Data sheet
6ES7532-5HF00-0AB0
SIMATIC S7-1500, analog output module AQ8xU/I HS, 16-bit resolution accuracy
0.3%, 8 channels in groups of 8, diagnostics; substitute value 8 channels in 0.125
ms oversampling; the module supports the safety-oriented shutdown of load
groups up to SIL2 according to EN IEC 62061:2021 and Category 3 / PL d
according to EN ISO 13849-1:2015. delivery including infeed element, shielding
bracket and shield terminal: front connector (screw terminals or push-in) to be
ordered separately
General information
Product type designation
AQ 8xU/I HS
HW functional status
From FS01
Firmware version
V2.1.0
● FW update possible
Yes
Product function
● I&M data
Yes; I&M0 to I&M3
● Isochronous mode
Yes
● Prioritized startup
No
● Output range scalable
No
Engineering with
● STEP 7 TIA Portal configurable/integrated from version
V14 / -
● STEP 7 configurable/integrated from version
V5.5 SP3 / -
● PROFIBUS from GSD version/GSD revision
V1.0 / V5.1
● PROFINET from GSD version/GSD revision
V2.3 / -
Operating mode
● Oversampling
Yes
● MSO
Yes
CiR - Configuration in RUN
Reparameterization possible in RUN
Yes
Calibration possible in RUN
Yes
Supply voltage
Rated value (DC)
24 V
permissible range, lower limit (DC)
19.2 V
permissible range, upper limit (DC)
28.8 V
Reverse polarity protection
Yes
Input current
Current consumption, max.
320 mA; with 19.2 V supply
Power
Power available from the backplane bus
1.15 W
Power loss
Power loss, typ.
7W
Analog outputs
Number of analog outputs
8
Voltage output, short-circuit protection
Yes
Voltage output, short-circuit current, max.
45 mA
Current output, no-load voltage, max.
20 V
Cycle time (all channels), min.
125 µs; independent of number of activated channels
Output ranges, voltage
6ES75325HF000AB0
Page 1/3
5/15/2024
Subject to change without notice
© Copyright Siemens
● 0 to 10 V
Yes
● 1 V to 5 V
Yes
● -5 V to +5 V
No
● -10 V to +10 V
Yes
Output ranges, current
● 0 to 20 mA
Yes
● -20 mA to +20 mA
Yes
● 4 mA to 20 mA
Yes
Connection of actuators
● for voltage output two-wire connection
Yes
● for voltage output four-wire connection
Yes
● for current output two-wire connection
Yes
Load impedance (in rated range of output)
● with voltage outputs, min.
1 kΩ
● with voltage outputs, capacitive load, max.
100 nF
● with current outputs, max.
500 Ω
● with current outputs, inductive load, max.
1 mH
Cable length
● shielded, max.
200 m
Analog value generation for the outputs
Integration and conversion time/resolution per channel
● Resolution with overrange (bit including sign), max.
16 bit
● Conversion time (per channel)
50 µs; independent of number of activated channels
Settling time
● for resistive load
30 µs; see additional description in the manual
● for capacitive load
100 µs; see additional description in the manual
● for inductive load
100 µs; see additional description in the manual
Errors/accuracies
Output ripple (relative to output range, bandwidth 0 to 50 kHz),
(+/-)
0.02 %
Linearity error (relative to output range), (+/-)
0.15 %
Temperature error (relative to output range), (+/-)
0.002 %/K
Crosstalk between the outputs, max.
-100 dB
Repeat accuracy in steady state at 25 °C (relative to output
range), (+/-)
0.05 %
note regarding accuracy
at temperatures below 0 °C, the figures for operating error and temperature
error are doubled
Operational error limit in overall temperature range
● Voltage, relative to output range, (+/-)
0.3 %
● Current, relative to output range, (+/-)
0.3 %
Basic error limit (operational limit at 25 °C)
● Voltage, relative to output range, (+/-)
0.2 %
● Current, relative to output range, (+/-)
0.2 %
Isochronous mode
Execution and activation time (TCO), min.
100 µs
Bus cycle time (TDP), min.
250 µs
Interrupts/diagnostics/status information
Diagnostics function
Yes
Substitute values connectable
Yes
Alarms
● Diagnostic alarm
Yes
Diagnoses
● Monitoring the supply voltage
Yes
● Wire-break
Yes; Only for output type "current"
● Short-circuit
Yes; Only for output type "voltage"
● Overflow/underflow
Yes
Diagnostics indication LED
● RUN LED
Yes; green LED
● ERROR LED
Yes; red LED
● Monitoring of the supply voltage (PWR-LED)
Yes; green LED
● Channel status display
Yes; green LED
6ES75325HF000AB0
Page 2/3
5/15/2024
Subject to change without notice
© Copyright Siemens
● for channel diagnostics
Yes; red LED
● for module diagnostics
Yes; red LED
Potential separation
Potential separation channels
● between the channels
No
● between the channels, in groups of
8
● between the channels and backplane bus
Yes
● Between the channels and load voltage L+
Yes
Permissible potential difference
between S- and MANA (UCM)
8 V DC
Isolation
Isolation tested with
707 V DC (type test)
Standards, approvals, certificates
Suitable for safety-related tripping of standard modules
Yes; from FS04
Highest safety class achievable for safety-related tripping of standard modules
● Performance level according to ISO 13849-1
PL d
● Category according to ISO 13849-1
Cat. 3
● SIL acc. to IEC 62061
SIL 2
● remark on safety-oriented shutdown
https://support.industry.siemens.com/cs/de/en/view/39198632
product functions / security / header
signed firmware update
No
data integrity
No
Ambient conditions
Ambient temperature during operation
● horizontal installation, min.
-30 °C; From FS03
● horizontal installation, max.
60 °C
● vertical installation, min.
-30 °C; From FS03
● vertical installation, max.
40 °C
Altitude during operation relating to sea level
● Installation altitude above sea level, max.
5 000 m; Restrictions for installation altitudes > 2 000 m, see manual
Dimensions
Width
35 mm
Height
147 mm
Depth
129 mm
Weights
Weight, approx.
325 g
last modified:
3/12/2024
6ES75325HF000AB0
Page 3/3
5/15/2024
Subject to change without notice
© Copyright Siemens