about the sensing ranges for FX-301-HS in H-SP mode.
2) Note that the sensing range of the free-cut type fiber may be reduced by 20 % max. depending upon how the fiber is cut.
3) The fiber cable length practically limits the sensing range.
4) Heat-resistant joint fibers and ordinary-temperature fibers (FT-42) are sold as a set.
5) Sold as a set comprising vacuum type fiber + photo-terminal (FV-BR1) + fiber at atmospheric side (FT-J8).
Digital Fiber Sensor
FX-300 SERIES
LIST OF FIBERS
FIBER
SENSORS
FX-301 / FX-305 (Red LED type) sensing range (Note 1)
The FX-305 and FX-301(-HS) have different sensing modes.
FX-305: H-SP, FAST, STD, STDF, LONG, U-LG (no S-D mode)
FX-301(-HS): S-D, H-SP (Note 1), FAST, STD, LONG (no STDF or U-LG mode)
Thru-beam type (one pair set)
Fibers are listed in alphabetic order. Refer to p.5~ “Fiber Selection” for details of each fiber.
Model No.
Red LED
U-LG
LONG
STDF
STD
FAST
H-SP
AREA
SENSORS
LIGHT
CURTAINS /
SAFETY
COMPONENTS
S-D
340 13.386
290 11.417
150
5.118
95
3.740
49
1.929
49
1.929
P.54
FT-R40
1,000 39.370
710 27.953
470 18.504
330 12.992
240
9.449
130
5.118
130
5.118
P.54
FT-R41W
1,000 39.370
710 27.953
460 18.110
330 12.992
240
9.449
130
5.118
130
5.118
P.54
FT-R42W
2,800 110.236
1,600 62.992
890 35.039
770 30.315
560 22.047
310 12.205
320 12.598
P.54
FT-R43
1,000 39.370
710 27.953
450 17.717
290 11.417
210
8.268
110
4.331
110
4.331
P.54
FT-R44Y
1,000 39.370
710 27.958
450 17.717
290 11.417
210
8.268
110
4.330
110
4.330
P.55
FT-R60Y
2,650 104.330
1,800 70.866
1,200 47.244
830 32.677
610 24.016
350 13.780
P.55
100
FT-S20
130
335 13.189
3.150
50
1.969
31
1.220
22
0.866
13
0.512
14
0.551
P.55
450 17.717
310 12.205
210
8.268
150
5.906
110
4.331
60
2.362
60
2.362
P.55
FT-S21
440 17.323
290 11.417
200
7.874
142
5.591
105
4.134
58
2.283
49
1.929
P.55
FT-S21W
300 11.811
230
130
5.118
100
3.937
65
2.559
30
1.181
30
1.181
P.55
3.937
80
9.055
PHOTOELECTRIC
SENSORS
Dimensions
FT-R31
5.906
LASER
SENSORS
MICRO
PHOTOELECTRIC
SENSORS
Sensing range (mm in) (Note 2)
FT-S11
146
PRESSURE /
FLOW
SENSORS
INDUCTIVE
PROXIMITY
SENSORS
PARTICULAR
USE
SENSORS
SENSOR
OPTIONS
SIMPLE
WIRE-SAVING
UNITS
WIRE-SAVING
SYSTEMS
MEASUREMENT
SENSORS
FT-S30
1,300 51.181
900 35.433
600 23.622
450 17.717
330 12.992
180
7.087
180
7.087
P.55
FT-S31W
1,000 39.370
710 27.953
460 18.110
330 12.992
240
130
5.118
130
5.118
P.55
STATIC
ELECTRICITY
PREVENTION
DEVICES
FT-S32
3,600 141.732
2,400 94.488
1,500 59.055
1,100 43.307
510 20.079
P.55
LASER
MARKERS
FT-V23
590 23.228
380 14.961
270 10.630
FT-V24W
120
4.724
90
3.543
55
FT-V25
310 12.205
200
7.874
130
FT-V30
620 24.409
FT-V40
FT-V80Y
9.449
840 33.071
460 18.110
170
6.693
125
4.921
60
2.362
63
2.480
P.55
2.165
40
1.575
30
1.181
13
0.512
15
0.591
P.56
5.118
90
3.543
60
2.362
35
1.378
35
1.378
P.56
420 16.535
270 10.630
200
7.874
140
5.512
70
2.756
70
2.756
P.56
3,600 141.732 (Note 3) 3,600 141.732 (Note 3)
1,600 62.992
1,700 66.929
1,200 47.244
680 26.772
690 27.165
P.56
ENERGY
CONSUMPTION
VISUALIZATION
COMPONENTS
280 11.024
120
4.724
140
5.512
P.56
FA
COMPONENTS
MACHINE
VISION
SYSTEMS
1,000 39.370
800 31.496
500 19.685
400 15.748
FT-Z20HBW
400 15.748
290 11.417
160
6.299
130
5.118
90
3.543
50
1.969
50
1.969
P.56
FT-Z20W
830 32.677
570 22.441
370 14.567
250
9.843
180
7.087
90
3.543
90
3.543
P.56
2,600 102.362
1,900 74.803
1,100 43.307
850 33.465
620 24.409
330 12.992
340 13.386
P.56
FT-Z30E
3,600 141.732 (Note 3)
3,100 122.047
2,100 82.677
1,600 62.992
1,100 43.307
650 25.591
670 26.378
P.56
FT-Z30EW
3,600 141.732 (Note 3)
2,700 106.299
1,400 55.118
1,200 47.244
900 35.433
500 19.685
500 19.685
P.57
FT-Z30H
3,600 141.732 (Note 3)
3,100 122.047
2,200 86.614
1,600 62.992
1,100 43.307
650 25.591
670 26.378
P.57
FT-Z30HW
FT-Z30
3,600 141.732 (Note 3)
3,100 122.047
2,200 86.614
1,500 59.055
1,000 39.370
590 23.228
610 24.016
P.57
FT-Z30W
2,000 78.740
1,400 55.118
890 35.039
640 25.197
460 18.110
250
9.843
260 10.236
P.57
FT-Z40HBW
1,000 39.370
710 27.953
460 18.110
330 12.992
240
9.449
130
5.118
130
5.118
P.57
FT-Z40W
1,900 74.803
1,300 51.181
900 35.433
630 24.803
460 18.110
240
9.449
260 10.236
P.57
FT-Z802Y
3,500 137.795
3,500 137.795
3,000 118.110
1,500 59.055
1,000 39.370
500 19.685
530 20.866
P.57
Notes: 1) Please contact our office about the sensing ranges for FX-301-HS in H-SP mode.
2) Note that the sensing range of the free-cut type fiber may be reduced by 20 % max. depending upon how the fiber is cut.
3) The fiber cable length practically limits the sensing range.
PLC
HUMAN
MACHINE
INTERFACES
UV
CURING
SYSTEMS
Selection
Guide
Fibers
Fiber
Amplifiers
FX-500
FX-100
FX-300
FX-410
FX-311
FX-301-F7/
FX-301-F
147
FIBER
SENSORS
Digital Fiber Sensor
FX-300 SERIES
LIST OF FIBERS
LASER
SENSORS
FX-301 / FX-305 (Red LED type) sensing range (Note 1)
PHOTOELECTRIC
SENSORS
Retroreflective type
MICRO
PHOTOELECTRIC
SENSORS
AREA
SENSORS
LIGHT
CURTAINS /
SAFETY
COMPONENTS
PRESSURE /
FLOW
SENSORS
INDUCTIVE
PROXIMITY
SENSORS
PARTICULAR
USE
SENSORS
SENSOR
OPTIONS
SIMPLE
WIRE-SAVING
UNITS
The FX-305 and FX-301(-HS) have different sensing modes.
FX-305: H-SP, FAST, STD, STDF, LONG, U-LG (no S-D mode)
FX-301(-HS): S-D, H-SP (Note 1), FAST, STD, LONG (no STDF or U-LG mode)
Fibers are listed in alphabetic order. Refer to p.5~ “Fiber Selection” for details of each fiber.
Sensing range (mm in) (Note 2, 3)
Red LED
STDF
STD
FAST
Model No.
U-LG
LONG
Dimensions
H-SP
S-D
FR-KZ22E
15 to 370 0.591 to 14.567 15 to 330 0.591 to 12.992 15 to 240 0.591 to 9.449 15 to 210 0.591 to 8.268 15 to 170 0.590 to 6.693 15 to 80 0.591 to 3.150 15 to 90 0.591 to 3.543
P.58
FR-KZ50E
20 to 350 0.787 to 13.780 20 to 300 0.787 to 11.811 20 to 250 0.787 to 9.843 20 to 200 0.787 to 7.874 20 to 200 0.787 to 7.874 20 to 200 0.787 to 7.874 20 to 200 0.787 to 7.874
P.58
FR-KZ50H
20 to 350 0.787 to 13.780 20 to 300 0.787 to 11.811 20 to 250 0.787 to 9.843 20 to 200 0.787 to 7.874 20 to 200 0.787 to 7.874 20 to 200 0.787 to 7.874 20 to 200 0.787 to 7.874
P.58
FR-Z50HW
100 to 920 3.937 to 36.220 100 to 810 3.937 to 31.890 100 to 660 3.937 to 25.984 100 to 580 3.937 to 22.835 100 to 490 3.937 to 19.291 100 to 340 3.937 to 13.385 100 to 270 3.937 to 10.630
P.58
Notes: 1) Please contact our office about the sensing ranges for FX-301-HS in H-SP mode.
2) Note that the sensing range of the free-cut type fiber may be reduced by 20 % max. depending upon how the fiber is cut.
The sensing range of FR-KZ22E is specified for the attached reflector. The sensing range of FR-KZ50E and FR-KZ50H is specified for the attached
reflector RF-003. The sensing range of FR-Z50HW is specified for the RF-13.
3) The sensing range is the possible setting range for the attached reflector. The fiber can detect an object less than setting range for the reflector. However,
note that if there are any white or highly-reflective surfaces near the fiber head, reflected incident light may affect the fiber head. If this occurs, adjust the
threshold value of the amplifier unit before use.
WIRE-SAVING
SYSTEMS
MEASUREMENT
SENSORS
STATIC
ELECTRICITY
PREVENTION
DEVICES
LASER
MARKERS
PLC
HUMAN
MACHINE
INTERFACES
ENERGY
CONSUMPTION
VISUALIZATION
COMPONENTS
Sensing range when using in combination with FR-Z50HW reflector (Optional)
The sensing ranges are the value for red LED types.
Sensing range (mm in)
Reflector
Model No.
FX-301 / 305
U-LG
LONG
STDF
STD
FX-301-HS
FAST
S-D
H-SP
H-SP
RF-230
100 to 7,500 3.937 to 295.276 100 to 3,200 3.937 to 125.984 100 to 2,900 3.937 to 114.173 100 to 2,000 3.937 to 78.740 100 to 1,600 3.937 to 62.992 100 to 1,000 3.937 to 39.370 100 to 900 3.937 to 35.433 100 to 700 3.937 to 27.559
RF-220
100 to 2,400 3.937 to 94.488 100 to 2,400 3.937 to 94.488 100 to 1,900 3.937 to 74.803 100 to 1,300 3.937 to 51.181 100 to 1,000 3.937 to 39.370 100 to 600 3.937 to 23.622 100 to 570 3.937 to 22.441 100 to 350 3.937 to 13.780
RF-210
100 to 2,100 3.937 to 82.677 100 to 1,700 3.937 to 66.929 100 to 1,300 3.937 to 51.181 100 to 910 3.937 to 35.827 100 to 710 3.937 to 27.953 100 to 460 3.937 to 18.110 100 to 440 3.937 to 17.323
–
Note: The sensing range is the possible setting range for the reflector. The fiber can detect an object less than setting range for the reflector. However, note that if
there are any white or highly-reflective surfaces near the fiber head, reflected incident light may affect the fiber head. If this occurs, adjust the threshold value
of the amplifier unit before use.
FA
COMPONENTS
MACHINE
VISION
SYSTEMS
UV
CURING
SYSTEMS
FX-301 / FX-305 (Red LED type) sensing range (Note 1)
The FX-305 and FX-301(-HS) have different sensing modes.
FX-305: H-SP, FAST, STD, STDF, LONG, U-LG (no S-D mode)
FX-301(-HS): S-D, H-SP (Note 1), FAST, STD, LONG (no STDF or U-LG mode)
Reflective type
Fibers are listed in alphabetic order. Refer to p.5~ “Fiber Selection” for details of each fiber.
Model No.
U-LG
LONG
Sensing range (mm in) (Note 2, 3) / Description
Red LED
STDF
STD
FAST
Dimensions
H-SP
S-D
FD-30
170
6.693
110
4.331
70
2.756
50
1.969
40
1.575
20
0.787
18
0.709
P.59
FD-31
150
5.906
95
3.740
63
2.480
45
1.772
35
1.378
17
0.669
16
0.630
P.59
FD-31W
60
2.362
40
1.575
30
1.181
20
0.787
15
0.591
8
0.315
10
0.394
P.59
FD-32G
210
8.268
120
4.724
100
3.937
60
2.362
42
1.654
20
0.787
20
0.787
P.59
FX-500
FD-32GX
240
9.449
140
5.512
100
3.937
70
2.756
50
1.969
25
0.984
25
0.984
P.59
FX-100
FD-40
170
6.693
110
4.331
70
2.756
50
1.969
40
1.575
20
0.787
18
0.709
P.59
FX-300
FD-41
150
5.906
95
3.740
63
2.480
45
1.772
35
1.378
17
0.669
16
0.630
P.59
FX-410
FD-41S
150
5.906
95
3.740
63
2.480
45
1.772
35
1.378
17
0.669
16
0.630
P.59
FX-311
FD-41SW
60
2.362
40
1.575
30
1.181
20
0.787
15
0.591
8
0.315
10
0.394
P.59
FD-41W
300 11.811
220
8.661
140
5.512
95
3.740
70
2.756
35
1.378
40
1.575
P.59
FD-42G
210
8.268
120
4.724
100
3.937
60
2.362
42
1.654
20
0.787
20
0.787
P.60
FD-42GW
160
6.299
85
3.346
70
2.756
35
1.378
25
0.984
13
0.512
14
0.551
P.60
FD-60
500 19.685
350 13.780
240
9.449
160
6.299
130
5.118
70
2.756
70
2.756
P.60
FD-61
440 17.323
320 12.598
205
8.071
145
5.709
105
4.134
65
2.559
60
2.362
P.60
FD-61G
460 18.110
200
7.874
210
8.268
90
3.543
65
2.559
35
1.378
40
1.575
P.60
FD-61S
440 17.323
320 12.598
205
8.071
145
5.709
105
4.134
60
2.362
60
2.362
P.60
Selection
Guide
Fibers
Fiber
Amplifiers
FX-301-F7/
FX-301-F
Notes: 1) Please contact our office about the sensing ranges for FX-301-HS in H-SP mode.
2) Note that the sensing range of the free-cut type fiber may be reduced by 20 % max. depending upon how the fiber is cut.
3) The sensing range is specified for white non-glossy paper.
Digital Fiber Sensor
FX-300 SERIES
LIST OF FIBERS
148
FIBER
SENSORS
FX-301 / FX-305 (Red LED type) sensing range (Note 1)
The FX-305 and FX-301(-HS) have different sensing modes.
FX-305: H-SP, FAST, STD, STDF, LONG, U-LG (no S-D mode)
FX-301(-HS): S-D, H-SP (Note 1), FAST, STD, LONG (no STDF or U-LG mode)
Reflective type
Fibers are listed in alphabetic order. Refer to p.5~ “Fiber Selection” for details of each fiber.
Model No.
U-LG
LONG
FD-61W
300 11.811
220
FD-62
690 27.165
FD-64X
Sensing range (mm in) (Note 2, 3) / Description
Red LED
STDF
STD
FAST
H-SP
Dimensions
AREA
SENSORS
LIGHT
CURTAINS /
SAFETY
COMPONENTS
S-D
95
3.740
70
2.756
35
1.378
40
1.575
P.60
480 18.898
310 12.205
220
8.661
160
6.299
85
3.346
90
3.543
P.60
270 10.630
200
7.874
100
3.937
85
3.346
60
2.362
35
1.378
35
1.378
P.61
FD-A16
230
9.055
200
7.874
150
5.906
150
5.906
100
3.937
45
1.772
50
1.969
P.61
FD-AL11
360 14.173
250
9.843
160
6.299
110
4.331
80
3.150
40
1.575
40
1.575
P.61
140
PHOTOELECTRIC
SENSORS
MICRO
PHOTOELECTRIC
SENSORS
5.512
8.661
LASER
SENSORS
PRESSURE /
FLOW
SENSORS
INDUCTIVE
PROXIMITY
SENSORS
PARTICULAR
USE
SENSORS
FD-E13
15
0.591
11
0.433
7
0.276
6
0.236
4
0.157
2
0.079
2
0.079
P.61
FD-E23
65
2.559
45
1.772
28
1.102
19
0.748
14
0.551
7
0.276
7
0.276
P.61
SENSOR
OPTIONS
FD-EG30
60
2.362
45
1.772
25
0.984
19
0.748
14
0.551
7
0.276
7
0.276
P.61
FD-EG30S
60
2.362
45
1.772
25
0.984
19
0.748
14
0.551
7
0.276
7
0.276
P.62
SIMPLE
WIRE-SAVING
UNITS
FD-EG31
20
0.787
15
0.591
9
0.354
8
0.315
5
0.197
2.5
0.098
3
0.118
P.62
WIRE-SAVING
SYSTEMS
Applicable pipe diameter: Outer dia. ø6 to ø26 mm ø0.236 to ø1.024 in transparent pipe
[PFA (fluorine resin) or equivalently transparent pipe, wall thickness 1 mm 0.039 in]
P.62
MEASUREMENT
SENSORS
Applicable pipe diameter: Outer dia. ø6 to ø26 mm ø0.236 to ø1.024 in transparent pipe
[PVC (vinyl chloride), fluorine resin, polycarbonate, acrylic, glass, wall thickness 1 to 3 mm 0.039 to 0.118 in]
P.62
STATIC
ELECTRICITY
PREVENTION
DEVICES
ø4 mm ø0.157 in form Protective tube: fluorine resin, length 500 mm 19.685 in (cuttable)
Liquid surface not contacted: Beam received, Liquid surface contacted: Beam interrupted
P.62
LASER
MARKERS
P.62
PLC
P.62
HUMAN
MACHINE
INTERFACES
1.850
P.63
ENERGY
CONSUMPTION
VISUALIZATION
COMPONENTS
2 to 6 0.079 to 0.236
P.63
FA
COMPONENTS
FD-F4
FD-F41
FD-F41Y
FD-F8Y
–
–
FD-FA93
FD-H13-FM2
FD-H18-L31
–
–
–
–
–
Applicable pipe diameter: Outer dia. ø8 mm ø0.315 in or more transparent pipe
(When used with the tying bands: ø8 to ø80 mm ø0.315 to ø3.150 in)
[PFA (fluorine resin), including translucent]
Liquid absent: Beam received, Liquid present: Beam interrupted
410 16.142
0 to 20 0 to 0.787
310 12.205
0 to 15 0 to 0.591
200
7.874
0 to 10 0 to 0.394
140
5.512
100
3.937
0 to 10 0 to 0.394 1 to 8 0.039 to 0.315
55
2.165
Cannot use
47
FD-H20-21
300 11.811
270 10.630
150 5.906
140 5.512
100 3.937
35 1.378
47 1.850
P.63
FD-H20-M1
300 11.811
270 10.630
150 5.906
140 5.512
100 3.937
35 1.378
47 1.850
P.63
FD-H25-L43 (Note 5) 3 to 28 0.118 to 1.102 3 to 25 0.118 to 0.984 4 to 23 0.157 to 0.906 4 to 20 0.118 to 0.787 4 to 19 0.118 to 0.748 4 to 16 0.118 to 0.630 4 to 16 0.118 to 0.630
P.63
–
–
P.63
FD-H30-KZ1V-S (Note 5,6) 20 to 300 0.787 to 11.811 20 to 200 0.787 to 7.874 20 to 150 0.787 to 5.906 25 to 130 0.984 to 5.118 30 to 100 1.181 to 3.937
Cannot use
Cannot use
P.64
FD-H30-L32
0 to 20 0 to 0.787 0 to 15 0 to 0.591 0 to 10 0 to 0.394 0 to 10 0 to 0.394 1 to 8 0.039 to 0.315
Cannot use
2 to 6 0.079 to 0.236
P.64
FD-H30-L32V-S (Note 5,6) 0 to 11 0 to 0.433 0 to 8 0 to 0.315 1.5 to 6 0.059 to 0.236 1.5 to 5 0.059 to 0.197 2 to 4 0.079 to 0.157
Cannot use
Cannot use
P.64
FD-H25-L45 (Note 5) 5 to 42 0.197 to 1.654 6 to 41 0.236 to 1.614 6 to 40 0.236 to 1.575 7 to 38 0.276 to 1.496
–
FD-H35-20S
190 7.480
160 6.299
80 3.150
80 3.150
57 2.244
20 0.787
26 1.024
P.64
FD-H35-M2
300 11.811
270 10.630
150 5.906
140 5.512
100 3.937
35 1.378
47 1.850
P.64
FD-H35-M2S6
300 11.811
270 10.630
150 5.906
140 5.512
100 3.937
35 1.378
47 1.850
P.64
FD-HF40Y
(Note 4)
ø4 mm ø0.157 in form Protective tube: fluorine resin, length:500 mm 19.685 in (allowable cutting)
Liquid surface not contacted: Beam received, Liquid surface contacted: Beam interrupted
P.64
MACHINE
VISION
SYSTEMS
UV
CURING
SYSTEMS
Selection
Guide
Fibers
Fiber
Amplifiers
FX-500
0 to 4 0 to 0.157 0 to 3.8 0 to 0.150 0 to 3.5 0 to 0.138 0 to 3.5 0 to 0.138
P.65
FX-100
0 to 7 0 to 0.906
0 to 7 0 to 0.276
P.65
FX-300
FD-L12W (Note 5) 0.5 to 9 0.020 to 0.354 0.5 to 8 0.019 to 0.315 1 to 6.5 0.039 to 0.256 1 to 5.5 0.039 to 0.217
1 to 5 0.039 to 0.197
P.65
FX-410
FD-L10 (Note 5)
FD-L11 (Note 5)
0 to 4.7 0 to 0.185 0 to 4.5 0 to 0.177 0 to 4.5 0 to 0.177
0 to 9 0 to 0.354
0 to 8 0 to 0.315
0 to 8 0 to 0.315
0 to 6 0 to 0.236
–
0 to 6 0 to 0.236
–
FD-L20H
1 to 29 0.039 to 1.142 2 to 23 0.079 to 0.906 3 to 17 0.118 to 0.669 4 to 14 0.157 to 0.551 4.5 to 11 0.177 to 0.433 5 to 8.5 0.196 to 0.335 4.8 to 9.5 0.188 to 0.374
P.65
FD-L21 (Note 5)
2 to 19 0.079 to 0.748 2 to 18 0.079 to 0.709 2 to 16 0.079 to 0.748 3 to 16 0.118 to 0.630 3 to 15 0.118 to 0.591 4 to 11 0.157 to 0.433 5 to 11 0.197 to 0.433
P.65
FD-L21W (Note 5) 3 to 14.5 0.118 to 0.571 3 to 14 0.118 to 0.551 4 to 14 0.157 to 0.551 6 to 12 0.236 to 0.472 7 to 12 0.276 to 0.472
FD-L22A (Note 5)
–
–
0 to 26 0 to 1.024 0 to 23 0 to 0.906 0 to 23 0 to 0.906 0 to 23 0 to 0.906 0 to 19 0 to 0.748 1 to 17 0.039 to 0.669 1 to 17 0.039 to 0.669
P.65
P.65
Notes: 1) Please contact our office about the sensing ranges for FX-301-HS in H-SP mode.
2) Note that the sensing range of the free-cut type fiber may be reduced by 20 % max. depending upon how the fiber is cut.
3) The sensing range of reflective type is the value for white non-glossy paper (as for FD-H30-L32 and FD-H18-L31 50 × 50 mm 1.969 × 1.969 in glass
substrate).
4) Liquid inflow prevention joint, protective tube extension joint, fiber mounting joint are available. Please refer to p.38 for details.
5) The sensing range is specified for transparent glass 100 × 100 × t0.7 mm 3.937 × 3.937 × t0.028 in (FD-L21 and FD-L21W: t2 mm t0.079 in) [FD-L10:
silicon wafers 100 × 100 mm 3.937 × 3.937 in].
6) Sold as a set comprising vacuum type fiber + photo-terminal (FV-BR1) + fiber at atmospheric side (FT-J8).
FX-311
FX-301-F7/
FX-301-F
149
FIBER
SENSORS
Digital Fiber Sensor
FX-300 SERIES
LIST OF FIBERS
LASER
SENSORS
FX-301 / FX-305 (Red LED type) sensing range (Note 1)
PHOTOELECTRIC
SENSORS
Reflective type
MICRO
PHOTOELECTRIC
SENSORS
AREA
SENSORS
LIGHT
CURTAINS /
SAFETY
COMPONENTS
PRESSURE /
FLOW
SENSORS
INDUCTIVE
PROXIMITY
SENSORS
PARTICULAR
USE
SENSORS
SENSOR
OPTIONS
SIMPLE
WIRE-SAVING
UNITS
WIRE-SAVING
SYSTEMS
MEASUREMENT
SENSORS
STATIC
ELECTRICITY
PREVENTION
DEVICES
LASER
MARKERS
PLC
HUMAN
MACHINE
INTERFACES
ENERGY
CONSUMPTION
VISUALIZATION
COMPONENTS
FA
COMPONENTS
MACHINE
VISION
SYSTEMS
UV
CURING
SYSTEMS
Fibers are listed in alphabetic order. Refer to p.5~ “Fiber Selection” for details of each fiber.
Model No.
U-LG
Fibers
Fiber
Amplifiers
FX-500
FX-100
FX-300
FX-410
FX-311
FX-301-F7/
FX-301-F
LONG
Sensing range (mm in) (Note 2, 3) / Description
Red LED
STDF
STD
FAST
Dimensions
H-SP
S-D
FD-L23 (Note 4)
0 to 30 0 to 1.181 0 to 30 0 to 1.181 0 to 30 0 to 1.181 0 to 30 0.039 to 1.181 1 to 28 0.039 to 1.102 2 to 27 0.079 to 1.063 2 to 27 0.079 to 1.063
P.65
FD-L30A (Note 4)
0 to 50 0 to 1.969 0 to 43 0 to 17.441 0 to 40 0 to 1.575 0 to 37 0 to 1.457 0 to 32 0 to 1.260 0 to 26 0 to 1.024 0 to 26 0 to 1.024
P.65
FD-L31A (Note 4)
4 to 33 0 to 13.110 4 to 33 0.157 to 1.299 5 to 32 0 to 1.260 5 to 32 0.197 to 1.260 5 to 32 0.197 to 1.259 6 to 18 0.236 to 0.709 6 to 18 0.236 to 0.709
P.65
FD-L32H (Note 4)
0 to 60 0 to 2.362 0 to 50 0 to 1.969 0 to 36 0 to 0.984 15 to 35 0.591 to 1.378 16 to 29 0.630 to 1.142
FD-R31G
–
–
P.66
160
6.299
92
3.622
75
2.953
44
1.732
32
1.260
17
0.669
17
0.669
P.66
FD-R32EG
60
2.362
45
1.772
25
0.984
19
0.748
13
0.512
7
0.276
7
0.276
P.66
FD-R33EG
17
0.669
15
0.591
8
0.315
6
0.236
4
0.157
2
0.079
2
0.079
P.66
FD-R34EG
51
2.008
38
1.496
21
0.827
16
0.630
11
0.433
6
0.236
6
0.236
P.66
FD-R41
230
9.055
150
5.906
100
3.937
70
2.756
50
1.969
28
1.102
28
1.102
P.66
FD-R60
310 12.205
240
9.449
170
6.693
120
4.724
90
3.543
45
1.772
45
1.772
P.66
FD-R61Y
350 13.780
230
9.055
160
6.299
110
4.330
80
3.150
45
1.772
45
1.772
P.66
FD-S21
80
3.150
50
1.969
40
1.575
25
0.984
19
0.748
9
0.354
9
0.354
P.66
FD-S30
170
6.693
110
4.331
70
2.756
50
1.969
40
1.575
20
0.787
18
0.709
P.67
FD-S31
150
5.906
95
3.740
63
2.480
45
1.772
35
1.378
17
0.669
16
0.630
P.67
FD-S32
440 17.323
270 10.630
200
7.874
140
5.512
100
3.937
55
2.165
55
2.165
P.67
FD-S32W
300 11.811
220
8.661
140
5.512
95
3.740
70
2.756
35
1.378
40
1.575
P.67
FD-S33GW
160
85
3.346
70
2.756
35
1.378
25
0.984
13
0.512
14
0.551
P.67
FD-S60Y
410 16.142
360 14.173
FD-V30
FD-V30W
FD-V50
FD-Z20HBW
FD-Z20W
6.299
250
9.843
170
6.693
120
4.724
65
2.559
70
2.756
P.67
45
1.772
30
1.181
20
0.787
15
0.591
6
0.236
7
0.276
P.67
0.984
15
0.591
10
0.394
7
0.276
5
0.197
6.693
100
3.937
55
2.165
45
1.772
32
1.260
80
3.150
25
170
–
–
P.67
0.630
P.68
1 to 70 0.039 to 2.756 1 to 70 0.039 to 2.756 1 to 32.2 0.039 to 1.268 2 to 30 0.079 to 1.181 2.5 to 20 0.098 to 0.787 3 to 10 0.118 to 0.394 3 to 10 0.118 to 0.394
P.68
1 to 87 0.039 to 3.425 1 to 59 0.0.9 to 2.323 2 to 39 0.079 to 1.535 3 to 27 0.118 to 1.063 3 to 19 0.118 to 0.748
15
0.591
–
16
–
P.68
FD-Z40HBW
350 13.780 0.5 to 230 0.02 to 9.055 1 to 160 0.039 to 6.299 1 to 100 0.039 to 3.937 1 to 70 0.039 to 2.756 1 to 40 0.039 to 1.575 1 to 40 0.039 to 1.575
P.68
FD-Z40W
270 10.630
4.724 1 to 87 0.039 to 3.425 1 to 63 0.039 to 2.480 2.5 to 32 0.098 to 1.260 2.5 to 32 0.098 to 1.260
P.68
10 to 870 0.394 to 34.252 10 to 540 0.394 to 21.260 10 to 400 0.394 to 15.748 10 to 250 0.393 to 9.843 10 to 190 0.394 to 7.480 15 to 100 0.196 to 3.937 15 to 100 0.591 to 3.937
P.68
FD-Z50HW
Selection
Guide
The FX-305 and FX-301(-HS) have different sensing modes.
FX-305: H-SP, FAST, STD, STDF, LONG, U-LG (no S-D mode)
FX-301(-HS): S-D, H-SP (Note 1), FAST, STD, LONG (no STDF or U-LG mode)
180
7.087
120
Notes: 1) Please contact our office about the sensing ranges for FX-301-HS in H-SP mode.
2) Note that the sensing range of the free-cut type fiber may be reduced by 20 % max. depending upon how the fiber is cut.
3) The sensing range of reflective type is the value for white non-glossy paper.
4) The sensing range is specified for transparent glass 100 × 100 × t0.7 mm 3.937 × 3.937 × t0.028 in (FD-L32H: R edge).
Digital Fiber Sensor
FX-300 SERIES
SENSING RANGE OF BLUE LED / GREEN LED / INFRARED LED
FIBER
SENSORS
LASER
SENSORS
Thru-beam type (One pair set)
Fibers are listed in alphabetic order. Refer to p.5~ for details of each fiber.
PHOTOELECTRIC
SENSORS
Sensing range (mm in) (Note 1)
FX-301B / 311B
Model No.
LONG
FT-140
150
STD
FX-301G / 311G
FAST
LONG
STD
FX-301H (Note 2)
FAST
LONG
STD
Dimensions
AREA
SENSORS
FAST
8,100 318.898 4,000 157.480 3,100 122.047 5,000 196.850 2,400 94.488 1,600 62.992 3,700 145.669 2,000 78.740 1,400 55.118
MICRO
PHOTOELECTRIC
SENSORS
P.51
LIGHT
CURTAINS /
SAFETY
COMPONENTS
FT-30
55 2.165
28 1.102
18 0.709
28 1.102
13 0.512
9 0.354
25 0.984
13 0.512
9 0.354
P.51
FT-31
50 1.969
25 0.984
16 0.630
24 0.945
12 0.472
8 0.315
23 0.906
11 0.433
8 0.315
P.51
FT-31S
50 1.969
25 0.984
16 0.630
24 0.945
12 0.472
8 0.315
23 0.906
11 0.433
8 0.315
P.51
FT-31W
31 1.220
15 0.591
10 0.394
15 0.591
8 0.315
5 0.197
18 0.709
8 0.315
5 0.197
P.51
FT-40
155 6.102
76 2.992
45 1.772
90 3.543
40 1.575
26 1.024
80 3.150
43 1.693
27 1.063
P.51
FT-42
150 5.906
75 2.953
40 1.575
80 3.150
35 1.378
24 0.945
75 2.953
40 1.575
25 0.984
P.51
FT-42S
150 5.906
75 2.953
40 1.575
70 2.756
35 1.378
24 0.945
75 2.953
40 1.575
25 0.984
P.51
FT-42W
110 4.331
50 1.969
30 1.181
56 2.205
28 1.102
20 0.787
64 2.520
32 1.260
21 0.827
P.51
FT-43
220 8.661
110 4.331
75 2.953
120 4.724
61 2.402
43 1.693
140 5.512
74 2.913
48 1.890
P.51
FT-45X
130 5.118
65 2.559
45 1.772
70 2.756
34 1.339
25 0.984
160 6.299
79 3.110
53 2.087
P.52
FT-A11
880 34.646
420 16.535
270 10.630
430 16.929
220 8.661
120 4.724
500 19.685
220 8.661
120 4.724
P.52
FT-A11W
820 32.283
420 16.535
280 11.024
460 18.110
220 8.661
140 5.512
520 20.472
240 9.449
140 5.512
P.52
FT-A32
1,800 70.866
710 27.953
400 15.748
970 38.189
320 12.598
180 7.087
910 35.827
340 13.386
150 5.906
P.52
STATIC
ELECTRICITY
PREVENTION
DEVICES
FT-A32W
2,000 78.740
830 32.677
420 16.535 1,000 39.370
350 13.780
180 7.087
910 35.827
340 13.386
150 5.906
P.52
LASER
MARKERS
100 3.937
48 1.890
18 0.709
54 2.126
27 1.063
18 0.709
P.52
FT-E13
2 0.079
1 0.039
2 0.079
1 0.039
FT-E23
8 0.315
4 0.157
3 0.118
4 0.157
2 0.079
1 0.039
10 0.394
5 0.197
3 0.118
P.52
FT-H13-FM2
72 2.835
36 1.417
26 1.024
32 1.260
16 0.630
10 0.394
70 2.756
35 1.378
25 0.984
P.52
FT-H20-J20-S (Note 3)
60 2.362
20 0.787
–
35 1.378
–
–
20 0.787
–
–
P.53
ENERGY
CONSUMPTION
VISUALIZATION
COMPONENTS
35 1.378
–
–
20 0.787
–
–
P.53
FA
COMPONENTS
35 1.378
–
–
20 0.787
–
–
P.53
280 11.024
160 6.299
P.53
30 1.181
–
–
P.53
30 1.181
–
–
P.53
FT-AL05
32 1.260
–
56 2.205
1 0.039
27 1.063
–
–
FT-H20-J30-S (Note 3)
60 2.362
20 0.787
–
FT-H20-J50-S (Note 3)
60 2.362
20 0.787
–
100 3.937
50 1.969
FT-H20-VJ50-S (Note 3)
85 3.346
30 1.181
–
50 1.969
–
–
FT-H20-VJ80-S (Note 3)
85 3.346
30 1.181
–
50 1.969
–
–
FT-H20W-M1
44 1.732
22 0.866
FT-H20-M1
35 1.378
14 0.551
22 0.866
25 0.984
11 0.433
7 0.276
220 8.661
100 3.937
70 2.756
–
–
P.53
FT-H35-M2
50 1.969
35 1.378
50 1.969
25 0.984
18 0.709
550 21.654
280 11.024
160 6.299
P.53
FT-H35-M2S6
100 3.937
50 1.969
35 1.378
50 1.969
25 0.984
18 0.709
550 21.654
280 11.024
160 6.299
P.53
80 3.150
40 1.575
25 0.984
110 4.331
55 2.165
40 1.575 1,100 43.307
550 21.654
350 13.780
P.53
FT-KS40
740 29.134
280 11.024
220 8.661
420 16.535
180 7.087
81 3.189
460 18.110
190 7.480
95 3.740
P.54
FT-KV26
81 3.189
36 1.417
21 0.827
44 1.732
8 0.315
53 2.087
19 0.748
FT-KV40
710 27.953
270 10.630
210 8.268
420 16.535
180 7.087
100 3.937
290 11.417
120 4.724
53 2.087
P.54
FT-KV40W
860 33.858
400 15.748
260 10.236
420 16.535
210 8.268
140 5.512
490 19.291
240 9.449
140 5.512
P.54
FT-L80Y
160 6.299
80 3.150
50 1.969
160 6.299
80 3.150
50 1.969
400 15.748
200 7.874
150 5.906
P.54
FT-R31
45 1.772
23 0.906
15 0.591
24 0.945
12 0.472
8 0.315
23 0.906
11 0.433
8 0.315
P.54
FT-R40
110 4.331
54 2.126
36 1.417
55 2.165
26 1.024
20 0.787
58 2.283
30 1.181
20 0.787
P.54
FT-R41W
110 4.331
50 1.969
30 1.181
56 2.205
28 1.102
20 0.787
64 2.520
32 1.260
21 0.827
P.54
FT-R42W
280 11.024
130 5.118
90 3.543
140 5.512
70 2.756
47 1.850
140 5.512
70 2.756
47 1.850
P.54
–
20 0.787
–
INDUCTIVE
PROXIMITY
SENSORS
PARTICULAR
USE
SENSORS
SENSOR
OPTIONS
SIMPLE
WIRE-SAVING
UNITS
WIRE-SAVING
SYSTEMS
MEASUREMENT
SENSORS
PLC
HUMAN
MACHINE
INTERFACES
MACHINE
VISION
SYSTEMS
UV
CURING
SYSTEMS
P.53
20 0.787
FT-HL80Y
–
550 21.654
40 1.575
20 0.787
–
18 0.709
P.52
100 3.937
FT-H30-M1V-S (Note 4)
–
50 1.969
–
PRESSURE /
FLOW
SENSORS
P.54
Notes: 1) Note that the sensing range of the free-cut type fiber may be reduced by 20 % max. depending upon how the fiber is cut.
2) Because infrared types are easily affected by humidity, please ask assistance when using them in a humid environment or in an environment with
varying humidity.
3) Heat-resistant joint fibers and ordinary-temperature fibers (FT-42) are sold as a set.
4) Sold as a set comprising vacuum type fiber + photo-terminal (FV-BR1) + fiber at atmospheric side (FT-J8).
Selection
Guide
Fibers
Fiber
Amplifiers
FX-500
FX-100
FX-300
FX-410
FX-311
FX-301-F7/
FX-301-F
151
FIBER
SENSORS
Digital Fiber Sensor
FX-300 SERIES
SENSING RANGE OF BLUE LED / GREEN LED / INFRARED LED
LASER
SENSORS
Thru-beam type (One pair set)
PHOTOELECTRIC
SENSORS
Fibers are listed in alphabetic order. Refer to p.5~ “Fiber Selection” for details of each fiber.
MICRO
PHOTOELECTRIC
SENSORS
Sensing range (mm in) (Note 1)
LIGHT
CURTAINS /
SAFETY
COMPONENTS
PRESSURE /
FLOW
SENSORS
INDUCTIVE
PROXIMITY
SENSORS
PARTICULAR
USE
SENSORS
SENSOR
OPTIONS
SIMPLE
WIRE-SAVING
UNITS
WIRE-SAVING
SYSTEMS
MEASUREMENT
SENSORS
FX-301B / 311B
Model No.
AREA
SENSORS
LONG
FX-301G / 311G
STD
FAST
LONG
FX-301H (Note 2)
STD
FAST
LONG
96 3.780
50 1.969
33 1.299
53 2.087
25 0.984
17 0.669
55 2.165
27 1.063
18 0.709
P.54
FT-R44Y
96 3.780
50 1.969
33 1.299
53 2.087
25 0.984
17 0.669
55 5.165
27 1.063
18 0.709
P.55
FT-R60Y
250 9.843
120 4.724
80 3.150
140 5.512
70 2.756
50 1.969
60 2.362
90 3.543
170 6.693
P.55
FT-S11
12 0.472
5 0.197
4 0.157
5 0.197
2.5 0.098
1.5 0.059
21 0.827
10 0.394
7 0.276
P.55
FT-S20
55 2.165
28 1.102
18 0.709
28 1.102
13 0.512
9 0.354
25 0.984
13 0.512
9 0.354
P.55
FT-S21
50 1.969
25 0.984
16 0.630
24 0.945
12 0.472
8 0.315
23 0.906
11 0.433
8 0.315
P.55
FT-S21W
31 1.220
15 0.591
10 0.394
15 0.591
8 0.315
5 0.197
18 0.709
8 0.315
5 0.197
P.55
FT-S30
155 6.102
76 2.992
45 1.772
90 3.543
40 1.575
26 1.024
80 3.150
43 1.693
27 1.063
P.55
FT-S31W
110 4.331
50 1.969
30 1.181
56 2.205
28 1.102
20 0.787
64 2.520
32 1.260
21 0.827
P.55
FT-S32
420 16.535
200 7.874
130 5.118
220 8.661
100 3.937
72 2.835
210 8.268
100 3.937
67 2.638
P.55
FT-V23
65 2.559
26 1.024
18 0.709
26 1.024
13 0.512
8 0.315
29 1.142
13 0.512
9 0.354
P.55
FT-V24W
6 0.236
2 0.079
25 0.984
12 0.472
–
3 0.118
–
–
3 0.118
FT-V25
FT-V30
80 3.150
40 1.575
22 0.866
40 1.575
14 0.551
8 0.315
47 1.850
LASER
MARKERS
FT-V40
400 15.748
200 7.874
130 5.118
200 7.874
100 3.937
65 2.559
290 11.417
FT-V80Y
120 4.724
60 2.362
35 1.378
80 3.150
40 1.575
25 0.984
75 2.953
FT-Z20HBW
39 1.535
19 0.748
12 0.472
20 0.787
10 0.394
6 0.236
FT-Z20W
82 3.228
37 1.457
23 0.906
44 1.732
18 0.709
HUMAN
MACHINE
INTERFACES
FAST
FT-R43
STATIC
ELECTRICITY
PREVENTION
DEVICES
PLC
Dimensions
STD
9 0.354
16 0.630
7 0.276
–
–
P.56
4 0.157
P.56
19 0.748
9 0.354
P.56
140 5.512
92 3.622
P.56
38 1.496
24 0.945
P.56
40 1.575
15 0.591
12 0.472
P.56
11 0.433
100 3.937
50 1.969
32 1.260
P.56
5 0.197
15 0.591
8 0.315
ENERGY
CONSUMPTION
VISUALIZATION
COMPONENTS
FT-Z30
120 4.724
60 2.362
40 1.575
96 3.780
45 1.772
30 1.181
140 5.512
72 2.835
47 1.850
P.56
FT-Z30E
540 21.260
250 9.843
170 6.693
270 10.630
130 5.118
91 3.583
280 11.024
140 5.512
88 3.465
P.56
FA
COMPONENTS
FT-Z30EW
540 21.260
260 10.236
170 6.693
260 10.236
120 4.724
88 3.465
290 11.417
140 5.512
92 3.622
P.57
FT-Z30H
650 25.591
310 12.205
200 7.874
340 13.386
160 6.299
110 4.331
330 12.992
160 6.299
100 3.937
P.57
FT-Z30HW
540 21.260
260 10.236
170 6.693
260 10.236
120 4.724
88 3.465
290 11.417
140 5.512
92 3.622
P.57
83 3.268
40 1.575
25 0.984
73 2.874
36 1.417
25 0.984
100 3.937
52 2.047
34 1.339
P.57
FT-Z40HBW
110 4.331
50 1.969
30 1.181
56 2.205
28 1.102
20 0.787
64 2.520
32 1.260
21 0.827
P.57
FT-Z40W
180 7.087
90 3.543
60 2.362
90 3.543
50 1.969
35 1.378
100 3.937
50 1.969
30 1.181
P.57
FT-Z802Y
320 12.598
160 6.299
120 4.724
160 6.299
80 3.150
60 2.362
320 12.598
160 6.299
120 4.724
P.57
MACHINE
VISION
SYSTEMS
UV
CURING
SYSTEMS
Selection
Guide
FT-Z30W
Notes: 1) Note that the sensing range of the free-cut type fiber may be reduced by 20 % max. depending upon how the fiber is cut.
2) Because infrared types are easily affected by humidity, please ask assistance when using them in a humid environment or in an environment with
varying humidity.
Fibers
Fiber
Amplifiers
Retroreflective type
FX-500
FX-100
FX-300
FX-410
Fibers are listed in alphabetic order. Refer to p.5~ “Fiber Selection” for details of each fiber.
Sensing range (mm in) (Note 1, 2)
FX-311
FX-301-F7/
FX-301-F
FX-301B / 311B
Model No.
FR-KZ22E
FX-301G / 311G
FX-301H
Dimensions
LONG
STD
FAST
LONG
STD
FAST
LONG
STD
FAST
–
–
–
–
–
–
–
–
–
P.58
FR-KZ50E
20 to 160 0.787 to 6.299 20 to 100 0.787 to 3.937 20 to 60 0.787 to 2.362 20 to 110 0.787 to 4.331 20 to 54 0.787 to 2.126
–
20 to 100 0.787 to 3.937 20 to 33 0.787 to 1.299
–
P.58
FR-KZ50H
20 to 140 0.787 to 5.512 20 to 70 0.787 to 2.76 20 to 52 0.787 to 2.047 20 to 90 0.787 to 3.543 20 to 40 0.787 to 1.575
–
20 to 80 0.787 to 3.150 20 to 43 0.787 to 1.693
–
P.58
–
100 to 410 3.937 to 16.142
–
P.58
FR-Z50HW
–
–
–
–
–
–
Notes: 1) Note that the sensing range of the free-cut type fiber may be reduced by 20 % max. depending upon how the fiber is cut.
2) The sensing range is the possible setting range for the attached reflector. The fiber can detect an object less than setting range for the reflector.
However, note that if there are any white or highly-reflective surfaces near the fiber head, reflected incident light may affect the fiber head. If this occurs,
adjust the threshold value of the amplifier unit before use.
Digital Fiber Sensor
FX-300 SERIES
SENSING RANGE OF BLUE LED / GREEN LED / INFRARED LED
152
FIBER
SENSORS
Reflective type
LASER
SENSORS
Fibers are listed in alphabetic order. Refer to p.5~ “Fiber Selection” for details of each fiber.
PHOTOELECTRIC
SENSORS
Sensing range (mm in) (Note 1, 2) / Description
FX-301B / 311B
Model No.
LONG
STD
FX-301G / 311G
FAST
LONG
STD
FX-301H
FAST
LONG
STD
Dimensions
AREA
SENSORS
FAST
FD-30
19 0.748
9 0.354
6 0.236
9 0.354
4.5 0.177
2.5 0.098
8 0.315
4 0.157
2.5 0.098
P.59
FD-31
18 0.709
8 0.315
5 0.197
8 0.315
4 0.157
2 0.079
7 0.276
3 0.118
2 0.079
P.59
6 0.236
3 0.118
–
–
FD-31W
7 0.276
FD-32G
22 0.866
11 0.433
8 0.315
15 0.591
6 0.236
4 0.157
11 0.433
6 0.236
2 0.079
P.59
FD-32GX
25 0.984
11 0.433
8 0.315
16 0.630
6 0.236
4 0.157
14 0.551
7 0.276
4 0.157
P.59
FD-40
19 0.748
9 0.354
6 0.236
9 0.354
4.5 0.177
2.5 0.098
8 0.315
4 0.157
2.5 0.098
P.59
FD-41
18 0.709
8 0.315
5 0.197
8 0.315
4 0.157
2 0.079
7 0.276
3 0.118
2 0.079
P.59
FD-41S
18 0.709
8 0.315
5 0.197
8 0.315
4 0.157
2 0.079
7 0.276
3 0.118
2 0.079
P.59
FD-41SW
4 0.157 1 to 2.5 0.039 to 0.098
5 0.197 1 to 2 0.039 to 0.079
9 0.354 1 to 4 0.039 to 0.157 1 to 2.5 0.039 to 0.098 1 to 4 0.039 to 0.157 1 to 2 0.039 to 0.079
–
6 0.236 1 to 3 0.039 to 0.118
–
MICRO
PHOTOELECTRIC
SENSORS
P.59
P.59
LIGHT
CURTAINS /
SAFETY
COMPONENTS
PRESSURE /
FLOW
SENSORS
INDUCTIVE
PROXIMITY
SENSORS
PARTICULAR
USE
SENSORS
SENSOR
OPTIONS
SIMPLE
WIRE-SAVING
UNITS
FD-41W
32 1.260 1 to 15 0.039 to 0.591 1 to 9 0.039 to 0.354
17 0.669 1 to 7.5 0.039 to 0.295 1.5 to 4.5 0.059 to 0.177
18 0.709 1 to 9 0.039 to 0.354 1.5 to 5 0.059 to 0.197
P.59
FD-42G
22 0.866
11 0.433
8 0.315
15 0.591
6 0.236
4 0.157
11 0.433
6 0.236
2 0.079
P.60
FD-42GW
14 0.551
7 0.276
5 0.197
6 0.236
4 0.157
2 0.079
9 0.354
5 0.197
2 0.079
P.60
FD-60
55 2.165
28 1.102
18 0.709
30 1.181
15 0.591
10 0.394
30 1.181
15 0.591
10 0.394
P.60
FD-61
48 1.890
24 0.945
16 0.630
26 1.024
13 0.512
8 0.315
27 1.063
12 0.472
8 0.315
P.60
STATIC
ELECTRICITY
PREVENTION
DEVICES
FD-61G
46 1.811
23 0.906
15 0.591
26 1.024
12 0.472
8 0.315
25 0.984
12 0.472
8 0.315
P..60
LASER
MARKERS
FD-61S
48 1.890
24 0.945
16 0.630
26 1.024
13 0.512
8 0.315
27 1.063
12 0.472
8 0.315
P.60
FD-61W
32 1.260 1 to 15 0.039 to 0.591 1 to 9 0.039 to 0.354
17 0.669 1 to 7.5 0.039 to 0.295 1.5 to 4.5 0.059 to 0.177
18 0.709 1 to 9 0.039 to 0.354 1.5 to 5 0.059 to 0.197
P.60
FD-62
80 3.150 1 to 40 0.039 to 1.575 1 to 27 0.039 to 1.063 1 to 42 0.039 to 1.654 1 to 21 0.039 to 0.827 1 to 14 0.039 to 0.551
54 2.126 1 to 26 0.039 to 1.024 1 to 17 0.039 to 0.669
P.60
FD-64X
32 1.260 0.5 to 16 0.020 to 0.630 0.5 to 10 0.020 to 0.394 0.5 to 16 0.020 to 0.630 0.5 to 8 0.020 to 0.315 0.5 to 5 0.020 to 0.197
27 1.063
22 0.866
P.61
FD-A16
19 0.748
14 0.551
18 0.709
15 0.591
FD-AL11
33 1.299
16 0.630
12 0.472
10 0.394
FD-E13
2 0.079
2 0.079
1 0.039
FD-E23
–
–
14 0.551
–
FA
COMPONENTS
18 0.709
8 0.315
0.8 0.031
0.5 0.020
0.8 0.031
6 0.236
3 0.118
2 0.079
3 0.118
1.5 0.059
1 0.039
8 0.315
4 0.157
2.5 0.098
P.61
FD-EG30
6 0.236
3 0.118
2 0.079
3 0.118
1.5 0.059
1 0.039
8 0.315
4 0.157
2.5 0.098
P.61
FD-EG30S
6 0.236
3 0.118
2 0.079
3 0.118
1 0.039
8 0.315
4 0.157
2.5 0.098
P.62
FD-EG31
2 0.079
1 0.039
0.5 0.020
1 0.039
4 0.157
2 0.079
1 0.039
P.62
FD-F4
FD-F41
FD-F41Y (Note 3)
FD-F8Y
FD-FA93
FD-H13-FM2
FD-H18-L31
1.5 0.059
–
–
–
–
Applicable pipe diameter: Outer dia. ø6 to ø26 mm ø0.236 to ø1.024 in transparent pipe
[PFA (fluorine resin) or equivalently transparent pipe, wall thickness 1 mm 0.039 in]
Liquid absent: Beam received, Liquid present: Beam interrupted
Applicable pipe diameter: Outer dia. ø6 to ø26 mm ø0.236 to ø1.024 in transparent pipe
[PVC (vinyl chloride), fluorine resin, polycarbonate, acrylic, glass, wall thickness 1 to 3 mm 0.039 to 0.118 in]
Liquid absent: Beam received, Liquid present: Beam interrupted
ø4 mm ø0.157 in form Protective tube: fluorine resin, length 500 mm 19.685 in (cuttable)
Liquid surface not contacted: Beam received, Liquid surface contacted: Beam interrupted
–
–
–
–
–
–
–
–
–
11 0.433
–
7 0.276
–
20 0.787
–
11 0.433
–
7 0.276
–
25 0.984
–
12 0.472
–
P.61
P.62
P.62
–
UV
CURING
SYSTEMS
8 0.315
–
Selection
Guide
Fibers
Fiber
Amplifiers
P.62
FX-500
P.62
P.63
P.63
FD-H20-21
36 1.417
18 0.709
12 0.472
20 0.787
10 0.394
7 0.276
140 5.512
70 2.756
45 1.772
P.63
FD-H20-M1
36 1.417
18 0.709
12 0.472
20 0.787
10 0.394
7 0.276
140 5.512
70 2.756
45 1.772
P.63
FD-H25-L43 (Note 4)
–
–
–
–
–
–
–
–
–
P.63
FD-H25-L45 (Note 4)
–
–
–
–
–
–
–
–
–
P.63
Notes: 1) Note that the sensing range of the free-cut type fiber may be reduced by 20 % max. depending upon how the fiber is cut.
2) The sensing range is specified for white non-glossy paper. (FP-H18-L31 50 × 50 mm 1.969 × 1.969 in. glass substrate).
3) Liquid inflow prevention joint, protective tube extension joint, fiber mounting joint are available. Please refer to p.38 for details.
4) The sensing range is specified for transparent glass 100 × 100 × t0.7 mm 3.937 × 3.937 × t0.028 in
MACHINE
VISION
SYSTEMS
P.62
Applicable pipe diameter: Outer dia. ø8 mm ø0.315 in or more transparent pipe
(When used with the tying bands: ø8 to ø80 mm ø0.315 to ø3.150 in) [PFA (fluorine resin), including translucent]
Liquid absent: Beam received, Liquid present: Beam interrupted
20 0.787
HUMAN
MACHINE
INTERFACES
P.61
10 0.394
–
PLC
P.61
13 0.512
6 0.236
MEASUREMENT
SENSORS
ENERGY
CONSUMPTION
VISUALIZATION
COMPONENTS
20 0.787
4.5 0.177
WIRE-SAVING
SYSTEMS
FX-100
FX-300
FX-410
FX-311
FX-301-F7/
FX-301-F
153
FIBER
SENSORS
Digital Fiber Sensor
FX-300 SERIES
SENSING RANGE OF BLUE LED / GREEN LED / INFRARED LED
LASER
SENSORS
Reflective type
PHOTOELECTRIC
SENSORS
Fibers are listed in alphabetic order. Refer to p.5~ “Fiber Selection” for details of each fiber.
MICRO
PHOTOELECTRIC
SENSORS
Sensing range (mm in) (Note 1, 2) / Description
LIGHT
CURTAINS /
SAFETY
COMPONENTS
PRESSURE /
FLOW
SENSORS
INDUCTIVE
PROXIMITY
SENSORS
PARTICULAR
USE
SENSORS
SENSOR
OPTIONS
SIMPLE
WIRE-SAVING
UNITS
WIRE-SAVING
SYSTEMS
MEASUREMENT
SENSORS
STATIC
ELECTRICITY
PREVENTION
DEVICES
LASER
MARKERS
PLC
HUMAN
MACHINE
INTERFACES
ENERGY
CONSUMPTION
VISUALIZATION
COMPONENTS
FA
COMPONENTS
MACHINE
VISION
SYSTEMS
UV
CURING
SYSTEMS
Selection
Guide
Fibers
Fiber
Amplifiers
LONG
FX-301G / 311G
FX-301H
Dimensions
STD
FAST
LONG
STD
FAST
LONG
STD
FAST
–
–
–
–
–
–
–
–
P.64
FD-H30-L32
–
–
–
–
–
–
–
–
–
P.64
FD-H30-L32V-S (Note 3,4)
–
–
–
–
–
–
–
–
–
P.64
FD-H30-KZ1V-S (Note 3,4) 30 to 40 1.181 to 1.575
FD-H35-20S
22 0.866
11 0.433
7 0.276
12 0.472
6 0.236
4 0.157
80 3.150
40 1.575
28 1.102
P.64
FD-H35-M2
36 1.417
18 0.709
12 0.472
20 0.787
10 0.394
7 0.276
140 5.512
70 2.756
45 1.772
P.64
FD-H35-M2S6
36 1.417
18 0.709
12 0.472
20 0.787
10 0.394
7 0.276
140 5.512
70 2.756
45 1.772
P.64
ø4 mm ø0.157 in form Protective tube: fluorine resin, length:500 mm 19.685 in (allowable cutting)
FD-HF40Y (Note 5) Liquid surface not contacted: Beam received, Liquid surface contacted: Beam interrupted
FD-L10 (Note 6)
FD-L11 (Note 6)
FD-L12W (Note 6)
FD-L20H
0 to 3.5 0 to 0.138 0 to 3 0 to 0.118 0.5 to 2.5 0.020 to 0.098 0 to 3 0 to 0.118 1 to 2 0.039 to 0.079
7 0.276
–
6.5 0.256 0.5 to 5.5 0.020 to 0.217
–
–
6.5 0.256 1 to 4 0.039 to 0.157
–
–
4.5 to 10 0.177 to 0.394 5 to 9 0.197 to 0.354 5.5 to 8 0.217 to 0.315 5 to 9 0.197 to 0.354 5.5 to 8 0.217 to 0.315
–
–
P.64
0 to 3 0 to 0.118 1 to 2 0.039 to 0.079
–
P.65
6.5 0.256 1 to 4.5 0.039 to 0.177
–
P.65
–
–
–
–
P.65
–
4.9 to 8.5 0.193 to 0.335
–
–
P.65
FD-L21 (Note 6)
–
–
–
–
–
–
–
–
–
P.65
FD-L21W (Note 6)
–
–
–
–
–
–
–
–
–
P.65
FD-L22A (Note 6)
–
–
–
–
–
–
–
–
–
P.65
FD-L23 (Note 6)
–
–
–
–
–
–
–
–
–
P.65
FD-L30A (Note 6)
–
–
–
–
–
–
–
–
–
P.65
FD-L31A (Note 6)
–
–
–
–
–
–
–
–
–
P.65
FD-L32H (Note 6)
–
–
–
–
–
–
–
–
–
P.66
FD-R31G
FD-R32EG
17 0.669
8 0.315
5 0.197
8 0.315
6 0.236
3 0.118
1.5 0.059
2 0.079
FD-R33EG
2 0.079
0.8 0.031
0.5 0.020
1 0.039
FD-R34EG
5 0.197
2 0.079
1.5 0.059
2 0.079
FD-R41
24 0.945 1 to 13 0.039 to 0.512
FD-R60
42 1.654
FD-R61Y
36 1.417
4 0.157
1 0.039
–
1 0.039
2 0.079
–
9 0.354
4 0.157
8 0.315
4 0.157
–
3 0.118
1.5 0.059
–
6 0.236
3 0.118
2 0.079
P.66
2.5 0.098
P.66
–
P.66
2 0.079
P.66
14 0.551 1 to 6 0.039 to 0.236 1 to 3 0.039 to 0.118
P.66
20 0.787 0.5 to 13 0.020 to 0.512
21 0.827 0.5 to 10 0.020 to 0.394 0.5 to 7 0.020 to 0.276
27 1.063
8 0.315
P.66
17 0.669 0.5 to 11 0.020 to 0.433
19 0.748 0.5 to 9 0.020 to 0.354 1 to 6 0.039 to 0.236
19 0.748 0.5 to 10 0.020 to 0.394 0.5 to 6 0.020 to 0.236
P.66
1 to 9 0.039 to0.354 1 to 15 0.039 to 0.591
1 to 8 0.039 to 0.315 3 to 6 0.118 to 0.236
12 0.472
FD-S21
8 0.315
3.5 0.138
2 0.079
5 0.197
2 0.079
1.3 0.051
9 0.354
4 0.157
3 0.118
P.66
FD-S30
19 0.749
9 0.354
6 0.236
9 0.354
4.5 0.177
2.5 0.098
8 0.315
4 0.157
2.5 0.098
P.67
FD-S31
18 0.709
8 0.315
5 0.197
8 0.315
4 0.157
2 0.079
7 0.276
3 0.118
2 0.079
P.67
FD-S32
48 1.890
24 0.945
16 0.630
26 1.024
13 0.512
8 0.315
27 1.063
12 0.472
8 0.315
P.67
FD-S32W
32 1.260 1 to 15 0.039 to 0.591 1 to 9 0.039 to 0.354
18 0.709 1 to 9 0.039 to 0.354 1.5 to 5 0.059 to 0.197
P.67
FD-S33GW
14 0.551
FX-500
FD-S60Y
FX-100
FD-V30
FX-300
FD-V30W
FX-410
FD-V50
FX-311
FD-Z20HBW
FX-301-F7/
FX-301-F
FX-301B / 311B
Model No.
AREA
SENSORS
FD-Z20W
50 1.969
9 0.354
–
7 0.276
5 0.197
20 0.787 3 to 12 0.118 to 0.472
17 0.669 1 to 7.5 0.039 to 0.295 1.5 to 4.5 0.059 to 0.177
6 0.236
4 0.157
28 1.102 3 to 9 0.118 to 0.354
2 0.079
–
2 0.079
P.67
30 1.181 2 to 13 0.079 to 0.512 5 to 6.5 0.197 to 0.256
P.67
9 0.354
5 0.197
–
–
–
–
–
–
–
–
P.67
–
–
–
–
–
–
P.67
–
–
–
–
P.68
–
P.68
–
P.68
–
–
12 0.472
–
–
4 to 10 0.157 to 0.394
–
–
–
–
–
3 to 11 0.118 to 0.433 4 to 6 0.157 to 0.236
–
–
–
–
–
–
5 to 8 0.197 to 0.315
6 0.236
6 0.236
–
FD-Z40HBW
1 to 36 0.039 to 1.417 3 to 17 1.181 to 0.669 3 to 11 1.181 to 0.433 2 to 19 0.079 to 0.748 3 to 8 0.118 to 0.315 4 to 5 0.157 to 0.197 2 to 20 0.0787 to 0.787 3 to 10 0.118 to 0.394 4 to 5.5 0.157 to 0.217
FD-Z40W
4 to 20 0.157 to 0.787
–
–
4 to 14 0.157 to 0.551
–
–
5 to 10 0.197 to 0.394
–
–
P.68
–
–
–
–
–
–
–
–
–
P.68
FD-Z50HW
Notes: 1) The standard sensing objects of the sensing ranges vary depending on the fibers.
2) Note that the sensing range of the free-cut type fiber may be reduced by 20 % max. depending upon how the fiber is cut.
3) The sensing range of reflective type is the value for white non-glossy paper.
4) Sold as a set comprising vacuum type fiber + photo-terminal (FV-BR1) + fiber at atmospheric side (FT-J8).
5) Liquid inflow prevention joint, protective tube extension joint, fiber mounting joint are available. Please refer to p.38 for details.
6) The sensing range is specified for transparent glass 100 × 100 × t.0.07 mm 3.937 × 3.937 × t0.028 in, (FD-L32H: R-edge,
FD-L21 and FD-L21W: t2 mm t0.079 in) [FD-L10: silicon wafers 100 × 100 mm 3.937 × 3.937 in]
P.68
Digital Fiber Sensor
FIBER OPTIONS
154
FX-300 SERIES
Refer to p. 69~ for details of lens dimensions.
LASER
SENSORS
Lens (for thru-beam type fiber)
Designation
Model No.
PHOTOELECTRIC
SENSORS
Description
Sensing range for red LED type (mm) [Lens on both sides] (Note 2)
Increases the sensing
range by 5 times or
more.
Expansion
lens
(Note 1)
FX-LE1
• Ambient
temperature:
–60 to +350 °C
–76 to +662 °F
(Note 5)
• Beam dia:
ø3.6 mm
ø0.142 in
Fiber
Mode
U-LG LONG STDF
STD
FAST
S-D
H-SP
2,900
2,100
1,300
1,200
2,800
1,600
1,600
FT-43
3,600 (Note 3) 3,600 (Note 3) 3,600 (Note 3)
FT-42
3,600 (Note 3) 3,600 (Note 3) 3,600 (Note 3) 3,600 (Note 3)
FT-45X
1,600 (Note 3) 1,600 (Note 3) 1,600 (Note 3) 1,600 (Note 3) 1,600 (Note 3) 1,600 (Note 3)
1,500
FT-R40
3,600 (Note 3) 3,600 (Note 3)
3,500
3,400
2,700
1,500
1,500
FT-H35-M2 3,500 (Note 3) 3,500 (Note 3)
2,500
2,000
1,500
750
700
1,300
900
500
400
1,100
900
600
FT-H20W-M1 1,600 (Note 3) 1,600 (Note 3) 1,600 (Note 3)
FT-H20-M1 1,600 (Note 3) 1,600 (Note 3) 1,600 (Note 3) 1,600 (Note 3)
Sensing range for red LED type (mm) [Lens on both sides] (Note 2)
Tremendously
increases the sensing
range with large
diameter lenses.
FX-LE2
For thru-beam type fiber
Superexpansion
lens
(Note 1)
• Ambient
temperature:
–60 to +350 °C
–76 to +662 °F
(Note 5)
• Beam dia:
ø9.8 mm
ø0.386 in
Beam axis is bent by
90°.
Side-view
lens
Expansion
lens for
vacuum
fiber
(Note 1)
Vacuum
resistant
side-view
lens
(Note 1)
FX-SV1
FV-LE1
FV-SV2
FIBER
SENSORS
• Ambient
temperature:
–60 to +300 °C
–76 to +572 °F
(Note 5)
• Beam dia:
ø2.8 mm
ø0.110 in
Fiber
Mode
U-LG LONG STDF
STD
FAST
S-D
H-SP
FT-43
3,600 (Note 3) 3,600 (Note 3) 3,600 (Note 3) 3,600 (Note 3) 3,600 (Note 3) 3,600 (Note 3) 3,600 (Note 3)
FT-42
3,600 (Note 3) 3,600 (Note 3) 3,600 (Note 3) 3,600 (Note 3) 3,600 (Note 3) 3,600 (Note 3) 3,600 (Note 3)
FT-45X
1,600 (Note 3) 1,600 (Note 3) 1,600 (Note 3) 1,600 (Note 3) 1,600 (Note 3) 1,600 (Note 3) 1,600 (Note 3)
FT-R40
3,600 (Note 3) 3,600 (Note 3) 3,600 (Note 3) 3,600 (Note 3) 3,600 (Note 3) 3,600 (Note 3) 3,600 (Note 3)
FT-H35-M2 3,500 (Note 3) 3,500 (Note 3) 3,500 (Note 3) 3,500 (Note 3) 3,500 (Note 3) 3,500 (Note 3) 3,500 (Note 3)
FT-H20W-M1 1,600 (Note 3) 1,600 (Note 3) 1,600 (Note 3) 1,600 (Note 3) 1,600 (Note 3)
1,500
1,600 (Note 3)
FT-H20-M1 1,600 (Note 3) 1,600 (Note 3) 1,600 (Note 3) 1,600 (Note 3) 1,600 (Note 3) 1,600 (Note 3) 1,600 (Note 3)
FT-H13-FM2 3,500 (Note 3) 3,500 (Note 3) 3,500 (Note 3) 3,500 (Note 3) 3,500 (Note 3) 3,500 (Note 3) 3,500 (Note 3)
MICRO
PHOTOELECTRIC
SENSORS
AREA
SENSORS
LIGHT
CURTAINS /
SAFETY
COMPONENTS
PRESSURE /
FLOW
SENSORS
INDUCTIVE
PROXIMITY
SENSORS
PARTICULAR
USE
SENSORS
SENSOR
OPTIONS
SIMPLE
WIRE-SAVING
UNITS
WIRE-SAVING
SYSTEMS
MEASUREMENT
SENSORS
STATIC
ELECTRICITY
PREVENTION
DEVICES
LASER
MARKERS
PLC
Sensing range for red LED type (mm) [Lens on both sides] (Note 2)
Fiber
Mode
U-LG LONG STDF
STD
FAST
S-D
H-SP
FT-43
1,900
1,200
840
580
420
250
240
FT-42
2,100
1,400
870
640
440
210
210
FT-45X
840
650
450
220
220
FT-H35-M2
1,600 (Note 3) 1,600 (Note 3)
840
550
370
280
200
90
90
FT-H20W-M1
400
310
180
140
100
50
50
FT-H20-M1
840
550
370
280
200
90
90
Sensing range increases Sensing range for red LED type (mm) [Lens on both sides] (Note 2, 4)
by 4 times or more.
Mode
U-LG LONG STDF STD FAST S-D
H-SP
• Ambient temperature: Fiber
–60 to +350 °C
FT-H30-M1V-S 1,600
1,200
650
450
300
150
200
–76 to +662 °F (Note 5)
• Beam dia:
ø3.6 mm
ø0.142 in
Beam axis is bent by Sensing range for red LED type (mm) [Lens on both sides] (Note 2, 4)
90°.
Mode
U-LG LONG STDF STD FAST S-D
H-SP
• Ambient temperature: Fiber
–60 to +300 °C
FT-H30-M1V-S 1,600
1,200
650
450
300
150
200
–76 to +572 °F (Note 5)
• Beam dia:
ø3.7 mm
ø0.146 in
Notes: 1) Be careful sure to use it only after you have adjusted it sufficiently when installing the thru-beam type fiber equipped with the expansion lens, as the
beam envelope becomes narrow and alignment is difficult.
2) The sensing ranges are the values for red LED type amplifier. Please contact our office for details on sensing ranges for other types of amplifiers.
3) The fiber cable length practically limits the sensing range.
4) The fiber cable length for the FT-H30-M1V-S is 1 m 3.281 ft. The sensing ranges in U-LG and LONG modes take into account the length of the FT-J8
atmospheric side fiber.
5) Refer to p.15, p18, p.33 and p.35 for the ambient temperatures of fibers to be used in combination.
HUMAN
MACHINE
INTERFACES
ENERGY
CONSUMPTION
VISUALIZATION
COMPONENTS
FA
COMPONENTS
MACHINE
VISION
SYSTEMS
UV
CURING
SYSTEMS
Selection
Guide
Fibers
Fiber
Amplifiers
FX-500
FX-100
FX-300
FX-410
FX-311
FX-301-F7/
FX-301-F
155
Digital Fiber Sensor
FIBER OPTIONS
FIBER
SENSORS
LASER
SENSORS
PHOTOELECTRIC
SENSORS
FX-300 SERIES
Refer to p. 69~ for details of lens dimensions.
Lens (for reflective type fiber)
Designation
MICRO
PHOTOELECTRIC
SENSORS
Model No.
Pinpoint spot of ø0.5 mm ø0.020 in. Enables detection of minute objects or small marks.
Pinpoint
spot lens
AREA
SENSORS
Description
FX-MR1
LIGHT
CURTAINS /
SAFETY
COMPONENTS
• Distance to focal point: 6 ± 1 mm 0.236 ± 0.039 in
• Applicable fibers: FD-42G, FD-42GW
• Ambient temperature: -40 to +70 °C -40 to +158 °F (Note)
The spot diameter is adjustable from ø0.7 to ø2 Sensing range for red LED type (Note 1)
mm ø0.028 to ø0.079 in according to how much
Screw-in depth Distance to focal point Spot diameter
the fiber is screwed in.
• Applicable fibers: FD-42G, FD-42GW
7 mm
18.5 mm approx. ø0.7 mm
• Ambient temperature:-40 to +70 °C
27 mm approx.
ø1.2 mm
12
mm
-40 to +158 °F (Note 2)
Spot
• Accessory: M
S-EX3 (mounting bracket)
43
mm
approx.
ø2.0 mm
14
mm
diameter
Screw-in
depth
PRESSURE /
FLOW
SENSORS
FX-MR2
Zoom lens
Distance to
focal point
INDUCTIVE
PROXIMITY
SENSORS
SENSOR
OPTIONS
SIMPLE
WIRE-SAVING
UNITS
WIRE-SAVING
SYSTEMS
MEASUREMENT
SENSORS
For reflective type fiber
PARTICULAR
USE
SENSORS
Finest spot
lens
FX-MR3
Distance to
focal point
Spot diameter
STATIC
ELECTRICITY
PREVENTION
DEVICES
Finest spot
lens
FX-MR6
LASER
MARKERS
PLC
side-view
type
Selection
Guide
Fibers
Fiber
Amplifiers
FX-500
FX-100
FX-300
Sensing range for red LED type (Note 1)
FX-MR5
Distance to
focal point
Spot diameter
FD-EG31
7.5 ±0.5 mm ø0.15 mm approx.
FD-EG30
7.5 ±0.5 mm ø0.3 mm approx.
FD-42G/42GW
7.5 ±0.5 mm ø0.5 mm approx.
FD-32G/32GX
Fiber model No. Distance to focal point Spot diameter
FD-EG31
7 ±0.5 mm
ø0.1 mm approx.
FD-EG30
7 ±0.5 mm
ø0.2 mm approx.
FD-42G/42GW
FD-32G/32GX
7 ±0.5 mm
ø0.4 mm approx.
Sensing range for red LED type (Note 1)
Screw-in depth Distance to focal point Spot diameter
8 mm
13 mm approx.
ø0.5 mm
10 mm
15 mm approx.
ø0.8 mm
14 mm
30 mm approx.
ø3.0 mm
Lens (For square head M3 reflective fiber)
Spot diameter
(mm in) (Note)
Type
Distance to
focal point
(mm in) (Note)
Lens
Shape
Model No.
(mm in)
Shape
ø0.1 ø0.004
approx.
ø0.15 ø0.006
approx.
Finest spot
lens
ø0.2 ø0.008
approx.
7 ± 0.5
0.276 ± 0.020 ø5 ø0.197
15.3
0.602
FX-MR7
ø0.4 ø0.016
approx.
FX-410
FX-311
Parallel
light lens
Zoom lens
Type
For Square head M3
reflective fiber
FX-301-F7/
FX-301-F
Fiber model No. Distance to focal point Spot diameter
Notes: 1) The sensing ranges are the values when used in combination with a red LED type amplifier. Please contact our office for details on sensing ranges for other types of amplifier.
2) Refer to p.16 or p.26 for the ambient temperatures of fibers to be used in combination.
For Square head M3 reflective fiber
UV
CURING
SYSTEMS
Extremely fine spot of ø0.1 mm ø0.004 in
approx. achieved.
• Applicable fibers:
FD-EG31, FD-EG30, FD-42G, FD-42GW,
FD-32G, FD-32GX
• Ambient temperature: -20 to +60 °C
-4 to +140 °F (Note 2)
can be mounted in a very small space.
• Applicable fibers: FD-42G, FD-42GW
• Ambient temperature: -40 to +70 °C
-40 to +158 °F (Note 2)
Zoom lens
ENERGY
CONSUMPTION
VISUALIZATION
COMPONENTS
MACHINE
VISION
SYSTEMS
Sensing range for red LED type (Note 1)
Screw-in FX-MR2 is converted into a side-view type and
depth
HUMAN
MACHINE
INTERFACES
FA
COMPONENTS
Extremely fine spot of ø0.15 mm ø0.006 in
approx. achieved.
• Applicable fibers:
FD-EG31, FD-EG30, FD-42G, FD-42GW,
FD-32G, FD-32GX
• Ambient temperature: -40 to +70 °C
-40 to +158 °F (Note 2)
Spot diameter
(mm in) (Note)
Sensing
range
(mm in) (Note)
Lens
Shape
fiber
Model No. Emitting
(mm in)
core (mm in)
ø0.4 to ø2.0 ø0.016 to ø0.079 approx.
ø0.4 to ø2.2 ø0.016 to ø0.087 approx.
10 to 30
ø5 ø0.197
ø0.5 to ø2.5 ø0.020 to ø0.098 approx. 0.394 to1.181
15
0.591
FX-MR8
ø0.8 to ø3.5 ø0.031 to ø0.138 approx.
ø4.0 ø0.157 approx.
0 to 30
0 to 1.181
10
0.394
ø5 ø0.197
FX-MR9
Fiber
Emitting fiber
core (mm in)
Model No.
ø0.125 ø0.005
FD-R33EG
ø0.125 ø0.005
FD-EG31
ø0.175 ø0.007
FD-R34EG
ø0.25 ø0.010
FD-R32EG
ø0.25 ø0.010
FD-EG30
ø0.5 ø0.020
FD-R31G
ø0.5 ø0.020
FD-32G
ø0.5 ø0.020
FD-32GX
ø0.5 ø0.020
FD-42G
ø0.5 ø0.020
FD-42GW
Applicable fibers
Model No.
ø0.125 ø0.005
FD-R33EG, FD-EG31
ø0.175 ø0.007
FD-R34EG
ø0.25 ø0.010
FD-R32EG, FD-EG30
ø0.5 ø0.020
FD-R31G, FD-32G, FD-32GX, FD-42G, FD-42GW
ø0.125 ø0.005
FD-R33EG, FD-EG31
ø0.175 ø0.007
FD-R34EG
ø0.25 ø0.010
FD-R32EG, FD-EG30
ø0.5 ø0.020
FD-R31G, FD-32G, FD-32GX, FD-42G, FD-42GW
Note: Spot diameter, distance to focal point and sensing range are specified for a red LED type amplifier.
Digital Fiber Sensor
FIBER OPTIONS
Model No.
FTP-500 (0.5 m 1.640 ft)
FTP-1500 (1.5 m 4.921 ft)
FTP-N500 (0.5 m 1.640 ft)
For M3
thread
FTP-N1000 (1 m 3.281 ft)
Applicable fibers
Protective tube
for thru-beam
type fiber
FT-42
FT-42S
FT-42W
For M4
thread
FTP-1000 (1 m 3.281 ft)
FTP-N1500 (1.5 m 4.921 ft)
FDP-500 (0.5 m 1.640 ft)
For M6
thread
FDP-1000 (1 m 3.281 ft)
Protective tube
for reflective
type fiber
FDP-1500 (1.5 m 4.921 ft)
FDP-N500 (0.5 m 1.640 ft)
FDP-N1500 (1.5 m 4.921 ft)
AREA
SENSORS
Fiber bender
FT-31
FT-31S
FT-31W
FD-31
FD-31W
FD-61
FD-61G
FD-61S
FD-61W
Using the arm which enables adjustment in
the horizontal direction, sensing can also be
done from above an assembly line.
FD-41S
FD-41SW
• MS-AJ1-F
MS-AJ1-F
Horizontal mounting type
MS-AJ2-F
Vertical mounting type
Fiber
mounting joint
(Note 2)
MS-FX-03Y
Single core
holder
Applicable fibers
Universal sensor
mounting stand
(Note 2)
MS-FX-02Y
The protective tube can be extended.
The joint is used for mounting fibers on a
tank.
The incident light intensity may vary when using a multi-core fiber or a
thin type sharp bending fiber. This holder suppresses the variation in
the incident light intensity. (Brown)
FX-AT15A
RF-210
Used with FR-Z50HW.
Refer to p.30 or p.41 for the sensing range of FR-Z50HW to be used
in combination.
RF-220
Reflector
Mounting stand assembly for fiber (For M3,
M4 or M6 threaded head fiber)
This joint suppresses false operations
due to liquid slip-in from the top of the
protective tube.
FD-HF40Y
FD-F41Y
RF-230
Notes: 1) Do not bend the sleeve part of any side-view type fiber or ultra-small diameter head type fiber.
2) The joint internal ferrule (MS-FX-YF) is available as a spare part. A distorted ferrule may result in leakage.
Liquid inflow prevention joint
MS-FX-01Y
• MS-FX-01Y
MS-FX-01Y
MS-FX-01Y
Ferrule (MS-FX-YF)
Union nut
Protective tube extension joint
MS-FX-02Y
• MS-FX-02Y
MS-FX-02Y
MS-FX-02Y
Union nut
Body
Ferrule (MS-FX-YF)
Body
Body
Union
nut
Ferrule
(MS-FX-YF)
• RF-210
33.3 mm
1.311 in
11 mm
0.433 in
MS-FX-03Y
• MS-FX-03Y
MS-FX-03Y
MS-FX-03Y
Body
Ferrule (MS-FX-YF)
Body
Body
Union
nut
Ferrule
(MS-FX-YF)
Union nut
• RF-220
35.3 mm
1.390 in
Ferrule (MS-FX-YF)
Union nut
8.3 mm
0.327 in
• RF-230
50.3 mm
1.980 in
12.8mm
0.504 in
42.3 mm
1.665 in
59.3 mm
2.335 in
360° rotation
Forward / back
adjustment:
130 mm
5.118 in approx.
360°
rotation
20°
20°
Angle adjustment: ±20°
Forward / back
adjustment:
130 mm
5.118 in approx.
360°
rotation
Height
adjustment:
150 mm 5.906 in
approx.
20°
20°
Angle adjustment: ±20°
PARTICULAR
USE
SENSORS
SENSOR
OPTIONS
SIMPLE
WIRE-SAVING
UNITS
WIRE-SAVING
SYSTEMS
MEASUREMENT
SENSORS
STATIC
ELECTRICITY
PREVENTION
DEVICES
LASER
MARKERS
PLC
360° rotation
Mounting hole
for M6 screw
HUMAN
MACHINE
INTERFACES
ENERGY
CONSUMPTION
VISUALIZATION
COMPONENTS
FA
COMPONENTS
MACHINE
VISION
SYSTEMS
UV
CURING
SYSTEMS
Single core holder
• FX-AT15A
Selection
Guide
Fibers
Fiber
Amplifiers
Union nut
Ferrule
(MS-FX-YF)
Union nut
Union nut
Ferrule
(MS-FX-YF)
Body
Ferrule (MS-FX-YF)
Body
Height
adjustment:
150 mm 5.906 in
approx.
Mounting hole
for M6 screw
• MS-AJ2-F
Fiber mounting joint
Ferrule (MS-FX-YF)
Union nut
Union nut
Ferrule (MS-FX-YF)
Ferrule (MS-FX-YF)
Body
Reflector
INDUCTIVE
PROXIMITY
SENSORS
Universal sensor mounting stand
FB-1
Protective tube
extension joint
(Note 2)
PRESSURE /
FLOW
SENSORS
The protective
tube, made of noncorrosive stainless
steel, protects the
FD-62
inner fiber cable from
FD-H13-FM2 any external forces.
Fiber bender
MS-FX-01Y
LIGHT
CURTAINS /
SAFETY
COMPONENTS
• FB-1
The fiber bender bends the sleeve part of the fiber head at the proper
radius. (Note 1)
Liquid inflow
prevention
joint
(Note 2)
MICRO
PHOTOELECTRIC
SENSORS
FT-43
FT-H13-FM2
FD-41
FD-41W
For M4
thread
FDP-N1000 (1 m 3.281 ft)
PHOTOELECTRIC
SENSORS
• FTP-□
• FDP-□
Description
FIBER
SENSORS
LASER
SENSORS
Protective tube
Designation
156
Refer to p. 69~ for details of lens dimensions.
Others
Union nut
FX-300 SERIES
FX-500
FX-100
FX-300
FX-410
FX-311
8.3 mm
0.327 in
FX-301-F7/
FX-301-F
157
Digital Fiber Sensor
SPECIFICATIONS
FIBER
SENSORS
LASER
SENSORS
Type
AREA
SENSORS
LIGHT
CURTAINS /
SAFETY
COMPONENTS
Model No.
PHOTOELECTRIC
SENSORS
MICRO
PHOTOELECTRIC
SENSORS
FX-300 SERIES
Item
PARTICULAR
USE
SENSORS
FX-301
FX-301B
FX-301G
FX-301H
FX-301-HS
FX-305
FX-301BP
FX-301GP
FX-301HP
FX-301P-HS
FX-305P
Power consumption
Output
PLC
HUMAN
MACHINE
INTERFACES
ENERGY
CONSUMPTION
VISUALIZATION
COMPONENTS
FA
COMPONENTS
MACHINE
VISION
SYSTEMS
UV
CURING
SYSTEMS
Selection
Guide
Fibers
Fiber
Amplifiers
FX-500
FX-100
FX-300
FX-410
FX-311
FX-301-F7/
FX-301-F
NPN open-collector transistor
NPN open-collector transistor 2 outputs
• Maximum sink current:100 mA (50 mA, if five, or more, amplifiers are connected in cascade.)
• Maximum sink current: 50 mA each (Note 2)
• Applied voltage: 30 V DC or less (between output and 0 V)
• Applied voltage: 30 V DC or less (between output and 0 V)
• Residual voltage: 1.5 V or less [at 100 mA (at 50 mA, if five, or more, amplifiers are connected in cascade) sink current.]
• Residual voltage: 1.5 V or less [at 50 mA (Note 2)]
PNP open-collector transistor 2 outputs
PNP open-collector transistor
• Maximum source current: 50 mA each (Note 2)
• Maximum source current: 100 mA (50 mA, if five, or more, amplifiers are connected in cascade.)
• Applied voltage: 30 V DC or less (between output and +V)
• Applied voltage: 30 V DC or less (between output and +V)
• Residual voltage: 1.5 V or less [at 50 mA (Note 2)]
• Residual voltage: 1.5 V or less [at 100 mA (at 50 mA, if five, or more, amplifiers are connected in cascade) source current.]
Selectable either Light-ON or Dark-ON, with jog switch
Short-circuit protection
Response time
Sensitivity setting
Incorporated
35 µs or less (H-SP),
65 µs or less [H-SP (Red LED type only)], 150 µs or less (FAST), 150 µs or less (FAST),
250 µs or less [STD / S-D (Red LED type only)],
250 µs or less (STD / S-D),
2 ms or less (LONG), selectable with jog switch
2 ms or less (LONG),
selectable with jog switch
Stability indicator
Orange LED (lights up when the output is ON)
–
Green LED (lights up under stable light received condition or stable dark condition)
MODE indicator
RUN: Green LED, TEACH • ADJ • L/D ON • TIMER • PRO: Yellow LED
Digital display
4 digit red LED display
Fine sensitivity adjustment function
Timer function
65 µs or less (H-SP), 150 µs or less (FAST),
250 µs or less (STD), 700 µs or less (STDF),
2.5 ms or less (LONG), 4.5 ms or less (U-LG),
selectable with jog switch
Normal mode: 2-point teaching / Limit teaching / Full-auto teaching /
Max. sensitivity teaching / Manual adjustment
Window comparator mode: Teaching (1-point / 2-point / 3-point) / Manual adjustment
2-point teaching / Limit teaching / Manual adjustment /
Full-auto teaching / Max. sensitivity teaching
Operation indicator
Incorporated
Incorporated with variable ON-delay / OFF-delay / ONE SHOT timer,
switchable either effective or ineffective.
Timer period: Red LED type; 0.5 ms approx., 1 to 9,999 ms
(Blue LED, Green LED, Infrared LED type; approx. 0.5 to 500 ms)
Incorporated with variable ON-delay / OFF-delay /
ONE SHOT / ON-delay • OFF-delay / ON-delay • ONE SHOT
timer, switchable either effective or ineffective.
(Timer period: Output 1; 0.5 ms, 1 to 9,999 ms, Output 2; 0.5 ms, 1 to 500 ms)
Light emitting amount
selection function
Incorporated (Red LED type only) (Note 3)
FAST, STD, LONG: 4 level, H-SP: 3 level, S-D: 2 level
Incorporated (Note 3)
FAST, STD, LONG: 4 level
H-SP, S-D: 2 level
Incorporated (Note 3)
FAST, STD, STDF, LONG, U-LG: 4 level
H-SP: 3 level
Automatic interference
prevention function
Incorporated (Up to four sets of fiber heads can be mounted
close together. However, 2 fiber heads in H-SP mode.) (Note 4)
–
Incorporated [Up to four sets of fiber heads can be
mounted close together. (However, 8 fiber heads in
U-LG mode, 2 fiber heads in H-SP mode.)] (Note 5)
Environmental resistance
LASER
MARKERS
12 to 24 V DC ±10 % Ripple P-P 10 % or less
Normal operation: 960 mW or less (Current consumption 40 mA or less at 24 V supply voltage)
Normal operation: 720 mW or less (Current consumption 30 mA or less at 24 V supply voltage)
ECO mode: 600 mW or less (Current consumption 25 mA or less at 24 V supply voltage)
ECO mode: 430 mW or less (Current consumption 18 mA or less at 24 V supply voltage)
Output operation
WIRE-SAVING
SYSTEMS
STATIC
ELECTRICITY
PREVENTION
DEVICES
High-function type
FX-301P
Supply voltage
SIMPLE
WIRE-SAVING
UNITS
High-speed
Green LED Infrared LED type
PNP output
SENSOR
OPTIONS
MEASUREMENT
SENSORS
Blue LED
NPN output
PRESSURE /
FLOW
SENSORS
INDUCTIVE
PROXIMITY
SENSORS
Standard type
Red LED
Ambient temperature
–10 to +55 °C +14 to +131 °F (If 4 to 7 units are connected in cascade: –10 to +50 °C +14 to +122 °F, if 8 to 16 units are
connected in cascade: –10 to +45 °C +14 to +113 °F) (No dew condensation or icing allowed), Storage: –20 to +70 °C – 4 to +158 °F
Ambient humidity
35 to 85 % RH, Storage: 35 to 85 % RH
Ambient illuminance
Incandescent light: 3,000 ℓx at the light-receiving face
Voltage withstandability
1,000 V AC for one min. between all supply terminals connected together and enclosure (Note 6)
Insulation resistance
20 MΩ, or more, with 250 V DC megger between all supply terminals connected together and enclosure (Note 6)
Vibration resistance
10 to 150 Hz frequency, 0.75 mm 0.030 in amplitude in X, Y and Z directions for two hours each
Shock resistance
Emitting element (modulated)
98 m/s2 acceleration (10 G approx.) in X, Y and Z directions for five times each
Red LED
Blue LED
Green LED
Infrared LED
Red LED
Red LED
Peak emission wavelength 650 nm 0.026 mil 470 nm 0.019 mil 525 nm 0.021 mil 940 nm 0.037 mil 650 nm 0.026 mil
Material
Enclosure: Heat-resistant ABS, Case cover: Polycarbonate, MODE key: Acrylic, Jog switch: Heat-resistant ABS (FX-301B/G/H: Acrylic)
Connecting method
Cable length
Connector (Note 7)
Total length up to 100 m 328.084 ft (50 m 164.042 ft for 5 to 8 units, 20 m 65.617 ft for 9 to 16 units) is possible with 0.3 mm2, or more, cable.
Weight
Accessory
650 nm 0.026 mil
Net weight: 20 g approx., Gross weight: 25 g approx.
FX-MB1 (amplifier
protection seal): 1 set
–
FX-MB1 (amplifier protection seal): 1 set
Notes: 1) Where measurement conditions have not been specified precisely, the conditions used were an ambient temperature of +23 °C +73.4 °F.
2) 50 mA per output. 25 mA if five, or more, amplifiers are connected in cascade.
3) The light emitting amount can be zero (emission halt) in all modes.
4) When the power supply is switched on, the light emission timing is automatically set for interference prevention.
5) When the interference prevention function “
” is set, the number of mountable fiber heads becomes double.
Furthermore, take care that the response time also becomes double.
6) The voltage withstandability and the insulation resistance values given in the above table are for the amplifier only.
7) The cable for amplifier connection is not supplied as an accessory. Make sure to use the optional quick-connection cables given below.
Main cable (3-core) for FX-301(P)(-HS): CN-73-C1 (Cable length 1 m 3.281 ft), CN-73-C2 (Cable length 2 m 6.562 ft), CN-73-C5 (Cable length 5 m 16.404 ft)
Sub cable (1-core) for FX-301(P)(-HS): CN-71-C1 (Cable length 1 m 3.281 ft), CN-71-C2 (Cable length 2 m 6.562 ft), CN-71-C5 (Cable length 5 m 16.404 ft)
Main cable (4-core) for FX-305(P): CN-74-C1 (Cable length 1 m 3.281 ft), CN-74-C2 (Cable length 2 m 6.562 ft), CN-74-C5 (Cable length 5 m 16.404 ft)
Sub cable (2-core) for FX-305(P): CN-72-C1 (Cable length 1 m 3.281 ft), CN-72-C2 (Cable length 2 m 6.562 ft), CN-72-C5 (Cable length 5 m 16.404 ft)
Digital Fiber Sensor
FX-300 SERIES
I/O CIRCUIT AND WIRING DIAGRAMS
FIBER
SENSORS
FX-301(-HS)
NPN output type
I/O circuit diagram
Sensor circuit
D
1
3
Tr
Terminal No.
Brown (Note)
(Brown) +V (Note 1)
(Black) Output
Load
+
100 mA max. (Note 2)
ZD
2
Load
Black
12 to 24 V DC
±10 %
+
Note: T
he quick-connection sub cable does not have brown lead wire and
blue lead wire.
Users’ circuit
Notes: 1) The quick-connection sub cable does not have +V (brown) and 0 V
(blue). The power is supplied from the connector of the main cable.
2) 50 mA max., if five amplifiers, or more, are connected together.
Terminal arrangement diagram
Symbols … D : Reverse supply polarity protection diode
ZD: Surge absorption zener diode
Tr : NPN output transistor
I/O circuit diagram
Sensor circuit
1
ZD
Tr
100 mA max. (Note 2)
3
D
2
+
(Black) Output
Load
(Blue) 0 V (Note 1)
Internal circuit
Users’ circuit
Notes: 1) The quick-connection sub cable does not have +V (brown) and 0 V
(blue). The power is supplied from the connector of the main cable.
2) 50 mA max., if five amplifiers, or more, are connected together.
2
0V
SENSOR
OPTIONS
Color code of quick-connection cable
+
12 to 24 V DC
±10 %
D
1
Tr1
3
Terminal arrangement diagram
PLC
1
+V
3
Output
2
0V
HUMAN
MACHINE
INTERFACES
ENERGY
CONSUMPTION
VISUALIZATION
COMPONENTS
Tr2
ZD1
4
ZD2
2
Load
+
(White) Output 2 50 mA max. (Note 2)
Black
12 to 24 V DC
±10 %
Load
Load
FA
COMPONENTS
MACHINE
VISION
SYSTEMS
UV
CURING
SYSTEMS
+
White
50 mA max. (Note 2)
12 to 24 V DC
±10 %
Blue (Note)
(Blue) 0 V (Note 1)
Internal circuit
Color code of quick-connection cable
Wiring diagram
Brown (Note)
Load
STATIC
ELECTRICITY
PREVENTION
DEVICES
LASER
MARKERS
(Brown) +V (Note 1)
(Black) Output
MEASUREMENT
SENSORS
Note: T
he quick-connection sub cable does not have brown lead wire and
blue lead wire.
NPN output type
Terminal No.
SIMPLE
WIRE-SAVING
UNITS
WIRE-SAVING
SYSTEMS
FX-305
Color code of quick-connection cable
PRESSURE /
FLOW
SENSORS
PARTICULAR
USE
SENSORS
Load
Blue (Note)
Symbols … D : Reverse supply polarity protection diode
ZD: Surge absorption zener diode
Tr : PNP output transistor
I/O circuit diagram
LIGHT
CURTAINS /
SAFETY
COMPONENTS
Output
Black
12 to 24 V DC
±10 %
AREA
SENSORS
INDUCTIVE
PROXIMITY
SENSORS
Brown (Note)
(Brown) +V (Note 1)
MICRO
PHOTOELECTRIC
SENSORS
3
Wiring diagram
Color code of quick-connection cable
PHOTOELECTRIC
SENSORS
+V
PNP output type
Terminal No.
LASER
SENSORS
1
FX-301P(-HS)
Sensor circuit
12 to 24 V DC
±10 %
Blue (Note)
(Blue) 0 V (Note 1)
Internal circuit
Color code of quick-connection cable
Wiring diagram
Color code of quick-connection cable
158
Note: T
he quick-connection sub cable does not have brown lead wire and
blue lead wire.
Users’ circuit
Notes: 1) The quick-connection sub cable does not have +V (brown) and 0 V
(blue). The power is supplied from the connector of the main cable.
2) 25 mA max., if five amplifiers, or more, are connected together.
Terminal arrangement diagram
Symbols … D: Reverse supply polarity protection diode
ZD1, ZD2: Surge absorption zener diode
Tr1, Tr2 : NPN output transistor
Selection
Guide
Fibers
Fiber
Amplifiers
1
+V
3
Output 1
2
0V
4
Output 2
FX-500
FX-100
FX-305P
PNP output type
Sensor circuit
I/O circuit diagram
ZD1
1
Terminal No.
50 mA max. (Note 2)
Tr2
D
Internal circuit
2
(White) Output 2
Load
Load
Black
+
12 to 24 V DC
±10 %
(Blue) 0 V (Note 1)
Users’ circuit
Notes: 1) The quick-connection sub cable does not have +V (brown) and 0 V
(blue). The power is supplied from the connector of the main cable.
2) 25 mA max., if five amplifiers, or more, are connected together.
Symbols … D: Reverse supply polarity protection diode
ZD1, ZD2: Surge absorption zener diode
Tr1, Tr2 : PNP output transistor
+
White
Load
12 to 24 V DC
±10 %
Load
Blue (Note)
Note: T
he quick-connection sub cable does not have brown lead wire and
blue lead wire.
Terminal arrangement diagram
1
+V
3
Output 1
2
0V
FX-300
FX-410
FX-311
Brown (Note)
(Brown) +V (Note 1)
ZD2 (Black) Output 1 50 mA max. (Note 2)
4
Wiring diagram
Color code of quick-connection cable
3
Tr1
Color code of quick-connection cable
4
Output 2
FX-301-F7/
FX-301-F
159
FIBER
SENSORS
Digital Fiber Sensor
PRECAUTIONS FOR PROPER USE
LASER
SENSORS
MICRO
PHOTOELECTRIC
SENSORS
AREA
SENSORS
PRESSURE /
FLOW
SENSORS
INDUCTIVE
PROXIMITY
SENSORS
PARTICULAR
USE
SENSORS
SENSOR
OPTIONS
SIMPLE
WIRE-SAVING
UNITS
WIRE-SAVING
SYSTEMS
MEASUREMENT
SENSORS
STATIC
ELECTRICITY
PREVENTION
DEVICES
LASER
MARKERS
PLC
HUMAN
MACHINE
INTERFACES
ENERGY
CONSUMPTION
VISUALIZATION
COMPONENTS
FA
COMPONENTS
MACHINE
VISION
SYSTEMS
UV
CURING
SYSTEMS
Selection
Guide
Fibers
Fiber
Amplifiers
FX-500
FX-100
FX-300
FX-410
FX-311
FX-301-F7/
FX-301-F
Refer to p.1458~ for general precautions and to the “PRO mode operation guide”
on our website for details pertaining to operating instructions for the amplifier.
• Never use this product as a sensing device
for personnel protection.
• In case of using sensing devices for
personnel protection, use products which
meet laws and standards, such as OSHA,
ANSI or IEC etc., for personnel protection
applicable in each region or country.
PHOTOELECTRIC
SENSORS
LIGHT
CURTAINS /
SAFETY
COMPONENTS
FX-300 SERIES
• The digital fiber sensor FX-301(P) has been modified
since its production in June 2004. The explanations
below are about the modified product.
Mounting
35 mm 1.378 in width
DIN rail
How to remove the amplifier
Push the amplifier forward.
Lift up the front part of the amplifier
to remove it.
Note: Take care that if the front part is lifted without pushing the
amplifier forward, the hook on the rear portion of the mounting
section is likely to break.
Fiber installation
• Insert the fiber into the amplifier after attaching the
attachment. Refer to the "Instruction Manual" included
with the fiber for details.
Fiber lock
lever
Fiber
Notes: 1) N
ote that if the fiber is not fully inserted, the sensing distance will
decrease. Also note that the flexible fiber may bend during insertion.
2) I n case of coaxial reflective type fibers (FD-G4, FD-FM2, etc.),
mount the central fiber (single-core) to the emitter part and the
peripheral fiber (multi-core) to the receiver. Note that sensing
precision will deteriorate when done in reverse.
Connection
• Make sure that the power supply is off while connecting
or disconnecting the quick-connection cable.
Connection method
H
olding the connector of the
quick-connection cable, align
its projection with the groove
at the top portion of the
amplifier connector.
Insert the connector till a click
is felt.
Projection
Note: Take care that if the connector
is pulled out without pressing the
projection, the projection may break.
Do not use a quick-connection cable
whose projection has broken.
Further, do not pull by holding the
cable, as this can cause a
cable-break.
Cascading
How to mount the amplifier
F
it the rear part of the mounting section of the
amplifier on a 35 mm 1.378 in width DIN rail.
P
ress down the rear part of the mounting
section of the unit on the 35 mm 1.378 in width
DIN rail and fit the front part of the mounting
section to the 35 mm 1.378 in width DIN rail.
P
ush the fiber lock lever down.
S
lowly insert the fiber into the insertion
slot until it stops. (Note 1)
P
ush the fiber lock lever back up until
it stops.
Disconnection method
P
ressing the projection at the
top of the quick-connection
cable, pull out the connector.
Groove
Projection
Quick-connection cable
• Make sure that the power supply is off while adding or
removing the amplifiers.
• Make sure to check the allowable ambient temperature,
as it depends on the number of amplifiers connected in
cascade.
• In case two, or more, amplifiers are connected in
cascade, make sure to mount them on a DIN rail.
• When the amplifiers move on the DIN rail depending on
the attaching condition or the amplifiers are mounted
close to each other in cascade, fit them between the
optional end plates (MS-DIN-E) mounted at the two
ends.
• Up to maximum 15 amplifiers can be added (total 16
amplifiers connected in cascade.)
• When connecting more than two amplifiers in cascade,
use the sub cable (CN-71-C□ / CN-72-C□) as the
quick-connection cable for the second amplifier
onwards.
• When connecting amplifiers not close to each other
in parallel, be sure to mount the optional end plate
(MS-DIN-E) at both sides of each amplifier or affix the
communication window seal of the accessory amplifier
protection seal (FX-MB1) to the communication
windows.
• The settings other than the interference prevention
function cannot be transmitted between FX-301(P)
FX-301B/G/H(P), FX-305(P). Therefore, in case both
models of amplifiers are mounted in cascade, be sure
to mount identical models together. However, the
interference prevention function is not incorporated in
the FX-301(P)-HS. Take care when the sensors are
mounted in cascade.
• If the FX-301(P) updated version unit or the FX-305(P)
is mounted with the FX-301(P) previous version unit or
the FX-301B/G/H(P) in cascade, place the FX-301(P)
updated version units and the FX-305(P) units to
the right side (seen from the connector side) of the
previous version units. For details, refer to “Cautions
on sensor connection in cascade”.
For a difference between the updated version unit
and the previous version unit, refer to “A difference
between the updated version unit and the previous
version unit”.
• The communication function of this product and that of
the FX-301(P)-F / F7 is different. If these models are
mounted in cascade, affix the accessory fiber amplifier
protection seal (FX-MB1) included in the FX-301(P)
and FX-305(P) to the communication windows of the
amplifiers.
Digital Fiber Sensor
35 mm 1.378 in
width DIN rail
Main unit
Sub unit
Sub cable
(CN-71/72-C□)
(Optional)
How to change the communication specification of Group B
• Change the communication specification of Group B
according to the following procedures. Make sure to set the
communication specification to “ (Group A communication
specification)” or “ (Optical Communication Stop)”.
End plate
(MS-DIN-E)
(Optional)
ong press the [Jog Switch] and
L
[MODE key] at the same time.
(Note 3)
Group B's Communication
Specification
Group A's Communication
Specification
• When the units in the group A and the group B shown in
the table below are connected in cascade, connect them
in cascade as shown below.
Group A
FX-301(P): Previous version unit
(Note 1), FX-301G(P)/B(P)/H(P),
FX-41□(P), LS-401(P) (Note 2)
Group B
FX-301(P): Updated version
unit (Note 1), FX-305(P)
Notes: 1) For the difference between the updated
version unit and the previous version
unit, refer to “A difference between the
updated version unit and the previous
version unit”.
2) W
hen LS-401(P) is connected with the
digital fiber amplifier in cascade, be sure to
locate LS-401(P) at the left-most position
(when viewed from the connector side).
• When the units of the group A and the group B are
connected in cascade as shown above,
optical communications cannot be done. When the
optical communications function is used, connect them as
shown above. If the units cannot be placed
as , the following measure 1 or 2 should be
taken.
1
2
Optical Communication Stop
Notes: 3) E
very time the [Jog Switch] and the [MODE key] is
simultaneously long pressed, the display changes in
this sequence: “ ”→“ ”→“ ”→“ ”→“ ”.
Cautions on sensor connection in cascade
Group A
Group B
Group B
Group A
PHOTOELECTRIC
SENSORS
MICRO
PHOTOELECTRIC
SENSORS
LIGHT
CURTAINS /
SAFETY
COMPONENTS
Slide
W
hen you release the [Jog Switch] and
[MODE key], the communication specification
will be set and “PRO4” will be displayed.
Slide
LASER
SENSORS
AREA
SENSORS
Display [PRO4].
Main cable
(CN-73/74-C□)
(Optional)
FIBER
SENSORS
PRESSURE /
FLOW
SENSORS
INDUCTIVE
PROXIMITY
SENSORS
PARTICULAR
USE
SENSORS
SENSOR
OPTIONS
Dismantling
Loosen the screws of the end
plates.
Remove the end plates.
Slide the amplifiers and remove
them one by one.
Optical communications Optical communications
are possible
are impossible
160
Refer to p.1458~ for general precautions and to the “PRO mode operation guide”
on our website for details pertaining to operating instructions for the amplifier.
PRECAUTIONS FOR PROPER USE
Cascading method
Mount the amplifiers, one by
one, on the 35 mm 1.378 in
width DIN rail.
Slide the amplifiers next to each
other, and connect the quickconnection cables.
Mount the optional end plates
(MS-DIN-E) at both the ends to
hold the amplifiers between
their flat sides.
Tighten the screws to fix the
end plates.
FX-300 SERIES
ffix the communication window seal of the accessory
A
fiber amplifier protection seal (FX-MB1) to the
communication window of the FX-301(P) updated
version unit or FX-305(P).
If the measure 1 described above cannot be taken,
change the optical communications spec. of the group B
units.
Notes: 4) When the communication specification is set to “ (Group A
communication specification)”, make sure to tightly attach the
products. Also make sure to take note of the following:
•T
here are instances when the optical communication function
cannot be used due to the usage environment, etc.
•D
o not perform batch channel loading or saving.
Part description
MODE indicator / L/D ON (Yellow)
MODE indicator / TIMER (Yellow)
Stability indicator
(Green)(Note2)
Operation indicator (Orange) (Note1)
MODE indicator / RUN (Green)
MODE indicator /
PRO (Yellow)
MODE indicator / TEACH (Yellow)
MODE indicator / ADJ (Yellow)
MODE key
SIMPLE
WIRE-SAVING
UNITS
WIRE-SAVING
SYSTEMS
MEASUREMENT
SENSORS
STATIC
ELECTRICITY
PREVENTION
DEVICES
LASER
MARKERS
PLC
HUMAN
MACHINE
INTERFACES
ENERGY
CONSUMPTION
VISUALIZATION
COMPONENTS
FA
COMPONENTS
MACHINE
VISION
SYSTEMS
UV
CURING
SYSTEMS
Jog switch
Digital display (Red)
Notes: 1
) FX-305(P); Output 1 operation indicator (Orange)
2) FX-305(P); Output 2 operation indicator (Orange)
Operation procedure
Selection
Guide
• When the power supply is switched on, communication
self-check is carried out and normal condition is
displayed [MODE indicator / RUN (green)] lights up and
the digital display shows the incident light intensity.
• When the MODE key is pressed, the mode will change as
shown in the following diagram.
Power ON
Press
MODE key
Press
MODE key
[Teaching]
TEACH
(P.161)
Press
MODE key
[Threshold
value fine
adjust] (P.162)
ADJ
Fiber
Amplifiers
FX-500
FX-100
FX-300
FX-410
Communication self-check
RUN
Fibers
FX-311
PRO
[PRO mode]
Press
MODE key
TIMER [Timer operation
setting] (P.162)
Press
MODE key
Press
MODE key
L/D
[Output operation
setting] (P.162)
When Jog switch is pressed, the setting is confirmed.
When MODE key is pressed for 2 sec., or more, the sensor returns to the ‘RUN’ mode.
Cancellation is possible by pressing MODE key during setting.
FX-301-F7/
FX-301-F
161
FIBER
SENSORS
LASER
SENSORS
PHOTOELECTRIC
SENSORS
MICRO
PHOTOELECTRIC
SENSORS
AREA
SENSORS
LIGHT
CURTAINS /
SAFETY
COMPONENTS
PRESSURE /
FLOW
SENSORS
INDUCTIVE
PROXIMITY
SENSORS
PARTICULAR
USE
SENSORS
SENSOR
OPTIONS
SIMPLE
WIRE-SAVING
UNITS
WIRE-SAVING
SYSTEMS
MEASUREMENT
SENSORS
STATIC
ELECTRICITY
PREVENTION
DEVICES
LASER
MARKERS
PLC
HUMAN
MACHINE
INTERFACES
ENERGY
CONSUMPTION
VISUALIZATION
COMPONENTS
FA
COMPONENTS
MACHINE
VISION
SYSTEMS
UV
CURING
SYSTEMS
Digital Fiber Sensor
PRECAUTIONS FOR PROPER USE
Fibers
Fiber
Amplifiers
FX-500
FX-100
FX-300
FX-410
FX-311
FX-301-F7/
FX-301-F
Refer to p.1458~ for general precautions and to the “PRO mode operation guide”
on our website for details pertaining to operating instructions for the amplifier.
For FX-305(P)
The FX-305(P) is equipped with two independent outputs, but
the items that can be set in output 1 and output 2 respectively
are only the following.
The items other than those are common.
1 Threshold value 2 Output operation
3 Timer operation and Timer period 4 Sensing mode
Teaching
• The threshold values can be set by 2-point teaching, limit
teaching, full-auto teaching or window comparator mode
(1-point, 2-point, 3-point teaching) [only for FX-305(P)],
when the MODE indicator / TEACH (yellow) lights up.
In case of 2-point teaching
• This is the method of setting the threshold value by teaching
two levels, corresponding to the object present and object
absent conditions. Normally, setting is done by this method.
Step
Description
Display
Set the fiber within the
sensing range.
Press MODE key to light
up MODE indicator /
TEACH (yellow).
For FX-305(P), select either Output 1 “
” or
Output 2 “
” beforehand, press jog switch
in the object present condition.
If the teaching is accepted, the read incident
light intensity blinks in the digital display.
Thru-beam type
Reflective type
Mark
Beam
blocked condition
Background
MODE indicator / TEACH (yellow) blinks.
Press jog switch in the object absent condition.
Thru-beam type Reflective type
Mark
Beam
incident condition
Selection
Guide
FX-300 SERIES
Background
If the teaching is accepted, the read incident
light intensity blinks in the digital display
and the threshold value is set at the midvalue between the incident light intensities
in the object present and the object absent
conditions. After this, the judgment on the
stability of sensing is displayed.
• In case stable sensing is possible: “
” is displayed.
• In case stable sensing is not possible: “
” blinks.
The threshold value is displayed.
“
” blinks in the digital display.
(only FX-301B/G/H)
The incident light intensity appears in the
digital display and the setting is complete.
Notes: 1) Do not move or bend the fiber cable after the sensitivity setting.
Detection may become unstable.
2) In case a reflective-type fiber is used, maximum sensitivity will be
set if the jog switch is pushed while in no work status in procedure
and .
In case of full auto-teaching
• Full auto-teaching is used when it is desired to set the
threshold value without stopping the assembly line, with
the object in the moving condition.
Step
Description
Display
Set the fiber within the
sensing range.
Press MODE key to light
up MODE indicator /
TEACH (yellow).
For FX-305(P), select either Output 1 “
” or
Output 2 “
” beforehand, press the jog switch
continuously for 0.5 sec. or more with the object
moving on the assembly line. (The incident light
intensity is displayed during sampling.)
“
” is displayed on the digital display. Release
the jog switch when the object has passed.
If the teaching is accepted, the read incident
light intensity blinks in the digital display
and the threshold value is set at the midvalue between the incident light intensities
in the object present and the object absent
conditions. After this, the judgment on the
stability of sensing is displayed.
• In case stable sensing is possible: “
” is displayed.
• In case stable sensing is not possible: “
” blinks.
The threshold value is displayed.
“
” blinks in the digital display.
(only FX-301B/G/H)
The incident light intensity appears in the
digital display and the setting is complete.
Notes: 1) The threshold value’s shift amount can be selected in PRO mode.
Refer to the “PRO Mode Operation Guide” for more details
pertaining to setting instructions. (Increments of 5 % between –45
and 45 % for setting possible. 0 % default.)
2) D
o not move or bend the fiber cable after the sensitivity setting.
Detection may become unstable.
Digital Fiber Sensor
PRECAUTIONS FOR PROPER USE
Description
Step
For FX-305(P), select either Output 1 “
”
or Output 2 “
” beforehand, in case the
threshold value is to be increased (sensitivity
to be reduced), turn the jog switch
to the “+” side to increase the
threshold value slowly. If the
jog switch is turned continuously to the “+”
side, the threshold value increases rapidly.
In case the threshold value is to be decreased
(sensitivity to be increased), turn the jog
switch to the “–” side to decrease the
threshold value slowly. If the jog
switch is turned continuously to
the “–” side, the threshold value
decreases rapidly.
When jog switch is pressed,
the threshold value is
confirmed.
Background
body
Beam
incident condition
MODE indicator / TEACH (yellow) blinks.
Turn jog switch to the “+” side or “–” side.
Threshold
value
100 %
Low
0
15 %
Threshold value
Incident light intensity
with object absent
15 %
ON
OFF
–
Threshold value
Turn to “+” side
Turn to “–” side
After this, the judgment on whether the setting
shift amount can be shifted or not is displayed.
• I n case shifting is possible: “
” blinks.
• I n case shifting is not possible: “
” blinks.
The threshold value is displayed.
“
” blinks in the digital display.
(only FX-301B/G/H)
The incident light intensity appears in the
digital display and the setting is complete.
Notes: 1) Scrolling display is not available in FX-301B/G/H.
2) The approx. 15 % amount of shift is the initial value. The amount of
shift can be changed in the PRO mode from approx. 5 to 80 %
(5 % step). Refer to the “PRO Mode Operation Guide” for more
details pertaining to setting instructions.
3) Do not move or bend the fiber cable after the sensitivity setting.
Detection may become unstable.
Please download the instruction manual from our website for
setting of threshold value when used in combination with liquid
level sensing fiber FD-F8Y and with pipe-mountable liquid level
sensing fiber FD-F4□.
For the wind comparator mode teaching in FX-305(P), refer to
the separately prepared “PRO Mode Operation Guide”.
PHOTOELECTRIC
SENSORS
MICRO
PHOTOELECTRIC
SENSORS
AREA
SENSORS
Thru-beam type Reflective type
ON
Display
Press MODE key to light
up MODE indicator / ADJ
(yellow).
For FX-305(P), select either Output 1 “
” or
Output 2 “
” beforehand, press jog switch
in the object absent condition. If the teaching
is accepted, the read incident light intensity
blinks in the display.
OFF
Description
Display
If jog switch is turned to the “+” side, “
” scrolls
(twice) the display from right to left (Note 1), and the
threshold level is shifted to a value
approx. 15 % higher (lower sensitivity)
than that set at . (Note 2)
This is used in case of reflective type fibers.
If jog switch is turned to the “–” side, “
” scrolls
(twice) the display from left to right, and the threshold
level is shifted to a value approx.
15 % lower (higher sensitivity)
than that set at . (Note 2)
This is used in case of thru-beam type fibers.
FIBER
SENSORS
LASER
SENSORS
Threshold value fine adjustment
Set the fiber within the
sensing range.
Press MODE key to light
up MODE indicator /
TEACH (yellow).
High
162
Refer to p.1458~ for general precautions and to the “PRO mode operation guide”
on our website for details pertaining to operating instructions for the amplifier.
In case of limit teaching
• This is the method of setting the threshold value by
teaching only the object absent condition (stable incident
light condition). This is used for detection in the presence
of a background body or for detection of small objects.
Step
FX-300 SERIES
LIGHT
CURTAINS /
SAFETY
COMPONENTS
PRESSURE /
FLOW
SENSORS
INDUCTIVE
PROXIMITY
SENSORS
or
PARTICULAR
USE
SENSORS
SENSOR
OPTIONS
SIMPLE
WIRE-SAVING
UNITS
WIRE-SAVING
SYSTEMS
–
MEASUREMENT
SENSORS
STATIC
ELECTRICITY
PREVENTION
DEVICES
LASER
MARKERS
Output operation setting
Step
Description
Press MODE key to light
up MODE indicator / L/D
ON (yellow).
For FX-305(P), select either Output 1 “
or Output 2 “
” beforehand,
if the jog switch is turn to
the “+” or “–” direction,
the output operation setting
will change.
When jog switch is pressed,
the threshold value is
confirmed.
Display
PLC
HUMAN
MACHINE
INTERFACES
”
Displays
present setting
ENERGY
CONSUMPTION
VISUALIZATION
COMPONENTS
Light state
FA
COMPONENTS
MACHINE
VISION
SYSTEMS
Dark state
UV
CURING
SYSTEMS
Displays
selected setting
Timer operation setting
• The setting for whether the timer is used or not can be
done when MODE indicator / TIMER (yellow) lights up.
For FX-301B/G/H, the timer type can be set in PRO
mode.
• Further, an OFF-delay (initial value) which is useful when
the response of the connected device is slow, etc., an
ON-delay which is useful to detect only objects taking a
long time to travel, and ONE SHOT, which is useful when
the input specifications of the connected device require a
signal of a fixed width, are possible with the FX-301□(-HS).
FX-305(P) is also equipped with ON-delay • OFF-delay and
ON-delay • ONE SHOT timers. Refer to the “PRO Mode
Operation Guide” for the setting method of the OFF-delay,
ON-delay and ONE SHOT timer intervals.
Selection
Guide
Fibers
Fiber
Amplifiers
FX-500
FX-100
FX-300
FX-410
FX-311
FX-301-F7/
FX-301-F
163
FIBER
SENSORS
LASER
SENSORS
PHOTOELECTRIC
SENSORS
MICRO
PHOTOELECTRIC
SENSORS
AREA
SENSORS
LIGHT
CURTAINS /
SAFETY
COMPONENTS
PRESSURE /
FLOW
SENSORS
INDUCTIVE
PROXIMITY
SENSORS
PARTICULAR
USE
SENSORS
SENSOR
OPTIONS
SIMPLE
WIRE-SAVING
UNITS
WIRE-SAVING
SYSTEMS
MEASUREMENT
SENSORS
STATIC
ELECTRICITY
PREVENTION
DEVICES
LASER
MARKERS
PLC
HUMAN
MACHINE
INTERFACES
Digital Fiber Sensor
FX-300 SERIES
PRECAUTIONS FOR PROPER USE
Refer to p.1458~ for general precautions and to the “PRO mode operation guide”
on our website for details pertaining to operating instructions for the amplifier.
Key-lock function
Wiring
• Make sure that the power supply is off while wiring.
• Verify that the supply voltage variation is within the rating.
• Take care that if a voltage exceeding the rated range is
applied, or if an AC power supply is directly connected,
the product may get burnt or damaged.
• If power is supplied from a commercial switching
regulator, ensure that the frame ground (F.G.) terminal of
the power supply is connected to an actual ground.
• In case noise generating equipment (switching regulator,
inverter motor, etc.) is used in the vicinity of this
product, connect the frame ground (F.G.) terminal of the
equipment to an actual ground.
• Take care that short circuit of the load wrong wiring may
burn or damage the product.
• Do not run the wires together with high-voltage lines or
power lines or put them in the same raceway. This can
cause malfunction due to induction.
• Make sure to use an isolation transformer for the DC
power supply. If an autotransformer (single winding
transformer) is used, this product or the power supply
may get damaged.
• Make sure to use the optional quick-connection cable for
the connection of the amplifier. Extension up to total 100
m 328.084 ft is possible with 0.3 mm2, or more, cable.
(5-8 unit expansion: 50 m 164.042 ft, 9-16 unit
expansion: 20 m 65.617 ft) However, in order to reduce
noise, make the wiring as short as possible.
• Note that the residual voltage will increase when the
cable is extended.
• If jog switch and MODE key are pressed for more than
2 sec. at the same time in ‘RUN’ mode condition, the
key operations are locked, and only the threshold value
confirmation function or the adjust function (valid only
when the adjust lock function is canceled) is valid.
To cancel the lock function, press both the keys for more
than 2 sec. once again.
Note: 3 seconds or more for FX-301B/G/H(P).
Others
• When the emission halt of the light emitting amount
selection function is set from “OFF” to “ON”, the output
may be unstable. Do not use the output control for 0.5
sec. after starting emission.
• Do not use during the initial transient time (0.5 sec.) after
the power supply is switched on.
• Take care that the sensor is not directly exposed to
fluorescent lamp from a rapid-starter lamp, a high
frequency lighting device or sunlight etc. , as it may affect
the sensing performance.
• Do not use this sensor in places having excessive vapor,
dust, etc., or where it may come in contact with corrosive
gas.
• Take care that the product does not come in direct
contact with water, oil, grease, or organic solvents, such
as, thinner, etc.
• This sensor cannot be used in an environment containing
inflammable or explosive gases.
• Never disassemble or modify the sensor.
ENERGY
CONSUMPTION
VISUALIZATION
COMPONENTS
FA
COMPONENTS
MACHINE
VISION
SYSTEMS
UV
CURING
SYSTEMS
Function table for FX-300 series
Previous models
Standard type
FX-301(P)
(Previous version unit)
Selection
Guide
Fibers
Fiber
Amplifiers
New models
High-function type High-speed type
FX-302(P)
FX-303(P)
Standard type
FX-301(P)
(Updated version unit)
High-speed type High-function type
FX-301(P)-HS
FX-305(P)
Four-chemical emitting element + APC circuit
No
No
No
Yes
Yes
Yes
Four-chemical emitting element only
Yes (Note)
Yes
Yes
–
–
–
Light emitting amount selection function
No
No
No
Yes
Yes
Yes
Reduced intensity mode (S-D)
Yes (Note)
Yes
No
Yes
Yes
–
9,999 digit display
No
No
No
No
No
Yes
FX-500
Response time (Max. speed)
150 μs
300 μs
90 μs
65 μs
35 μs
65 μs
FX-100
Interference prevention function (Effective no. of units)
Incorporated (4)
Incorporated (8)
Not incorporated (0)
Incorporated (4)
Not incorporated (0)
Incorporated (16)
FX-300
Independent 2 outputs
No
No
No
No
No
Yes
Alarm output function
No
No
No
No
No
Yes
Error output function
No
No
No
No
No
Yes
Differential sensing
No
No
No
No
No
Yes
Window comparator mode
No
Yes
No
No
No
Yes
FX-410
FX-311
FX-301-F7/
FX-301-F
Peripheral units that can be combined
Bank selection unit
FX-CH(-P)
Yes
Yes
No
No
No
No
External input unit
FX-CH2(-P)
No
No
No
Yes
No
Yes
Upper communication unit
SC-GU1-485
No
No
No
Yes
No
Yes
Note: Except FX-301B/G/H.
Digital Fiber Sensor
PRECAUTIONS FOR PROPER USE
• The product has been modified as shown below since its
production in June 2004.
Changes in appearance
Top view
After change
Top view
Name
plate
Display
Uses special parts
Side view
1. Timer selection method
Previous version unit: Timer type was changed using PRO1 mode.
The “TIMER” setting in NAVI mode could
only be turned on or off.
After change: T
he type of timer can be changed using the “TIMER”
function in NAVI mode.
Display changes
Change in shape
of jog switch
* “NAVI” is printed on the both sides * “NAVI” is printed only on a side
1. Checking blinking of sensitivity surplus
The stable surplus display method after teaching has been changed.
Previous version unit: Sensitivity surplus is indicated by the number
of blinks of the stability indicator.
After change
1. Response times added
An ultra high-speed mode (H-SP) has been added to
the existing 4 response time modes [high-speed (FAST),
reduced intensity (S-D), standard (STD) and long range
(LONG)].
This is changed using “
” in “
”
Before change
4 steps
2. Initial direct code value changed
The factory default settings for the direct codes have been changed.
Previous version unit 0000
Upgraded functions
After change
After change 0004
*T
he default setting for the timer period is 10 ms, and the direct code for
10 ms is “4”, so this has been changed.
Internal circuit changes
1. Addition of an APC circuit
A four-chemical emitting element which provides stable
sensing over• long• periods• has been added, as well
as an APC (Auto Power Control) circuit that improves
stability during short periods.
Cautions on sensor connection in cascade
5 steps
150 μs (FAST)
65 μs (added) (H-SP)
250 μs (S-D)
150 μs (FAST)
250 μs (STD)
250 μs (S-D)
2 ms (LONG)
250 μs (STD)
PHOTOELECTRIC
SENSORS
MICRO
PHOTOELECTRIC
SENSORS
AREA
SENSORS
LIGHT
CURTAINS /
SAFETY
COMPONENTS
PRESSURE /
FLOW
SENSORS
INDUCTIVE
PROXIMITY
SENSORS
PARTICULAR
USE
SENSORS
SENSOR
OPTIONS
SIMPLE
WIRE-SAVING
UNITS
Digital display only
• Checking minor changes between previous and
updated models can be done by checking whether the
printing is on both sides or only one side.
FIBER
SENSORS
LASER
SENSORS
Changes in operation
2. Checking threshold value in RUN mode
The threshold values can be checked by turning the jog switch.
Added to
name plate
Side view
164
Refer to p.1458~ for general precautions and to the “PRO mode operation guide”
on our website for details pertaining to operating instructions for the amplifier.
A difference between the updated version unit and
the previous version unit for FX-301(P) (Red LED type)
Before change
FX-300 SERIES
When connecting the previous version unit (including
FX-301B/G/H) and updated version unit to be used in a
cascade, refer to “Cautions on sensor connection in
cascade”.
WIRE-SAVING
SYSTEMS
MEASUREMENT
SENSORS
STATIC
ELECTRICITY
PREVENTION
DEVICES
LASER
MARKERS
PLC
HUMAN
MACHINE
INTERFACES
ENERGY
CONSUMPTION
VISUALIZATION
COMPONENTS
FA
COMPONENTS
MACHINE
VISION
SYSTEMS
UV
CURING
SYSTEMS
2 ms (LONG)
2. Extension of timer period
The setting range for the timer period was previously
500 ms, but this has been extended to a new range of
9,999 ms.
3. Light emitting amount selection function
The light emitting amount can be changed to one of
4 levels (5 levels when emission halt is included).
4. Backup, copy lock and key lock functions added
Backup: This selects whether or not threshold values
set by teaching are written to (stored in) an
EEPROM.
Copy lock: This selects whether copy function and data
bank function communication are possible or
not.
Key lock: This disables input using switches to prevent
accidental changing of settings.
Selection
Guide
Fibers
Fiber
Amplifiers
FX-500
FX-100
FX-300
FX-410
FX-311
FX-301-F7/
FX-301-F
165
FIBER
SENSORS
Digital Fiber Sensor
FX-300 SERIES
PRECAUTIONS FOR PROPER USE
Refer to p.1458~ for general precautions and to the “PRO mode operation guide”
on our website for details pertaining to operating instructions for the amplifier.
LASER
SENSORS
Diagram of functions and settings
PHOTOELECTRIC
SENSORS
The amplifier features and settings are generally classified into two main modes; the “NAVI mode” for items and settings that
are frequently reconfigured, and the “PRO mode” that contains more detailed settings.
MICRO
PHOTOELECTRIC
SENSORS
RUN
AREA
SENSORS
LIGHT
CURTAINS /
SAFETY
COMPONENTS
PRESSURE /
FLOW
SENSORS
TEACH
Run
This indicates normal sensing operation.
NAVI
mode
PRO
INDUCTIVE
PROXIMITY
SENSORS
TIMER
Pro
Allows various detailed settings to be
configured, such as optical communications,
save / load and other settings.
PARTICULAR
USE
SENSORS
Teaching
The “threshold value” can be set by
utilizing either “2-point teaching”, “limit
teaching”, or “full-auto teaching”.
* When the FX-305(P) is in window comparator mode,
the “threshold value” can be set by either “1-point
teaching”, “2-point teaching” or “3-point teaching”.
ADJ
Allows fine adjustment of the
“threshold value”.
L/D
Timer
Configures operation of the timer.
Adjust
L-ON / D-ON
Sets output operation either Light-ON,
or Dark-ON.
SENSOR
OPTIONS
Response Time Change
SIMPLE
WIRE-SAVING
UNITS
PRO1
Switches among response times.
WIRE-SAVING
SYSTEMS
MEASUREMENT
SENSORS
LASER
MARKERS
PRO2
Allows selection of different content
to be indicated in the digital display.
HUMAN
MACHINE
INTERFACES
ENERGY
CONSUMPTION
VISUALIZATION
COMPONENTS
MACHINE
VISION
SYSTEMS
UV
CURING
SYSTEMS
PRO3
PRO
mode
Sets the viewing orientation of the
digital display.
Data Bank Save
Loads configuration setting from the
data bank.
Saves configuration setting into the
data bank.
Copy
PRO4
* The FX-301(P)-HS is not
equipped with a PRO4
setting function.
Backup
Allows not to save the threshold value, by
teaching via external input in EEPROM.
[FX-301(P), FX-305(P) only]
Selection
Guide
Fibers
Fiber
Amplifiers
PRO5
Remote Data Bank Save
Using optical communication, current
configuration settings can be saved into
respective data banks all at once.
Communication Change
To Permit / Not to Permit
When using optical communication for carrying out
copy / load / save operations all at once, this function
allows optical communication to pass through the unit.
Verifies whether optical communications
have been properly established.
(FX-301B/G/H only)
Allows fine adjustment of the “threshold
value” to be directly performed during
RUN mode.
The items that can be set are different for output 1 and output 2.
Normal Mode
PRO6
Sets a threshold value for ON /
OFF operation.
Reset
All settings, except for data bank
information, revert to factory settings.
Interference Prevention
Switching
Switches the number of units for which
interference prevention switching is enabled.
* FX-305(P) only.
FX-410
Available only in FX-305(P)
Test
Adjust Lock
Allows basic configuration information
to be set in a single step, by inputting
a 4-digit code.
FX-300
FX-311
Sets the digital display to turn
ON / OFF.
Remote Data Bank Load
FX-100
FX-301-F7/
FX-301-F
ECO Mode
Using optical communication, configuration
settings can be loaded from respective data
banks all at once.
Code
FX-500
Stability
Permits selection of stability indicator response
levels for changes in the range for lighting up.
[excluding the FX-305(P)]
Digital Display Inversion
Data Bank Load
Using optical communications, configuration
settings from the main unit are copied to
connected sub units all at once.
Sets hysteresis level.
Shift
Shifts the “threshold value” by a
certain percentage increment in
“limit teaching”.
Digital Display Setting
PLC
FA
COMPONENTS
Configures timer operation.
Light Emitting Amount Selection
Changes the light emitting amount
selection setting.
[FX-301(P)(-HS), FX-305(P) only]
STATIC
ELECTRICITY
PREVENTION
DEVICES
Hysteresis
Timer Setting
Rising Differential Mode
Window Comparator Mode
Output 1 Judges if set two threshold values are within the
required range or not. This can be selected in
1-point / 2-point / 3-point teaching.
Sensing mode that cancels out slight changes in
light intensity so that only sudden increases in
incident light intensity are sensed.
Output 2
Error Output
Alarm Output
Trailing Differential Mode
Output when overcurrent occurs or when
a communication error occurs from
connected incompletely.
Be used as alarm output when the threshold
value for output 2 is linked to output 1 and
the light amount drops.
Sensing mode that cancels out slight changes in
light intensity so that only sudden decreases in
incident light intensity are sensed.
* The 0-ADJ setting function equipped on the FX-301□ and FX-305(P) has been deleted since the production in May 2005.
Digital Fiber Sensor
DIMENSIONS (Unit: mm in)
PHOTOELECTRIC
SENSORS
12
0.472
AREA
SENSORS
MODE key
Jog switch
Digital display (Red)
3
0.118
64.5
2.539
Communication
window
Beamemitting
part
7 0.276
Beamreceiving
part
MICRO
PHOTOELECTRIC
SENSORS
0.7
0.028
Stability indicator
(Green) (Note 2)
10
0.394
LIGHT
CURTAINS /
SAFETY
COMPONENTS
PRESSURE /
FLOW
SENSORS
3.3
0.130
27.8
1.094
INDUCTIVE
PROXIMITY
SENSORS
7
0.276
30.5
1.201
PARTICULAR
USE
SENSORS
10.5
0.413
7 0.276
3
0.118
13.5
0.531
SENSOR
OPTIONS
(Note 3)
SIMPLE
WIRE-SAVING
UNITS
3.95
0.156
Suitable for 35 mm
1.378 in width DIN rail
36.5
1.437
WIRE-SAVING
SYSTEMS
Notes: 1) FX-305□; Output 1 operation indicator (Orange)
2) FX-305□; Output 2 operation indicator (Orange)
3) FX-301□; 3-pin, FX-305□; 4-pin
CN-73-C□ CN-74-C□
MEASUREMENT
SENSORS
STATIC
ELECTRICITY
PREVENTION
DEVICES
Main cable (Optional)
• Length L
L
50
1.969
CN-71-C□ CN-72-C□
Sub cable (Optional)
• Length L
Model No.
Length L
Model No.
Length L
1,000 39.370
CN-71/72-C1
1,000 39.370
CN-73/74-C2
2,000 78.740
CN-71/72-C2
2,000 78.740
CN-73/74-C5
5,000 196.850
CN-71/72-C5
5,000 196.850
ø3.3 ø0.130 cable
14
(0.551
)
2.54
0.100
2.65
0.104
(Note 2)
2.9
(0.114
)
10
0.394
6
0.236
( )
12 10.5
(0.472
) 0.413
2.54
0.100
Notes: 1) CN-74-C□ only
2) CN-73-C□; 3-core
7
0.276
10
0.394
13.6
0.535
3
0.118
(Note 2)
(
14
0.551
)
3
0.118
2.9
(0.114
)
2.54
0.100
HUMAN
MACHINE
INTERFACES
ENERGY
CONSUMPTION
VISUALIZATION
COMPONENTS
10
0.394
6
0.236
( )
FA
COMPONENTS
MACHINE
VISION
SYSTEMS
UV
CURING
SYSTEMS
12 10.5
(0.472
) 0.413
2.65
0.104
7.2
0.283
50
1.969
ø3.3 ø0.130 cable
2.54
0.100
(Note 1)
0.2
0.008
LASER
MARKERS
PLC
L
CN-73/74-C1
(Note 1)
FIBER
SENSORS
LASER
SENSORS
Amplifier
48.2
26.3 1.898
1.0352.5
0.098
166
The CAD data in the dimensions can be downloaded from our website.
FX-301□ FX-305(P)
8.3
Operation indicator
(Orange) (Note 1) 0.327
FX-300 SERIES
0.2
0.008
Notes: 1
) CN-72-C□ only
2) CN-71-C□: 1-core
7
0.276
10
0.394
13.6
0.535
3
0.118
7.2
0.283
Selection
Guide
Fibers
MS-DIN-2
Amplifier mounting bracket (Optional)
21.6 0.850
16 0.630
5.2
0.205
MS-DIN-E
End plate (Optional)
2.75
0.108
3.2
0.126
FX-500
10
0.394
8.5
0.335
3.2
0.126
0.4
0.016 ø1.8
ø0.071
7.5
0.295 4.2 0.165
5.2
0.205
35
1.378
2
0.079
2
0.079
2-ø3.2 ø0.126 holes
Material: Cold rolled carbon steel (SPCC)
(Uni-chrome plated)
5
0.197
15
0.591
60
2.362
3
0.118
5.6 M3 square nut
0.220
24.7
0.972
t1
t 0.039
27
1.063
M3 (length 18 mm 0.709 in) pan head screws
3
0.118
1.6
0.063
Fiber
Amplifiers
32
1.260
Material: Polycarbonate
4
0.157
Suitable for 35 mm 1.378 in width DIN rail
FX-100
FX-300
FX-410
FX-311
FX-301-F7/
FX-301-F